Goodman SSZ 14 SEER - page 1
SSZ 14 SEER S plit System Heat Pump s • Refer to Service Manual RS6200005 for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. • Models listed on page 3. RT6213005r7 November 2011 Copyri ...
-
Goodman SSZ 14 SEER - page 2
PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause p ...
-
Goodman SSZ 14 SEER - page 3
PRODUCT IDENTIFICA TION 3 The United States Environmental Protection Agency (“EPA”) has issued various regulations re- garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. These regulations may vary by ju ...
-
Goodman SSZ 14 SEER - page 4
PRODUCT DESIGN 4 SSZ14 models are available in 1 1/2 through 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet. These units are designed for ...
-
Goodman SSZ 14 SEER - page 5
HEA T PUMP SPECIFICA TIONS 5 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...
-
Goodman SSZ 14 SEER - page 6
HEA T PUMP SPECIFICA TIONS 6 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/ circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. SSZ140[18,30]1AF; SSZ140241AJ; SSZ140361AH * Up to 24' in equivalent line length (1) Wire ...
-
Goodman SSZ 14 SEER - page 7
HEA T PUMP SPECIFICA TIONS 7 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...
-
Goodman SSZ 14 SEER - page 8
HEA T PUMP SPECIFICA TIONS 8 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/ circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. SSZ140361B* SS Z1 4 036 1B* Coo lin g Ca paci ty , BTU H 35,000 Co m pressor R. L . Amp s 14.1 ...
-
Goodman SSZ 14 SEER - page 9
9 COOLING PERFORMANCE DA T A SSZ140181A* EXP AN DE D PE RFORM ANCE DA T A C OOL I N G OP E R AT ION M O DE L : S S Z 1 40181A* / CA*F 3131*6A* + TX V / M BR800** - 1 O ut door Am bi e nt Te m pe r a ture 65 75 8 5 95 105 115 E nter i ng I ndo or Wet B u lb Te m pe r at ure I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 9 ...
-
Goodman SSZ 14 SEER - page 10
10 COOLING PERFORMANCE DA T A SSZ140181A* EXP AN DE D PERF O RM ANCE DATA C OOL I N G OP E R A T I ON M O DE L : S S Z 1 40181A* / CA*F 3131*6A* + TX V / M BR800 **-1 O ut door Am bi e nt Te m pe r at ure 65 75 8 5 95 105 115 E nter i ng I ndoor W e t B u lb Te m pe rat ur e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 ...
-
Goodman SSZ 14 SEER - page 11
11 COOLING PERFORMANCE DA T A SSZ140241A* EXPANDED PERF O RM ANCE DATA C OOL I N G OP E R ATIO N M O DE L : S S Z 14 0241A* / CA*F3 636*6A*+ T X V / M B R800**-1 O utdoor Am bient Te m pe rature 65 75 85 95 105 115 E nte ring I ndoor We t B ulb Te m pe rature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 77 15 96 ...
-
Goodman SSZ 14 SEER - page 12
12 COOLING PERFORMANCE DA T A SSZ140241A* EX PANDED P ERF ORM ANCE DAT A C OOLIN G OP E R ATI ON M ODEL: S S Z 140241A* / CA*F3636*6A*+ T X V / M BR800**-1 O utdoor Am bi e nt Tem pe r at ur e 65 75 85 95 105 115 E nte r ing I ndoor We t B ul b Te m pe ra tur e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 77 15 9 ...
-
Goodman SSZ 14 SEER - page 13
13 COOLING PERFORMANCE DA T A SSZ140301A* EXPA NDED PERFO RM ANC E DA T A C OOLI N G OP E R ATI ON M O D EL: S S Z 140301A* / CA*F 3642*6A*+T X V / M BR1600**- 1 O utdoo r Am bi e nt Te m pe ra ture 65 75 85 95 105 11 5 E nte r ing I ndoor We t B ul b Te m pe r at ur e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 ...
-
Goodman SSZ 14 SEER - page 14
14 COOLING PERFORMANCE DA T A SSZ140301A* EX PANDED PERF O RM A NCE DATA C O O L IN G O P E R A T IO N M O D EL: S S Z 140301A* / CA*F 3642*6A*+ TX V / M BR1600**-1 O utdoor Am bient Te m pe r ature 65 75 85 95 105 115 E nte r i ng Indoo r We t B ul b Te m pe r at ure I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 3 ...
