APC 3500 - page 1
Inst allation Smart-UPS ® VT and MGE™ Galaxy™ 3500 Maintenance Byp ass Panel with Powe r Dis tributio n (wall-mount) 10-30 kV A 208 V ...
-
APC 3500 - page 2
...
-
APC 3500 - page 3
Content s Smart-UPS® VT and MGE™ Galaxy™ 35 00 10-30 kVA 208 V MBP Installa tion i Safety .......... ............ ......... ............. ......... ................ .......... 1 SAVE THESE INS TR UCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Safety wa rnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
-
APC 3500 - page 4
...
-
APC 3500 - page 5
1 Smart-UPS® VT and MGE™ Galax y™ 3500 10 -30 kVA 20 8 V MBP Installatio n Safety SA VE THESE INSTRUCTIONS This manua l contains im portant i nstruct ions for the Smar t-UPS ® VT and MGE™ Galaxy™ 3 500 series that sh ould be followed whe n handling the Main tenance Bypass Pane l with Power Distr ibution ( wall- mount). This UL-l isted uni ...
-
APC 3500 - page 6
Smart-UPS® VT a nd MGE™ Galaxy™ 350 0 10-30 kVA 208 V M BP Installa tion 2 Live maintenance pr ecautions APC does NOT recommend p erforming live maint e nance to the MBP with Power Distr ibution. However , APC is aware that due to the critical nature of data center l oads, l ive mainte nance may occur . If prov iding liv e maintenance, obs erv ...
-
APC 3500 - page 7
3 Smart-UPS® VT and MGE™ Galax y™ 3500 10 -30 kVA 20 8 V MBP Installatio n Product Overview Feature s The wall-m ount versi on of the Smart-UPS VT and MGE Gal axy 3500 MBP combines bypa ss functi onality wi th power di stribution ca pabilit y in a common enclosur e.The lower secti on of the MBP contain s switches that facili t ate the transfer ...
-
APC 3500 - page 8
Smart-UPS® VT a nd MGE™ Galaxy™ 350 0 10-30 kVA 208 V M BP Installa tion 4 Internal comp onents Panel Board (42-posi tion) Neutral Bar Neutral Bar Ground Bar Ground Bar S train-r elief Bar S train-r elief Bar Fuse Bl ock ([3]90 A Fuses) Power T ermina l Block Con trol T erm ina l Bloc k UPS Inputs UPS Outputs Q1 Switch Q3 Switch Q2 Switc h Neu ...
-
APC 3500 - page 9
5 Smart-UPS® VT and MGE™ Galax y™ 3500 10 -30 kVA 20 8 V MBP Installatio n Schematic ...
-
APC 3500 - page 10
Smart-UPS® VT a nd MGE™ Galaxy™ 350 0 10-30 kVA 208 V M BP Installa tion 6 Consider ations Environment al • The wall area selected f or th e MBP insta llatio n must be structur ally soun d and able to accommodate the size and weig ht of the unit. Re fer to “Mounting t he MBP” on pa ge 9. • The MBP s hould be ke pt in a climate -control ...
-
APC 3500 - page 11
7 Smart-UPS® VT and MGE™ Galax y™ 3500 10 -30 kVA 20 8 V MBP Installatio n Inst allation Overview W arning: Revie w “Safety” on page 1 before starting this installatio n. Pay str ict attenti on to all safety warnings and c aution noti ces! • ALL INTERNAL cable connections were made prior to shi pment. • EXTERNAL cable c onnections with ...
-
APC 3500 - page 12
Smart-UPS® VT a nd MGE™ Galaxy™ 350 0 10-30 kVA 208 V M BP Installa tion 8 Removing the fr ont doo r (optional ) Note: Front d oor remo val is NOT a r equir ement for t his inst allation. However , re m oving th e door wil l allow be tter access t o the inte rnal component s. 1. Place the MBP on its back such t hat its front door is facing str ...
-
APC 3500 - page 13
9 Smart-UPS® VT and MGE™ Galax y™ 3500 10 -30 kVA 20 8 V MBP Installatio n Mounting th e MBP APC by Schnei der Electric reco m mends mounti ng the MBP to 3/4 inc hes ply wood backing (36 in [914 mm] high x 28 in [71 1 m m] wide). 1. Attach th e 3/4 inches plywoo d securel y to the designat ed wall ar ea. The wall shoul d be stron g enough to s ...
-
APC 3500 - page 14
Smart-UPS® VT a nd MGE™ Galaxy™ 350 0 10-30 kVA 208 V M BP Installa tion 10 Internal cable connectio ns For the convenience of the install er , ALL int ernal MBP c a ble conn ections were mad e prior to s hipment. Check to mak e certai n the following int ernal cab le connections we re completed: • Power T erminal Block [L1, L2, L3, N, to p- ...
-
APC 3500 - page 15
11 Smart-UPS® VT an d MGE™ Galaxy™ 3500 10-30 kVA 208 V MBP Insta llation Making extern al cable connections Note: Utility cables ca n enter through t he top or the bot tom of the MBP . Ho w ever , BOTT OM is recommende d. External cables c an enter the MBP thr ough any of the available 1 -inch [25.4 mm] knockouts, or by making la rger cutout ...
-
APC 3500 - page 16
Smart-UPS® VT a nd MGE™ Galaxy™ 350 0 10-30 kVA 208 V M BP Installa tion 12 UPS co nnec tions . Note: UPS cables can en ter throug h the top or the bot tom of the MBP . However , BOTTOM is recommended. Refer t o the Smart -UPS VT 10-30 kV A or MGE Galaxy 3500, 2 08 V Installation Manual for MBP cabl e connecti ons at the UPS. 1. Connect th e f ...
-
APC 3500 - page 17
13 Smart-UPS® VT an d MGE™ Galaxy™ 3500 10-30 kVA 208 V MBP Insta llation Re-att a ching the front door Note: This se ction appl ies only if the f ront door w as rem oved at t he start of the installatio n proces s. If you ch ose not to remove t he door , ignore this s ection. Re-att aching the front door requires at least two peop le: one to ...
-
APC 3500 - page 18
Smart-UPS® VT a nd MGE™ Galaxy™ 350 0 10-30 kVA 208 V M BP Installa tion 14 Inst alling Panel Boa rd Breaker s This sec tion describes how to inst all breakers to the MBP’ s 42-positi on panel boa rd. Electrica l Hazard: Befor e installing br eakers, mak e sure ALL MBP switches ar e in the OFF positi on. From nor mal operation, fir st switch ...
-
APC 3500 - page 19
15 Smart-UPS® VT an d MGE™ Galaxy™ 3500 10-30 kVA 208 V MBP Insta llation Appendix A: Changing Fuses W arning: Befor e changing fuses , make sur e ALL MBP switches ar e in the OFF positi on. From nor mal operation, fir st switch Q2 OFF , and the n switch Q1 OFF . Note: Replac e ALL blown fus es with Bussmann “Cla ss J” 90 Amp fuses (p/n JK ...
-
APC 3500 - page 20
...
-
APC 3500 - page 21
...
-
APC 3500 - page 22
...
-
APC 3500 - page 23
...
-
APC 3500 - page 24
8/2009 990-4198D-001 *990-4198D-001* APC W orldwide Customer Support Customer s upport for this or any other AP C product i s available at no char ge in any of the following ways: • V isit the APC W eb si te to a ccess docu m ents i n the APC Kno wledge Base a nd to submit cu stomer support requests. – www .apc.com ( Corpora te Headquar ters) C ...