    MS-A•W A · MU-A•W A MSZ-A•NA · MUZ-A•NA · MUZ-A•NA - U MSY -A•NA · MUY -A•NA MSZ-FD•NA · MUZ-FD•NA · MUZ-FD•NA - U MSZ-D•NA · MUZ-D•NA · MUZ-D•NA - U MSY -D•NA · MUY -D•NA · MXZ-A•NA SER VICE TECHNICAL GUIDE CONTENTS 1. MS MICROPROCESSOR CONTROL ·················· 4 2. MSZ, MSY MICROPROCES ...

  • Mitsubishi Electronics MU-AWA - page 2

    2 Revision A: • MXZ-3A30NA- 1 has been added. Revision B: • MXZ-2A20NA- 1 , MXZ-4A36NA, MSZ-FD, MSZ-D and MSY -D have been added. ...

  • Mitsubishi Electronics MU-AWA - page 3

    1. MS MICROPROCESSOR CONTROL ··························································· 4 Indoor unit models Outdoor unit models MS-A09W A MU-A09W A MS-A12W A MU-A12W A 1-1. COOL OPERA TION ·················································· ...

  • Mitsubishi Electronics MU-AWA - page 4

    4 MS MICROPROCESSOR CONTROL 1 1-1. COOL ( ) OPERA TION MS-A•W A MU-A•W A 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat’s OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Thermostat is ON or OFF by difference between room temperature an ...

  • Mitsubishi Electronics MU-AWA - page 5

    5 1. Thermostat control Thermostat is ON or OFF by difference between room temperature and set temperature. 2. Indoor fan speed control Indoor fan operates at the set speed by F AN SPEED CONTROL button. When thermostat OFF (compressor OFF), fan speed becomes V ery Low . In AUTO the fan speed is as follows. 4. Coil frost prevention Coil frost preven ...

  • Mitsubishi Electronics MU-AWA - page 6

    6 1-3. AUTO V ANE OPERA TION 1. Horizontal vane <SWING operation> In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”. According to the temperature of indoor coil thermistor at starting of this operation, next downward blow time is decided. Then when the downward blow has been finish ...

  • Mitsubishi Electronics MU-AWA - page 7

    7 MSZ,MSY MICROPROCESSOR CONTROL 2 2-1. COOL ( ) OPERA TION 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat’s OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Thermostat is ON or OFF by difference between room temperature and set temperature ...

  • Mitsubishi Electronics MU-AWA - page 8

    8 Set temperature is as shown on the right chart. The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room tem- perature. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease. 2-2. DR Y ( ) OP ...

  • Mitsubishi Electronics MU-AWA - page 9

    9 (2) Cold air prevention control MSZ-A09/12/15/17 MSZ-FD MSZ-D When the compressor is not operating, ( ) if the temperature of room temperature thermistor is less than 66 °F , the fan stops. ( ) if the temperature of room temperature thermistor is 66 °F or more and ( ) if the temperature of indoor coil themistor is less than 32 °F , the fan sto ...

  • Mitsubishi Electronics MU-AWA - page 10

    set position set speed set position set speed Indoor fan Compressor normal Outdoor fan R.V . coil (21S4) OFF (COOL) OFF Maximum frequency horizontal Horizontal vane V ery Low (temperature of indoor coil thermistor > 64 °F) 30 seconds 30 seconds 30 seconds 40 seconds 5 seconds 5 seconds 40 seconds OFF OFF OFF ON (HEA T) ON ON ON (HEA T) horizont ...

  • Mitsubishi Electronics MU-AWA - page 11

    11 (2) Mode change In case of the following conditions, the operation mode is changed. COOL mode changes to HEA T mode when 15 minutes have passed with the room temperature 4 °F below the set temperature. HEA T mode changes to COOL mode when 15 minutes have passed with the room temperature 4 °F above the set temperature. In the other cases than t ...

  • Mitsubishi Electronics MU-AWA - page 12

    12 <SWING operation> In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”. According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is decided. Then when the downward blow has been finished, next horizontal blow time is decided ...

  • Mitsubishi Electronics MU-AWA - page 13

    13 MUZ-A24 MUY -A24 MUZ-D MUY -D POWER SUPPL Y NOISE FIL TER CIRCUIT RESISTOR RELA Y SMOOTHING CAP ACITOR CURRENT TRANSFORMER COMPRESSOR REACTOR P W V U N IPM PFC U W MS 3~ V + Function of main parts NAME FUNCTION INTELLIGENT POWER MODULE (IPM) It supplies three-phase AC power to compressor . SMOOTHING CAP ACIT OR It stabilizes the DC voltage and s ...

