Summary
  • Mitsubishi FR-S500 - page 1

    TRANSIST ORIZED INV ER TER FR-S 500 INSTR U CTION MANU AL (D etailed) FUNC TIONS Chapter 2 HEAD OFFICE:MITSUBISHI DENKI BLDG M AR UNOUCHI TOKY O 100-8310 WIRING Chapter 1 PR O TECTIVE FUNC TIONS Chapter 3 SPECIFICA TIONS Chapter 4 FR-S 500E -NA TRANSIST ORIZED INVER TER INSTRU C TION MANU AL (Detailed) A SIMPLE INVER TER FR-S520E-0.1K to 3.7K -NA F ...

  • Mitsubishi FR-S500 - page 2

    A-1 1. Elec tric Sh ock Pr eventio n Thank you for choosing this Mit subishi T ransistorized inverter . This instruction manual (detail ed) provides instructions for advanced use of the FR- S500 series inverters. Incorrect handling might cause an unexpected fault. Before using the inverter , always read this instruction manual and the instruction m ...

  • Mitsubishi FR-S500 - page 3

    A-2 2. Fire P revent ion 3. Injur y Preven tion 4. Additional Instructions Also note the following point s to prev ent an accidental failure, injury , electric shock, etc. (1) T r ansport atio n and installation CAUTION  Mount the invert er on an incom bustible s urface. In stall ing the inv erter direc tly on or n ear a comb ustible surface cou ...

  • Mitsubishi FR-S500 - page 4

    A-3 (2) Wirin g (3) T rial run (4) Operatio n CAUTION  Do not fit capaciti v e equipment such as power factor c orrection capacitor , radio noise filter (option FR-BIF(-H)) or surge suppressor to the output of the inverter .  The connection orientati on of the output cables U, V , W to the motor will affect the direction of rotati on of the m ...

  • Mitsubishi FR-S500 - page 5

    A-4 (5) Emergency stop (6) Maintenance, in spection and par ts replacement (7) Disposing of the inverter (8) General inst ructions CAUTION  The electronic thermal relay function does not guarantee protec tion of the motor from overheating.  Do not use a magnetic cont actor on the inverter input for frequent starting/stopping of the inverter . ...

  • Mitsubishi FR-S500 - page 6

    I CONTENTS CONTENTS 1. WIRING 1 1.1 Standar d connecti on diagram and termi nal specifications ..2 1.1.1 Standa rd connectio n diagram ......... ................ ................. ................. ............ 2 1.1.2 Expla nation of mai n circuit te rminals ............... ............ ................. ................ . 3 1.2 Main cir cuit te r ...

  • Mitsubishi FR-S500 - page 7

    II 1.5.4 Start s elf-holdin g selection (STOP signal ): Pr. 60 to Pr. 63 s etting "5 " ....... 34 1.5.5 Outp ut shut-off (MRS signal): Pr. 60 to Pr . 63 settin g "6" ...... ................. .... 34 1.5.6 Extern al thermal rel ay input: Pr. 60 to Pr. 63 s etting "7" ... ................. ......... 35 1.5.7 Jog o perati ...

  • Mitsubishi FR-S500 - page 8

    III CONTENTS 2.3.1 8 Biase s and gains of the frequ ency se tting voltag e (current) (Pr. 38 , Pr. 39 , C2 to C7 ). ................. ................. ................. ................. .... 82 2.3.1 9 Start-tim e ground fault detec tion selec tion (Pr. 40 ) ............... ................. .... 86 2.4 Outp ut t ermi na l fun cti on p ara meter ...

  • Mitsubishi FR-S500 - page 9

    IV 2.12.1 Mainten ance output f unction (H1 , H2 ) ...... ................. ................. ............. 122 2.12.2 Current average v alue mon itor signa l (H3, H4, H 5) .... .... .... ..... .. 123 2. 13 Cal ibra tio n pa ram eter s .... .... ..... .... ..... .... ..... .... .... ..... .... ..... .... 126 2.13.1 Meter (freq uency mete r) calibra ...

  • Mitsubishi FR-S500 - page 10

    V CONTENTS 3.2.1 1 Motor produces an noying soun d ..... ................ ................. ................. ........ 168 4. SPECIFICATIONS 169 4.1 Spec ifi cati on lis t ...... .... .... ..... .... .. ..... .... ..... .... ..... .... .... ..... .... ... 17 0 4.1.1 Ratings .......... ................. ................. ................ ........... ...

  • Mitsubishi FR-S500 - page 11

    1 Cha pt e r 2 Cha pt e r 3 Cha pt e r 4 Cha pt e r 1 1. WIRING This chapter explains the basic "wiring" for use o f this product. Always read the instructions before use. For description of "inst allation", refer to the instruction manual (basic ) . 1.1 St andar d connection diagra m and terminal spec ifi cati ons . .... ..... ...

  • Mitsubishi FR-S500 - page 12

    2 S tan dard co nnectio n diagr am and t erminal specif icatio ns 1.1 S t andard connection diagram and termin al specifi cations 1.1.1 S tandard connection di agram  Three-phase 200V power input  Three-phase 400V power input REMARKS *1. The N/- te rminal is not pro v ided f or the FR-S52 0E-0.1K to 0.75 K -NA. *2. The PR termi nal is p rovid ...

  • Mitsubishi FR-S500 - page 13

    3 S tan dard c onnectio n diagr am and t ermina l specif icatio ns 1 WIRING  Single-phase 100V power input 1.1.2 Ex planation of main circui t termina ls (1) Main circ uit REMARKS • T o ensure saf ety , c onne ct the power inpu t to the inver ter via a magn etic cont actor and ear th leakage cir c uit bre aker or no-fus e breaker , and us e th ...

  • Mitsubishi FR-S500 - page 14

    4 S tan dard co nnectio n diagr am and t erminal specif icatio ns (2) Control ci rcuit Symbol T ermina l Na me Definition Input sign als Cont act input STF Forward rota tion st art T ur n on the STF sign al to st art f orwar d rot atio n and turn it off to stop. Wh en the STF and STR si gnals ar e turn ed on simu ltaneous ly , the stop com mand i s ...

  • Mitsubishi FR-S500 - page 15

    5 S tan dard c onnectio n diagr am and t ermina l specif icatio ns 1 WIRING *1. Do not co nnect termina ls SD and PC each ot her or to the groun d. For si nk l ogic ( fact ory set tin g), ter minal SD ac ts as t he commo n term inal of cont act input . For source log ic, term inal PC acts as the c ommo n termi nal of contact i nput. (Refer to page ...

  • Mitsubishi FR-S500 - page 16

    6 Main circuit terminals 1.2 Mai n circuit termi nals 1.2. 1 T erminal block layout 1) T hree- phase 200V pow er input • FR-S520 E-0. 1K, 0.2 K-NA • FR-S520E-1.5K, 2.2K, 3.7K-NA • FR-S520 E-0. 4K, 0.7 5K-NA 2) T hree- phase 400V pow er input • FR-S540E-0.4K, 0.75K, 1.5K, 2.2K, 3.7K -NA P/+ P1 U V W IM R/L1 S/L2 T/L3 Jumpe r Power supply Mot ...

  • Mitsubishi FR-S500 - page 17

    7 Main circu it terminals 1 WIRING 3) S ing le-phase 100V power input • FR-S510WE-0.1K, 0.2K, 0.4K-NA • FR-S510WE-0.75K-NA CAUTION • Make sure the po wer cables ar e connected to the R/L1, S/L2, T/L3 of the inve r ter . Never con nect the power ca ble to the U, V , W of the inverter . (Phase ne ed not be mat che d) • Connect the motor to U, ...

  • Mitsubishi FR-S500 - page 18

    8 Main circuit terminals 1.2.2 Cable s, wiring length, and crimping terminals The following t able indicates a selection example for the wiring length of 20m (65.62 feet). 1) Three-phase 200V power input 2) Three-phase 400V power input 3) Single-phas e 100V power input  Wiring length 100m (328.08 feet) maximum. (50m (164.04 feet) maximum for the ...

  • Mitsubishi FR-S500 - page 19

    9 Main circu it terminals 1 WIRING 1.2 .3 Wir in g in str uct ions 1) Use insulation-sleeved crimping terminal s for the power supply and motor cables. 2) Appli cation of power to the output terminal s (U, V , W) of the inverter will damage the inverter . Never perform s uch wiring. 3) Af ter wiring, wire offcut s must not be left i n the inverter. ...

  • Mitsubishi FR-S500 - page 20

    10 Main circuit terminals 1.2. 4 Selecti on of peripheral devices Check the cap ac ity of the motor applic able to the inverter y ou purchased. Appropriate peripheral devices must be selec ted ac cording to the cap acity . Refer to the following list and prep are appropriate peripheral devices: 1) Three-phase 200V power input 2) Three-phase 400V po ...

  • Mitsubishi FR-S500 - page 21

    11 1 WIRING Main circu it terminals 3) Single-phase 100V power input *2. For inst allat ions in the United S tates or Canada , the circ uit breaker m ust be inv erse time o r insta ntaneo us trip type. *3. The pow er facto r may be slightly lower . *4. When th e breaker on the invert er primary side trip s, ch eck for th e wiring fau lt (short circ ...

  • Mitsubishi FR-S500 - page 22

    12 Main circuit terminals 1.2.5 Lea kage current and install ation of ground leakage circuit break er Due to st atic capacit anc es existing in the inverter I/O wiring and motor , leakage currents flow through them. Since th eir values depend on the s tati c capacitanc es , carrier frequency , etc., tak e the following countermeasures. (1) T o-grou ...

  • Mitsubishi FR-S500 - page 23

    13 Main circu it terminals 1 WIRING (2) Line-t o-line leakage curre nt s Countermeasures • Use the electronic thermal relay fun c tion of the inv er ter . • Decrease the carrier frequency . Note that motor noise increases. Selection of Soft-PWM (Pr . 70) makes it unof fending. T o ensure that the motor is protected against line-to-line leakage ...

  • Mitsubishi FR-S500 - page 24

    14 Main circuit terminals (3) Selec ting the rated sensiti vity current for the ear th leakage circui t breaker When using the earth leakage circuit breaker with the inverter circuit, select its rated sensitivity c urr ent as follows, independently of the PWM carrier frequency: • Breaker for harmonic and surge Rated sensitivity current: I ∆ n ? ...

