York EVAPORATOR BLOWERS K2EU060 - page 1
® Technical Guide SPLIT -SYSTEM EV APORA TOR BLOW ERS K2EU060, K4EU090, K3EU120 & K3EU180 5 THRU 15 NOMINAL TONS 036-21300-002-A-09 05 FOR DISTRIBUTION USE ONL Y - NOT TO BE USED A T POINT OF RET AIL SALE DESCRIPTION These completely assembled un its include a well-insulated cabinet, a DX cooling coil with copper tubes and aluminum fin s, expa ...
-
York EVAPORATOR BLOWERS K2EU060 - page 2
036-21300-002-A-09 05 2 Unitary Products Group TABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 ACCESSORIES—FIELD INSTALLED . . . . . . . . . . . . . . . . 1 NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 APPLICATION FLEXIBILITY . . . . . . . . . . . . . . . . . ...
-
York EVAPORATOR BLOWERS K2EU060 - page 3
036-21300-002-A-0905 Unitary Products Group 3 NOMENCLATURE ACCESSORIES-FIELD INS T ALLED (CONT .) HOT W A TER COILS These drainable coi ls have 2 rows of 1/2" co pper tubes, 12 aluminum fins per inch, a casing th at is finished to match the exterior of the basic unit, but no wate r control valve. The coils slide out of their casings for easy f ...
-
York EVAPORATOR BLOWERS K2EU060 - page 4
036-21300-002-A-09 05 4 Unitary Products Group MODEL 15 TON These units have two distinct mod ules . . . a blower module and a coil module. Although th e unit is always shipped in the vertical position with a vertical air discharge as shown in illus- tration (a), the blower module can be repositioned in the field as shown in illustrations (b) and ( ...
-
York EVAPORATOR BLOWERS K2EU060 - page 5
036-21300-002-A-0905 Unitary Products Group 5 FIGURE 3 - SUSPENSION MOUNTING (H ORIZONTAL) - KEU060, 090 AND 120 + %5 + %5 +%5 + %5 !)2 /54 !)2 ). &(17(5 2)? ...
-
York EVAPORATOR BLOWERS K2EU060 - page 6
036-21300-002-A-09 05 6 Unitary Products Group NOTE: These values have been accessed using a mode l of soun d pr op agation from a poi nt source into t he hemispheric f ree field. Th e dBA values provided are for reference only . Calcul ation of dBA values cove r mat ters of system design and the fan ma nufacturer has no wa y of knowing the details ...
-
York EVAPORATOR BLOWERS K2EU060 - page 7
036-21300-002-A-0905 Unitary Products Group 7 T ABLE 4: HEATING CAPACITY - ELECTRIC HEAT ACCESSORY UNIT MODEL HEA TER MODEL VOL T AGE TEST NOMINAL RA TINGS 1 CAP AC ITY 1ST ST AGE 2ND ST AGE KW MBH KW MBH KW MBH 060 2HT045010 25 208 / 240 2 10 34.2 10 34.2 - - 2HT045016 25 208 / 240 2 16 54.7 10 34.2 6 20.5 2HT045026 25 208 / 240 2 26 88.9 16 54.7 ...
-
York EVAPORATOR BLOWERS K2EU060 - page 8
036-21300-002-A-09 05 8 Unitary Products Group NOTE: Steam rate (lb./hr.) = 1.025 x MBH CAUTION: Do NOT operate a motor above its nominal HP ratin g when a unit is equipped with a steam coi l acces- sory. NOTE: W ater T emperature Drop, 0 F = 2 x MBH CAUTION: Do NOT operat e a motor above it s nominal HP rati ng when a unit is equipped with a hot w ...
-
York EVAPORATOR BLOWERS K2EU060 - page 9
036-21300-002-A-0905 Unitary Products Group 9 T ABLE 9: SUPPLY AIR BLOWER PERFORMANCE - KEU060 (5 TON) CFM EXTERNAL ST A TIC PRESSURE 0.2 0.4 0.6 0.8 RPM W BHP RPM W BHP RPM W BHP RPM W B HP 1400 677 74 0.08 753 174 0.19 831 2 68 0.29 912 355 0.38 1600 725 225 0.24 801 325 0.35 879 419 0.45 959 506 0.54 1800 773 366 0.39 849 466 0.50 927 560 0.60 1 ...
-
York EVAPORATOR BLOWERS K2EU060 - page 10
036-21300-002-A-09 05 10 Unitary Products Group T ABLE 10: SUPPLY AIR BLOWER PERFORMANCE - K EU090 (7.5 TON) CFM EXTERNAL ST A TIC PRESSURE 0.2 0.4 0.6 0.8 RPM W BHP RPM W BHP RPM W BHP RPM W B HP 2200 561 281 0.30 612 400 0.43 670 530 0.57 734 661 0.71 2400 579 414 0.44 630 533 0.57 688 663 0.71 752 794 0.85 2600 599 542 0.58 649 662 0.71 707 792 ...