-
Goodman SSZ 14 SEER - page 15
15 COOLING PERFORMANCE DA T A SSZ140361A* EXPA N DED PER FORM AN CE D ATA M ODEL: S S Z 140361A* / CA* F 4860*6A*+ TX V / M BR1600* *-1 O utdoor Am bie nt Te m pe r atur e 65 75 85 95 105 115 E n t e r in g In d o o r We t B u lb T e m p e r at u r e ID B Air flo w 59 63 67 71 59 63 67 71 59 6 3 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 M Bh 33.9 ...
-
Goodman SSZ 14 SEER - page 16
16 COOLING PERFORMANCE DA T A SSZ140361A* EX PANDED PE RF O RM ANCE DAT A C OOL I N G OP E R AT I ON M ODEL: S S Z 140361A* / CA* F 4860*6A*+ TX V / M BR1600* *-1 O utdoor Am bie nt Te m pe r atur e 65 75 85 95 105 115 E nter ing I nd oor Wet B u l b T e m pe r ature I D B * A i r f l o w 5 9 6 3 6 77 1 5 9 6 36 7 7 1 5 9 6 3 6 77 15 9 6 3 6 7 7 15 ...
-
Goodman SSZ 14 SEER - page 17
17 COOLING PERFORMANCE DA T A SSZ140421A* EXPAN DED PERFORMAN C E DATA M ODEL : S S Z140421A* / CA*F 4860*6 A*+ T X V / M BR 2000**-1 O utdoor Am bi e nt Te m pe rature 65 75 85 95 105 115 E nter ing I ndoo r We t B ulb Te m pe rature ID B A ir flo w 59 63 67 71 59 63 67 71 5 9 63 6 7 71 59 63 67 71 59 63 6 7 71 59 63 67 71 M Bh 39. 2 40.6 4 4.5 - ...
-
Goodman SSZ 14 SEER - page 18
18 COOLING PERFORMANCE DA T A SSZ140421A* EXPA NDED PER F O RM AN CE DA TA C OOL I N G OP E R AT I ON M O DE L : S S Z140421A* / CA*F 4860*6 A*+ TX V / M BR2000* *- 1 O u tdoor Am bi e nt Te m pe rature 65 75 85 95 105 115 E nter ing I ndoo r We t B ulb Te m pe rature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 3 ...
-
Goodman SSZ 14 SEER - page 19
19 COOLING PERFORMANCE DA T A SSZ140481A* EXPA ND ED PER FOR M AN CE D ATA C OOL I N G OP E R A TIO N M O DEL: S S Z 14 0481A* / CA*F 4860*6A* + T X V / M BR2000* *-1 O utdoor Am bi e nt Te m pe rature 65 75 85 95 105 115 E n t e r in g Ind o o r W e t B u lb T e m p e r at u r e I D B * A i r f l o w 5 96 3 6 7 7 1 5 9 6 36 77 15 9 6 3 6 77 15 9 6 ...
-
Goodman SSZ 14 SEER - page 20
20 COOLING PERFORMANCE DA T A SSZ140481A* EXPA ND ED PER FO RM AN CE D ATA C OOLIN G OP E R AT I O N M O DEL: S S Z 14 0481A* / CA*F 4860*6A* + T X V / M BR2000* *-1 O u tdoor Am bi e nt Te m pe rature 65 75 85 95 105 115 E n t e r in g Ind oo r We t B u lb Te m p e r atu r e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 ...
-
Goodman SSZ 14 SEER - page 21
21 COOLING PERFORMANCE DA T A SSZ140601A* EXP AND E D PERF O RM ANCE DAT A C OOL I N G OP E R ATION M O DE L: S S Z 140601 A* / CA*F4860*6 A*+ T X V / M BE2 000**- 1 O utd oor Am bi e nt Tem pe r a ture 65 75 8 5 95 105 115 E nter i ng I ndoor W e t B u lb T e m per at ur e ID B Air flow 59 63 67 71 59 63 6 7 71 59 63 67 71 59 63 67 71 59 63 67 71 ...
-
Goodman SSZ 14 SEER - page 22
22 COOLING PERFORMANCE DA T A SSZ140601A* EXP AND E D PERF ORM ANCE DAT A C OOL IN G OP E R ATION M ODEL: S S Z 140601A* / CA*F4860*6A *+ TX V / M BE 2000**- 1 O utdoo r Am bi e nt Tem pe ra ture 65 75 8 5 95 105 115 E nter i ng I ndoor W e t B ul b Te m pe ratu r e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 77 ...