  • Mitsubishi FR-S500 - page 25

    15 Main circu it terminals 1 WIRING CAUTION • The ground leakage circuit breaker should be inst alled to the primary (power supply) side of th e inverter . • In the conn ection neutral point grounded system, th e sensitivity current becomes worse for ground fau lt s on th e inverter secondary side. Grou nding must conf orm to the requir ements ...

  • Mitsubishi FR-S500 - page 26

    16 Main circuit terminals 1.2.6 Power-of f and magnetic contac tor (M C) (1) Invert er input s ide magnetic co nt actor (MC) On the inverter's input side, it is recommended to provide an MC for the following purposes. (Refer to page 10 for selection) 1) T o r elease the inverter fr om the power supply when the inverter protective function is a ...

  • Mitsubishi FR-S500 - page 27

    17 Main circu it terminals 1 WIRING 1.2.7 Regar ding the installation of the power factor improving reactor When the i nv erter is ins talled near a large-cap acity power transformer (500kV A or more with the wiring length of 10m ( 32.81feet ) or l ess) or the power cap acitor is to be switched, an excessive peak current will flow in the power supp ...

  • Mitsubishi FR-S500 - page 28

    18 Main circuit terminals 1.2.8 Rega rding noise and the insta llation of a noise filter Some noise enters the inverter c ausing it to malfunction and others are gener ated by the inverter causing the malfunction of peripheral devices. Though the inverter is designed to be insusceptible to noi se, it handles low-level signals, so it requires the fo ...

  • Mitsubishi FR-S500 - page 29

    19 Main circu it terminals 1 WIRING 1.2.9 Grounding precautions  Leakage currents flow in the inv erter. T o prevent an electric shock, the inverter and motor must be grounded. Grounding must conform to the requirements of national and local safety regulat ions and electrical codes. (JIS, NEC section 250, IEC 536 class 1 and other applicabl e s ...

  • Mitsubishi FR-S500 - page 30

    20 Main circuit terminals 1.2. 10 Powe r supply harmonics The inverter may generate power supply harmoni cs from its converter circuit to af fect the power generator , power capacitor etc. Power s upply harmonics are different from noise and leakage currents in sourc e, frequency band and transmission path. T ake the following countermeasure suppre ...

  • Mitsubishi FR-S500 - page 31

    21 Main circu it terminals 1 WIRING 1.2.1 1 Inverter- driven 400V cl ass motor In the PWM type inverter , a surge voltage attributable to wiring const ants is generated at the motor terminals . Especially for a 400V class motor , the surge volt age may deteriorate the insu lation. When the 400V class motor is driven by the inverter , consider the f ...

  • Mitsubishi FR-S500 - page 32

    22 How to u se the co ntrol circuit termi nals 1.3 How to use the control circ u it termi n als 1.3. 1 T erminal block layout In the control circuit of the inverter , the terminals are arranged as shown below: 1.3 .2 Wir in g in stru cti ons 1) T erminals, SE and 5 are common to the I/O signals isolated from each other . Do not ground them. Avoid c ...

  • Mitsubishi FR-S500 - page 33

    23 How to use the control circuit terminals 1 WIRING 1.3.3 Changing the c ont rol logic The input signals are set to sink logic. T o change the control logic, the jumper connector under the setting dial must be moved to the other position. Chang e the jum per connec tor pos iti on usin g twe ezer s, a pair of long -nose pl iers etc . Chang e the ju ...

  • Mitsubishi FR-S500 - page 34

    24 How to u se the co ntrol circuit termi nals 2) Source logic ty pe • In this logic, a signal switches on w hen a current flows i nto the corresponding signal input terminal. T erminal PC is common to the contact input si gnals. For the open collector output signals, terminal SE is a positive external power supply terminal. • Connecting the 0V ...

  • Mitsubishi FR-S500 - page 35

    25 Input terminals 1 WIRING 1.4 Input terminal s 1.4.1 Run (start) and s t op (STF , STR, STOP) T o start and stop the moto r , first switch on the input power supply of the inverter (switch on the magnetic contactor , if any , in the input c i rcuit during prep aration for operation), then start the motor with the forward or reverse rotation start ...

  • Mitsubishi FR-S500 - page 36

    26 Inpu t terminal s *1: Also stopped by the . Refer to page 105. (2) Three-wir e type connect ion (STF , STR, STOP) A three-wire type connection is shown on the right. Assign the st art self-holding signal (STO P) to any of the input terminals. T o make a reverse rotation s tart, set Pr . 63 to "- - -" (factory setting). 1) Short the sig ...

  • Mitsubishi FR-S500 - page 37

    27 Input terminals 1 WIRING St art/Stop Timing Chart (fo r two -wire type) Forward-Reverse Rot at ion Switch- Over T iming Chart REMARKS *1. The "startin g freq uency " in Pr . 13 (fa ctory- set to 0.5Hz) may be se t betw een 0 and 60Hz. *2. If the next start signa l is give n during DC injecti on bra ke operat ion, th e DC inje ction br ...

  • Mitsubishi FR-S500 - page 38

    28 Inpu t terminal s 1.4.2 Connection of fre q uency se t ting potentiometer a nd output fre q uency meter (10, 2, 5, 4, AU) The analog frequency setting input signals that may be entered are voltage and current signals. For the relationship s between the frequency setting input volt ages (c urrents) and output frequencies, refer to the following d ...

  • Mitsubishi FR-S500 - page 39

    29 Input terminals 1 WIRING (2) Current input (4, 5, AU) T o automatically perform operation under cons tant pressure or temperature control using a fan, pump etc ., enter the controll er output signal of 4 to 20mADC across terminals 4-5. T erminals AU-SD must be shorted to use the 4 to 20mADC signal for operation. (Assign the signal AU us ing any ...

  • Mitsubishi FR-S500 - page 40

    30 Inpu t terminal s *When using the REX signal, an external command cannot be used to make a reverse rotation start. Multi-Speed Operatio n Connectio n Example Multi-Speed Setting Spe e d T ermina l Input Parameter Set Fr equency Range Remarks REX- SD* RH- SD RM- SD RL- SD* Sp e e d 1 (high speed) OFF OFF O FF Pr . 4 0 to 120H z  ...

  • Mitsubishi FR-S500 - page 41

    31 Input terminals 1 WIRING 1.4.4 Indicator conne ction and adjustment (AM) A full-scale 5VDC analog s ignal can be output from across terminals AM- 5. The analog output level can be calibrated by the operation panel or parameter unit (FR-PU04). T er minal AM function selecti on c an be set in Pr . 54 "AM terminal function sele ction". T ...

  • Mitsubishi FR-S500 - page 42

    32 Inpu t terminal s 1.4.5 Control cir cuit common terminals (SD, 5, SE) T erminals SD, 5, and SE are all common ter minals (0V) for I/O signals and are isolated from each other . T erminal SD is a common terminal for the cont act input terminals (STF , STR, RH, RM, RL). T erminal 5 is a common termi nal for the frequenc y setting analog input sign ...

  • Mitsubishi FR-S500 - page 43

    33 How t o us e the input s ignal s (a ssign ed ter minal s RL, RM, RH, STR) 1 WIRING 1.5 How to use the input signals (assigned terminals RL, RM, RH, STR) 1.5.1 Multi - spee d setting (RL, RM, RH, REX signals): Pr . 60 to Pr . 63 setting "0, 1, 2, 8" Remote setti ng (RL, RM, RH s ignals ): Pr . 60 to Pr . 63 setting "0, 1, 2" ? ...

  • Mitsubishi FR-S500 - page 44

    34 How to use th e inpu t sign als (a ssign ed ter minals RL, RM, RH, STR) 1.5.4 S tart self-holding selection (ST OP signal): Pr . 60 to Pr . 63 setting "5" 1.5.5 Output shut-off (MRS signal): Pr . 60 to P r . 63 setting "6" Short the output stop terminal MRS-SD dur ing inverter output to cause the inverter to immediately st op ...

  • Mitsubishi FR-S500 - page 45

    35 How t o us e the input s ignal s (a ssign ed ter minal s RL, RM, RH, STR) 1 WIRING 1.5.6 Ex t ernal thermal relay input: Pr . 60 to P r . 63 settin g "7" 1.5.7 Jog operation (JO G signal): Pr . 60 to Pr . 63 set ting "9" (1) Jog operation using exter nal signals Jog operation can be st ar ted/stopped by shorting the jog m ode ...

  • Mitsubishi FR-S500 - page 46

    36 How to use th e input signa ls (assig ned ter min als RL, RM, RH, STR) 1.5. 8 Reset si gn al: Pr. 60 to Pr . 6 3 setting "10" Used to reset the alarm stop s tate e stablished when the in verter 's protective function is activated. The reset signal immediately se ts the control circuit to the ini tial (cold) st atus , e.g. ini tial ...

  • Mitsubishi FR-S500 - page 47

    37 How t o us e the input s ignal s (a ssign ed ter minal s RL, RM, RH, STR) 1 WIRING 1.5.9 PID c ontrol valid t erminal: Pr . 60 to Pr . 63 setting "14" T o exercise PID control, turn on the X14 signal. When this signal is off, ordinary inverter operation is performed. For more information, refer to page 1 13. 1.5.10 PU operation/externa ...

  • Mitsubishi FR-S500 - page 48

    38 Connection to the Stand-Alone Option 1.6 Connection to the St and-Alone Option The inverter accepts a v ariety of st and-alone option units as required. Incorrect connectio n will cause inverter damage or acc ident. Connec t and operate the option unit caref ully in accordance with the corresponding option unit manual. 1.6.1 Connection of the b ...

  • Mitsubishi FR-S500 - page 49

    39 Conne ction to the S tand-Al one Option 1 WIRING 1.6.2 Connection of the high power factor converter (FR-HC) When c onnec ting the high power factor conv erter (FR-HC) to s uppress power supply harmonics, perform wiring se c urely as shown bel ow . Incorrect connection wi ll damage the high power factor converter and inverter . CAUTION 1. Use si ...

  • Mitsubishi FR-S500 - page 50

    40 Connection to the Stand-Alone Option 1.6.3 Connection of the p ower r e generation c ommon converte r (FR-CV) When connecting the FR-C V type power regeneration common converter , connect the inverter terminals (P, N) and FR-CV type power regeneration c ommon converter terminals as shown below so that their signals m atc h with each other . CAUT ...

