Manual Emerson Process Management 00809-0700-4530

96 pages 5.63 mb
Download

Go to site of 96

Summary
  • Emerson Process Management 00809-0700-4530 - page 1

    Reference Manual 00809-0700-4530, Rev AA September 2013 R osemount Proc ess Radar in P o wer Applications Best Prac tices User Guide ...

  • Emerson Process Management 00809-0700-4530 - page 2

    ...

  • Emerson Process Management 00809-0700-4530 - page 3

    iii Reference Manu al 00809-0700-4530, Rev AA September 2013 R osemount Proce ss Radar in Po w er Applications Best Prac tice s User Guide The products described in this document are NO T rated f or use in nuc lear-qualified applications. Using non-nuclear qualified product s in applications t hat require nuclear-qu alified hard ware or products ma ...

  • Emerson Process Management 00809-0700-4530 - page 4

    iv Reference Manu al 00809-0700-4530, Rev AA September 2013 ...

  • Emerson Process Management 00809-0700-4530 - page 5

    i Reference Manu al 00809-0700-4530, Rev AA Table of Contents September 2013 Ta b l e o f C o n t e n t s 1 Section 1: Power ap plications 1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2 Boile r systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 00809-0700-4530 - page 6

    ii Reference Manu al 00809-0700-4530, Rev AA Table of Contents September 2013 T able of Cont ents 3.3.2 Changing the Upper Null Zone (UNZ) . . . . . . . . . . . . . . . . . . . . . . . . . . 38 3.3.3 Measure and learn function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 3.3.4 Vapor compensation . . . . . . . . . . . . . . ...

  • Emerson Process Management 00809-0700-4530 - page 7

    iii Reference Manu al 00809-0700-4530, Rev AA Table of Contents September 2013 Ta b l e o f C o n t e n t s 5.5.6 R econciling r adar with ot her level mea surements . . . . . . . . . . . . . . . 79 A Appendix A: Checklists A.1 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 A ...

  • Emerson Process Management 00809-0700-4530 - page 8

    iv Reference Manu al 00809-0700-4530, Rev AA Table of Contents September 2013 T able of Cont ents ...

  • Emerson Process Management 00809-0700-4530 - page 9

    1 Reference Manu al 00809-0700-4530, Rev AA Section 1: Power Applications September 2013 Pow er applica tions Sec t ion 1 Po we r applications Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Boiler systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 00809-0700-4530 - page 10

    2 Reference Manu al 00809-0700-4530, Rev AA Section 1: Power Applications September 2013 Powe r applications 1.2 Boiler systems For boile r systems, rad ar transmitters are co mmonly used f or the following applications:  Boile r drum leve l cont rol  High pressu re feedwater heater  Low pres sure feedwate r heat er  Ste am separat or s ...

  • Emerson Process Management 00809-0700-4530 - page 11

    3 Reference Manu al 00809-0700-4530, Rev AA Section 1: Power Applications September 2013 Pow er applica tions 1.6 F uel supply For fue l supply , radar transmitt ers are comm only us ed for the foll owing applicatio ns:  Fu el o i l s to r a g e  Natural g as se parators  Coal cr usher hopper  Coal mill supply silo (bunke r)  Coal st ...

  • Emerson Process Management 00809-0700-4530 - page 12

    4 Reference Manu al 00809-0700-4530, Rev AA Section 1: Power Applications September 2013 Powe r applications 1.10 Miscellaneous For misce llaneous, radar transmitters are commonly used for the following applications:  Sumps (drain pit for waste oil, c ondensate)  Wat e r wa s h t a n k s  Fir e wa te r tanks  Lake or pond level ...

  • Emerson Process Management 00809-0700-4530 - page 13

    5 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerations September 2013 Installation conside rations Sec t ion 2 Installa tion conside rations Safety m essages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Introduction . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 00809-0700-4530 - page 14

    6 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerat ions September 2013 Installation considerations 2.2 Introduc tion In addition to select ing the appropriate radar le vel transmitter , mechanical inst allation is one of the most critical ste ps of the commis sioning pr ocedure. When done c orrec tly , the subsequen t tr ...

  • Emerson Process Management 00809-0700-4530 - page 15

    7 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerations September 2013 Installation conside rations Apar t from the addition al cost of inst allati on, th ere are some sizing and se lec tion criteri a for the radar g auges that m ust be c onsidered. This document outlines those conside rations. GWR is the pref erred techn ...

