Manual Watlow Electric EM00-GATE-0000

28 pages 0.66 mb
Download

Go to site of 28

Summary
  • Watlow Electric EM00-GATE-0000 - page 1

    EM Gateway User’s Manual For Watlow part number EM00-GATE-0000 1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota USA 55987-5580 Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507, Internet: http://www.watlow.com 0600-0040-0001 Rev D $10.00 February 2004 ...

  • Watlow Electric EM00-GATE-0000 - page 2

    2 EM Gateway Table of Contents Chapter 1: Product Overvi ew 4 Ethernet Gateway 4 Ethernet Gateway Architecture 4 Program Upgrades 5 Chapter 2: Installation and Wiring 6 Dimensions 7 Chapter 3: Configuration 8 Getting Started 8 Network Services 8 Email Alarm Notification 8 Data Logging 9 Control Monitoring and Configuration 9 Chapter 4: HTML Pages 1 ...

  • Watlow Electric EM00-GATE-0000 - page 3

    3 EM Gateway Table of Contents – cont. Chapter 6: Reference Documents 25 Reference Documents 25 Serial Numbers 25 Chapter 7: Specifications 26 Power Supply 26 Environmental 26 Indication 26 Agency 26 Communications 26 Control Output Signals 26 Enclosure Size 26 User Interface 26 Ordering Information 26 Declaration of Conformity 27 How to Reach Us ...

  • Watlow Electric EM00-GATE-0000 - page 4

    4 Chapter One Product Overview The EM00-GATE-0000 is a gateway / bridge that allo ws up to 32 Watlow controllers to be directly connected to an Ethernet network. Using an HTTP Brow ser such as Microsoft Internet Explorer or Netscape Navigator you may access 16 controllers and view several controllers’ parameters via an onboard Web (HTTP) server. ...

  • Watlow Electric EM00-GATE-0000 - page 5

    5 Program Upgrades The gateway has a TFTP server for the purposes of reprogramming the program memory. A program update will be initiated when a TFTP client, residing on a PC, begins to write a new program file to the gateway TFTP server. When reprogramming the progr am memory, all other gateway services are unavailable. The gateway provides no mea ...

  • Watlow Electric EM00-GATE-0000 - page 6

    6 Chapter Two Installation & Wiring UL Approved, Class 2 power supply required ...

  • Watlow Electric EM00-GATE-0000 - page 7

    7 Dimensions are in inches ...

  • Watlow Electric EM00-GATE-0000 - page 8

    8 Chapter Three Configuration Getting Started Perform these steps; 1. Connect the EM00-GATE-0000 gateway to your com puter’s Ethernet port using a cross-wired RJ45 cable or connect the EM00-GATE-0000 to a hub or net work using a straight wired RJ45 Category 5 cable. The EM00-GATE-0000 is limited to a 10B aseT connection and will not work on an Et ...

  • Watlow Electric EM00-GATE-0000 - page 9

    9 You will need to configure your Gateway with your SMTP server name or address. A DNS server address must also be configured if using a SMTP name. Contac t your system administrator if you don’t know the SMTP name or address. Data Logging The gateway provides no explicit means of data logging. Data can be polled via Modbus TCP by an external PC ...

  • Watlow Electric EM00-GATE-0000 - page 10

    10 Chapter Four HTML Pages The section describes the pages availabl e from the EM Gateway’s Web server. When the web page is first accessed, you are prom pted for a User name and Password. The default User name is ‘new’. The default Password is ‘user’. Thes e are case sensitive. The user name and password may be changed on the security co ...

  • Watlow Electric EM00-GATE-0000 - page 11

    11 Use this page to disable or enable automatic page refreshing or to change the time in between refreshes. In addition, you can force a rescan of the Modbus Ne twork. This will cause the Gateway to detect any new devices added to the serial network. Set the baud rate of the network to 9600 or 19200-baud. The value selected must match the value in ...

  • Watlow Electric EM00-GATE-0000 - page 12

    12 Use this page to change the Gateway identificati on name or to change the IP Address Resolution Method. Contact your IS administrator for questions regarding these settings. ...

  • Watlow Electric EM00-GATE-0000 - page 13

    13 Use this page to enable notification and configure the addresses for email recipients. These recipients will receive an email when an alarm occurs on any c ontroller. Contact your IS administrator for questions regarding these settings. ...

  • Watlow Electric EM00-GATE-0000 - page 14

    14 Use this page to update the time and date stored in the Gateway. This information is used to identify the time and date of alarms when emails are sent. ...

  • Watlow Electric EM00-GATE-0000 - page 15

    15 1 0 0 0 0 1174 0 2 0 0 0 0 1174 0 3 0 0 0 0 1174 0 4 0 0 0 0 1174 0 5 0 0 0 0 1174 0 6 0 0 0 0 1174 0 7 0 0 0 0 1174 0 8 0 0 0 0 1174 0 9 0 0 0 0 1174 0 10 0 0 0 0 1174 0 11 5 2 0 3 1167 0 12 0 0 0 0 1174 0 13 0 0 0 0 1174 0 14 0 0 0 0 1174 0 15 0 0 0 0 1174 0 16 0 0 0 0 1174 0 The Serial Statistic page is used to monitor the health of the contr ...