  • Mitsubishi FR-S500 - page 51

    41 Handling of the RS-485 connector 1 WIRING 1.7 Handlin g of the RS-485 connector 1.7.1 Connection of the param eter unit (FR-PU04) When connecting the parameter unit to the RS-485 connector , use the optional parameter unit connecti on c able (FR-CB2 ) . Refer to page 151 for the p arameters related to p arameter unit setting. <RS-485 connecto ...

  • Mitsubishi FR-S500 - page 52

    42 Handling of the RS-485 connector 1.7.2 Wi ring of RS-485 communication Use the RS-485 connector to perform communication operation from a personal computer etc. When the RS-485 connector is connected with a personal, F A or other c omputer by a communication cable, a us er progr am can run and monitor the inverter or read and write to the parame ...

  • Mitsubishi FR-S500 - page 53

    43 Handling of the RS-485 connector 1 WIRING (2) Combination of computer an d multiple inver ters (1: n connection) REMARKS Refe r to the f ollow ing when f abri catin g the ca ble on th e user si de. Examp le of p roduc t avail able on the mar ket ( as of Apri l, 2004) Computer RS-232C connector RS-232C cable Converter Inverter Station 0 Computer ...

  • Mitsubishi FR-S500 - page 54

    44 Handling of the RS-485 connector <Wiri ng methods> 1) Wiring of one RS-485 computer and one inverter 2) Wiring of one RS-485 computer and "n" inverters (several inverters) REMARKS *1. Make co nnect ion in a ccor dance with th e inst ructi on manu al of the com puter to be u sed with . Fully check t he term inal num ber s of the c ...

  • Mitsubishi FR-S500 - page 55

    45 Design information 1 WIRING 1.8 Desi gn information 1) Provide electrical and mechanic al interlocks for MC1 and MC2 w hich are used for commercial power supply-inverter switc hov er . When the wiring is incorrect or if there is a commercial power supply-inverter switch-over circuit as s hown below , the inverter will be damaged by leakage curre ...

  • Mitsubishi FR-S500 - page 56

    46 MEMO ...

  • Mitsubishi FR-S500 - page 57

    47 Cha pt e r 2 Cha pt e r 3 Cha pt e r 4 Cha pt e r 1 2. FUNCTIONS This chapter explains the "functions" for use of this product. For simple variable-speed operation of the inverter , the factory s ettings of the parameters may be us ed as they are. Set the necessary p arameters to meet the load and operational sp ec ifications. Refer to ...

  • Mitsubishi FR-S500 - page 58

    48 Function (Parame ter) list Para me ter List 2.1 Function (Parameter) list *1. T he fac tory sett ing va ries wi th the i nver ter c apacity: 5% for FR-S 540E- 1.5K and 2 .2K, 4% for FR -S540E -3.7K. CAUTION indicates that the setting can be changed during operation if Pr . 77 "p arameter write disable s election" has been set to " ...

  • Mitsubishi FR-S500 - page 59

    49 Function (Parameter) list 2 FUNCTIONS Paramet er List The extended function parameters are made valid by setting "1" in P r . 30 "extended function display selection". (For more det ailed information on the way to set Pr . 30, refer to the instruction manual (basic).) Func - tion Para - meter Indi ca- tio n Name Setting Ran g ...

  • Mitsubishi FR-S500 - page 60

    50 Function (Parame ter) list Para me ter List S tandard op erati on funct ions 24 Multi-s peed setti ng (spe ed 4) 0 to 12 0Hz, - - - 0.1Hz - - - 66 25 Multi-s peed setti ng (spe ed 5) 0 to 12 0Hz, - - - 0.1Hz - - - 66 26 Multi-s peed setti ng (spe ed 6) 0 to 12 0Hz, - - - 0.1Hz - - - 66 27 Multi-s peed setti ng (spe ed 7) 0 to 12 0Hz, - - - 0.1Hz ...

  • Mitsubishi FR-S500 - page 61

    51 Function (Parameter) list 2 FUNCTIONS Paramet er List Outp ut term inal funct ions 41 Up-to- freq uency sensi tiv ity 0 to 10 0% 1% 10% 86 42 Output freq uency detec tion 0 to 120Hz 0.1Hz 6Hz 8 7 43 Output freq uency detec tio n for rever se rotati on 0 to 12 0Hz, - - - 0.1Hz - - - 87 Se con d fu nc ti on s 44 Second accel erati on/ decel erati ...

  • Mitsubishi FR-S500 - page 62

    52 Function (Parame ter) list Para me ter List Displa y function s 52 Oper ation panel displ ay data se lect ion 0: Outpu t freque ncy , 1: Ou tput c urrent, 100:Set freq uency dur ing stop /outpu t freque ncy dur ing oper atio n 10 9 0 53 Fre quenc y setti ng oper ation sele ction 0: Set ting di al freq uency set tin g mode 1: Setti ng dial potent ...

  • Mitsubishi FR-S500 - page 63

    53 Function (Parameter) list 2 FUNCTIONS Paramet er List T ermin al fu ncti on s elect ion 60 RL termi nal funct ion selec tio n 0: RL, 1: RM, 2: RH, 3: RT , 4: AU, 5: STOP , 6: MRS, 7: OH, 8: REX, 9: JOG , 10: RE S, 14: X14, 16: X1 6, - - - : STR ( The STR sig nal can be assi gned to t he STR ter minal only .) 10 9 8 61 RM terminal funct ion selec ...

  • Mitsubishi FR-S500 - page 64

    54 Function (Parame ter) list Para me ter List Oper ati on se lecti on functions 70 So ft-PW M setti ng Prese nce/absence of Sof t-PWM control c an be sele cted. When Soft-PWM is valid, the m et allic tone of mot or noise can be chang ed into unof fending compo site tone. 0: Soft-P WM invalid 1: Soft-P WM valid 11 1 0 3 71 Applied m otor 0, 1 00: T ...

  • Mitsubishi FR-S500 - page 65

    55 Function (Parameter) list 2 FUNCTIONS Paramet er List Operat ion s election fu nction s 75 Reset selec tion/ PU stop s electi on 0: Reset nor mally enabl ed/PU st op key di sabled 1: Enabled at ala rm occur renc e only /PU sto p key di sabled 14: Res et nor mally enab led/no rma lly dec elerat ed to st op 15: Enabled at alarm occurren ce only/ n ...

  • Mitsubishi FR-S500 - page 66

    56 Function (Parame ter) list Para me ter List Multi-sp ee d operatio n functi on 84 Multi-s peed setti ng (spe ed 12) 0 to 12 0Hz, - - - 0.1Hz - - - 66 85 Multi-s peed setti ng (spe ed 13) 0 to 12 0Hz, - - - 0.1Hz - - - 66 86 Multi-s peed setti ng (spe ed 14) 0 to 12 0Hz, - - - 0.1Hz - - - 66 87 Multi-s peed setti ng (spe ed 15) 0 to 12 0Hz, - - - ...

  • Mitsubishi FR-S500 - page 67

    57 Function (Parameter) list 2 FUNCTIONS Paramet er List Maintenance p ar ameters Additional p arameters Parameter for manufacturer setting Func- tion Parame- ters Indi- catio n Name Setting Range Minimu m Setti ng Incre- ment s Fact ory Setti ng Ref er To : Cus- tomer Setting Main tenance f unction H1 (5 03) Ma inten ance timer 0 to 999 1 (100 0h) ...

  • Mitsubishi FR-S500 - page 68

    58 Function (Parame ter) list Para me ter List Calibration parameters * Factory settings may dif fer because of calibration p arameters. Func- tion Parame- ters Indi- catio n Name Setting Ra nge Minimum Setting Incre- ment s Fact ory Setti ng Refer To : Cus- tome r Setting Calibratio n paramete rs C1 (9 01) AM termi nal cali bration    ...

  • Mitsubishi FR-S500 - page 69

    59 Function (Parameter) list 2 FUNCTIONS Paramet er List Communication Pa r ameters Func tion Parame- ter Indi ca- tion Name Settin g Range Minimu m Setting Incre- ments Facto ry Settin g Refer To : Cus- tomer Setti ng Communicatio n Parameters n1 ( 331) Commun ication statio n number 0 to 31: S peci fy the s tation number of th e inver ter . 10 1 ...

  • Mitsubishi FR-S500 - page 70

    60 Function (Parame ter) list Para me ter List PU parameters When the p arameter unit (FR-PU04) is used, operation from the operation p anel is not accepted. (The stop key ( ) is valid) Func tio n Para me- ter Indi ca- tion Name Setting Range Minimu m Sett ing Incre- ments Facto ry Setting Refer To : Cus- tomer Setting PU p arameter s n13 (145 ) PU ...

  • Mitsubishi FR-S500 - page 71

    61 List of pa rameters classifie d by purpose of use 2 FUNCTIONS 2.2 List of p aram eters classified by pu rpose of use Set the p arameters according to the operating conditi ons. The following list i ndicates purpose of use and corresponding parameters. Purpo se of Use Parameter Numbe rs Parameter numbers which must be s et Rela ted to ope ration ...

  • Mitsubishi FR-S500 - page 72

    62 List of parameters classified b y purpose o f use Related to monit o rin g Fre quenc y meter calibr ation Pr . 54, Pr . 55, Pr . 56, cali brat ion p aram eter C 1 Dis play of mon itor on o perat ion panel or parame ter un it (FR-P U04) Pr . 52, Comm unicat ion parameter n16 Disp lay of speed , etc. Pr . 37, Pr . 52 Related to inc o rrect opera t ...

  • Mitsubishi FR-S500 - page 73

    63 Explanati on of fun ctions (param eters) 2 FUNCTIONS 2.3 E xp lanation of f unctions (p arameters) 2.3.1 T orque boost (Pr . 0 , Pr . 46 ) <Setting> • Assuming that the base frequency volt age is 100%, set the 0Hz voltage in %. Use the R T signal to s witch between two dif ferent torque boosts. (T ur n on the RT signal to make Pr . 46 va ...