-
Goodman SSZ 14 SEER - page 23
23 COOLING PERFORMANCE DA T A SSZ140361B* E XPA NDED PERF ORM A NCE DA TA CO O L ING O PE RAT I ON M OD E L : SS Z 140 361 B* / AR *F 374 316 B* Outdoor Am bi ent Tempera t u r e 65 75 85 95 105 1 15 E nte r i ng Indoor W e t Bul b Tempera t ur e I D B Ai rfl o w 5 9 63 6 7 7 1 59 63 67 71 5 9 63 67 71 59 63 6 7 71 59 6 3 6 7 71 59 63 67 7 1 MBh 3 ...
-
Goodman SSZ 14 SEER - page 24
24 COOLING PERFORMANCE DA T A SSZ140361B* EX PAN DE D P ER FO R MANC E D ATA CO OLI NG O P ERATION MOD EL : SSZ 14 0 361 B* / AR *F 374 316 B* O utdoor Am bi e nt Tempe r at u re 65 75 85 95 105 1 15 E nte r i ng Indoor W e t Bul b Te m perat ur e I D B * A i r f l o w 5 9 6 3 6 7 7 1 5 9 6 36 7 7 1 5 9 6 3 6 77 15 9 6 3 6 7 7 15 96 3 6 77 15 96 36 ...
-
Goodman SSZ 14 SEER - page 25
25 PERFORMANCE DA T A Outdoor Te m p. ° F . Tot a l Bt uh S e ns ible Bt uh La te n t Btu h Tot a l Wat t s 75° 36, 330 24, 713 11, 617 2, 662 80° 35, 898 24, 729 11, 169 2, 742 85° 35, 465 24, 738 10, 727 2, 822 90° 35, 033 24, 830 10, 203 2, 892 95° 34, 600 24, 912 9, 688 2, 963 100° 33 ,735 24, 749 8, 986 3, 023 105° 32 ,870 24, 563 8, 3 ...
-
Goodman SSZ 14 SEER - page 26
26 SPLIT SYSTEM HEA TING PERFORMANCE H i gh pre s s u r e i s meas u red at th e s uc ti on s erv i c e v al v e ( t he l a r ge r v a l v e). Low pre s s u re i s me as ure d at t he gau ge po r t c on nec t i on . C a l c ula tio ns ar e b as ed on n om i n al C FM a nd 70 ° F indo or dry bul b. A M PS = O ut do o r un i t am p s ( c o m p .+f a ...
-
Goodman SSZ 14 SEER - page 27
27 SPLIT SYSTEM HEA TING PERFORMANCE EXP ANDED PERFORMANCE DA T A H i gh pre s s u r e i s meas u red at th e s uc ti on s erv i c e v al v e ( t he l a r ge r v a l v e). Low pre s s u re i s me as ure d at t he gau ge po r t c on nec t i on . C a l c ula tio ns ar e b as ed on n om i n al C FM a nd 70 ° F indo or dry bul b. A M PS = O ut do o r ...
-
Goodman SSZ 14 SEER - page 28
28 SPLIT SYSTEM HEA TING PERFORMANCE H i gh pre s s u r e i s meas u red at th e s uc ti on s erv i c e v al v e ( t he l a r ge r v a l v e). Low pre s s u re i s me as ure d at t he gau ge po r t c on nec t i on . C a l c ula tio ns ar e b as ed on n om i n al C FM a nd 70 ° F indo or dry bul b. A M PS = O ut do o r un i t am p s ( c o m p .+f a ...
-
Goodman SSZ 14 SEER - page 29
29 SPLIT SYSTEM HEA TING PERFORMANCE EXP ANDED PERFORMANCE DA T A H i gh pre s s u r e i s meas u red at th e s uc ti on s erv i c e v al v e ( t he l a r ge r v a l v e). Low pre s s u re i s me as ure d at t he gau ge po r t c on nec t i on . C a l c ula tio ns ar e b as ed on n om i n al C FM a nd 70 ° F indo or dry bul b. A M PS = O ut do o r ...
-
Goodman SSZ 14 SEER - page 30
30 SPLIT SYSTEM HEA TING PERFORMANCE H i gh pre s s u r e i s meas u red at th e s uc ti on s erv i c e v al v e ( t he l a r ge r v a l v e). Low pre s s u re i s me as ure d at t he gau ge po r t c on nec t i on . C a l c ula tio ns ar e b as ed on n om i n al C FM a nd 70 ° F indo or dry bul b. A M PS = O ut do o r un i t am p s ( c o m p .+f a ...