-
York EVAPORATOR BLOWERS K2EU060 - page 11
036-21300-002-A-0905 Unitary Products Group 11 T ABLE 1 1: SUPPLY AIR BLOWER PERFORMA NCE - KEU120 (10 TON) CFM EXTERNAL ST A TIC PRESSURE 0.2 0.4 0.6 0.8 RPM W BHP RPM W BHP RPM W BHP RPM W BHP 2800 571 122 0.13 630 332 0.36 682 489 0.52 733 618 0.66 3000 595 349 0.37 654 559 0.60 706 716 0.77 756 845 0.91 3200 619 558 0.60 678 768 0.82 730 925 0. ...
-
York EVAPORATOR BLOWERS K2EU060 - page 12
036-21300-002-A-09 05 12 Unitary Products Group T ABLE 12: SUPPLY AIR BLOWER PERFORMANCE - K EU180 (15 TON) CFM EXTERNAL ST A TIC PRESSURE 0.2 0.4 0.6 0.8 RPM W BHP RPM W BHP RPM W BHP RPM W BHP 4000 555 382 0.41 594 620 0.67 633 851 0.91 676 1085 1.16 4200 562 616 0.66 600 854 0.92 640 1085 1.16 683 1319 1.42 4400 569 828 0.89 608 1066 1.14 648 12 ...
-
York EVAPORATOR BLOWERS K2EU060 - page 13
036-21300-002-A-0905 Unitary Products Group 13 T ABLE 13: ST ATIC RESIST ANCE FOR UN IT ACCESSORIES (I WG) - KEU060-120 CFM Electric Heat KW Supply Air Plenum Return Air Grill Hot W ater Coil Steam Coil 10 16 26 36 2200 0.01 0.01 0.03 0.04 0.02 0.02 0.07 0.1 1 2400 0.01 0.0 2 0.03 0.05 0.03 0.03 0.09 0.13 2600 0.01 0.0 2 0.04 0.06 0.03 0.03 0.10 0. ...
-
York EVAPORATOR BLOWERS K2EU060 - page 14
036-21300-002-A-09 05 14 Unitary Products Group T ABLE 15: SUPPLY AIR PLENUM PERFORMANCE DATA Model CFM Face Ve l o c i t y (FPM) Angle of Deflection Ve r t i c a l Louvers 1 (Plan Vie w) Horizontal Louvers 2 (Elevati on View) Ve r t i c a l Louvers (Plan View ) Horizontal Louvers (Elevation View ) Ve r t i c a l Louvers (Plan View ) Horizontal Lou ...
-
York EVAPORATOR BLOWERS K2EU060 - page 15
036-21300-002-A-0905 Unitary Products Group 15 T ABLE 17: KEU PHYS ICAL DATA Component Descript ion Model 060 090 120 180 EVAPORATOR BLOWER 1 Centrifugal Blower (Dia. X Wd. in.) 15 X 15 15 X 15 15 X 15 18 X 18 Fan Motor HP (Belt Drive) 3/4 1-1/2 2 3 EVAPORATOR COIL Rows Deep 3 3 3 3 Finned Length (in.) 30 46 46 54 Fins per Inch 13 13 13 13 Face Are ...
-
York EVAPORATOR BLOWERS K2EU060 - page 16
036-21300-002-A-09 05 16 Unitary Products Group ACCESSORIES • ELECTRIC HEA TER - Add 13” to unit height when used. • SUPPL Y AIR PLENUM - Add 24-1/4” to unit height when used. • BASE - Add 20” to unit height when used. FIGURE 1 - UNIT DIMENSIONS KEU060 +./#+/54 2EMOVEDONLYWHEN %LECTRIC(EAT!CCESSOR ...
-
York EVAPORATOR BLOWERS K2EU060 - page 17
036-21300-002-A-0905 Unitary Products Group 17 ACCESSORIES • ELECTRIC HEA TER - Add 14-1/4” to unit h eight when used. • SUPPL Y AIR PLENUM - Add 27-1/2” to unit height when used. • BASE - Add 20” to unit height when used. FIGURE 2 - UNIT DIMENSIONS KEU090 & 120 +./#+/54 2EMOVEDONLYWHEN %LECTRIC( ...
-
York EVAPORATOR BLOWERS K2EU060 - page 18
036-21300-002-A-09 05 18 Unitary Products Group ACCESSORIES • ELECTRIC HEA TER - Add 14-1/4” to unit height when using 10, 16, 26, or 36 KW heater • SUPPL Y AIR PLENUM - Add 27” to unit height when used. • BAS E - Add 24” to unit height when used. • HOT W A TER OR STEAM COIL - Add 6” to unit depth w hen used. FIGURE 3 - UNIT DIMENSI ...
