    343615-YTG-A-0807 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE SINGLE P ACKAGE GA S/ELECTRIC UNITS AND SINGLE P ACKAGE AIR CONDITIONERS DY 036, 048 & 060 3, 4 & 5 NOMINAL TONS 14.00 SEER ® TECHNICAL GUIDE DESCRIPTION YORK Sunline Magnum ™ units are convertible single pack- age air conditioners with a commo n cabin e ...

  • York DY 036 - page 2

    343615-YTG-A-0807 2 Unitary Products Group T ABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMEN CLATURE . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 5 FIELD-INSTALLED ACCESSORIES ...

  • York DY 036 - page 3

    343615-YTG-A-0807 Unitary Products Group 3 PRODUCT NOMENCLA TURE D Y 048 N04 A 2 A AA 2 0 1 2 4 A D = A/C, Single Pkg., R-22 Product Category Airflow D = Direct Drive/Motorized Damper B = Direct Drive/Single Input Economizer A = Direct Drive Product Generation 2 = Second Generation C00 = Cooling Only. Suitable for Field Installed Electric Heat Heat ...

  • York DY 036 - page 4

    343615-YTG-A-0807 4 Unitary Products Group FEA TURES All models are available with a wide variety of factory- mounted options such as stainless steel heat exchangers, electric heaters, phase monito r , convenience outlet, dirty filter switch, disconnect switch, smo ke detectors, and coil guard to make them suitable for almost every application. All ...

  • York DY 036 - page 5

    343615-YTG-A-0807 Unitary Products Group 5 F ACTOR Y -INST ALLED OPTIONS • SINGLE INPUT ELECTR ONIC ENTHALPY ECONO- MIZERS - Includes a slide-in / plug-in damper assemb ly with fully modulating spring-return motor actuator capa- ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers. The enthalpy system co ntains one senso ...

  • York DY 036 - page 6

    343615-YTG-A-0807 6 Unitary Products Group air temperature. The pate nted economizer-l oading alg o- rithm will protect the equipment when harsh operating conditions exist. Humidity in the occupi ed sp ace or return duct can be monitored and controlled via humidity sen sors and the on-board connection for hot gas re-heat system. It uses the INTELLI ...

  • York DY 036 - page 7

    343615-YTG-A-0807 Unitary Products Group 7 • ROOF CURBS - Eight and fourteen-in ch high roof curbs provide a water-tig ht seal betwe en the unit and the finished roof. These full perimeter curbs mee t the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-dow n for field assembly . Roof curbs are designed ...

  • York DY 036 - page 8

    343615-YTG-A-0807 8 Unitary Products Group T AB LE 4: DY036 INDOOR SOUND POWER LEVELS (HORIZONT AL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP 63 80 82 80 82 78 83 81 85 1 2 5 7 6 7 77 6 7 7 8 2 8 38 1 8 2 2 5 0 5 6 5 95 6 6 0 6 0 6 15 8 6 0 5 0 0 5 0 5 0 ...

  • York DY 036 - page 9

    343615-YTG-A-0807 Unitary Products Group 9 T AB LE 6: DY036 IN DOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP 63 78 82 78 82 80 85 80 84 125 70 75 70 74 71 80 71 79 250 55 60 55 60 59 61 58 62 500 47 50 47 50 52 53 49 52 1 0 ...

  • York DY 036 - page 10

    343615-YTG-A-0807 10 Unitary Products Group T AB LE 8: DY048 INDOOR SOUND POWER LEVELS (HORIZONT AL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP 63 74 97 74 95 77 90 77 90 125 70 86 69 86 73 78 72 77 250 53 58 52 57 60 61 58 61 500 49 55 47 54 54 56 51 53 ...

  • York DY 036 - page 11

    343615-YTG-A-0807 Unitary Products Group 11 T AB LE 10: DY048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP 63 76 95 77 93 80 91 79 91 1 2 5 6 8 8 46 7 8 2 7 6 8 47 3 8 0 2 5 0 5 4 5 75 2 5 6 6 3 6 15 7 5 9 5 0 0 4 8 5 34 ...