  • Emerson Process Management 00809-0700-4530 - page 16

    8 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerat ions September 2013 Installation considerations Any de nsit y-based leve l measure ment devic e will need compensa tion to disce rn the ac tual lev el from the density-associa ted errors. Algori thms have bee n deve loped to make this compensation as seamless as possible ...

  • Emerson Process Management 00809-0700-4530 - page 17

    9 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerations September 2013 Installation conside rations Heavy vibrations Heavy vibratio ns from pumps can cause a noisy signal from mechanical-based tec hn iques. Advantages of GWR ov er other techniques Since GWR meas urement de vices are complet ely independe nt of density , t ...

  • Emerson Process Management 00809-0700-4530 - page 18

    10 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerat ions September 2013 Installation considerations DV C requires a sp ecial probe wi th a built-in re flector for me asure ment o f the dielectric of th e steam. DV C works by using a target a t a fixed distance . With this target, the vapor dielec tric is mea su red conti ...

  • Emerson Process Management 00809-0700-4530 - page 19

    11 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerations September 2013 Installation conside rations Ro semount design advantages Ro semoun t 5300 GWR extreme te mperat ure and pressur e probes are de signed to prev en t leakage and pe r form reli ably when exposed to extreme proces s conditions for extended pe riods of t ...

  • Emerson Process Management 00809-0700-4530 - page 20

    12 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerat ions September 2013 Installation considerations D VC installation be st prac tices The GWR should be mounted in a bypa ss chambe r with flanges appropria tely siz ed for the pressure and te mperature of the applica tion. A 3 or 4 inch (75 or 100 mm) diamet er cha mber i ...

  • Emerson Process Management 00809-0700-4530 - page 21

    13 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerations September 2013 Installation conside rations For high pressure ste am applications above 400 psi (28 bar), it is also impor t ant to limit the ove rall dist ance from the flange to w here the level is co ntrolled (indicated by A in Figur e 2-6 ), since the high pres ...

  • Emerson Process Management 00809-0700-4530 - page 22

    14 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerat ions September 2013 Installation considerations How to c hoose reflector length The long reflector , 20 in. (500 mm), has the best acc urac y and is recommen ded for all chambe rs where the dimensions o f the chamber allo w for it. If the distanc e from the flange to th ...

  • Emerson Process Management 00809-0700-4530 - page 23

    15 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerations September 2013 Installation conside rations to ce nte r the probe. Ch ambers large r than 6 in. (150 mm) can be u sed, but provide no advantages f or the radar me asureme nt (1) . When specif ying a chamber , it is also imp or ta nt to consider the physical we ight ...

  • Emerson Process Management 00809-0700-4530 - page 24

    16 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerat ions September 2013 Installation considerations Probe length is between 3 f t (1 m) and 10 f t (3 m) (1) : Use either a rigid single or a flexible single probe with weight and a cen tering disk. The rigid single is easie r to cle an and has smalle r transition zones, wh ...

  • Emerson Process Management 00809-0700-4530 - page 25

    17 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerations September 2013 Installation conside rations T able 2-4. T ransition zones for the Rosemo unt 3300 S eries inst alled in met allic pi pes T able 2-5. T ransition zones in chambers for the Rosemount 5300 Series installed in metallic pipes Figure 2-8. Measuring zones i ...

  • Emerson Process Management 00809-0700-4530 - page 26

    18 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerat ions September 2013 Installation considerations An example usin g the guid elines for fabricatio n of cages (see T able 2-5 on page 17 for transition z ones). Assuming leve l measure ment of oil (worst-ca se): A > 6.3 in. (16 cm) and C > 9.8 i n. (25 cm) for a rig ...

  • Emerson Process Management 00809-0700-4530 - page 27

    19 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerations September 2013 Installation conside rations 2.3.3 Ch amber moun ting Chambers should be mounted onto the tank to correspond with the desired me asureme nt and area of c ontrol. This is of ten a small por tion of the overall height. F or f ur ther informa tion o n ch ...

