  • Hubbell Electric Heater Company D - page 1

    OPERATING AND MAINTENANCE MANUAL FOR ELECTRIC STAINLESS STEEL HEATER FOR DEIONIZED (DI) WATER ELECTRIC HEATER COMPANY BASE MODEL “ D ” ...

  • Hubbell Electric Heater Company D - page 2

    2 HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET: http://www.hubbellheaters.com/ -- IMPORTANT -- Always reference the f ull model num ber and serial number when calling the factory. WARNING / CAUTION 1. Tank is to be complete ly fille d with water and a ll air is to be vente d bef ...

  • Hubbell Electric Heater Company D - page 3

    3 TABLE OF CONTENTS SECTION TITLE PAG E # I GENERAL DESCRI P TI ON AND CONSTRUCTION 5 II INSTAL LATI ON 9 III S C H E D U LE D M A IN TE NANC E AND OPERATION 12 I V TROUBL ES HOOTI NG 14 V SER VI CING AND REP LACEMENT OF PARTS 16 VI MI SCELL ANEOUS C HARTS AND FORMULAS 23 ...

  • Hubbell Electric Heater Company D - page 4

    4 ...

  • Hubbell Electric Heater Company D - page 5

    5 SECTION I - GENERAL DESCRIPTION AND CONST RUCTION GENERAL DESCRIPTION This booklet describes an electric heater designed specifically for use in deionized (DI ) water applications. The complete assembly consists of a type 316L stainless steel storage tank, ty pe 316L stainless steel imme rsion electr i c heating element(s), thermostat, safety rel ...

  • Hubbell Electric Heater Company D - page 6

    6 CONTROL THERMOS TAT The water heater is supplied with a single stage imme rsion thermostatic switch that i s installed and wi red at the factory. The thermostat can be adjusted through a range of 100° - 195° F, (an optional low range, 30° - 110° F, is available), and is adjustable with a flat tip screwdriver. Other thermostati c controls are ...

  • Hubbell Electric Heater Company D - page 7

    7 OUTER SHELL AND INSULATION The tank is encapsulated in 2-inches of high-density fiberglass insulation. The protective shell is constructed of galvaneel and is coated with a durable silver hammertone finish. OPTIONS The following optional features may be included in y our water heater. Reference included drawing specific to y our heater for furthe ...

  • Hubbell Electric Heater Company D - page 8

    8 Individually Fused Ele me nts To prevent the possibility of damage to c ontrol circuits a nd other eleme nts in case of electric al overloads, fuses may be supplied for each circuit. Two ty pes of fuses m ay be used; a type NON for voltages less than 250-volt or ty pe JJ S for voltage less than 600-volt. Ty pe JJ S Ty pe NON Digital Display A 1/1 ...

  • Hubbell Electric Heater Company D - page 9

    9 SECTION II – INSTALLATION WARNING / CAUTION DO NOT TURN ON THE ELECTRI C POWER SUPPL Y to this equipment until heate r is completely filled with water and all air ha s been released. I f the heater is NOT filled with water when the power is turned on, the heating elements will burn out. For protection against excessive pressures and temperature ...

  • Hubbell Electric Heater Company D - page 10

    10 Outlet to floor drain I nstall into provided tapping Manual Release Lev e r Temperature and Pressure Relief Valve 3. I nstall a relief valve overflow pipe to a nearby floor drain. CAUTION: No valve of any ty pe should be installed between the relief valve and tank or in the drain line. FILLING THE HEATER 1. Open the pressur e relief valve test l ...

  • Hubbell Electric Heater Company D - page 11

    11 THERMOSTAT SETTING (BULB AND CAPILLARY IMMERSION TYP E) The bulb and capillary type thermostat is immersed in a Ty pe 316L stainless steel well in the storage vessel. The full thermostat range is 100-240 ° F, but should not be operated over 195 ° F. There is a setting screw, which can be locked at a pa rticular se tting to prevent an opera tor ...

  • Hubbell Electric Heater Company D - page 12

    12 SECTION III - SCHEDULED MAINTE NANCE AND OPERATION WARNING / CAUTION Before performing any maintenance procedure, make certain power supply is OFF and cannot accidentally be turned on. MAINTENANCE AND OPERATION The water heater is automatic in its operation. I t will maintain a full tank of water at the temperature setting of the thermostat. The ...

  • Hubbell Electric Heater Company D - page 13

    13 ANNUAL INSPECTION 1. Flush tank as follows a. Shut off power supply . b. Close valve on hot water outlet piping. c. Open valve on drain piping. d. Cold water inlet line pressure will be strong enough to flush sediment from the bottom of the tank out through the drain. L et water run for 3-4 minutes. e. Close drain valve. f. Open hot water valve. ...

  • Hubbell Electric Heater Company D - page 14

    14 SECTION IV – TROUBLESHOOTING Symptom Probable Cause Corrective Action / Remedy Circuit breaker tripped at source. Reset circuit breaker. Blown fuse in transformer, if installed. Replace fuse. Circuit breaker at control cabinet tripped, if installe d. Reset circ uit breaker. Blown fuse in element fuse block, if installed. Replace fuse. High lim ...

  • Hubbell Electric Heater Company D - page 15

    15 Faulty thermostat. Che ck thermostat a djustment. Monitor thermostat as described i n S e c t i o n III, Q u a rt er l y I nspection. Replace if necessary . Heating e lement not working on all phases Check to see that heating element is working on all phases, by checking the resistance (ohms) value for each element and c omparing with the chart ...