  • Mitsubishi FR-S500 - page 74

    64 Explanation of functi ons (parameters) 2.3. 2 Maximum a nd minimum frequenc y (Pr . 1 , Pr . 2 ) <Setti ng> • Use Pr . 1 to set the upper limit of the output frequenc y . If the frequency of the frequency command enter ed is higher than the setting, the output frequency is clamped at the maximum frequency . • Use Pr . 2 to set the lowe ...

  • Mitsubishi FR-S500 - page 75

    65 Explanati on of fun ctions (param eters) 2 FUNCTIONS 2.3.3 Base fr equency , base frequency volt age (Pr .3 , Pr .19 , Pr .47 ) *1. 1 .9 ti mes gre ater than the powe r supply v oltage for the FR- S510W E-0. 1K to 0.75 K. *2 . T wic e greate r than the pow er supp ly volt age fo r the FR -S510WE- 0.1K to 0 .75K. <Setting> • In Pr . 3 and ...

  • Mitsubishi FR-S500 - page 76

    66 Explanation of functi ons (parameters) 2.3.4 Multi-speed operation (Pr . 4 , Pr . 5 , Pr . 6 , Pr . 24 to Pr . 27 , Pr . 80 to P r . 87 ) <Setti ng> • Set the running frequencies in the c orr esponding parameters. Each speed (frequency) can be set as desired between 0 and 120Hz during inverter operation. When the pa r ameter of any multi ...

  • Mitsubishi FR-S500 - page 77

    67 Explanati on of fun ctions (param eters) 2 FUNCTIONS 2 . 3. 5 Accelerat ion/deceleration time (Pr . 7 , Pr . 8 , Pr . 20 , Pr . 44 , Pr . 45 ) CAUTION 1. The multi-speed settings o verride the main sp eeds (across terminals 2-5, 4- 5, setting dial). When the multi- speed settings and set ting dial are used in the co mbined operatio n mode (Pr . ...

  • Mitsubishi FR-S500 - page 78

    68 Explanation of functi ons (parameters) <Setti ng> • Use Pr . 7 and Pr . 44 to set the accelerati on time required to reach the frequency set in Pr . 20 from 0Hz. • Use Pr . 8 and Pr . 45 to set the dec elerati on time required to reach 0Hz from the frequency set in Pr . 20. • Pr . 44 and Pr . 45 are valid when the R T signal is on. ( ...

  • Mitsubishi FR-S500 - page 79

    69 Explanati on of fun ctions (param eters) 2 FUNCTIONS 2.3 .6 Selecti on and protection of a motor ( Pr . 9 , Pr . 71 , H7 ) • The parameter nu mber i n parentheses is the one fo r use with t he parameter uni t (FR-PU0 4). <Setting> • Refer to the followi ng list an d set Pr . 7 1 accordin g to the motor u s ed. Sett ing "100 or 101 ...

  • Mitsubishi FR-S500 - page 80

    70 Explanation of functi ons (parameters) REMARKS • When running tw o motor s with one inv ert er , you c an set the electr onic therm al re lay fun ctio n of e ach invert er . CAUTION Set this para m eter correctly according to the m otor used. Incorrect setting may cause the motor to overheat and burn. Pr . 71 appli ed motor Firs t Mo tor E lec ...

  • Mitsubishi FR-S500 - page 81

    71 Explanati on of fun ctions (param eters) 2 FUNCTIONS 2.3.7 DC injec tion brake (Pr . 10 , Pr . 1 1 , Pr . 12 ) * The fac tory setting va ries acc ording to the inve rter capacity . (Refer to the follo wing table fo r details.) <Setting> • Use Pr . 10 to set the frequency at which the DC injection brake operation is st ar ted. • Use Pr ...

  • Mitsubishi FR-S500 - page 82

    72 Explanation of functi ons (parameters) 2.3.8 S tarting frequency (Pr . 13 ) The starting frequency at which the st art signal is turned on can be set in the range 0 to 60Hz. Paramet er Name Factory Sett ing Sett ing Range Remarks 13 S tart ing freq uency 0.5Hz 0 to 60Hz Setti ng is enabl ed when Pr . 30 = "1". CAUTION The inverter will ...

  • Mitsubishi FR-S500 - page 83

    73 Explanati on of fun ctions (param eters) 2 FUNCTIONS 2.3.9 Load pattern se lection (Pr . 14 ) Y ou can select the optimum output c haracteristic (V/F characteris tic ) for the application and load charac teristics. Parame ter N a m e Fact ory Sett ing Set ting Range Remar ks 14 Load patt ern sele ctio n 1 0, 1, 2, 3 0: Fo r const ant-to rque lo ...

  • Mitsubishi FR-S500 - page 84

    74 Explanation of functi ons (parameters) 2.3.10 Jog operation (Pr .15 , Pr .16 ) Set the frequency and acceleration/deceleration time for jog operation. 2.3 .1 1 RUN key rotation dir ection selection (Pr .17 ) Re fer t o (pag e 65 ) Refer to , (page 67) T o s tart/stop jog ope ration in the exter nal op erat ion mo de, ch oose t he jog operat ion ...

  • Mitsubishi FR-S500 - page 85

    75 Explanati on of fun ctions (param eters) 2 FUNCTIONS 2 .3 . 1 2 S t all preven t ion function and c urrent limit function (Pr . 21 ) Y ou c an make setting to prev ent stall caused by overcurre nt and/or to prev ent the inverter from r esulting in an overcurr ent trip (to disable high- respons e current restriction tha t limits the current) when ...

  • Mitsubishi FR-S500 - page 86

    76 Explanation of functi ons (parameters) CAUTION • If the load is heavy , th e lif t is pred etermined, o r the acceleration/deceleration time is short, the stall prevention may be activated and t he motor no t stopped in the preset acceleration/deceleration time. Th erefore, set optimum values to the Pr . 21 a n d st all preven tion operation l ...

  • Mitsubishi FR-S500 - page 87

    77 Explanati on of fun ctions (param eters) 2 FUNCTIONS 2.3.1 3 S tall preve ntion (Pr . 22 , Pr . 23 , Pr . 2 8 ) <Setting> • Generally , set 150% (factory s etting) in Pr . 22 "stal l prevention operation level". Setting "0" in Pr . 22 disables stall prevention operation. • T o reduce the stall prevention operation l ...

  • Mitsubishi FR-S500 - page 88

    78 Explanation of functi ons (parameters) to Refer to to (page 66 ) REMARKS When the hi gh resp onse c urre nt lim it is se t in Pr . 21 "s tal l prev enti on func tion se lecti on" (factor y setting ), do not set any val ue abo ve 170% i n Pr . 22. The torqu e will not be devel oped by doing so. If the Pr . 22 value is set to high er tha ...

  • Mitsubishi FR-S500 - page 89

    79 Explanati on of fun ctions (param eters) 2 FUNCTIONS 2.3.14 Acceleration/decel e ration pattern (Pr . 29 ) <Setting> Set the acceleration/deceleration p attern. Para m eter N a m e F actor y Sett ing Sett ing Range Remarks 29 Acceler ation/ deceler ation patter n 0 0, 1 , 2 Setting is enab led when Pr . 30 = "1". Pr . 29 Sett ing ...

  • Mitsubishi FR-S500 - page 90

    80 Explanation of functi ons (parameters) 2.3.15 Extended function disp lay selection (Pr . 30 ) 2.3. 16 Frequency jump ( Pr . 31 to P r . 36 ) <Setti ng> Used to display the extended function p arameters. Refer to page 48 for the extended func tion parameter list. Refer to the instruction manual (basic) for the parameter setting method. Para ...

  • Mitsubishi FR-S500 - page 91

    81 Explanati on of fun ctions (param eters) 2 FUNCTIONS 2.3 .17 Sp eed d ispl ay (P r . 3 7 ) <Setting> • T o display the machine speed, set in Pr . 37 the machine speed for 60Hz operation. Y ou can change the output fr equency indi c ation or set frequency of the operation panel and p ar ameter unit (FR-PU04) to the motor speed or machine ...

  • Mitsubishi FR-S500 - page 92

    82 Explanation of functi ons (parameters) 2.3. 18 Biases and ga ins of the fr equency sett ing voltage (current ) (Pr . 38 , Pr . 39 , C2 to C7 ) *1. Fact ory setting s may differ be caus e of cali brat ion para meter s. *2. The para meter numb er in parent hese s is th e one for use wi th the paramete r unit (FR-P U04). Y ou can set the m agnitude ...

  • Mitsubishi FR-S500 - page 93

    83 Explanati on of fun ctions (param eters) 2 FUNCTIONS <Setting> (1) How to change the highest frequency (2) Adjusting th e deviation of the highest frequency from the Pr . 38 (Pr . 39) setting. (2) -1) Make ad just ment with a vo ltage appl ied direc tly across term inals 2-5 (with a current fl owing ac ross terminal s 4-5) (2)-2) Mak e adj ...

  • Mitsubishi FR-S500 - page 94

    84 Explanation of functi ons (parameters) (2) Adjusting a deviat ion of the highest frequency from the Pr . 38 (Pr . 39) set t ing. (2)- 1 Making a djustment wi th a volt age applied dire ctly across termin als 2-5 (with a current flowing acros s termina ls 4-5) Changing examp le Changing the c al ibration parameter C4 "frequency setting volta ...

  • Mitsubishi FR-S500 - page 95

    85 Explanati on of fun ctions (param eters) 2 FUNCTIONS (2) - 2 Mak ing ad justment at any poin t with a volt age not applie d across ter minals 2- 5 (without a curr ent fl owing acros s terminals 4-5 ) REMARKS For the way to ch ange th e outp ut freq uency s etting of the frequ ency se tting potent iometer , ref er to the in stru ctio n man ual (b ...

  • Mitsubishi FR-S500 - page 96

    86 Output terminal function param eters 2.3.19 S tart-time g round faul t detection selection (Pr . 40 ) 2.4 Out p ut terminal function p arameters 2.4.1 Up-to-f requency (Pr . 41 ) Use Pr . 64 or Pr . 65 (output terminal function selection) to assign the terminal used for SU signal output. Y ou can choos e whether to make gr ou n d fault det ectio ...

  • Mitsubishi FR-S500 - page 97

    87 Output terminal functio n parameters 2 FUNCTIONS 2.4.2 Output frequency detection (Pr . 42 , Pr . 43 ) <Setting> Refer to the above chart and set the corresponding parameters. • When Pr . 43 "output frequency detection for reverse rotation" ≠ "- - -", the Pr .42 setting applies to forward rotation and the P r .43 se ...