  • York DY 036 - page 12

    343615-YTG-A-0807 12 Unitary Products Group T AB LE 12: DY060 INDOOR SOUND POWER LEVELS (HORIZONT AL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP 63 77 84 77 84 81 85 79 84 12 57 1 7 1 7 2 7 3 7 4 7 5 7 1 7 2 25 05 7 5 8 5 5 5 6 6 6 6 6 6 0 6 1 50 05 3 5 3 ...

  • York DY 036 - page 13

    343615-YTG-A-0807 Unitary Products Group 13 T AB LE 14: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP 63 77 86 79 88 81 86 83 87 1 2 5 6 97 0 7 0 7 2 7 17 3 7 27 2 2 5 0 5 66 3 5 6 5 8 6 47 2 6 36 9 5 0 0 5 05 2 4 8 ...

  • York DY 036 - page 14

    343615-YTG-A-0807 14 Unitary Products Group T AB LE 16: DY036 COOLING CAP ACITIES (3 TON) Air on Evap- orator Co il T emperature of Air on Co ndenser Coil 75°F 85°F CFM WB (°F) To t a l Cap. 1 (MBH) To t a l 2 Input (kW) Sensible Capacity (MBH) 1 Return Dry Bulb (°F) To t a l Cap. 1 (MBH) To t a l 2 Input (kW) Sensible Capa ci ty (MBH) 1 Return ...

  • York DY 036 - page 15

    343615-YTG-A-0807 Unitary Products Group 15 T AB LE 17: DY048 COOLING CAP ACITIES (4 TON) Air on Evap- orator Co il T emperature of Air on Co ndenser Coil 75°F 85°F CFM WB (°F) To t a l Cap. 1 (MBH) To t a l 2 Input (kW) Sensible Cap acity (MBH) 1 Return Dry Bulb (°F) To t a l Cap. 1 (MBH) To t a l 2 Input (kW) Sensible Capa ci ty (MBH) 1 Retur ...

  • York DY 036 - page 16

    343615-YTG-A-0807 16 Unitary Products Group T ABLE 18: DY060 COOLING CAP ACITIES (5 TON) Air on Evap- orator Co il T emperature of Air on Co ndenser Coil 75°F 85°F CFM WB (°F) To t a l Cap. 1 (MBH) To t a l 2 Input (kW) Sensible Capacity (MBH) 1 Return Dry Bulb (°F) To t a l Cap. 1 (MBH) To t a l 2 Input (kW) Sensible Capa ci ty (MBH) 1 Return ...

  • York DY 036 - page 17

    343615-YTG-A-0807 Unitary Products Group 17 T AB LE 19: SUPPLY AIR BLOWER PERFORMANCE (DY036, 048, & 060 DIRECT DRIVE) SIDE DUCT APPLICATION UNIT TONNAGE MOT OR SPEED A V AILABLE EXTERNAL ST A TIC PRESSURE - IWG 1 0.2 0.3 0.4 0. 5 0.6 0.7 0.8 0 .9 1.0 CFM WATT S CFM WATT S CFM WATT S CFM WATT S CFM WATT S CFM WATT S CFM WATT S CFM WATT S CFM WA ...

  • York DY 036 - page 18

    343615-YTG-A-0807 18 Unitary Products Group 1. Deduct these resistance values from the available external st atic pressure shown in SUPPL Y AIR BLOWER PERFORMANCE T ables. 2. Add these resistance values to the available stat ic r e sistance values on SUPPL Y AIR BLOWER PERFORMANCE T ables. 3. The pressure through the economizer is greater for 100% ...

  • York DY 036 - page 19

    343615-YTG-A-0807 Unitary Products Group 19 T AB LE 23: ELECTRICAL DA T A - DY036, 048 & 060 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET MODEL TONNAGE VOL T A GE COMPRES SORS OD F AN MOTOR FLA ID BLOWER MOTOR FLA CONV OUTLET FLA ELECTRIC HEA TER MODEL NO. HEA TER KW HEA TER AMPS MIN. CIRCUIT AMP ACITY (AMPS) MAX. FUSE/ BRKR 1 SIZE (AMPS ) RLA E ...