  • Watlow Electric EM00-GATE-0000 - page 16

    16 This page was loaded Wed Feb 1318: 00:28 2002 IP Address 7.3.37.91 Subnet 255.255.224.0 Gateway 7.3.63.250 Mac Address 00:03:AA:00:00:C1 Receives 128349 Unicasts 1207 Multicasts 0 Broadcasts 127061 Rx Errors 0 Rx Missed 2089 Rx CRC Errors 28 Rx Drops 0 Transmits 1251 Buffer Defers 0 Tx Errors 0 Tx Collisions 0 Tx Coll. Overflow 0 Tx FILO Errors ...

  • Watlow Electric EM00-GATE-0000 - page 17

    17 Chapter Five Controller Parameters and Registers The EM Gateway supports the following parameter s for each type of controller when using an HTTP browser: Series 96 – non-ramping Operation Mode – register 200 with choice of Auto or Manual as read only Input Error – register 101 with choice of Sensor Error or Ok as read only Process Value I ...

  • Watlow Electric EM00-GATE-0000 - page 18

    18 Series 988 / 989 Operation Mode – register 10 with choice of Auto or Manual as read only Input Error – register 4 with choice of Sensor Error or Ok as read only Process Value Input 1 – register 1 as read only Process Value Input 2 – register 2 as read only Auto Set Point – register 7 as read/write Alarm Status Output 2/3 – register 3 ...

  • Watlow Electric EM00-GATE-0000 - page 19

    19 Series F4P Operation Mode – register 200 with choice of Auto or Manual as read only Input 1 Error – register 101 with choice of Sensor Error or Ok as read only Input 2 Error – register 105 with choice of Sensor Error or Ok as read only Input 3 Error – register 109 with choice of Sensor Error or Ok as read only Process Value Input 1 – r ...

  • Watlow Electric EM00-GATE-0000 - page 20

    20 CLS200 Series (Loop 1 to 16 if available) Operation Mode – register 264 to 279 with choice of Auto or Manual as read only Input Error – registers 660 to 675 with choice of Ok, TC Reversed, TC Short, TC Open, RTD Open, or RTD Short as read only Process Value – registers 363 to 378 as read only Auto Set Point – registers 330 to 345 as read ...

  • Watlow Electric EM00-GATE-0000 - page 21

    21 ...

  • Watlow Electric EM00-GATE-0000 - page 22

    22 ...

  • Watlow Electric EM00-GATE-0000 - page 23

    23 ...

  • Watlow Electric EM00-GATE-0000 - page 24

    24 ...

  • Watlow Electric EM00-GATE-0000 - page 25

    25 Chapter Six Reference Documents The MODBUS RTU specification is located at: http://www.modicon.com/techpubs/toc7.html or http://www.modbus.org Serial Numbers Gateways are labeled with a unique serial number in numeric and bar code formats. The serial number is embedded in the gateway firmware. EM Gatew ay Features and Benefits • Ethernet/Inter ...

  • Watlow Electric EM00-GATE-0000 - page 26

    26 Chapter Seven Specifications Pow er supply • Voltage input 24 V (ac/dc) +10%, -15% 50/60 Hz +/- 5 • Connection through 2-position removable screw style terminal block • 22 to 12 AWG • Power consumption 10 VA MAX • UL Approved, Class 2 power supply required • Real-time Clock backed by 3v-lithium battery – RAYOVAC BR1225 Environmenta ...

  • Watlow Electric EM00-GATE-0000 - page 27

    27 Declaration of Conformity Gateway Products Watlow Winona, Inc. 1241 Bundy Blvd. Winona, MN 55987 USA Declares that the following product: Model Numbers: EM00-GATE-0000, NGW0-0000-2400 and NGW0-0000-0000* Classification: Communications interface card, Installation Category I, Pollution degree II Rated Voltage: 24V  (ac or dc) or 5V  (dc) Ra ...

  • Watlow Electric EM00-GATE-0000 - page 28

    28 How to Reach Us Technical Assistance If you encounter a problem with your EM Gateway, revi ew all of your wiring and configuration information to verify that your selections ar e consistent with your application. If the problem persists after checking the above, you can get technical assistance from your local Watlow r epresentative, or by diali ...

Manufacturer Watlow Electric Category Network Router

Documents that we receive from a manufacturer of a Watlow Electric EM00-GATE-0000 can be divided into several groups. They are, among others:
- Watlow Electric technical drawings
- EM00-GATE-0000 manuals
- Watlow Electric product data sheets
- information booklets
- or energy labels Watlow Electric EM00-GATE-0000
All of them are important, but the most important information from the point of view of use of the device are in the user manual Watlow Electric EM00-GATE-0000.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Watlow Electric EM00-GATE-0000, service manual, brief instructions and user manuals Watlow Electric EM00-GATE-0000. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Watlow Electric EM00-GATE-0000.

A complete manual for the device Watlow Electric EM00-GATE-0000, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Watlow Electric EM00-GATE-0000 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Watlow Electric EM00-GATE-0000.

A complete Watlow Electric manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Watlow Electric EM00-GATE-0000 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Watlow Electric EM00-GATE-0000, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Watlow Electric EM00-GATE-0000, that we can find in the current document
3. Tips how to use the basic functions of the device Watlow Electric EM00-GATE-0000 - which should help us in our first steps of using Watlow Electric EM00-GATE-0000
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Watlow Electric EM00-GATE-0000
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Watlow Electric EM00-GATE-0000 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Watlow Electric EM00-GATE-0000?

Use the form below

If you did not solve your problem by using a manual Watlow Electric EM00-GATE-0000, ask a question using the form below. If a user had a similar problem with Watlow Electric EM00-GATE-0000 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)