  • Mitsubishi FR-S500 - page 98

    88 Cur rent detec tion fu nction pa rameters 2.5 Current detection function p aram eters 2.5.1 Outp ut current detection f unctions (Pr . 48 , Pr . 49 ) <Setti ng> Use Pr . 64 or Pr . 65 (output terminal function selection) to assign the terminal used for Y12 signal output. If the output remains higher than the Pr . 48 setting during i nv ert ...

  • Mitsubishi FR-S500 - page 99

    89 Cur rent detec tion fu nction pa rameters 2 FUNCTIONS 2.5.2 Zero current detection (Pr . 50 , Pr . 51 ) <Setting> Use Pr . 64 or Pr . 65 (output terminal func tion selection) to assign the term i nal used for Y13 signal output. When the inverter's output current falls to "0[A]", torque will not be generated. This may cause a ...

  • Mitsubishi FR-S500 - page 100

    90 Display functi on parameters 2.6 Display function p arameters 2.6. 1 Monitor display (Pr . 52 , Pr . 54 ) <Setti ng> When "100" is set in Pr . 52, the monitored values during stop and during operation differ as indic ated bel ow . Y ou can choose the display of the operation panel "monitor/frequency setting screen". Par ...

  • Mitsubishi FR-S500 - page 101

    91 Disp lay funct ion param eters 2 FUNCTIONS 2.6.2 Setting dial function selection (Pr . 53 ) Using the setti ng dial like a poten tio meter to perform operation Refer to (pag e 90). Y ou can use the dial like a potentiometer to perform operation. Para meter N ame Fact ory Sett ing Setting Range Remarks 53 Freq uency setti ng oper ation se lecti o ...

  • Mitsubishi FR-S500 - page 102

    92 Restart operation parameters 2.6. 3 Monitoring refer ence (Pr . 55 , Pr . 56 ) <Setti ng> Refer to the a bove d iag rams a nd s et t he freq uenc y moni tor ing r efer ence va lue in Pr . 55 and the current moni toring reference value in Pr . 56. Pr . 55 is set when Pr . 54 "A M terminal function selection" = "0" and Pr ...

  • Mitsubishi FR-S500 - page 103

    93 Restart operation parameters 2 FUNCTIONS <Setting> Refer to the following table and set the parameters: Par ameter S etti ng Descri ption 57 0 0.1K to 1. 5K Co asting t ime of 0.5 s Gen erally , this setting w ill pose no pr oblem s. 2.2K , 3.7K Coas ting ti me of 1.0s 0.1 to 5s W ai ting ti me f or inve rter-t rigg ered re start afte r po ...

  • Mitsubishi FR-S500 - page 104

    94 Restart operation parameters REMARKS • When the start si gnal is turne d off duri ng powe r fail ure and power i s rest ored Wi thout speed sea rch (H6=1): Dece lerat es to stop af ter run ning in th e same dire ctio n before power f ailure. Note that the motor will coast if the st art si gnal is tu rned o f f duri ng res tart opera tio n. If ...

  • Mitsubishi FR-S500 - page 105

    95 Addit ional fu nction par ameters 2 FUNCTIONS 2.8 Addition al function p arameters 2.8.1 Remote setting function sele ction (Pr . 59 ) * External running fr equency (other than multi-speed) or PU running frequency If the operation panel is located away from the control box, you can use contact signals to perform continuous v ar iable-speed opera ...

  • Mitsubishi FR-S500 - page 106

    96 Addit ional funct ion param eters <Setti ng> • Use Pr . 59 to select whether the remote setting function is used or not and whether the frequency setting storage function* in the remote s etting mode is used or not. When "remote setting functi on - yes" i s selected, the functions of signals RH, RM and RL are changed to acceler ...

  • Mitsubishi FR-S500 - page 107

    97 Addit ional fu nction par ameters 2 FUNCTIONS <Frequenc y setting stor age conditions > • The frequency at which the start signal (STF or STR) turns off is stored. • The remotely-set frequency is stored every one minute after one minute has elapsed since turn of f (on) of both the RH (acceleration) and RM (dec el eration) signals. (The ...

  • Mitsubishi FR-S500 - page 108

    98 T ermin al funct ion sel e cti on param eters 2.9 T ermi n al fun ction selec tion p arameter s 2.9.1 Input terminal function s election (Pr . 60 , Pr . 61 , Pr . 62 , Pr . 63 ) CAUTION • The frequency can be varied by RH (acceleration) and RM (deceleration) between 0 and the m aximum frequen cy (Pr . 1 sett ing). • When the acceleration or ...

  • Mitsubishi FR-S500 - page 109

    99 Termi nal function s election p arameters 2 FUNCTIONS <Setting> Refer to the following table and set the parameters: *1.W hen Pr . 59 = "1 or 2" , the functions of the RL, RM and RH signals change as listed above. *2.A c tuated when the relay contact "opens". *3.W hen using the REX signal, an external command cannot be ...

  • Mitsubishi FR-S500 - page 110

    100 T ermin al funct ion sel e cti on param eters 2. 9 . 2 Outpu t terminal function selec tion (Pr . 64 , Pr . 65 ) <Setti ng> Y ou can change the functions of the open collector output terminal and cont act output terminal. Parameter Name Fact ory Sett ing Settin g Ra nge Rem arks 64 RUN ter minal fun ction sele ction 0 0, 1, 3, 4, 1 1 to 1 ...

  • Mitsubishi FR-S500 - page 111

    101 Oper ation select ion funct ion paramete rs 2 FUNCTIONS 2.10 Operati on selection function p arameters 2 . 1 0 . 1 Retry function (Pr . 66 , Pr . 67 , Pr . 68 , Pr . 69 ) <Setting> • Use Pr . 66 to s elect the protective functions (major faults) to be activated for retries. * Indicates the retry items selected. (OCT denotes any of OC1 t ...

  • Mitsubishi FR-S500 - page 112

    102 Operation selection function param eters CAUTION • The cumu lative number in Pr . 69 is incremented by "1" when retry op eration is regarded as successfu l, i.e. when no rmal operation is continued without the protective fun ction (major f ault) acti vated during a p eriod four times longer than the time set in Pr . 68. • If the p ...

  • Mitsubishi FR-S500 - page 113

    103 Oper ation select ion funct ion paramete rs 2 FUNCTIONS 2.10 .2 PWM ca rrier frequency ( Pr . 70 , Pr . 72 ) <Setting> • By p ar ameter setting, you c an s et whether to ex ercise Sof t- PWM c ontr ol that changes the motor tone. • Soft-PWM c ontrol is a control system that c hanges the motor noise from a metallic tone into an unoffen ...

  • Mitsubishi FR-S500 - page 114

    104 Operation selection function param eters 2.10.3 V oltage input selection (P r . 73 ) Y ou c an change th e input (terminal 2 ) specifi cations ac cording to the frequ ency setting voltage signal. Whe n entering 0 to 10VDC , always make thi s setting. Parameter Name Factor y Sett ing Sett ing Range R emarks 73 0-5V/0- 10V sele cti on 00 , 1 T er ...

  • Mitsubishi FR-S500 - page 115

    105 Oper ation select ion funct ion paramete rs 2 FUNCTIONS 2.10.4 Input filter time constant (Pr . 74 ) <Setting> Increase the filter ti me constant if steady operation cannot be performed due to noise. A larger setting result s in slower response. (The time constant c an be set between approximately 1ms to 1s with the setting of 0 to 8. A l ...

  • Mitsubishi FR-S500 - page 116

    106 Operation selection function param eters (1) How to make a rest art af ter a stop by the input from the operati on p anel (Rest artin g method with shown) (2) How to make a rest art when a stop is made by the in put from t he PU Besides the above operations, a rest art c an be made by performing a power-on reset or resetting the inverter with t ...

  • Mitsubishi FR-S500 - page 117

    107 Oper ation select ion funct ion paramete rs 2 FUNCTIONS 2.10.6 Cooling fan operation selection (Pr . 76 ) <Setting> CAUTION Do not reset the inverter w ith the st art sign al on. Otherwise, the motor wi ll st art inst ant ly af ter resetting, leading to potentially ha zardous conditions. Y ou can control the operation of the cooling fan b ...

  • Mitsubishi FR-S500 - page 118

    108 Operation selection function param eters 2.10 .7 Paramet er write disable selection (Pr . 77 ) <Setti ng> Y ou can select between write-enable and disable for parameters. This fu nc tion is used to prevent parameter values from being rewritten by incorrect operation. Parameter Name Fact ory Setting Se tting Range R emarks 77 Para meter wr ...

  • Mitsubishi FR-S500 - page 119

    109 Oper ation select ion funct ion paramete rs 2 FUNCTIONS 2.10 .8 Reverse rotation preven tion selection (P r . 78 ) <Setting> 2.10 .9 Operation mode selec tion (Pr . 79 ) This function can prevent reverse rot ation faults resulting from the in correct input of the start signal. POINT Used for a machine which runs on ly in one direction, e. ...

  • Mitsubishi FR-S500 - page 120

    11 0 Operation selection function param eters <Setti ng> In the following table, operation using the op er ation panel or parameter unit is abbreviated to PU operation. Pr . 79 Setting Function LED I ndicati on * RUN PU EXT 0 At powe r on, the inver ter is put i n the extern al oper ation m ode. The ope rat ion mode can be chang ed bet ween t ...

  • Mitsubishi FR-S500 - page 121

    111 Oper ation select ion funct ion paramete rs 2 FUNCTIONS (1) PU operati on interl ock PU operation interlock forces the operation mode to be chan ged to the external operation mode when the MRS signal switches off. This function prevents the inverter from being inoperative by the external command if the mode is accidentally lef t unswitched from ...

  • Mitsubishi FR-S500 - page 122

    11 2 Operation selection function param eters (2) Operation mode switching by exter nal signal 1) Preparation Set "8" (switching to other than external operation mode) in Pr . 79 . Use any of Pr . 60 to Pr . 63 ( input terminal function selection) to s et the terminal used for X16 signal input. 2) Function This switching is enabled during ...