  • York DY 036 - page 20

    343615-YTG-A-0807 20 Unitary Products Group MODEL TONNAGE VOL T A GE COMPRES SORS OD F AN MOTOR FLA ID BLOWER MOTOR FLA CONV OUTLET FLA ELECTRIC HEA TER MODEL NO. HEA TER KW HEA TER AMPS MIN. CIRCUIT AMP ACITY (AMPS) MAX. FUSE/ BRKR 1 SIZE (AMPS ) RLA EACH LRA EACH DY060 208-1-60 28.8 145.0 2.3 10.6 0.0 None - - 48.9 50 2CE04510506 4.0 19.2 48.9 50 ...

  • York DY 036 - page 21

    343615-YTG-A-0807 Unitary Products Group 21 T AB LE 24: ELECTRICAL DA T A - DY036, 048 & 060 DIRECT DRIVE W/ POWERED CONVENIENCE OUTLET MODEL TONNAGE VOL T A GE COMPRES SORS OD F AN MOTOR FLA ID BLOWER MOTOR FLA CONV OUTLET FLA ELECTRIC HEA TER MODEL NO. HEA TER KW HEA TER AMPS MIN. CIRCUIT AMP ACITY (AMPS) MAX. FUSE/ BRKR 1 SIZE (AMPS ) RLA EA ...

  • York DY 036 - page 22

    343615-YTG-A-0807 22 Unitary Products Group MODEL TONNAGE VOL T A GE COMPRES SORS OD F AN MOTOR FLA ID BLOWER MOTOR FLA CONV OUTLET FLA ELECTRIC HEA TER MODEL NO. HEA TER KW HEA TER AMPS MIN. CIRCUIT AMP ACITY (AMPS) MAX. FUSE/ BRKR 1 SIZE (AMPS ) RLA EACH LRA EACH DY060 208-1-60 28.8 145.0 2.3 10.6 10.0 None - - 58.9 60 2CE04510506 4.0 19.2 58.9 6 ...

  • York DY 036 - page 23

    343615-YTG-A-0807 Unitary Products Group 23 T ABLE 25: DY PHYSICAL DATA MODELS DY 036 048 060 EV APORA TOR BLOWER Centrifuga l Blower (Di a. x Wd. in.) 12 X 10 12 X 10 12 X 10 Fan Motor HP (Direc t Dr ive ) 3/4 1 1 EV APORA TOR COIL Rows Deep 3 4 4 Fins Per Inch 13 13 13 Face Area (Ft . 2 ) 5.1 5.1 5.1 CONDENSER F ANS Propeller Dia. (in .) 24 24 24 ...

  • York DY 036 - page 24

    343615-YTG-A-0807 24 Unitary Products Group FIGURE 2 - TYPICAL FIEL D POWER & CONTROL WIRING REFER TO THE ELECTRICAL DA T A T ABLES TO SIZE THE DISCONNECT SWITCH, O VERCURRENT PRO TEC- TION AND WIRING. RC RH Y1 Y2 W1 W2 G LED 1 LED 2 COM A1 A2 T T B R Y1 Y2 G C X OCC W2 W1 THERMOSTAT 1 TERMINALS UNIT TERMINAL STRIP TB1 24 VOLT TRANSFORMER TO RE ...

  • York DY 036 - page 25

    343615-YTG-A-0807 Unitary Products Group 25 FIGURE 3 - UNIT DIMENSIONS (3 - 5 TO N COOLING ONL Y/ELECTRIC HEA T) FRONT VIEW FIGURE 4 - UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEA T) FRONT VIEW ...

  • York DY 036 - page 26

    343615-YTG-A-0807 26 Unitary Products Group FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD DETAIL “A” FIGURE 6 - UNIT WITH FIXED OUTD OOR AIR/MOTORIZE D DAMPER RAINHOOD DETAIL “B” ...

  • York DY 036 - page 27

    343615-YTG-A-0807 Unitary Products Group 27 FIGURE 7 - UNIT DIMENSIONS (REAR VIEW) FIGURE 8 - DISCONNECT/BLOWER ACCESS LOCA TION T ABLE 28: UTILITIES ENTR Y HOLE OPENIN G SIZE (DIA.) USED FOR A 7/8” KO 1 1. Opening in the bottom to the unit can be located by the side in the insulation. Control Wi ri ng 2 2. Do not remove the 2” knockout ring. S ...

