    SAFETY CONSIDERA TIONS Due t o sys tem pr essu re, moving par ts and electrical com ponent s, inst allati on an d ser vicing of air conditioning equipm ent can be haza rdous . Only quali fied, trai ned, s ervice personnel should install, repair , maintain or service this equipm ent. Obser ve all pr ecau tion s in the lite ratu re, on la bels and t ...

  • York B1CH180 - page 2

    Gene ral ... ...... ...... .... ...... ...... ...... .... ...... ...... .... ...... ...... .... ...... . 1 Inspe ction ...... .... ...... ...... .... ...... ...... .... ...... ...... ...... .... ...... ...... . 1 Referen ce ... ...... .... .... .... ...... .... .... .... ...... .... .... .... ...... .... .... .... .. 1 App rovals ..... .... .... .. ...

  • York B1CH180 - page 3

    LIMIT A TIONS These unit s must be inst alle d in ac corda nce w ith the followin g natio nal and lo cal sa f ety co de s: In U .S.A. : 1. National Electrica l Code ANSI/ NFP A No . 70. 2. Lo cal elec tr ic ut ility r equi rem en ts. In Ca nada: 1. C ur re nt Cana dian Elec tri cal C ode C S A C22. 1. 2. Lo cal elec tr ica l code s. Refer to the Un ...

  • York B1CH180 - page 4

    FIXED OUTDOOR AIR INT AKE D AMPER This d ampe r is ship ped ins ide t he r etur n air co mpar tm ent. It is completely assembled and ready for installation. A damper baffle ins ide t he hood is adju stab le t o pro vide v ariable amounts of outdoor air intake on units that are not provided with an economizer or a motorized damper option. Gask etin ...

  • York B1CH180 - page 5

    The i nter n al w ir ing h ar n ess fur nishe d wi th this unit is an inte gral par t of a ET L a nd CG A de si gn ce rtified u ni t. Field a lt er atio n to com ply wit h elec tri cal co des sh ould not be req uired . A fus ed di scon nect switch sh ould be fi eld p rovided for the unit . The switch must b e se parat e fro m all ot her c irc uits. ...

  • York B1CH180 - page 6

    Ref er to the T ypical Field Wiring Fi gure and to the a ppropriate unit wiring diagr am f or control circui t and p ow er w iring inf or matio n. OPTIONAL ELECTRIC HE A TERS The f actory install ed heat ers are w ired f or s ingle point pow er supply . P ow er suppl y need only be brough t into th e singl e point terminal b loc k and thermostat wi ...

  • York B1CH180 - page 7

    FIG. 6 - ENTHAL PY SET POI NT ADJU STME NT 511.06-N3Y Unitar y Products Group 7 ...

  • York B1CH180 - page 8

    T ABLE 4 - PHYSIC AL D A T A MODELS UNIT SIZE 15 T ON 20 TO N SUPPL Y AIR BLOWER CENT RIFUGAL B LO WER (Dia. x Wd. in.) 15 x 15 18 x 15 F AN MOT OR HP 5 7.5 INDOOR COIL RO WS DEEP 4 4 FINS PER INCH 13 13 F ACE ARE A (Sq. Ft.) 15.5 20.5 OUTD OOR FA N S (T wo P er Unit) PR OP ELLE R DIA. (in.) (Each) 30 30 F AN MO T OR HP ( Eac h) 1 1 NOM. CFM T O T ...

  • York B1CH180 - page 9

    DUCT CO VERS - Units are shi pped with the bottom duct openings covered. An accessory flange kit is a v ail- able f or connecti ng side ducts. For bottom duct appl ications: 1. Remov e the side panels from the supply and return ai r compar tm ents to gain access to the bot tom suppl y and retur n air duct covers . 2. Remove and discard the bottom d ...

  • York B1CH180 - page 10

    A B C D FRONT 4 POINT LO ADS FIG. 8 - FOUR AND SIX POINT LO A DS A E D B F C FRONT 6 POINT LO ADS UNIT 4 - POINT LOADS (LBS) TOT A L A B C D 180 2,190 513 535 583 559 240 2,390 514 538 684 654 NO TE: These we ig ht s a r e wi th econom iz er and 36kW el ec tric h ea t. UNIT 6 - PO INT LOADS (LBS) TOT A L A B C D E F 180 2,190 342 358 373 388 372 35 ...

  • York B1CH180 - page 11

    T ABLE 6 - SUPPL Y AI R BL O WER PER FO R MAN CE (1 5 T ON) 180 MBH - BO TT OM DUCT CONNECTIONS BLOWER SPEED , (RPM) MO T OR PULLEY (TURNS OPEN)* CFM 4500 5250 6000 6750 7200 ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW 208 V OL T AND ST AND ARD DRIVE 850 6.0** 0.9 2.4 2.2 0.7 3.0 2. 7 0.5 3.2 2.9 - - - - - - 870 5.5 1.0 2.5 2.3 0.8 3.1 2 ...

