    SPLIT -SYSTEM AIR CONDITIONERS 13 SEER – R- 410A – 1 PHASE MODELS: TCGD18 THRU 60 (1.5 THRU 5 NOMINAL TONS) Due to continuous product im provement, specifications a re subject to cha nge with ou t notice. Visit us on the web at www . york.com Additional rating informa tion can be foun d at www . ahridirectory .org W ARRANTY S tandard 5-year li ...

  • Johnson Controls TCGD18 THRU 60 - page 2

    359319-BTG-G-0509 2 Johnson Controls Unitary Products All dimensions are in inche s. They are subject to ch ange with- out notice. Certified dimensions will be provi ded upon request. Physical and Electr ical Dat a MODEL TCGD18 S41S1(H) TCGD24 S41S1 TCGD30 S41S1( H) TCGD36 S41S1(H) TCGD42 S41S1(H) TCGD48 S41S1(H) TCGD60 S41S1 Unit Supply V oltage 2 ...

  • Johnson Controls TCGD18 THRU 60 - page 3

    359319-BTG-G-0509 Johnson Controls Unitary Pro ducts 3 PROCEDURES: 1. Unit factory charge listed on the u nit nameplate includes re friger ant for the condenser , the smallest evaporator and 15 feet of int erconnecting line tub ing. 2. V erify the TXV and additional charge required for specific evaporator coil in the system using the above table. 3 ...

  • Johnson Controls TCGD18 THRU 60 - page 4

    359319-BTG-G-0509 4 Johnson Controls Unitary Products COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 13 SEER AC WITH MA TCGD18S41S1(H) MA08B 17 FC/MC18B 600 17.5 12.9 13.00 1 1.00 TCGD24S41S1(H) MA08B 17 FC/MC36B 800 24.0 16.7 13.00 1 1.00 MA08B 17 FC/MC35B 800 ...

  • Johnson Controls TCGD18 THRU 60 - page 5

    359319-BTG-G-0509 Johnson Controls Unitary Pro ducts 5 — = Not applicable. 13 SEER AC WITH AHP / SHP / AHX / F*FP TCGD18S41S1(H) AHP18 17 – 650 17.5 12.9 13.00 1 1.00 AHX18 17 - 630 18.0 13.8 14.50 12.00 F4FP024 18 – 600 17.5 12.9 13.00 1 1.00 F6FP018 17 - 600 17.8 13.3 14.50 12.00 TCGD24S41S1(H) AHP30 17 – 795 24.0 16.8 13.00 1 1.00 AHX30 ...

  • Johnson Controls TCGD18 THRU 60 - page 6

    359319-BTG-G-0509 6 Johnson Controls Unitary Products COOLING CAP ACITY - Upflow , Downflow & Horizontal Furnace s and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RA TED CFM NET MBH SEER 1 EER TOT AL SENS. TCGD18S41S1(H) 450 - 750 14,17 FC/MC/PC18 600 17 .5 12.9 13.00 1 1.00 450 - 750 14 HC18 600 17 .5 12.9 13.00 1 1.0 ...

  • Johnson Controls TCGD18 THRU 60 - page 7

    359319-BTG-G-0509 Johnson Controls Unitary Pro ducts 7 COOLING CAP ACITY - With High Efficiency Motor Furna ces MODELS FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT AL SE N S. 13 SEER HP WITH V ARIABLE SPEED FURNACES 2 TCGD18S41S1(H) T*(8,L)X*A12 FC/MC/PC18A 14 540 17.7 12.9 14.50 12.50 T*(8,L)X*B12 FC/MC/PC18B 17 580 18.0 13 ...

  • Johnson Controls TCGD18 THRU 60 - page 8

    359319-BTG-G-0509 8 Johnson Controls Unitary Products TCGD30S41S1(H) T*9X*C20 FC/MC/PC43C 21 720 28.2 19.3 14.00 12.00 T*(8,L)C*A12 FC/MC/PC32A 14 1045 29.2 21.8 13.20 1 1.00 T*(8,L)C*B12 FC/MC/PC35B 17 995 29.6 21.4 14 .00 1 1.50 (T*9C/T*9V)*B12 FC/MC/PC35B 17 1045 29.4 22.0 13.50 1 1.50 T*(8,L)C*C16 FC/MC/PC35C 21 1025 29.6 22.0 14.00 12.00 T*(8, ...