  • York DY 036 - page 28

    343615-YTG-A-0807 28 Unitary Products Group FIGURE 9 - TYPICAL APPLICA TIONS ...

  • York DY 036 - page 29

    343615-YTG-A-0807 Unitary Products Group 29 FIGURE 10 -FOUR AND SIX POINT LOADING 44 7 / 8 82 1 / 4 Y X A B C D CONDENSER COIL END OF UNIT FRONT OF UNIT APPROXIMATE CENTER OF GRAVITY BACK OF UNIT 44 7 / 8 82 1 / 4 Y X A B C D E F CONDENSER COIL END OF UNIT FRONT OF UNIT APPROXIMATE CENTER OF GRAVITY BACK OF UNIT T AB LE 30: DY 4 AND 6 POINT LOADS W ...

  • York DY 036 - page 30

    343615-YTG-A-0807 30 Unitary Products Group T ABLE 32: OPERA TING WEIGHTS (LBS.) MO DE L S IZ E 3 TON 4 TO N 5 TO N BASIC UNIT DY (Cooling Onl y) 575 585 59 0 DY (Gas/Electric) N04 615 - - N06 - 635 - N08 635 - 650 N10 - 655 660 D06 625 635 640 D10 645 655 660 OPTIONS Economizer 5 0 Motorized Damper 26 Electric H eater 5 - 7 kW 18 10 - 15 kW 23 20 ...

  • York DY 036 - page 31

    343615-YTG-A-0807 Unitary Products Group 31 GUIDE SPECIFICA TIONS GENERAL Units shall be manufactured by Y ork International Unitary Products Group in an ISO 9001 certified facility . Y ork's Sunline Magnum ™ units are convertibl e single pack- age units. Although the units are primarily designed fo r curb mounting on a roof, they can also b ...

  • York DY 036 - page 32

    343615-YTG-A-0807 32 Unitary Products Group Coils: a. Evaporator and condenser coils shall have alumi- num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. S pecia l Pheno lic coating shall be available as a factory option. b. Evaporator and Condenser coils shall be of the direct expansion, draw-th ...

  • York DY 036 - page 33

    343615-YTG-A-0807 Unitary Products Group 33 OPTIONAL OUTDOOR AIR (Shall be made availa ble by either/or): • ELECTRONIC ENTHALPY AUT OMA TIC ECONO- MIZER - Outdoor and return air dampers that are inter- locked and positioned by a fully-modulating, spring return damper actuator . Th e maximum leakage rate for the outdoor air intake dampers shall n ...

  • York DY 036 - page 34

    343615-YTG-A-0807 34 Unitary Products Group ...

  • York DY 036 - page 35

    343615-YTG-A-0807 Unitary Products Group 35 ...

  • York DY 036 - page 36

    Subject to change without notice. Printed in U.S.A. 343615-YTG-A-0807 Copyright © 2007 by Unitary Products Group. All ri ghts reserved. Supersedes: Nothing Unitary 5005 Norman Product s Y ork O K Group Drive 73069 ...

Manufacturer York Category Air Conditioner

Documents that we receive from a manufacturer of a York DY 036 can be divided into several groups. They are, among others:
- York technical drawings
- DY 036 manuals
- York product data sheets
- information booklets
- or energy labels York DY 036
All of them are important, but the most important information from the point of view of use of the device are in the user manual York DY 036.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals York DY 036, service manual, brief instructions and user manuals York DY 036. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product York DY 036.

Similar manuals

A complete manual for the device York DY 036, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use York DY 036 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of York DY 036.

A complete York manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual York DY 036 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the York DY 036, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the York DY 036, that we can find in the current document
3. Tips how to use the basic functions of the device York DY 036 - which should help us in our first steps of using York DY 036
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with York DY 036
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of York DY 036 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning York DY 036?

Use the form below

If you did not solve your problem by using a manual York DY 036, ask a question using the form below. If a user had a similar problem with York DY 036 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)