-
York EVAPORATOR BLOWERS K2EU060 - page 19
036-21300-002-A-0905 Unitary Products Group 19 Plenum Model Unit Model Plenum Dimensions (inches) ABC DE F G H K L 1SP0450 060 36 25-1/2 34-2/8 31-3/4 15-3/4 7-5/8 7/8 2-1/8 1 1-1/4 2 1SP0451 090 120 52-1/8 28-1/4 27-1/2 49-3/8 17-7/8 8-3/4 7/8 1-1/8 1 5-1/4 1-3/4 1SP0452 180 60-3/4 31 27 55-3/4 19-7/8 6-1/8 1 - 2-1/2 19-1/2 1-3/4 ( * ) + ' $ ...
-
York EVAPORATOR BLOWERS K2EU060 - page 20
036-21300-002-A-09 05 20 Unitary Products Group T ABLE 21: ELECTRIC HEA TER DIME NSIO NS KEU060, 09 0, 120 & 18 0 Heater Model Nom. kW Unit Model Heater Dimensions (inches) ABC D E F GHK LM 2HT04501025 1 2HT04501625 1 2HT04502625 1 10 16 26 060 25-1/8 22-1/2 13 7 /8 4 1/2 5-1/4 1-1 1/16 1-3/4 20 -1/8 16-7/8 2HS04501025, 46, 58 2HS04501625, 46, ...
-
York EVAPORATOR BLOWERS K2EU060 - page 21
036-21300-002-A-0905 Unitary Products Group 21 FIGURE 8 - STEAM COIL B A D 2 E F 1-1/2" NPTE CONNS. C Coil Model Unit Model Steam Coil Dimensions ( inches) A BCD E F 1NF0450 1 1. Installs ove r the return air opening of the unit- before the filters. 060 36 21-7/8 5 2-1/2 2-5/8 10-5/8 1NF0451 1 090 52 25 5 2-1/2 2-5/8 13-5/8 1NF0451 1 120 52 25 ...
-
York EVAPORATOR BLOWERS K2EU060 - page 22
036-21300-002-A-09 05 22 Unitary Products Group T ABLE 22: KEU ELECTRICAL DATA Model (TONS) Power Supply Vo l t a g e Indoor Motor FLA Heater Model Number Nominal Heater KW Applied Heater KW Electric Heat Amps Min. Circuit Ampacity (AMPS) Max. Fuse 1 / HACR Breaker 2 (AMPS) 060 3 (5) 208 7.6 None -- -- -- 9.5 15 2HT04501025 10 7.5 20.8 35.6 40 2HT0 ...
-
York EVAPORATOR BLOWERS K2EU060 - page 23
036-21300-002-A-0905 Unitary Products Group 23 T ABLE 22: KEU ELECTRICAL DATA (CONTINUED) Model (TONS) Power Supply Vo l t a g e Indoor Motor FLA Heater Model Number Nominal Heater KW Applied Heater KW Electric Heat Amps Min. Circuit Ampacity (AMPS) Max. Fuse 1 / HACR Breaker 2 (AMPS) 180 (15) 208 10.6 None -- -- -- 13.3 20 2HS04501025 10 7.5 20.8 ...
-
York EVAPORATOR BLOWERS K2EU060 - page 24
036-21300-002-A-09 05 24 Unitary Products Group FIGURE 10 - FIELD WIRING FOR POWER SUPPLY COOLING ONLY UNITS AN D UNITS WITH STEAM OR HOT WATER COIL ACCESSORY T ERMINALS ON SU PP LY AIR B LOWER MOTOR CONTACTOR 10M GROUN D SCREW P OWER WIRING, D ESCONNECT SWITCH AN D FUSING TO B E SU PP LIE D B Y FIEL D LINE VOLTAGE P OWER SU PP LY *Not required on ...
-
York EVAPORATOR BLOWERS K2EU060 - page 25
036-21300-002-A-0905 Unitary Products Group 25 FIGURE 13 - FIELD WIRI NG FO R UNITS WITH ELECTRIC HEAT R Y 1 Y 2 W 1 W 2 G 1 1 2 R Y O 6 6 6 0 5 3 G B 2 4 - V O L T C O N T R O L W I R I N G T E R M I N A L B L O C K 4 T B O N B L O W E R U N I T J U M P E R A n o u t d o o r t h e r m o s t a t c a n b e w i r e d b e t w e e n t e r m i n a l s 5 ...
-
York EVAPORATOR BLOWERS K2EU060 - page 26
036-21300-002-A-09 05 26 Unitary Products Group ...
-
York EVAPORATOR BLOWERS K2EU060 - page 27
036-21300-002-A-0905 Unitary Products Group 27 ...
-
York EVAPORATOR BLOWERS K2EU060 - page 28
Subject to change without notice. Pr inted in U.S.A. 036-21300-002-A-09 05 Copyright © by Unitary Products Group 2005. All rights reserved. Supersedes: 036-21 300-001-A-0901 Unitary 5005 Norman Product s Y ork OK Group Drive 73069 ...