  • Emerson Process Management 00809-0700-4530 - page 28

    20 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerat ions September 2013 Installation considerations Product Data Sheet f or more inf ormation. The ambient t empera ture is affected by the pr ocess temperatu re. Figure 2-11 shows the ambient te mperature vs. process t emperature . Figure 2-11. Ambient t emperat ure vs. pr ...

  • Emerson Process Management 00809-0700-4530 - page 29

    21 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerations September 2013 Installation conside rations Figure 2-12. Ro semount 5300 Series with remote housing When the re mote housing is u sed togethe r with the Ro semount 5300 Se ries, there m ay be a limit on meas uring range and a decrea se in ac curacy . This is beca us ...

  • Emerson Process Management 00809-0700-4530 - page 30

    22 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerat ions September 2013 Installation considerations 2.3.7 Insula tion The chamber should always be insulated in hot applications to prevent pe r sonal injuries and reduce the amount of ener gy needed for hea ting. It is of ten an advantage, and so metimes even required, f o ...

  • Emerson Process Management 00809-0700-4530 - page 31

    23 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerations September 2013 Installation conside rations For the R ose mount GWR tr ansmitte rs:  Do not mount clo se to inlet pipes and ensure th at the probe does not c ome in contact with the nozzle (X)  If there is a ch ance that the probe ma y come in con t ac t with ...

  • Emerson Process Management 00809-0700-4530 - page 32

    24 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerat ions September 2013 Installation considerations The Rose mount 5400 Series non-contac ting radar transmitters should be in stalled i n locations with a clear and unobstruc ted view of the l eve l sur face (A) for optimum performance :  Filling in lets creating turbul ...

  • Emerson Process Management 00809-0700-4530 - page 33

    25 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerations September 2013 Installation conside rations 2.4.2 Nozzle c onside rations Depending on the selectio n of transmitter model and probe/ante nna, special considera tions may h ave t o be taken becau se of the nozzle . Ro semount GWR transmitter s The coaxia l probe sig ...

  • Emerson Process Management 00809-0700-4530 - page 34

    26 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerat ions September 2013 Installation considerations Ro semount 5400 Series non-co nt ac ting radar transmitter  Ro semount 5402 with c one ante nna The antenn a can be used in nozzles equal to or l arger than 2.2 in (55 mm). It can be recessed in sm oot h noz zl es up to ...

  • Emerson Process Management 00809-0700-4530 - page 35

    27 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerations September 2013 Installation conside rations Figure 2-19. R osemount 5401 with cone ante nna If the signal is dampened by hea v y condensation at the ante nna, it of ten helps to insulat e the nozzle . This is to minimize the te mperature dis parit y bet ween the int ...

  • Emerson Process Management 00809-0700-4530 - page 36

    28 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerat ions September 2013 Installation considerations 2.5 Solids measurement Solids generally provide a difficult measuring en vironment with low dielec tric produ ct s in tall tanks, wh ere pull forc es may act on the probe, and dust, st eam, or risk of co ating are of ten p ...

  • Emerson Process Management 00809-0700-4530 - page 37

    29 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerations September 2013 Installation conside rations  Probe installation should occur when the silo is empt y , and the probe should be regularly insp ec ted f or damage .  Av oid 10-in. (250 mm) / DN250 or large r diamete r nozzles, es pecially in appli cations with l ...

  • Emerson Process Management 00809-0700-4530 - page 38

    30 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerat ions September 2013 Installation considerations  When probes are anchore d, the forces are t wo to ten times gre ater than with free-hanging probes. T o preve nt an ex tremely high tensile load whe n fixing the probe, and to reduce the risk of probe bre akage, the pr ...

  • Emerson Process Management 00809-0700-4530 - page 39

    31 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerations September 2013 Installation conside rations 2.5.2 R ose mount 5600 Se ries The Ro semoun t 5600 Series can be us ed in tanks up to 165 f t (50 m). As solids gene rally provi de a difficult mea suring envir on ment an d t he si gna l l evels ar e of ten ver y low , i ...

  • Emerson Process Management 00809-0700-4530 - page 40

    32 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerat ions September 2013 Installation considerations Step 2: ta nk co nn ec ti on Figure 2-28. Ro semount 5600 Series with cone/parabolic ant enna HINT: If the signal is dampened by hea v y condensation at the ante nna, it of ten helps to insulat e th e nozzle . This minimi ...