  • Johnson Controls TCGD18 THRU 60 - page 9

    359319-BTG-G-0509 Johnson Controls Unitary Pro ducts 9 TCGD36S41S1(H) T*(8,L)C*C20 HC42 21 1 190 35.6 25.6 14.00 12.00 (T*9C/T*9V)*C16 HC42 21 124 0 35.4 25.2 13.50 1 1.50 (T*9C/T*9V)*C20 HC42 21 120 0 35.6 25.4 14.00 1 1.50 T*(8,L)C*C16 UC48C 21 1210 34.6 24.8 13.50 1 1.50 T*(8,L)C*C20 UC48C 21 1 155 34.8 24.8 14.00 1 1.50 (T*9C/T*9V)*C16 UC48C 21 ...

  • Johnson Controls TCGD18 THRU 60 - page 10

    359319-BTG-G-0509 10 Johnson Controls Unitary Products TCGD48S41S1(H) T*(8,L)X*C16 FC/MC/PC48C 21 1600 48.0 34.4 13.30 1 1.00 T*(8,L)X*C20 FC/MC/PC48C 21 1660 48.0 34.4 13.20 1 1.00 T*9X*C16 FC/MC/PC48C 21 1565 48.0 34.8 13.10 1 1.00 T*9X*C20 FC/MC/PC48C 21 1615 48.0 34.4 13.20 1 1.00 T*9X*D20 FC/MC/PC48D 24 1635 48.0 34.8 13.20 1 1.00 T*(8,L)X*C16 ...

  • Johnson Controls TCGD18 THRU 60 - page 11

    359319-BTG-G-0509 Johnson Controls Unitary Pro ducts 11 ACCESSORIES Refer to Price Manua l for specific model numbers. Off Cycle Timer Delay - Provides a 5-minu te off cycle to pre- vent rapid recycling of the compressor . Hard St art Kit - Required when using TXV indoor coil. Also , provides increased starting torque for areas with low voltage. Th ...

  • Johnson Controls TCGD18 THRU 60 - page 12

    359319-BTG-G-0509 12 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • Johnson Controls TCGD18 THRU 60 - page 13

    359319-BTG-G-0509 Johnson Controls Unitary Pro ducts 13 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7 3-87 F), sensible capacity increase s by 1060 BTUH per 1000 CFM per degree above the l isted temperature and decrease s by 1060 BTUH per 1000 CFM per ...

  • Johnson Controls TCGD18 THRU 60 - page 14

    359319-BTG-G-0509 14 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • Johnson Controls TCGD18 THRU 60 - page 15

    359319-BTG-G-0509 Johnson Controls Unitary Pro ducts 15 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7 3-87 F), sensible capacity increase s by 1060 BTUH per 1000 CFM per degree above the l isted temperature and decrease s by 1060 BTUH per 1000 CFM per ...

  • Johnson Controls TCGD18 THRU 60 - page 16

    359319-BTG-G-0509 16 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • Johnson Controls TCGD18 THRU 60 - page 17

    359319-BTG-G-0509 Johnson Controls Unitary Pro ducts 17 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7 3-87 F), sensible capacity increase s by 1060 BTUH per 1000 CFM per degree above the l isted temperature and decrease s by 1060 BTUH per 1000 CFM per ...

  • Johnson Controls TCGD18 THRU 60 - page 18

    Subject to change without notice. Publishe d in U.S.A. 359319-BTG-G-0509 Copyright © 2009 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 359319-FTG-F-0309 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif fe ...

Manufacturer Johnson Controls Category Air Conditioner

Documents that we receive from a manufacturer of a Johnson Controls TCGD18 THRU 60 can be divided into several groups. They are, among others:
- Johnson Controls technical drawings
- TCGD18 THRU 60 manuals
- Johnson Controls product data sheets
- information booklets
- or energy labels Johnson Controls TCGD18 THRU 60
All of them are important, but the most important information from the point of view of use of the device are in the user manual Johnson Controls TCGD18 THRU 60.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Johnson Controls TCGD18 THRU 60, service manual, brief instructions and user manuals Johnson Controls TCGD18 THRU 60. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Johnson Controls TCGD18 THRU 60.

A complete manual for the device Johnson Controls TCGD18 THRU 60, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Johnson Controls TCGD18 THRU 60 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Johnson Controls TCGD18 THRU 60.

A complete Johnson Controls manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Johnson Controls TCGD18 THRU 60 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Johnson Controls TCGD18 THRU 60, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Johnson Controls TCGD18 THRU 60, that we can find in the current document
3. Tips how to use the basic functions of the device Johnson Controls TCGD18 THRU 60 - which should help us in our first steps of using Johnson Controls TCGD18 THRU 60
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Johnson Controls TCGD18 THRU 60
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Johnson Controls TCGD18 THRU 60 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Johnson Controls TCGD18 THRU 60?

Use the form below

If you did not solve your problem by using a manual Johnson Controls TCGD18 THRU 60, ask a question using the form below. If a user had a similar problem with Johnson Controls TCGD18 THRU 60 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)