  • Hubbell Electric Heater Company D - page 16

    16 SECTION V - SERVICING & REPLACEMENT OF PARTS WARNING / CAUTION Before servicing or replacing any part make sure to turn the power supply switch to the OF F position. SURFACE TEMPERATURE HIGH LIMIT CUT -OFF 1. Disconnect power from unit. 2. Remove access cover. 3. Disconnect the four (4) 14 gauge wires. Control Wires 4. Remove the two (2) mou ...

  • Hubbell Electric Heater Company D - page 17

    17 IMMERSION TEMPERATURE HIGH L IMIT CUT-OFF 1. Disconnect power from unit. 2. Remove access cover. 3. Remove high limit c over screw and cover. Cover Cover Screw Reset Switch 4. Disconnect the two (2) 14 gauge wires. Wires Capillary Tube 5. Remove capilla ry tube a nd bulb from thermowell 6. Remove two (2) mounting screws. Mounting Screws 7. Remov ...

  • Hubbell Electric Heater Company D - page 18

    18 HEATING ELEM ENT 1. Disconnect power from unit. 2. Shut off incoming water supply . 3. Attach hose to drain connection. 4. Lift manual release lever on relief valve to let air into sy stem or break union on outgoing water line. 5. Drain water from tank. 6. Disconnect the wires from the heating elem ent terminal s. 7. Remove the 3/8-16 nuts. Tank ...

  • Hubbell Electric Heater Company D - page 19

    19 ...

  • Hubbell Electric Heater Company D - page 20

    20 IMMERSION THE RMOSTAT 1. Disconnect power from unit. 2. Remove access cover and locate t hermostat. 3. Remove high limit c over screw and cover. Cover Cover Screw 4. Disconnect the two (2) 14 gauge wires. Wires Capillary Tube 5. Remove capilla ry tube a nd bulb from thermowell. 6. Remove two (2) mounting screws. Mounting Screws 7. Replace thermo ...

  • Hubbell Electric Heater Company D - page 21

    21 MAGNETIC CONTACTOR 1. Disconnect power from unit. 2. Disconnect line and load wires to contactor. 3. Disconnect two (2) 14 gaug e control circuit wires. Control Wires Line Wires Load Wires 4. Loosen two (2) holding screws and remove contactor. Mounting Screws (Bottom screw not shown) 5. Replace with new cont actor using reverse procedure. ...

  • Hubbell Electric Heater Company D - page 22

    22 RELIEF VALVE 1. Disconnect power from unit. 2. Shut off incoming water supply . 3. Lift test lever on relief valve to relieve pressure in tank. 4. Disconnect overflow piping. 5. Unscrew relief valve, remove assemb ly and repl ace with new one. 6. Connect overflow piping. 7. Turn on incoming water supply and check for leaks. 8. Turn safety switch ...

  • Hubbell Electric Heater Company D - page 23

    23 SECTION VI – MISCELL ANEOUS CHARTS AND FORMULAS ELEMENT CHA RT Power (kW) Resistance (Ohms) Element Part # 208V 240V 480V I mmersion L ength Hairpin 1 Φ 3 Φ DELTA 3 Φ WYE 50-38683SSN 5 6 8 13" 27.9 9.3 27.9 18.7 60-38683SSN 6 8 10 13" 21.6 7.2 21.6 14.5 70-38683SSN 8 10 12 13" 17.1 5.7 17.1 11.5 80-38683SSN 10 12 15 13" ...

  • Hubbell Electric Heater Company D - page 24

    24 TORQUE VALUE S BOLT SIZE 18-8 S/S IN. - LB S . BRASS IN. - LB S . SI LI CON BRONZE IN. - LB S . ALUMI NUM 2024-T4 IN. - LB S . 316 S/S IN. - LB S . MONEL IN. - LB S . 4-40 5.2 4.3 4.8 2.9 5.5 5.3 4-48 6.6 5.4 6.1 3.6 6.9 6.7 5-40 7.7 6.3 7.1 4.2 8.1 7.8 5-44 9.4 7.7 8.7 5.1 9.8 9.6 6-32 9.6 7.9 8.9 5.3 10.1 9.8 6-40 12.1 9.9 11.2 6.6 12.7 12.3 8 ...

Manufacturer Hubbell Electric Heater Company Category Electric Heater

Documents that we receive from a manufacturer of a Hubbell Electric Heater Company D can be divided into several groups. They are, among others:
- Hubbell Electric Heater Company technical drawings
- D manuals
- Hubbell Electric Heater Company product data sheets
- information booklets
- or energy labels Hubbell Electric Heater Company D
All of them are important, but the most important information from the point of view of use of the device are in the user manual Hubbell Electric Heater Company D.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Hubbell Electric Heater Company D, service manual, brief instructions and user manuals Hubbell Electric Heater Company D. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Hubbell Electric Heater Company D.

A complete manual for the device Hubbell Electric Heater Company D, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Hubbell Electric Heater Company D by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Hubbell Electric Heater Company D.

A complete Hubbell Electric Heater Company manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Hubbell Electric Heater Company D - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Hubbell Electric Heater Company D, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Hubbell Electric Heater Company D, that we can find in the current document
3. Tips how to use the basic functions of the device Hubbell Electric Heater Company D - which should help us in our first steps of using Hubbell Electric Heater Company D
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Hubbell Electric Heater Company D
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Hubbell Electric Heater Company D in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Hubbell Electric Heater Company D?

Use the form below

If you did not solve your problem by using a manual Hubbell Electric Heater Company D, ask a question using the form below. If a user had a similar problem with Hubbell Electric Heater Company D it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)