    31005009 01 170AMM11030 Analog/Digital Momentum I/O Base Use r Guide Version 1.0 31005009 01 ...

  • Schneider Electric 170AMM11030 - page 2

    2 31005009 00 November 2 003 Safe ty Info rmation NOTICE Read th ese instr uctions carefully , and loo k at the e quipment to become f amiliar wi th the devic e before t rying t o install , operate, o r maintai n it. The fo llowing s pecial messag es may app ear througho ut this docum entation or o n the equipm ent to warn of potenti al hazard s or ...

  • Schneider Electric 170AMM11030 - page 3

    31005009 01 N ovember 20 03 3 170AMM11030 Analog/Digit al Momentum I/O Base Overview This docu ment conta ins th e follow ing t opics : Front Panel Components Overview Thi s section contains an illustra tion of the fro nt panel of th e 170AMM1103 0 I/O base and a des cription of th e LEDs. Fron t Pa nel Illustration The illus tration bel ow sho ws ...

  • Schneider Electric 170AMM11030 - page 4

    4 31005009 01 November 2 003 Component s of the I/O Module: LED Illustratio n The illus tration be low sho ws the LE Ds. LED Descrip tions The follow ing table d escribes th e LEDs. Label Descrip tion 1 Internal interface (ATI) connector 2 Locking and ground contact for the adapter 3 LED status display 4 Pro tect ive cover 5 Sockets for the termina ...

  • Schneider Electric 170AMM11030 - page 5

    31005009 01 N ovember 20 03 5 Specifications Overview Thi s sectio n contains s pecificati ons for the 170AMM1103 0 Momen tum I/O base . General Specif ications The follow ing tabl e contains general s pecificat ions for t he I/O base. Each disc rete output is protec ted against sho rt-circuiti ng and overload . External Power Requirement Normal Op ...

  • Schneider Electric 170AMM11030 - page 6

    6 31005009 01 November 2 003 Analog Inpu ts The follow ing tab le contains specific ations f or analog inp uts. Number of Chann els 2 Input Rang es ± 10 VDC Inpu t Type Single-ended Resolution 14 bit Surge Tolerance Voltage Input ± 30 VDC Over-range Tolerance 5% full scale Protection P olar ity inve rsio n Common Mode Reject ion 250 VAC @ 47 to 6 ...

  • Schneider Electric 170AMM11030 - page 7

    31005009 01 N ovember 20 03 7 Analog Outputs The follow ing tabl e contains specific ations fo r analog o utputs. Discrete Inp uts The follow ing tabl e contai ns speci fications fo r discrete inputs. Number of C hannels 2 Output Ranges ± 10 VDC Resol ution 14 Bit Conversion T imes 1.60 ms fo r all cha nnels Output Se tting Time 3.2 m s to 0. 1% o ...

  • Schneider Electric 170AMM11030 - page 8

    8 31005009 01 November 2 003 Discret e Output s The follow ing tab le contains specific ations f or discret e outputs. Description Solid state switch Operating Voltage 16 - 4 2 VDC Absolute Minimum Vol tage 12 VDC Absolute Maximum Volt age 45 VDC Maximum V oltage 50 VDC for 1 ms Number of P oints 8 Number of Gro ups 1 Points per Group 8 Current Cap ...

  • Schneider Electric 170AMM11030 - page 9

    31005009 01 N ovember 20 03 9 Physical Dimensions The follow ing tabl e outline s physica l dimension s for the I /O base. Internal Pin Connections Overview This sec tion cont ains an illu stration s howing the internal connecti ons betwee n terminals on the I/O b ase and a n optional busbar. Illustration The following illus tration shows the int e ...

  • Schneider Electric 170AMM11030 - page 10

    10 31005009 01 November 2 003 Field Wir ing Guidelines Overv iew This sec tion cont ains wirin g guidelines and prec autions f or wiring the 170AMM11 030 Momentu m I/O ba se. Term inal Connector To connec t field devic es to the I/O bas e, you need a field wiring terminal con nector. Schneider Electric s ells termin al conne ctors in s ets of three ...

  • Schneider Electric 170AMM11030 - page 11

    31005009 01 N ovember 20 03 11 Wiring Diagrams Overview Thi s sectio n contai ns diagra ms to as sist you in wiring the follo wing types of devic es. discret e input an d output analog i nput and o utput Discrete I/O Device s The diagra m below s hows field wiring for discrete input and discrete out put devic es. Recomm ended fus es: F1, F3: U se a ...

  • Schneider Electric 170AMM11030 - page 12

    12 31005009 01 November 2 003 Analog I/O Devices The diagra m below s hows field wiring for a nalog inp ut and ana log output devices. Recom mended fu ses: F3: Us e a 1A fuse , Wickman 1 9181-1A or equivalen t. I/O Ma p I/O Map Modul e Configuration The modu le must b e I/O map ped as 8 contiguo us input w ords an d 8 contig uous output words. Row ...

  • Schneider Electric 170AMM11030 - page 13

    31005009 01 N ovember 20 03 13 Register for Output s Overview 170 AMM11030 analog and d iscrete out put channe ls are confi gured by ente ring the appropriate informati on in outp ut words 1 t hrough 5 a s follows. Note: The module w ill go to fail st ate values if netw ork or commu nication adap ter ATI commu nication is lost. Word Functi on 1 Sys ...