  • Emerson Process Management 00809-0700-4530 - page 41

    33 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerations September 2013 Installation conside rations Ste p 4: inclination of antenna NOTE: T oo grea t of an angle can creat e problems in de tecting sur face echo at the bottom region. The angle of the slope diffe rs during filling and em pt yin g. Th erefor e, mo nito r t ...

  • Emerson Process Management 00809-0700-4530 - page 42

    34 Reference Manu al 00809-0700-4530, Rev AA Section 2: Installation Considerat ions September 2013 Installation considerations Step 5: soft ware settings  Note that solids applications in general are diff icult, therefore Emerson Pro cess Manage ment ha s developed a spec ial solids mode in the radar database . This means that the radar da taba ...

  • Emerson Process Management 00809-0700-4530 - page 43

    35 Reference Manu al 00809-0700-4530, Rev AA Section 3: Commissioning September 2013 Commis sioning Sec t ion 3 Commis sioning Safety m essages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 00809-0700-4530 - page 44

    36 Reference Manu al 00809-0700-4530, Rev AA Section 3: Commissionin g September 2013 Commis sioning 3.2 Introduc tion The transmitter installa tion should be carr ied out as described in the Qu ick Installation Guide that is enc losed with ever y transmi tter . Ev en though the tran smitter ma y be inst alled on the benc h, it must be co nfigured ...

  • Emerson Process Management 00809-0700-4530 - page 45

    37 Reference Manu al 00809-0700-4530, Rev AA Section 3: Commissioning September 2013 Commis sioning T able 3-3. Solids measurement 3.3.1 T rim Ne ar Zone (GWR transmitte rs) The Ro semoun t 3300 and 5300 Series are equipped with a fi rmware functionalit y that minimiz es the Uppe r T ransition Z one based on actual moun ting condit ions. T rimming ...

  • Emerson Process Management 00809-0700-4530 - page 46

    38 Reference Manu al 00809-0700-4530, Rev AA Section 3: Commissionin g September 2013 Commis sioning Figure 3-1. Echo curve before and after TNZ NOTE : The eff ec t of TNZ is only visible whe n an e cho is present in the near zone . 3.3.2 Ch anging the Upper Null Z one (UNZ) Meas ur ement s ar e n ot per fo rm ed w it hi n th e Up per Null Zone (UN ...

  • Emerson Process Management 00809-0700-4530 - page 47

    39 Reference Manu al 00809-0700-4530, Rev AA Section 3: Commissioning September 2013 Commis sioning  Ro semoun t 3300 Series Radar C onfiguration T ool > Se tup > T ank Con fig tab (click Rec ei ve P ag e ) > Upper Null Zon e (ent er desired value in fie ld and click Send Page ) 3.3.3 Mea sure and le arn f unc tion The Ro semoun t 5300 ...

  • Emerson Process Management 00809-0700-4530 - page 48

    40 Reference Manu al 00809-0700-4530, Rev AA Section 3: Commissionin g September 2013 Commis sioning of a R osemoun t 5300 Series le vel transmitte r can be configured f or static compe nsation of vapor by manu all y en tering the dielectric cons tant of va por , to comp ensate fo r th e er ror induced b y the saturated st eam. F or applications wi ...

  • Emerson Process Management 00809-0700-4530 - page 49

    41 Reference Manu al 00809-0700-4530, Rev AA Section 3: Commissioning September 2013 Commis sioning dynamica lly used to c ompensa te for c hanges in vapor die lec tric constant and elimina tes the ne e d to d o any co m p ens a ti o n i n t h e co nt r ol s y s t em. T o check if the DV C function is suppor ted: RRM > Device > P roper ties ( ...

  • Emerson Process Management 00809-0700-4530 - page 50

    42 Reference Manu al 00809-0700-4530, Rev AA Section 3: Commissionin g September 2013 Commis sioning Installation setup It is important tha t the vapor compe nsation function is calibr ated afte r installation an d af te r the basic con figuration is complete . The basic configuration includes setup of the unit in a chamber installation and th e us ...

  • Emerson Process Management 00809-0700-4530 - page 51

    43 Reference Manu al 00809-0700-4530, Rev AA Section 3: Commissioning September 2013 Commis sioning 3.3.5 R emo te hou sing (GWR transmitters) If a remo te housing is added to a unit af ter th e D VC calcul ation is done, the unit needs to be recalibrated. When using re mote housing, the remot e connec tion length should be configured. If the remot ...