  • Mitsubishi Electronics MU-AWA - page 14

    Input current waveform without P AM Input current waveform with P AM Due to the time of no electricity; · Power factor gets worse. · Harmonic gets increased. Input voltage Energized time is short in case L inductance is small. No electricity runs into diode module because the voltage at both sides of smoothing capacitor is higher than input volta ...

  • Mitsubishi Electronics MU-AWA - page 15

    15 4. Intelligent power module IPM consists of the following components · IGBT (x6) : Converts DC waveform to three-phase AC waveform and outputs it. · Drive Circuit : Drives transistors. · Protection circuit : Protects transistors from overcurrent. Since the above components are all integrated in IPM, IPM has a merit to make the control circuit ...

  • Mitsubishi Electronics MU-AWA - page 16

    16 2-7-3. Sine wave control In these air conditioners, compressor equips brushless DC motor which doesn't have Hall element. In short, the motor is sensorless. However , it's necessary to locate the polar direction of rotor in order to drive brushless DC mo- tor ef fi ciently . The general detection method of the polar direction for such ...

  • Mitsubishi Electronics MU-AWA - page 17

    17 2-8. OPERA TIONAL FREQUENCY CONTROL OF OUTDOOR UNIT 1. Outline The operational frequency is as following: First, the target operational frequency is set based on the difference between the room temperature and the set tem- perature. Second, the target operational frequency is regulated by discharge temperature protection, high pressure protectio ...

  • Mitsubishi Electronics MU-AWA - page 18

    18 2-9. EXP ANSION V AL VE CONTROL (LEV CONTROL) (1) Outline of LEV control The LEV basic control is comprised of setting LEV opening degree to the standard opening °F set for each operational frequency of the compressor . However , when any change in indoor/outdoor temperatures or other factors cause air con- ditioning load fluctuation, the LEV c ...

  • Mitsubishi Electronics MU-AWA - page 19

    19 (2) T ime chart OFF T ime Ti m e ON Operational frequency of the compressor Commanded to open Standard opening degree Opening degree is corrected according to discharge temperature. Positioning Air conditioner ON Air conditioner OFF (thermostat off) LEV opening degree about 5 minutes <COOL, DRY> about 15 minutes <HEA T> (3) Control d ...

  • Mitsubishi Electronics MU-AWA - page 20

    20 (b) Reference value of LEV standard opening degree (pulse) Applied model A B C D E F MUZ-A09/12 COOL 130 190 240 260 260 260 HEA T 100 130 170 210 230 230 MUZ-A15/17 MUY -A15/17 COOL 290 300 350 350 370 370 HEA T 130 150 220 250 280 300 MUZ-A24 MUY -A24 COOL 150 166 186 206 230 260 HEA T 130 150 170 196 210 226 MUZ-FD COOL 180 240 300 320 320 32 ...

  • Mitsubishi Electronics MU-AWA - page 21

    21 MXZ MICROPROCESSOR CONTROL 3 3-1. INVERTER SYSTEM CONTROL MXZ-A•NA POWER SUPPL Y NOISE FIL TER CIRCUIT RESISTOR RELA Y SMOOTHING CAP ACITOR CURRENT TRANSFORMER COMPRESSOR REACTOR P W V U N IPM PFC U W MS 3~ V + 3-1-1. Inverter main power supply circuit Function of main parts NAME FUNCTION INTELLIGENT POWER MODULE (IPM) It supplies three-phase ...

  • Mitsubishi Electronics MU-AWA - page 22

    22 3. Power factor improvement Booster coil reactor and PFC rectify AC to DC and control its voltage. In the motor drive system of sine wave control, power factor can be improved by reducing harmonics. PFC and reactor stabi- lize the voltage of DC supplied to inverter circuit and make its waveform smooth. 4. Power transistor module IPM consists of ...

  • Mitsubishi Electronics MU-AWA - page 23

    23 3-2. EXP ANSION V AL VE CONTROL (LEV CONTROL) Linear expansion valve (LEV) is controlled by “Thermostat ON” commands given from each unit. Indoor unit status LEV opening Stop of all indoor unit Opening before stop → 500 pulse in 15 minutes When outdoor unit is operating, some indoor units stop and some operate. COOL : 5 pulse (full closed) ...

  • Mitsubishi Electronics MU-AWA - page 24

    24 In COOL mode, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (super heat) at the heat exchanger , and when temperature difference have developed, the indoor coil thermistors adjust LEV opening to dimin- ish the super heat. This action is called Evaporation T emperature Protection. Indoor heat exchanger (MXZ ...

  • Mitsubishi Electronics MU-AWA - page 25

    25 23 54 69 84 100 1 15 131 146 38 14 32 41 50 59 68 77 86 MXZ-2A MXZ-3A/4A 23 Compressor operating frequency (Hz) 4Hz 01 02 03 04 05 06 07 08 09 10 LEV Opening (code) Determination of LEV standard opening in each indoor unit • The standard opening is on the straight line, which connects an each standard point in the section where divided into se ...