  • Schneider Electric 170AMM11030 - page 14

    14 31005009 01 November 2 003 Word 1 System In fo Register This wo rd enables th e module ’s operati on, and spec ifies if user shutdow n value s are expected . Valid se tting for wor d one are 0 001 ... FFFF T h e m o d ul e ’s d e fau l t v al u e a t p o w er- u p f o r th i s reg i st e r is z e ro (module shut d o w n ) . Word 2 Discrete F ...

  • Schneider Electric 170AMM11030 - page 15

    31005009 01 N ovember 20 03 15 Words 4 ... 5 Analog Fai l State Valu e Register The modul e always expects two words of u ser defin ed data, ev en if the data is n ot used. Th e first wo rd of the user s hutdown fi eld is used for c hannel 1 , the s econd for channel 2 . Word 6 Discrete O utput Registe r This word c ontains a right justifi ed binar ...

  • Schneider Electric 170AMM11030 - page 16

    16 31005009 01 November 2 003 Range Outpu t Operatin g Range Register for Inputs Overv iew The input regist er is arranged as follows . Output Voltage Data is L eft Justif ied Comment Output Range -10. 000 ... +10. 000 00382 ... 32382 Nominal out put voltage range Output Over Range +10.000 ... +10.238 32384 ... 32764 Linear over range output voltag ...

  • Schneider Electric 170AMM11030 - page 17

    31005009 01 N ovember 20 03 17 Word 1 The status word (word 1) contains information a bout the h ealth of th e module an d the status of the di screte out puts, inc luding over temperature or short c ircuit of the discrete outp uts. Word 2 Discret e Input Regi ster This word c ontains a right justifi ed binary 16 bit data f ield. Bit(s) Descripti o ...

  • Schneider Electric 170AMM11030 - page 18

    18 31005009 01 November 2 003 Words 3 ... 4 Analog Input Regis ter Each wor d in this rang e contain s a left j ustified 15 bit data fi eld. The ra nge is fro m 0H to 7FFE hex, but the resolutio n is 14 bit (0 ... 32766 decimal or 0 ... 7FFE hex ). Words 5 ... 8 Words 5 ... 8 are no t used . 3x Reg ister s The 3x registers tra ffic copp ed to this ...

  • Schneider Electric 170AMM11030 - page 19

    31005009 01 N ovember 20 03 19 Analog Map Overview 170 AMM11030 analog v alues are mapped as follows. Note: The d isplay i s standar dized, and , in ea ch case, the analog value wil l appear left ju stified. Note: The module re solution is 14-bit (0 ... 32766 decimal or 0 ... 7FFE hex). 0 ... 32766 Input Word 2 Output Word 7 to to 15 14 13 12 11 10 ...

  • Schneider Electric 170AMM11030 - page 20

    20 31005009 01 November 2 003 Discr ete I /O Po ints an d IEC Comp liant Data M appin g Overv iew The 170AM M11030 b ase returns 16 discrete input bit s to the pr ocessor i n one 16- bit word (3x). The inpu t points a re field wire d to row 2 of the ba se. The proce ssor sends 8 discrete output bits to the base as a single 16-bit w ord (4x). Th e o ...

  • Schneider Electric 170AMM11030 - page 21

    31005009 01 N ovember 20 03 21 Input and Output Ranges Ranges an d Decimal Va lues Input Mea suring Range ± 10 V The volta ge value is calc ulated with the followi ng formul a using th e digital measuran d: Vn = 1600 Va + 16382 (for the li near range). 10V >10.238V 10.238V 382 <-10.238V -10V 16382 32 764 32 382 (Overflow error) 32 766 linear ...

  • Schneider Electric 170AMM11030 - page 22

    22 31005009 01 November 2 003 Output Measuring Range ± 10 V The v oltag e valu e is c alcul ated wi th th e foll owing f ormu la usi ng the digit al measuran d: Vn = 160 0 Va + 1638 2 (for the linea r range) . -10.000V 0V 10.238V 10.000V >10.238V linear range Va -10.238V <-10.238V 2 382 32382 32764 32766 Vn 16382 0 Printed in F rance *310050 ...

Manufacturer Schneider Electric Category Network Card

Documents that we receive from a manufacturer of a Schneider Electric 170AMM11030 can be divided into several groups. They are, among others:
- Schneider Electric technical drawings
- 170AMM11030 manuals
- Schneider Electric product data sheets
- information booklets
- or energy labels Schneider Electric 170AMM11030
All of them are important, but the most important information from the point of view of use of the device are in the user manual Schneider Electric 170AMM11030.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Schneider Electric 170AMM11030, service manual, brief instructions and user manuals Schneider Electric 170AMM11030. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Schneider Electric 170AMM11030.

A complete manual for the device Schneider Electric 170AMM11030, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Schneider Electric 170AMM11030 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Schneider Electric 170AMM11030.

A complete Schneider Electric manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Schneider Electric 170AMM11030 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Schneider Electric 170AMM11030, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Schneider Electric 170AMM11030, that we can find in the current document
3. Tips how to use the basic functions of the device Schneider Electric 170AMM11030 - which should help us in our first steps of using Schneider Electric 170AMM11030
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Schneider Electric 170AMM11030
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Schneider Electric 170AMM11030 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Schneider Electric 170AMM11030?

Use the form below

If you did not solve your problem by using a manual Schneider Electric 170AMM11030, ask a question using the form below. If a user had a similar problem with Schneider Electric 170AMM11030 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)