  • Emerson Process Management 00809-0700-4530 - page 52

    44 Reference Manu al 00809-0700-4530, Rev AA Section 3: Commissionin g September 2013 Commis sioning Option 1 - Matching the output of +/- devia tio n from the nominal refere nce point Choos e leve l as primary variable t o show on the local displ ay . For example , if a GWR is repl acing a 14 in. (356 mm) displ acer , the span woul d be -7 in. (-1 ...

  • Emerson Process Management 00809-0700-4530 - page 53

    45 Reference Manu al 00809-0700-4530, Rev AA Section 3: Commissioning September 2013 Commis sioning Opt ion 2 - Setting LR V to 0 in. (0 mm) at the lowe r tap The tank height should be set to the distance to the zero leve l point. In this example, it is the lower side-pipe , located 19 in. (483 mm) below the ref erence point. Output range values wi ...

  • Emerson Process Management 00809-0700-4530 - page 54

    46 Reference Manu al 00809-0700-4530, Rev AA Section 3: Commissionin g September 2013 Commis sioning Option 3 - Ma tching displace r output The t an k h eigh t ( referen ce gau ge heig ht ) a nd th e probe length should be set to the same value. The LRV is th e distance from the bott om of the probe to the lower tap . The URV is the LRV plus the di ...

  • Emerson Process Management 00809-0700-4530 - page 55

    47 Reference Manu al 00809-0700-4530, Rev AA Section 3: Commissioning September 2013 Commis sioning 3.3.7 Signal Qu alit y Metrics (R os e mount 5300 and 5400 Se ries) Signal Quality Metrics (SQM) indicat es the sur face signal in tegrit y compared to the noise. It can be used to schedule main tenanc e to clean the pr obe or det ec t and monitor tu ...

  • Emerson Process Management 00809-0700-4530 - page 56

    48 Reference Manu al 00809-0700-4530, Rev AA Section 3: Commissionin g September 2013 Commis sioning 3.3.9 Probe End Projection (Ro s emo u nt 53 0 0 S er i es so l i ds meas u rem ent ) Probe End Projec tion (PEP) handles long measurin g ranges on media with lo w dielectrics, such as soli ds. If the signal is not re flec ted at the surface , the R ...

  • Emerson Process Management 00809-0700-4530 - page 57

    49 Reference Manu al 00809-0700-4530, Rev AA Section 3: Commissioning September 2013 Commis sioning 3.3.10 St ore backup and v eri fication file s As the last st ep of the c ommissioning pro cedure, it is recomme nded that bo th the transmitte r settings and the echo cur ve be stored. F or example, these can be u sed for sub sequent transmitte r ve ...

  • Emerson Process Management 00809-0700-4530 - page 58

    50 Reference Manu al 00809-0700-4530, Rev AA Section 3: Commissionin g September 2013 Commis sioning Figure 3-11. The d ifference bet ween the a mplitude of sur face peaks in the case of simulated an d ac tual liqui d levels Example A Ro semount 5300 Se ries transmitte r mounted in a ch amber can be v erified by c onnec ting fl ex ib le t ra nsp ar ...

  • Emerson Process Management 00809-0700-4530 - page 59

    51 Reference Manu al 00809-0700-4530, Rev AA Section 4: Measurement validation September 2013 Meas ur ement v al idat io n Sec tion 4 Me asure men t valid ation Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Introduction . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 00809-0700-4530 - page 60

    52 Reference Ma nual 00809-0700-4530, Rev AA Section 4: Measurement va lidation September 2013 Measurement valid atio n 4.2 Introduc tion In this sec tio n, the steps of me asurement validation at operating c ondit ions are descr ibed. The mea surement valida tion should be per formed un der ope rating co nditions, and the actual liquid must be use ...

  • Emerson Process Management 00809-0700-4530 - page 61

    53 Reference Manu al 00809-0700-4530, Rev AA Section 4: Measurement validation September 2013 Meas ur ement v al idat io n Figure 4-1. The verification of m easurement data using a sight-glass St ep 2: analog output signal validation Note th at this section re fers to 4-20 mA/HAR T units only . Ensure that the loop h as bee n set to manual mode in ...