  • York B1CH180 - page 12

    T ABLE 7 - SUPP L Y AIR BLOWER PERFORMANCE (20 T ON) BLOWER SPEED , (RPM) MO TO R PULLEY (TURNS OPEN)* CFM 6000 7000 8000 9000 9400 ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW 208 V OL T AND ST AND ARD DRIVE 8 7 0 6 . 0 * * 0 . 4 2 . 1 1 . 8 0 . 1 2 . 3 2 . 0 --------- 9 0 0 5 . 0 0 . 8 3 . 2 2 . 7 0 . 5 3 . 5 2 . 9 0 . 2 3 . 8 3 . 2 --- ...

  • York B1CH180 - page 13

    T ABLE 8 - ST A TIC RESIST ANCES 1 T ABLE 9 - PO WER EXHA US T PERFORMANCE MO TO R SPEED ST A TIC RESI ST ANCE OF RETURN DUCTWORK, IWG 0.2 0.3 0.4 0.5 0.6 CFM KW CFM KW CFM KW CF M KW CFM KW HIGH* 5250 0.83 4500 0.85 4200 0. 88 3750 0.93 3000 0.99 MEDIUM 4900 0.77 3900 0.79 3500 0.82 2900 0.85 - - LOW 4400 0. 72 3700 0.74 3000 0.78 - - - - * F a ct ...

  • York B1CH180 - page 14

    MODEL POWER SUPPL Y COMPRESSORS OUTDOOR F AN MO TO RS (#1 & #2) SUPPL Y AIR BLOWER MO TO R MINIM UM CIRCUIT AMP A CITY (AMPS) MAXIMUM TIME DEL A Y FUSE SI ZE (AMPS) #1 #2 RLA LRA RLA LRA HP EA CH FLA EA CH HP FLA B1CH180 208/230-3-60 28.2 260 28. 2 260 1 4.1/4.2 5 14.4/15.4 86.1/87.3 110 460-3-60 14. 1 128 14.1 128 1 2.1 5 7.2 43.1 50 575-3-60 ...

  • York B1CH180 - page 15

    COOL ING SY STEM The un it ha s an air -c ooled cooling section and is f act or y- c har ged wit h Refr ig er ant- 2 2. The co mpres sor s are h er met ical ly se aled , inter n ally spr ung and b as e-mou nted with r ubbe r-in sula ted hold -down bolts. Compress ors ha v e inhere nt (inte rnal) protecti on. If t here is an abnormal tem pera ture r ...

  • York B1CH180 - page 16

    HEA T ANTICIP A T OR SETPOINTS It is im po rtant tha t t he an ti ci pa tor se tp oi nt be co rrect. T oo high of a set ting wi ll result in longe r heat cycles and a greate r temper ature sw ing in th e cond itione d space . Reducing t he value be low the corr ect setpoi nt will gi v e shor te r “ON ” cyc les and ma y result in the l oweri ng ...

  • York B1CH180 - page 17

    DEFROST SEQUENCE OF OPERA TION These heat pumps hav e a unique “ambient modified” time-temperature d ef r os t c on t ro l t ha t a u t om at i c al l y ad j us t s t o change s in t he outd oor temp erat ure. The def rost control will shorten the de frost in itia tion ti me perio ds abo v e 35 ° F and will extend the defrost init iation time ...

  • York B1CH180 - page 18

    NORMAL MAINTENANCE CA UTION: P rior to any of th e f o llowing ma intenanc e proce- dures , shut off all el ectric po wer t o the un it to pre v ent pe rso na l in ju r y . FIL T ERS - In spec t on ce a mo nth. Repla ce di spos able or cl ean permanent ty pe as n ecessary . DO NO T replace permanent type wi th di spos able. The dim ensi onal size o ...

  • York B1CH180 - page 19

    511.06-N3Y Unitar y Products Group 19 ...

  • York B1CH180 - page 20

    Code: SBY 51 1.06 -N3Y 5005 Y or k Dr ive, Nor man , OK 7306 9 Subje ct to ch ange wit hout n otice. Prin ted in U.S .A Cop yright  by Y ork International Corporation 200 0. All Rights Reserved. ...

Manufacturer York Category Heat Pump

Documents that we receive from a manufacturer of a York B1CH180 can be divided into several groups. They are, among others:
- York technical drawings
- B1CH180 manuals
- York product data sheets
- information booklets
- or energy labels York B1CH180
All of them are important, but the most important information from the point of view of use of the device are in the user manual York B1CH180.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals York B1CH180, service manual, brief instructions and user manuals York B1CH180. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product York B1CH180.

Similar manuals

A complete manual for the device York B1CH180, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use York B1CH180 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of York B1CH180.

A complete York manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual York B1CH180 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the York B1CH180, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the York B1CH180, that we can find in the current document
3. Tips how to use the basic functions of the device York B1CH180 - which should help us in our first steps of using York B1CH180
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with York B1CH180
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of York B1CH180 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning York B1CH180?

Use the form below

If you did not solve your problem by using a manual York B1CH180, ask a question using the form below. If a user had a similar problem with York B1CH180 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)