-
Goodman SSZ 14 SEER - page 31
31 SPLIT SYSTEM HEA TING PERFORMANCE EXP ANDED PERFORMANCE DA T A H i gh pre s s u r e i s meas u red at th e s uc ti on s erv i c e v al v e ( t he l a r ge r v a l v e). Low pre s s u re i s me as ure d at t he gau ge po r t c on nec t i on . C a l c ula tio ns ar e b as ed on n om i n al C FM a nd 70 ° F indo or dry bul b. A M PS = O ut do o r ...
-
Goodman SSZ 14 SEER - page 32
32 SPLIT SYSTEM HEA TING PERFORMANCE H i gh pre s s u r e i s meas u red at th e s uc ti on s erv i c e v al v e ( t he l a r ge r v a l v e). Low pre s s u re i s me as ure d at t he gau ge po r t c on nec t i on . C a l c ula tio ns ar e b as ed on n om i n al C FM a nd 70 ° F indo or dry bul b. A M PS = O ut do o r un i t am p s ( c o m p .+f a ...
-
Goodman SSZ 14 SEER - page 33
33 SPLIT SYSTEM HEA TING PERFORMANCE EXP ANDED PERFORMANCE DA T A H i gh pre s s u r e i s meas u red at th e s uc ti on s erv i c e v al v e ( t he l a r ge r v a l v e). Low pre s s u re i s me as ure d at t he gau ge po r t c on nec t i on . C a l c ula tio ns ar e b as ed on n om i n al C FM a nd 70 ° F indo or dry bul b. A M PS = O ut do o r ...
-
Goodman SSZ 14 SEER - page 34
34 HEA TING SPECIFICA TIONS capacit y btuh c.o.p. 4.8 9.6 14.4 19.2 65 22.63 4.23 39.01 55.39 71.77 88.16 60 21.42 4.09 37.80 54.18 70.57 86.95 55 20.16 3.93 36.54 52.92 69.31 85.69 50 18.85 3.75 35.23 51.61 67.99 84.38 45 17.44 3.54 33.82 50.21 66.59 82.97 40 16.20 3.36 32.58 48.96 65.35 81.73 35 14.94 3.16 31.32 47.70 64.09 80.47 30 12.80 2.70 29 ...
-
Goodman SSZ 14 SEER - page 35
35 HEA TING SPECIFICA TIONS capaci t y btuh c. o.p . 4. 8 9. 6 14. 4 19 . 2 65 51.5 4 4 .44 67. 92 84. 30 1 00. 68 117 .07 60 48.7 9 4 .28 65. 17 8 1.55 9 7. 94 114. 32 55 45.9 2 4 .11 62. 30 7 8.68 9 5. 07 111. 45 50 42.9 3 3 .92 59. 31 7 5.69 9 2. 07 108. 46 45 39.7 3 3 .70 56. 11 7 2.49 8 8. 88 105. 26 40 36.9 0 3 .50 53. 28 6 9.66 8 6. 05 102. ...
-
Goodman SSZ 14 SEER - page 36
36 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Perfor- mance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a ...
-
Goodman SSZ 14 SEER - page 37
WIRING DIAGRAMS 37 HIGH VOL T AGE! DIS CONNECT ALL POWER BEFORE SERVICING OR INST A LLIN G THIS UNIT . MUL T IPLE POW ER SOURCES MA Y BE PRESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAMAGE, PERSONAL I NJURY OR DEA TH . Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. SSZ140[18,30,42-60 ...
-
Goodman SSZ 14 SEER - page 38
WIRING DIAGRAMS 38 HIGH VOL T AGE! DIS CONNECT ALL POWER BEFORE SERVICING OR INST A LLIN G THIS UNIT . MUL T IPLE POW ER SOURCES MA Y BE PRESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAMAGE, PERSONAL I NJURY OR DEA TH . USE N.E.C. CLASS 2 WI R E NOTES: 1) TO I NDO OR UNI T LO W VOLT A GE TE RM INAL BL OC K & INDO O R TH ERM OS T A T . 2) S ...
-
Goodman SSZ 14 SEER - page 39
WIRING DIAGRAMS 39 HIGH VOL T AGE! DIS CONNECT ALL POWER BEFORE SERVICING OR INST A LLIN G THIS UNIT . MUL T IPLE POW ER SOURCES MA Y BE PRESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAMAGE, PERSONAL I NJURY OR DEA TH . SSZ140[18,30,42-60]1AG , 241AK, 361AH SSZ140361B* US E N. E.C . CLA SS 2 WI RE NOTES: 1) T O IND OOR U NI T L OW VO LTAGE T E ...