  • Emerson Process Management 00809-0700-4530 - page 62

    54 Reference Ma nual 00809-0700-4530, Rev AA Section 4: Measurement va lidation September 2013 Measurement valid atio n Figure 4-3. Loop test f or Analog Out 1 Step 3: e ch o- cu r ve ve ri f ic a tion at operating conditions At normal opera tin g conditions, download and review the echo-cur ve acc ording to the foll owing ste ps: 1. Check referenc ...

  • Emerson Process Management 00809-0700-4530 - page 63

    55 Reference Manu al 00809-0700-4530, Rev AA Section 4: Measurement validation September 2013 Meas ur ement v al idat io n Figure 4-4. GWR transmitter peak amplit udes and threshold settings Figure 4-5. Rosemount 5300 Series with D V C, reference reflector peak and threshold settings St ep 4: transmitter diagnostics re view The trans mitter contain ...

  • Emerson Process Management 00809-0700-4530 - page 64

    56 Reference Ma nual 00809-0700-4530, Rev AA Section 4: Measurement va lidation September 2013 Measurement valid atio n Figure 4-6. Diagnostics St ep 5: mo nitor leve l while em pt ying During St ep 1, the curren t level (and/or interface) re ading was ve rified. This step will v erif y that the transmitter c orrec tly tracks the sur face during th ...

  • Emerson Process Management 00809-0700-4530 - page 65

    57 Reference Manu al 00809-0700-4530, Rev AA Section 4: Measurement validation September 2013 Meas ur ement v al idat io n Figure 4-8. Emptying a tank o r chamber Finally , review the level trend f or accurac y. Step 6: e ch o- cu r ve ve ri f ic at i on wi t h e m pt y t an k When the tank or chamber is emp t y , download and review the echo-curve ...

  • Emerson Process Management 00809-0700-4530 - page 66

    58 Reference Ma nual 00809-0700-4530, Rev AA Section 4: Measurement va lidation September 2013 Measurement valid atio n 4.4 Operation and maintenanc e - proof testing f or SIS The Ro semount 5300 Series Prior-Us e option must be t ested at regula r intervals to con firm that the ov erfill and emp t y tank protection function result in th e desired ...

  • Emerson Process Management 00809-0700-4530 - page 67

    59 Reference Manu al 00809-0700-4530, Rev AA Section 4: Measurement validation September 2013 Meas ur ement v al idat io n 5. Pe r form a two-point calibra tion check o f the transmitte r by applying the le vel t o t wo points on the probe within the measuring range (1) . V erif y that the current output corres ponds to the leve l input values usin ...

  • Emerson Process Management 00809-0700-4530 - page 68

    60 Reference Ma nual 00809-0700-4530, Rev AA Section 4: Measurement va lidation September 2013 Measurement valid atio n ...

  • Emerson Process Management 00809-0700-4530 - page 69

    61 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s Sec tion 5 T roubleshoo ting procedure s Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Introduction . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 00809-0700-4530 - page 70

    62 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s 5.2 Introduc tion This sec tion provides information on identifyin g the most common problems found with radar level transmitters. A t ypica l workflow may look like this (local restr ict ions and va riations may apply): 1. ...

  • Emerson Process Management 00809-0700-4530 - page 71

    63 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s 5.3 Diagnostics Basic rules and philosophy about the diagnostic messages is that the transmitter will ge nerate an alarm curren t if the diagnostic message indica ted is a "device error" or a "lost measure me ...

  • Emerson Process Management 00809-0700-4530 - page 72

    64 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s 5.4 Echo cur ve analysis The echo cur ve represen ts the t ank, as seen by the radar tr ansmitter . Each peak corresponds to a reflection of the radar signal - the sur face of the level, an obstacle, or something else. By v ...

  • Emerson Process Management 00809-0700-4530 - page 73

    65 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s 5.4.1 E cho cur v e constitue nts Figure 5-2. Echo curve presentation in RRM Amplitude Distance Refe re nce peak Surface peak UNZ Surface threshold Refe re nce p eak Surface peak Amplitude Distance As pr esented in RRM ...

  • Emerson Process Management 00809-0700-4530 - page 74

    66 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s Figure 5-3. Rosemount 5300 Series with D V C - Echo curve presentation in RRM In a t ypica l measureme nt situation, the following peaks appear in the echo cur ve : Reference peak. This ref erenc e pulse is caused by the tr ...