  • Mitsubishi FR-S500 - page 123

    11 3 Oper ation select ion funct ion paramete rs 2 FUNCTIONS 2.10 .10 PID control ( Pr . 88 to Pr . 94 ) <Setting> (1) Basic PI D cont rol configurat ion (2) PID action overvi ew The inverter can be used to exercise process control, e.g. flow rate, air volume or pressure. The voltage input signal (0 to +5V or 0 to +10V) or Pr . 93 setting is ...

  • Mitsubishi FR-S500 - page 124

    11 4 Operation selection function param eters 2) P D action A combination of proportional control action (P) and differential control action (D) for providing a manipulated variable in response to dev iation speed to improve the transient characteristic. [Operation example f or proportional changes of m easured value] REMARKS PD act ion is th e sum ...

  • Mitsubishi FR-S500 - page 125

    11 5 Oper ation select ion funct ion paramete rs 2 FUNCTIONS Relationship s b etween deviation and ma nipulated variable ( output frequency) (3) Wiring ex ample 5) Forward action Increases the manipulated variable (output frequency) if deviation X = (set point - measured value) is negative, and decreases the manipulated variable if deviation is pos ...

  • Mitsubishi FR-S500 - page 126

    11 6 Operation selection function param eters (4) I/O s ign als • Enter the set point across inverter terminals 2-5 or in Pr . 93 and enter the measured value signal across inverter terminals 4-5. • T o exercise PID control, turn on the X14 signal. When this signal is off, P ID control is not exercised. (5) Parameter sett i ng Signal T erminal ...

  • Mitsubishi FR-S500 - page 127

    11 7 Oper ation select ion funct ion paramete rs 2 FUNCTIONS (6) Adjustm ent procedure 91 PID upper lim it 0 t o 10 0% Set th e upper limit . If the f eedba ck valu e exce eds th e sett ing, th e FUP signa l is outp ut. ( Meas ured value of 4mA is eq uiva lent to 0 % and 20 mA to 100 %.) - - - No func tio n 92 PID lower lim it 0 t o 10 0% Set t he ...

  • Mitsubishi FR-S500 - page 128

    11 8 Operation selection function param eters (7) Calibra tion exampl e (A detector of 4mA at 0°C (32°F) and 20mA at 50°C ( 122°F) is used to adj ust the room temperature to 25°C (77°F) under PID control. The set point is gi ven to across inverter terminals 2-5 (0-5V).) ST ART Is the setting value steady? Adjust parameters. END Ye s No Set &q ...

  • Mitsubishi FR-S500 - page 129

    11 9 Oper ation select ion funct ion paramete rs 2 FUNCTIONS <Set point input calibration> 1. Apply the input volta ge of 0% set point setting (e.g. 0V) across terminals 2-5. 2. Make calibration using the calibration p ar ameters C2, C3. At thi s time, enter in C2 the frequency which should be output by the i nverter at the deviation of 0% (e ...

  • Mitsubishi FR-S500 - page 130

    120 Auxiliary parameters 2.1 1 Auxiliary p arameters 2.1 1.1 Slip compe nsation (Pr . 95 , Pr . 96 , Pr . 97 ) <Setti ng> *When this value is made smaller , response will be faster . However , as load inertia is greater , a regenerative overvoltag e (O VT) error is more liable to occur . The inverter output current may be used to as s ume mot ...

  • Mitsubishi FR-S500 - page 131

    121 Auxiliary parameters 2 FUNCTIONS 2.1 1 .2 Automatic torque boo st se lection (Pr . 98 ) <Operat i ng conditi ons> • The number of motor poles should be any of 2, 4 and 6 poles. • Single-motor operation (One motor for one inver ter) • The wiring length from inverter to motor s hould be within 30m (98.42feet). <Setting> • Also ...

  • Mitsubishi FR-S500 - page 132

    122 Maintenance parameters 2.1 1.3 Motor primar y resist ance (Pr . 99 ) 2.12 Maintenance p ar ameters 2.12.1 Maintenance output function (H1 , H2 ) The parameter numbers in parentheses are those for use with the parameter unit (FR- PU04). <Setti ng> Generally this parameter need not be set. At the factory setting of "- - -", the st ...

  • Mitsubishi FR-S500 - page 133

    123 Maintenance parameters 2 FUNCTIONS 1) H1 (Pr . 503) "maintenance timer" • The cumulative energization time of the inverter is stored i nto the E 2 PROM every hour and indicated in 1000h increments . ( Cannot be written.) • The maintenance timer is clamped at 999 (999000h). 2) H2 (Pr . 504) "maintenance alarm output set time&q ...

  • Mitsubishi FR-S500 - page 134

    124 Maintenance parameters <Pulse operation> The output pulse of the Y93 signal is shown below . <Setting> Perform setting according to the following steps. 1) Setting of maintenance p arameter H4 " dat a output mask time" The output current is unstable (transient state) right af ter the operation is changed from the accelerat ...

  • Mitsubishi FR-S500 - page 135

    125 Maintenance parameters 2 FUNCTIONS 4) Output of maintenance timer value (maintenance parameter H1) After the output current average value is output as low pul se shape, the maintenance timer value is output as high pulse shape. The output time of the maintenance timer value is obtai ned from the fol lowing calculation. Refer to (page 92). Refer ...

  • Mitsubishi FR-S500 - page 136

    126 Cal ibration pa rameter s 2.13 Calibrati on p aramet ers 2.13.1 Meter (frequency meter) calibration (C1 ) The parameter number in parentheses is the one for us e with the parameter unit (FR- PU04). The AM terminal is factory-set to provide 5VDC output in the full-scale status of each monitor item. However , calibration parameter C1 can be used ...

  • Mitsubishi FR-S500 - page 137

    127 Calibration parameters 2 FUNCTIONS Changing example Deflecting the meter ( analog indicator) to full-s cale (5V) at the preset frequency of 60Hz (for frequency setting, refer to the instruction manual (basic).) POINT • The calibration parameters "C1" can be made to be ready by setting "1" (extended function parameter valid ...

  • Mitsubishi FR-S500 - page 138

    128 Cal ibration pa rameter s to Refer to , ( page 82). POINT By setting the Pr . 54 "A M terminal function selection" value, preset Pr . 55 "fr equency monitoring reference" or Pr . 56 "current monitoring refer ence" to the running frequency or current value at which the output signal is 5V . At 5V , the meter general ...

  • Mitsubishi FR-S500 - page 139

    129 Clear parameters 2 FUNCTIONS 2.14 Clear p arameters 2.14.1 Paramete r clear (CLr ) *1.P ar ameters are not cl eared by setting "1" in Pr . 77 "p arameter write di sable selec tion". Pr . 75, Pr . 38, Pr . 39, Pr . 53, Pr . 60 to Pr . 65, Pr . 99, maintenance p arameters H1, H2, calibration parameters C1 to C7 and communicati ...

  • Mitsubishi FR-S500 - page 140

    130 Communication parameters 2.15 Communicati on p arameters (1) Operationa l functions 1) Operation mode switching [Operation mode switching method] *1. * When "1" is set in the communication p arameter n10 "link st artup mode selection", the inverter is placed in the compute r link operation mode at power on or inverter reset. ...

  • Mitsubishi FR-S500 - page 141

    131 2 FUNCTIONS Communication parameters 2) Operation mode-based functions *1. As set in the co mmun icati on paramet ers n8 "op erati on comman d sourc e" and n9 "sp eed comm and sou rce". (refer to page 147 ) *2. A t occurrence of RS -485 communi cation error , the inverter c annot be res et from the computer . *3. As set in P ...

  • Mitsubishi FR-S500 - page 142

    132 Communication parameters 2.15.1 Communication settings (n1 to n7 , n1 1 ) Communication-related parameters • The parameter numbers within p arentheses are those for use of the p ara meter unit (FR-PU04). • Refer to page 180 for the instruction codes. Communication specifications Paramet er N a m e Factory Setting Sett ing Range Remark s Ref ...

  • Mitsubishi FR-S500 - page 143

    133 Communication parameters 2 FUNCTIONS <Setting> T o make communication between the per sonal computer and inverter , i nitialization of the communication s pec ifications mus t be made to the inverter . If initial setting i s not made or there is a setting fault, data transfer cannot be made. * Af ter making the initial setting of the para ...

  • Mitsubishi FR-S500 - page 144

    134 Communication parameters <Computer programming> (1) Communication prot ocol Data communic ati on between the computer and inverter is performed using the following procedure: (2) Communication operation presence/absence and dat a format types Communication operation presence/absence and data format typ es are as follows: * In the c ommuni ...

  • Mitsubishi FR-S500 - page 145

    135 Communication parameters 2 FUNCTIONS (3) Dat a format Data used is hex adecimal. Data is automati c ally transferred in ASCII between the co mputer and i nverter . Data format types 1) Communication reques t dat a fr om computer to inverter 2) Reply dat a fr om inverter to computer during data write 3) Reply dat a fr om inverter to computer dur ...

  • Mitsubishi FR-S500 - page 146

    136 Communication parameters 4) S end dat a fr om comp uter to inverter dur ing data read (4) Dat a definit ions 1) Co ntrol codes 2) In verter st ation number S pecify the st ati on number of the inverter which communicates with the computer . 3) In struction code S pecify the processing reques t, e.g. operation or monitoring, given by the compute ...

  • Mitsubishi FR-S500 - page 147

    137 Communication parameters 2 FUNCTIONS 5) W aitin g time S pecify the waiting time between the receipt of dat a at the inverter from the computer and the transmission of reply data. Set the waiting time in accord anc e with the response time of the computer between 0 and 150ms in 10ms increment s (e.g. 1 = 10ms, 2 = 20ms). 6) Resp onse time [Form ...

  • Mitsubishi FR-S500 - page 148

    138 Communication parameters 7) O pen cable detection (Commu nication par am eter n6 "communicatio n check time interval") · If disconnection (communication stop) is detected between the inverter and computer as a result of disconnection check, a communication error (OPT) occurs and the inverter output is shut off. · Disconnection check ...

  • Mitsubishi FR-S500 - page 149

    139 Communication parameters 2 FUNCTIONS 8) Sum check code The sum check code is 2-digit ASCII (hex adecimal) representing the lower 1 by te (8 bits) of the sum (binary) derived from the checked ASCII dat a 9) Error code If any error i s found in the data received by the inverter , its definition is sent back to the computer together with the NAK c ...