  • Mitsubishi Electronics MU-AWA - page 26

    26 MXZ-3A30NA- 1 MXZ-4A36NA Exclusive LEV Standard opening (pulse) LEV Opening (code) 123456789 1 0 COOL 126 130 134 138 150 160 170 180 190 200 HEA T 248 248 258 266 274 280 286 292 300 306 Difference in capacity Difference in operation number Code3,4 Code5,6 Code7,8 Code9,10 Code1 1,12 Code13,14 Code15or above 23 4( MXZ-4A ) COOL 3 6 9 12 15 25 3 ...

  • Mitsubishi Electronics MU-AWA - page 27

    27 (1) LEV opening correction by discharge temperature The target discharge temperature is determined according to frequency zone and number of operation unit of the com- pressor . <Correction> COOL DRY HEA T Discharge temperature ● 2 ● 2 ● Each correction • (Each gas pipe temperature thermistor - Minimum gas pipe temperature thermist ...

  • Mitsubishi Electronics MU-AWA - page 28

    28 Correct the LEV opening according to the difference between target discharge temperature and discharge temperature. (2) Separate correction (COOL,DR Y) (Correction by the separate super heat) a) Correct the LEV separately by temperature difference between each gas pipe temperature and the minimum gas pipe temperature of all. Calculate each super ...

  • Mitsubishi Electronics MU-AWA - page 29

    29 3-3. OPERA TIONAL FREQUENCY RANGE b) Correct the LEV separately by temperature difference “ ∆ RT” between main/sub indoor coil thermistor . ∆ RT LEV opening correction (pulse) 10.8 ∆ RT 2 7.2 ∆ RT < 10.8 1 ∆ RT < 7.2 1 In addition, decrease the target discharge temperature corresponding ∆ RT . ∆ RT T emperature to be decr ...

  • Mitsubishi Electronics MU-AWA - page 30

    30 3-6. OUTDOOR F AN CONTROL Fan speed is switched according to the number of operating indoor unit and the compressor frequency . 3-5. DISCHARGE TEMPERA TURE PROTECTION CONTROL This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge tempera- ture thermistor . (1) Compressor ON/OFF When tempe ...

  • Mitsubishi Electronics MU-AWA - page 31

    31 1. Pre-heat control is turned ON for 15 or 30 min, after the breaker is turned ON. 2. 30 min. after the unit is stopped, pre-heat control is turned ON for 15 or 30 min. and turned OFF for 30 min." This is repeated as shown in the graph until the breaker is turned OFF . When outside temperature is 68 °F or below , pre-heat control is ON for ...

  • Mitsubishi Electronics MU-AWA - page 32

    New publication, effective Feb. 2008 Specifications subject to change without notice. Copyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO.,L TD Distributed in Feb. 2008. No. OBT16 REVISED EDITION-B 6 Distributed in May 2007. No. OBT16 REVISED EDITION-A 7 Distributed in Apr . 2006. No. OBT16 7 Made in Japan HEAD OFFICE: TOKYO BLDG.,2-7-3, MARUNOUCHI, ...

Manufacturer Mitsubishi Electronics Category Air Conditioner

Documents that we receive from a manufacturer of a Mitsubishi Electronics MU-AWA can be divided into several groups. They are, among others:
- Mitsubishi Electronics technical drawings
- MU-AWA manuals
- Mitsubishi Electronics product data sheets
- information booklets
- or energy labels Mitsubishi Electronics MU-AWA
All of them are important, but the most important information from the point of view of use of the device are in the user manual Mitsubishi Electronics MU-AWA.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Mitsubishi Electronics MU-AWA, service manual, brief instructions and user manuals Mitsubishi Electronics MU-AWA. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Mitsubishi Electronics MU-AWA.

A complete manual for the device Mitsubishi Electronics MU-AWA, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Mitsubishi Electronics MU-AWA by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Mitsubishi Electronics MU-AWA.

A complete Mitsubishi Electronics manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Mitsubishi Electronics MU-AWA - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Mitsubishi Electronics MU-AWA, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Mitsubishi Electronics MU-AWA, that we can find in the current document
3. Tips how to use the basic functions of the device Mitsubishi Electronics MU-AWA - which should help us in our first steps of using Mitsubishi Electronics MU-AWA
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Mitsubishi Electronics MU-AWA
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Mitsubishi Electronics MU-AWA in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Mitsubishi Electronics MU-AWA?

Use the form below

If you did not solve your problem by using a manual Mitsubishi Electronics MU-AWA, ask a question using the form below. If a user had a similar problem with Mitsubishi Electronics MU-AWA it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)