  • Emerson Process Management 00809-0700-4530 - page 75

    67 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s T able 5-1. T ypical peak amplitudes for the Ros emount 5300 Series with a single lead probe in 4 in. (100 mm) chamber s T able 5-2. T ypical reference pulse amplitudes for the Ro semount 5300 Series with different probe t ...

  • Emerson Process Management 00809-0700-4530 - page 76

    68 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s R osemount 5400 and 5600 Series V arious amplitude thresholds are u sed to filter out unw anted signals and pi ck up the diffe rent peaks. The transmitter us es certain criteri a to select which pe aks correspond t o the ac ...

  • Emerson Process Management 00809-0700-4530 - page 77

    69 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s 5.4.2 R ose mount GWR transmitt er threshold se tting s R ecommend ations for the R osemount 3300 and 5300 Se ries: 1. Use the aut omatic threshold settings and e nsure that the die lec tric constants of the vapor and produ ...

  • Emerson Process Management 00809-0700-4530 - page 78

    70 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s Figure 5-7. Sur face peak is below the sur face threshold Figure 5-8. Surface peak is above the surface threshold Amplitude Distance Surface thres hold (A TC) Rose mount 5301 The sur face peak is un detec ted because it is ...

  • Emerson Process Management 00809-0700-4530 - page 79

    71 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s Disturbance misinterpret ed as leve l In this example, the transmitter incorrectl y identifies the re flec tio n from an inlet- pipe as the product sur face , because it is the firs t peak above the sur face threshold, see ...

  • Emerson Process Management 00809-0700-4530 - page 80

    72 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s Incorrect reading due to be nt probe or probe contac ting the nozzle w all A bent, twisted probe (in the case of flexible prob es) in c ontac t with metal crea tes a strong echo that the mea surement will lock onto , see Fi ...

  • Emerson Process Management 00809-0700-4530 - page 81

    73 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s Strong ant enna echo and w eak sur face ec ho W ate r conde nsation in a c one anten na or build-up on a proc ess se al window will cre ate a stro ng echo from the an tenna and a we ak sur face echo . Examine installation a ...

  • Emerson Process Management 00809-0700-4530 - page 82

    74 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s Figure 5-14. Installation error - le vel/inte r face r ange is not co vered adequately The connections bet ween the ve ssel and the c h amber mu st allow for flow of the product. Clogging should be a voided. Figure 5-15. In ...

  • Emerson Process Management 00809-0700-4530 - page 83

    75 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s R osemount 5600 Series solids measurement In a nozzle installation, review th e installation considerations. For solids mea surement with we ak sur face echo , mechani cal installation i s es peci ally import ant, sinc e no ...

  • Emerson Process Management 00809-0700-4530 - page 84

    76 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s 5.5.3 Probe End Pulse offse t (only rele vant f or PEP) An offset of the probe end pulse is n ormal if there is produ ct in the vessel. Howeve r , it can al so be caused b y mis-configured pr obe length. Ens ure that c orre ...

  • Emerson Process Management 00809-0700-4530 - page 85

    77 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s Figure 5-20. Analog output settings - range values and reference points The analog out put depe nds on how the range valu es are set, see Figur e 5-21 for ex am pl es . Figure 5-21. Analog output settings Upper Reference Po ...

  • Emerson Process Management 00809-0700-4530 - page 86

    78 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s 5.5.5 Incorrect static vapor compe nsation Specific high-te mperature and high-pressure a pplications, lik e those with saturated steam vapors, require that a c ompensated value be e n tered f or the vapor die lec tric cons ...

  • Emerson Process Management 00809-0700-4530 - page 87

    79 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s 5.5.6 R ec onciling radar with o ther lev e l mea sureme nts When c omparing lev el me asurem ents to e ach othe r , they often do no t matc h up as expected. There are numerou s reasons f or this with the mo st promine nt ...

  • Emerson Process Management 00809-0700-4530 - page 88

    80 Reference Manu al 00809-0700-4530, Rev AA Section 5: Troubleshooting Procedures September 2013 T roubleshooting procedure s Po tenti al problems inc lude:  Fluid density changes: sourc e, grade , produc t and temperature a ffect the density of the fluid, and th ere by the level output.  In case of a wet le g , is it completely filled? Or , ...