  • Mitsubishi FR-S500 - page 150

    140 Communication parameters CAUTION Always set the commu nication check tim e interval before st arting operation t o prevent hazardous conditio ns. Dat a com munication is not st arted automat ically but is made on ly once when the comp uter provides a comm unicat ion request. If co mmunication is disabled during op eration due to signal cable b ...

  • Mitsubishi FR-S500 - page 151

    141 Communication parameters 2 FUNCTIONS <Setting items and set dat a> Af ter complet ion of p arame ter settin gs, set t he instruct ion codes a nd dat a then s tart communica tion from t he comp uter to allo w various types of operation control a nd monit oring. No. It e m Instruction Code Description Num ber of Dat a Digit s 1 Oper ation m ...

  • Mitsubishi FR-S500 - page 152

    142 Communication parameters 3 Run command HF A * F un ction ch ange ca n be ma de using Pr . 60 to Pr . 63 (inp ut ter minal func tion sel ect ion). 2 digi ts 4 Inv erter st at us monitor H7A * F un ction c hange can b e made usin g Pr . 64 an d Pr . 6 5 (ou tput termi nal functi on sele cti on). 2 digi ts No. It e m I nstruction Code Descrip tion ...

  • Mitsubishi FR-S500 - page 153

    143 Communication parameters 2 FUNCTIONS 5 Set freque ncy read (RAM) H6D • When P r . 3 7 = "0" ( factor y setting ) The set freq uency (RAM or E 2 PR OM) is read . H0000 t o H2EE0: 0.01H z increme nts • When Pr . 37 = " 0.1 to 999", ex pansio n link parame ter (HF F) = 0 Th e set speed is read. H0000 t o H03E7: 1r/mi n incr ...

  • Mitsubishi FR-S500 - page 154

    144 Communication parameters 8 All par amete r cle ar HFC All p aramet ers retu rn to the factor y sett ings. Any of four different all cle ar ope ration s are pe rfor med acco rdin g to th e data. Whe n all parame ter clea r is ex ecuted f or H969 6 or H9966 , c ommunic ation- rel ated par ameter se ttings al so ret urn to th e fact ory se tting s ...

  • Mitsubishi FR-S500 - page 155

    145 Communication parameters 2 FUNCTIONS <Error Code List> The corresponding error code in the following list is displayed i f an error is detected i n any communication request data from the c omputer: (5) Operation at alarm occurre nce *3: C an be selected using the corresponding parameter (factory-set to stop). (6) Communication error Erro ...

  • Mitsubishi FR-S500 - page 156

    146 Communication parameters (7) Program example Program General flowchart T o change the oper ation mode to computer link operation 1000 *R EC 1010 IF L OC(1)=0 THEN RE TURN 1020 PRIN T"RE CEIVE D ATA" 1040 RET URN 140 GOT O 50 Interru pt d ata r eceive 10 30 P RINT INPU T$(L OC(1 ),# 1) 130 PRI NT#1,D$ Data send Initia l s etting of I/ ...

  • Mitsubishi FR-S500 - page 157

    147 2 FUNCTIONS Communication parameters 2.15.2 Operation and speed command source (n8 , n9 ) The parameter numbers within parenthes es are those for use of the p arameter unit (FR-PU04). <Setting> In the computer operati on mode, commands from the ex ternal terminals and c omputer are as listed below . (Refer to page 98 for Pr . 60 to Pr . 6 ...

  • Mitsubishi FR-S500 - page 158

    148 Communication parameters [Explanation o f t able] External : Operation is valid only from external terminal s ignal. Computer : Operati on is valid only from computer . Combined : Operation is valid from either of external terminal and computer .  : Operation is invalid from either of external terminal and computer . 2.15.3 Link startup mode ...

  • Mitsubishi FR-S500 - page 159

    149 2 FUNCTIONS Communication parameters <Setting> • n10 can be changed independently of the operation mode of the operation p anel . • Setting of n10 = "1" is made valid when "0" or "2" is s et in Pr . 79 "operation mode sele ction" . Refer to to ( p age 132) n10 Sett ing Pr . 79 Se tting Oper atio ...

  • Mitsubishi FR-S500 - page 160

    150 Communication parameters 2.1 5.4 E 2 PROM write selection (n 12 ) The par amete r num ber in parenth eses is th e one f or use wit h the paramet er uni t (FR- PU04) . Y ou can choose whether the parameters are stored into the E 2 PROM or not at the p ar ameter setting for c omputer communication. When performi ng p arameter write frequently , w ...

  • Mitsubishi FR-S500 - page 161

    151 Parameter u nit (FR-P U04) setti ng 2 FUNCTIONS 2.16 Parameter unit (FR-PU04) setti n g 2.16.1 PU display language selection ( n13 ) The parameter number in parentheses is the one for us e with the parameter unit (FR- PU04). <Setting> 2.16.2 PU buzzer control (n14 ) The parameter number in parentheses is the one for us e with the paramete ...

  • Mitsubishi FR-S500 - page 162

    152 Parameter un it (FR-PU 04) setting 2.16 .3 PU contra st adjustment ( n15 ) The parameter number in parentheses is the one for us e with the parameter unit (FR- PU04). 2.16 .4 PU main disp lay screen dat a selecti on (n16 ) The parameter number in parentheses is the one for us e with the parameter unit (FR- PU04). <Setti ng> When "100 ...

  • Mitsubishi FR-S500 - page 163

    153 Parameter u nit (FR-P U04) setti ng 2 FUNCTIONS 2.16.5 Disconnected PU dete ction/PU setting lock selection (n17 ) The parameter number in parentheses is the one for us e with the parameter unit (FR- PU04). <Setting> * The monitor display and the are valid. Y ou can choose the connector disconnection detection function of the parameter un ...

  • Mitsubishi FR-S500 - page 164

    154 MEMO ...

  • Mitsubishi FR-S500 - page 165

    155 Cha p t er 2 Cha p t er 3 Cha p t er 4 Cha p t er 1 3. PROTECTIVE FUNCTIONS This chapte r explains the "prot ective funct ions" of this product. Always r ead the in structions b efore using the equipment . 3.1 Erro rs (A larm s) . .... ..... .... .. ..... .... ..... .... ..... .... .... ..... 156 3.2 T r oubleshooting ..... .......... ...

  • Mitsubishi FR-S500 - page 166

    156 Errors (Alarms) 3.1 E rrors (Alarms) If any fault has occurred in the inverter , the corresponding protective function is activated to bring the inverter to an alarm stop and auto mati cally give the corresponding error (alarm) indication on the PU display . If your fault does not correspond to any of the following errors or i f you have any ot ...

  • Mitsubishi FR-S500 - page 167

    157 Errors (Alarms) 3 PROTECTIVE FUNCTIONS 3.1.1 Error (alarm) definitions (1) Maj or fai lur es When the pr otective f uncti on i s activated, the inverter output is shut of f and the al arm is output. Operat ion Panel Indi cation OC1 FR-PU04 O C During Acc Name Overcu rrent s hut-o ff du ring a ccele ration Description When the in verte r outpu t ...

  • Mitsubishi FR-S500 - page 168

    158 Errors (Alarms) Operat ion Pane l Indi cati on OV1 FR-PU04 OV During Acc Name Regen erat ive ov ervoltag e shut-off durin g acceler ati on Descript ion When the ma in circuit DC volt age in the inverter ris es to or above the spe cified value due to e xcessive reg enerative ene rgy during accele ration, the protective circuit is activated to st ...

  • Mitsubishi FR-S500 - page 169

    159 Errors (Alarms) 3 PROTECTIVE FUNCTIONS *1. Resetting the inverter initializes the internal thermal integratied data of the electronic thermal relay function. Operat ion Panel Indi cation THM FR-PU04 Motor Overload Name Mot or ov erload sh ut- off (ele ctroni c the rmal re lay f unct ion) (* 1) Description The el ectr onic ther mal rel ay fu nct ...

  • Mitsubishi FR-S500 - page 170

    160 Errors (Alarms) *2. F unctions only when any of Pr . 60 to Pr . 63 (input terminal function selection) is set to OH. Operat ion Pane l Indi cati on GF FR-PU04 G round Fa ult Name S tart- time o utput side ground faul t over curren t prot ect ion Descript ion This func tion stops the i nver ter o utpu t if a grou nd fau lt o vercu rren t flow s ...

  • Mitsubishi FR-S500 - page 171

    161 Errors (Alarms) 3 PROTECTIVE FUNCTIONS (2) Minor failures When the protective function i s activated, the output is not shut off. Y ou can m ak e parameter setting to output the minor fault signal. (Set " 98" in any of Pr . 64, Pr . 65 (output terminal function selection). Refer to page 100.) Operat ion Panel Indi cation PUE FR-PU04 P ...

  • Mitsubishi FR-S500 - page 172

    162 Errors (Alarms) (3) W arni ngs *3. T he stall preventi on oper ation current can be set as desired. It is factory-set to 150%. Operat ion Pane l Indi cati on OL F R-PU04 OL Name S tall prev ention (over current ) Descript ion During accel era tion If a cur rent of more than 1 50% ( * 3) of t he rat ed inv erter cu rrent f lows i n the moto r , ...

  • Mitsubishi FR-S500 - page 173

    163 Errors (Alarms) 3 PROTECTIVE FUNCTIONS Operat ion Panel Indi cation PS FR-PU04 PS Name PU sto p Description Pr . 75 "r eset sele ction/ PU st op se lecti on" ha d bee n set and a sto p was made by pres sing t he of the ope rati on pan el o r param eter uni t (FR- PU04) during op erat ion in the ex tern al oper ation mod e. Check p oin ...

  • Mitsubishi FR-S500 - page 174

    164 Errors (Alarms) (4) Write e rro rs Operat ion Pane l Indi cati on Er1 FR-PU04 Control Mode Name Write di sable er ror Descript ion • W rite was perfor med wi th "1" ( write disabl e) set in Pr . 77 "paramet er writ e disabl e sele ction". • Frequ ency jump se tting r ange overla pped. • P arame ter wri te was per forme ...

  • Mitsubishi FR-S500 - page 175

    165 3 PROTECTIVE FUNCTIONS Errors (Alarms) 3.1.2 T o know the operating status at the occurrence of alarm (only whe n FR-PU04 is used) When any al arm has o ccurred, th e display automatic ally swit ches to the i ndication of the corres ponding prot ective function (e rror). By pressi ng the at this poi nt without resetti ng the invert er , the dis ...