  • Emerson Process Management 00809-0700-4530 - page 89

    81 Reference Manu al 00809-0700-4530, Rev AA Appendix A: Checklists September 2013 Checklists Appe ndix A Checklists Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Checklists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 00809-0700-4530 - page 90

    82 Reference Manu al 00809-0700-4530, Rev AA Appendix A: Checkl ists September 2013 Checklists A .2 Checklists A .2.1 Commissioning procedure Step Ta s k Comple ted 1 Syste m readines s is confirmed (R osemoun t 5300 and 5400 Series only) a. HART revision capabili t y is checked b . The lat est Device Driver is downlo aded c. HART revision mode i s ...

  • Emerson Process Management 00809-0700-4530 - page 91

    83 Reference Manu al 00809-0700-4530, Rev AA Appendix A: Checklists September 2013 Checklists A .2.2 M e asure ment valid ation proc edure Step Ta s k Comple ted 1 The tran smitter is in operation 2 Level re ading correc tness is verified a. The transmitter lev el re ading is compared with an i ndepende nt meas ur ement 3 The analog ou tput signal ...

  • Emerson Process Management 00809-0700-4530 - page 92

    84 Reference Manu al 00809-0700-4530, Rev AA Appendix A: Checkl ists September 2013 Checklists A .2.3 T roubleshooting proc edure Step Ta s k Comple ted 1 V oltage at transmitt er te rminals are check ed 2 DCS trends are check ed 3 T a nk sur vey is done to iden tif y the application 4 Basic e rror s (cables, transmitte r diagnostics etc .) are che ...

  • Emerson Process Management 00809-0700-4530 - page 93

    Index-1 Reference Manu al 00809-0700-4530, Rev AA Index September 2013 Index A Amplitude Threshold Curve (AT C) . . . . . . . . . . . . . . . . . . . 39 Analog output settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 Antenna selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27, 31 C Chamber Fabrication . . . . ...

  • Emerson Process Management 00809-0700-4530 - page 94

    Index-2 Reference Manu al 00809-0700-4530, Rev AA Index September 2013 Index T Tank instal lations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Threshold settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Guided Wave Radar (GWR) . . . . . . . . . . . . . . . . . . . . . 69 Non-conta cting radar . . ...

  • Emerson Process Management 00809-0700-4530 - page 95

    ...

  • Emerson Process Management 00809-0700-4530 - page 96

    Reference Manual 00809-0700-4530, Rev AA September 2013 St andard T erms and Con ditions of Sale c an be found at www .rosem ount.com/te rms_of_sale . The Emerson logo is a trademark and service mark of Emerson Electric Co. Ro semount and the Rose mount logotype are registered trad emarks of Ro semount In c. HART is a registered trade mark of the H ...

Manufacturer Emerson Process Management Category Radar Detector

Documents that we receive from a manufacturer of a Emerson Process Management 00809-0700-4530 can be divided into several groups. They are, among others:
- Emerson Process Management technical drawings
- 00809-0700-4530 manuals
- Emerson Process Management product data sheets
- information booklets
- or energy labels Emerson Process Management 00809-0700-4530
All of them are important, but the most important information from the point of view of use of the device are in the user manual Emerson Process Management 00809-0700-4530.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Emerson Process Management 00809-0700-4530, service manual, brief instructions and user manuals Emerson Process Management 00809-0700-4530. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Emerson Process Management 00809-0700-4530.

A complete manual for the device Emerson Process Management 00809-0700-4530, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Emerson Process Management 00809-0700-4530 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Emerson Process Management 00809-0700-4530.

A complete Emerson Process Management manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Emerson Process Management 00809-0700-4530 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Emerson Process Management 00809-0700-4530, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Emerson Process Management 00809-0700-4530, that we can find in the current document
3. Tips how to use the basic functions of the device Emerson Process Management 00809-0700-4530 - which should help us in our first steps of using Emerson Process Management 00809-0700-4530
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Emerson Process Management 00809-0700-4530
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Emerson Process Management 00809-0700-4530 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Emerson Process Management 00809-0700-4530?

Use the form below

If you did not solve your problem by using a manual Emerson Process Management 00809-0700-4530, ask a question using the form below. If a user had a similar problem with Emerson Process Management 00809-0700-4530 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)