  • Mitsubishi FR-S500 - page 176

    166 Trou bles hoo ting 3.2 T r oubleshooting POINTS If the cause is still unknown after every check, it i s recommended to initialize the parameters (return to factory setting) then r e-set the required p ar ameter values and check again. 3. 2.1 Mot or re mai ns stop ped 1) Check the main circuit Check that a pr oper power supply voltage is applied ...

  • Mitsubishi FR-S500 - page 177

    167 T roublesho oting 3 PROTECTIVE FUNCTIONS 3.2.2 Motor r otates i n oppo site directi on Check that the phase sequence of output terminals U, V and W i s correct. Check that the start signals (forward rotation, reverse rotation) are connected properly . Check the setting of Pr . 17 "RUN key rotation direction selection". 3.2.3 S peed gr ...

  • Mitsubishi FR-S500 - page 178

    168 Trou bles hoo ting ................ C heck the Pr . 79 setting. When the Pr . 79 "operati on mode selection" setting is "0", switching input power on places the inverter in the external operati on mode. Press the to switch to the PU operation mode. For other settings (1 to 8), the operation mode is limited accordingly . (For ...

  • Mitsubishi FR-S500 - page 179

    169 Cha pt e r 2 Cha pt e r 3 Cha pt e r 4 Cha pt e r 1 4. SPECIFICA TIONS This ch apter provides the "speci fications" of thi s product. Always r ead the in structions b efore using the equipment 4.1 Specif icat ion l ist ... ..... .... ..... .... .... ..... .... ..... .... ..... .. 170 4.2 Outl ine d rawi ng s .. ..... .... ..... .... . ...

  • Mitsubishi FR-S500 - page 180

    170 Specification list 4.1 S pecifi cation list 4.1.1 Rati n gs (1) Three-phase 200V power supply *1. T he ap plied motor capaci ty in dicate d is t he max imu m capacity app licabl e for us e of t he Mitsu bishi 4- pole standar d motor . *2. T he rat ed out put ca pacity ind icat ed ass umes th at the outpu t voltage i s 230V . *3. T he % va lue o ...

  • Mitsubishi FR-S500 - page 181

    171 Spec ific ati on li st 4 SPECIFICATIONS (2) Three-phase 400V power supply *1. T he applied mot or ca pacity indica ted i s the max imum capaci ty app licabl e fo r use o f th e Mitsu bish i 4-pole standar d motor . *2. T he r ated outpu t capacity indi cated assum es th at the out put v oltage is 440V . *3. T he % va lue of the ov erload cur re ...

  • Mitsubishi FR-S500 - page 182

    172 Specification list (3) Single-phase 100V power supply *1. T he a pplied moto r capaci ty indi cated i s the maxim um capaci ty app lic able w hen a Mitsu bishi 4-po le s tandar d mot or i s u sed. *2. T he rat ed out put ca pacity ind icat ed ass umes th at the outpu t voltage i s 230V . *3. T he % va lue of the ov erload c urre nt rati ng ind ...

  • Mitsubishi FR-S500 - page 183

    173 Spec ific ati on li st 4 SPECIFICATIONS 4.1 .2 Common specifications Control specifications Cont rol sy stem Sele ctable b etwee n Soft-P WM cont rol and h igh ca rrie r freque ncy PW M contr ol, V /F contr ol or aut omati c torque boost cont rol are se lectab le. Outp ut fr equen cy r ange 0.5 to 12 0Hz (star tin g freq uency variabl e betw ee ...

  • Mitsubishi FR-S500 - page 184

    174 Specification list *1. When underv oltage or inst antane ous powe r failure oc curs, no a larm outpu t is provide d but the outp ut is shut of f. After p ower restor ation, the inverter may be run a s it is. Depend ing on the runnin g status ( e.g. load mag nitude), howe ver , over current, regen erative overvo ltage or other pro tection may be ...

  • Mitsubishi FR-S500 - page 185

    175 Outli ne drawin gs 4 SPECIFICATIONS 4. 2 Out line draw ings • FR-S520E-0.1K, 0.2K, 0.4K, 0.75K-NA • FR-S510WE-0.1K, 0.2K, 0.4K-NA • Three-phase 200V power supply • Single-phase 100V power supply (Unit: mm (inches)) Capacity D D1 D2 0.1K ,0.2 K 80 .5 (3.1 7) 10 (0.3 9) 52 (2.0 5) 0.4K 11 2 . 5 (4.4 3) 42 (1.6 5) 52 (2.0 5) 0.75 K 132.5 ( ...

  • Mitsubishi FR-S500 - page 186

    176 Out line dra wings • FR-S520E-1.5K, 2.2K, 3.7K-NA • FR-S540E-0.4K, 0.75K, 1.5K, 2.2K, 3.7K-NA • FR-S510WE-0.75K-NA • Three-phase 200V power supply • Three-phase 400V power supply • Single-phase 100V power supply (Unit: mm (inches)) Cap ac ity W W1 D D1 D2 D3 1.5K ,2.2K 108 (4.2 5) 96 (3.7 8) 135. 5 (5.3 3) 65 (2.5 6) 52 (2.0 5) 8 (0 ...

  • Mitsubishi FR-S500 - page 187

    177 Outli ne drawin gs 4 SPECIFICATIONS • Parameter unit (FR- PU04) <Outline drawing> <Panel cut dimension drawing> Choose the mounting screws whose length will not exceed the effective depth of the mounting threads. 125 ( 4. 92) 5- M3 hol e 5- 4 hol e Effec ti ve de pth 4.5 40 ( 1. 57) 23.75 (0.93) 11. 75 (0 .46 ) 81. 5 ( 3. 21) 1.25 ...

  • Mitsubishi FR-S500 - page 188

    178 MEMO ...

  • Mitsubishi FR-S500 - page 189

    179 APPENDIX APPENDIX 1 Parameter In struction Code List . ...... 180 ...

  • Mitsubishi FR-S500 - page 190

    180 Parameter Instruction Cod e List APPEND IX 1 Pa rameter Ins tructi on Code List The extended function parameters are made valid by setting "1" in Pr . 30 "ex tended function display selection". Func- tion Parameter Number Name Inst ruction Code Compu ter Link Dat a Se tting Incr ements* Link Pa rameter Exte nsion Sett ing (I ...

  • Mitsubishi FR-S500 - page 191

    181 Parameter Instruction Code List S tandard ope ratio n function s 23 S t all pr eventi on ope ration leve l compensa tion facto r at do uble spee d 17 97 0.1% 0 24 Mult i-s peed se tting (spe ed 4 ) 18 98 0.01Hz 0 25 Mult i-s peed se tting (spe ed 5 ) 19 99 0.01Hz 0 26 Mult i-s peed se tting (spe ed 6 ) 1A 9A 0.01 Hz 0 27 Mult i-s peed se tting ...

  • Mitsubishi FR-S500 - page 192

    182 Parameter Instruction Cod e List Disp lay fu nctio ns 52 Oper ation p ane l disp lay dat a select ion 34 B4 1 0 53 Frequ ency s etting oper ation se lecti on 35 B5 1 0 54 AM te rmin al fu nct ion sele cti on 36 B6 1 0 55 Frequ ency mo nito ring ref erenc e 37 B7 0.01H z 0 56 Current monit oring ref erenc e 38 B8 0.01 A 0 Aut omat ic restart fun ...

  • Mitsubishi FR-S500 - page 193

    183 Parameter Instruction Code List Mu lti-speed o perati on 80 Mult i-s peed se tting (spe ed 8 ) 50 D0 0.01Hz 0 81 Mult i-s peed se tting (spe ed 9 ) 51 D1 0.01Hz 0 82 Mult i-s peed se tting (spe ed 1 0) 52 D2 0.01Hz 0 83 Mult i-s peed se tting (spe ed 1 1) 53 D3 0.01Hz 0 84 Mult i-s peed se tting (spe ed 1 2) 54 D4 0.01Hz 0 85 Mult i-s peed se t ...

  • Mitsubishi FR-S500 - page 194

    184 Parameter Instruction Cod e List Additional functio n H6 (16 2) Automa tic rest art af ter instan taneous power fail ure sele ction 3E BE 1 1 H7 (55 9) Sec ond elec tron ic ther mal O/L rela y 3B BB 0. 01A 5 – b1 ( 560) Param et er for m anufa ctur er sett ing. b2 ( 561) Cal ibrat ion p ara meter s C1 (90 1) AM ter minal calib ration 5D DD ? ...

  • Mitsubishi FR-S500 - page 195

    185 Parameter Instruction Code List The parameter numbers in parentheses are those for use with the parameter unit (F R- PU04). * T hough parameter setting by RS-485 communication can be made in the setting increments indic ated i n the t able, note that the valid setting inc rements are as indicated in the para meter list (p age 48) . Communicat i ...

  • Mitsubishi FR-S500 - page 196

    REVI SIONS *The manual number is given on t he bottom lef t of the back cover . Prin t Date * Manual Numb er Revisi on Dec., 20 04 I B(NA)- 0600 209ENG-A Fir st edit ion ...

Manufacturer Mitsubishi Category Power Supply

Documents that we receive from a manufacturer of a Mitsubishi FR-S500 can be divided into several groups. They are, among others:
- Mitsubishi technical drawings
- FR-S500 manuals
- Mitsubishi product data sheets
- information booklets
- or energy labels Mitsubishi FR-S500
All of them are important, but the most important information from the point of view of use of the device are in the user manual Mitsubishi FR-S500.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Mitsubishi FR-S500, service manual, brief instructions and user manuals Mitsubishi FR-S500. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Mitsubishi FR-S500.

A complete manual for the device Mitsubishi FR-S500, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Mitsubishi FR-S500 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Mitsubishi FR-S500.

A complete Mitsubishi manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Mitsubishi FR-S500 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Mitsubishi FR-S500, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Mitsubishi FR-S500, that we can find in the current document
3. Tips how to use the basic functions of the device Mitsubishi FR-S500 - which should help us in our first steps of using Mitsubishi FR-S500
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Mitsubishi FR-S500
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Mitsubishi FR-S500 in a specific country, if it was not possible to solve the problem on our own.