    SSI ERP2U (Entry Redundant Power 2U) Power Supply Design Guide A Server System Infrastructure (SSI) Specification For 2U Rack Chassis Power Supplies Version 2.31 ...

  • SSI America ERP2U - page 2

    SSI ERP2U Power Supply Design Guide, V2.31 - 2 - Revision History Orig./Rev. Description of Changes 2.0 Post design guide 2.2 Added higher power levels up to 800W. Added 350mm depth. Removed lower power levels. Added standby fan operation. Added option for tighter 12V regulation. Added 12V4. Add new SSI efficiency requirements (reco mmended level & ...

  • SSI America ERP2U - page 3

    SSI ERP2U Power Supply Design Guide, V2.31 - 3 - Disclaimer: THIS SPECIFICATION IS PROVIDED "AS IS" WITH NO WARRA NTIES WHATSOEVER, INCLUDING ANY WARRANTY OF MERCHANTABILITY, NONINFRINGEMENT, FITNESS FOR ANY PARTICULAR PURPOSE, OR ANY WARRANTY OTHERWISE ARISING OUT OF ANY PROPOSAL, SPECIFICATION OR SAMPLE. WITHOUT LIMITATION, THE PR OMOTE ...

  • SSI America ERP2U - page 4

    SSI ERP2U Power Supply Design Guide, V2.31 - 4 - Contents 1 Purpose........................................................................................................................ .................................. 7 2 Conceptual Overview ....................................................................................................... ...

  • SSI America ERP2U - page 5

    SSI ERP2U Power Supply Design Guide, V2.31 - 5 - 8.4 Power Supply Managem ent Interface .............................................................................................. ......... 31 8.5 Field Replacement Un it (FRU) Signals ........................................................................................... .......... 32 8.5.1 ...

  • SSI America ERP2U - page 6

    SSI ERP2U Power Supply Design Guide, V2.31 - 6 - Table 34: FRU Device Product Inform ation Area ................................................................................. .................. 33 Table 35: LE D Indica tors ...................................................................................................... .................... ...

  • SSI America ERP2U - page 7

    SSI ERP2U Power Supply Design Guide, V2.31 - 7 - 1 2 Purpose This 2U Rack Power Supply Desig n Guide defines a common re dundant power sub -sy stem used in 2U rack mount servers. The power sub-system is made up of a cage and h ot swa p redundant powe r module s. This Design Guide covers the m ech anical and electrical re quirem ents of this power s ...

  • SSI America ERP2U - page 8

    SSI ERP2U Power Supply Design Guide, V2.31 - 8 - 3 Definitions/T erms/Acronyms Required The status given to items within this design guide, which are required to meet SSI guidelines and a large ma jority of system appl ications. Recommended The status given to items within this design guide which are not requ ired to meet SSI guidelines, however, a ...

  • SSI America ERP2U - page 9

    SSI ERP2U Power Supply Design Guide, V2.31 - 9 - 4 Mechanical Overview STATUS Required (Optional) The ERP2U is a power sub-sy stem made up of a cage and redundant, hot swappable power supply modules. A mechanical drawing of the cag e is shown below in Figure 1 . Two depths are defined to the cage; 400m m and 350mm. This cage is intended to be mount ...

  • SSI America ERP2U - page 10

    SSI ERP2U Power Supply Design Guide, V2.31 - 10 - 4.1 Acoustic Requirements STATUS Recommended It is recommended the power su pplie s have a variable speed fan b ase d on temperature and loading co nditions. There are three different acoustic sound powe r levels defined at different ambient temperatures and loadin g conditions. Table 1 Recommended ...

  • SSI America ERP2U - page 11

    SSI ERP2U Power Supply Design Guide, V2.31 - 11 - The power supply shall ope rate within all specified limits over the T op temperatu re rang e. All airflow shall pass through the power supply and not over t he ex terior surfaces of the power supply . Table 2: Thermal Requirements ITEM DESCRIPTION MIN MAX UNITS T op Operating temperature range. 0 5 ...

  • SSI America ERP2U - page 12

    SSI ERP2U Power Supply Design Guide, V2.31 - 12 - Table 3: AC Input Rating PA RAME TE R MIN RA TED MA X Voltage (110) 90 V rms 100-127 V rm s 140 V rms Voltage (220) 180 V rms 200-240 V rms 264 V rms Frequency 47 Hz 63 Hz 5.4 Input Under Voltage STATUS Required The power supply shall con t ain prote ction circuitry such that application of an input ...

  • SSI America ERP2U - page 13

    SSI ERP2U Power Supply Design Guide, V2.31 - 13 - AC line shall not cause damage to the powe r su pply. In the case of redundant AC inputs, the AC line dropout may occur on either or both AC inlet. 5.7 AC Line Fuse STATUS Required The power supply shall incorpo rate one input fuse on the LINE side for input over-cur rent protection to prevent damag ...

  • SSI America ERP2U - page 14

    SSI ERP2U Power Supply Design Guide, V2.31 - 14 - recoverable Table 6: AC Line Surge Transient Performance AC Line Surge Duration Surge Operating AC Voltage Line Frequenc y Performance Criteria Continuous 10% Nominal AC Voltages 50/ 60 Hz No loss of func tion or performance 0 to ½ AC cycl e 30% Mid-point of nominal AC Voltages 50/60 Hz No loss of ...

  • SSI America ERP2U - page 15

    SSI ERP2U Power Supply Design Guide, V2.31 - 15 - 6 DC Output Specification These are the output requirements for the po we r supply assembly including cage and module . 6.1 Output Connectors The power supply distribution boa rd shall have one of the two following output connector and wire harne ss configurations, depending upon the type of 12V rai ...

  • SSI America ERP2U - page 16

    SSI ERP2U Power Supply Design Guide, V2.31 - 16 - If 240VA limiting is not a requirement for the power supply than all +12V outputs are common and ma y have the same wire color (yellow) . 6.1.2 +12V4 Baseboard Power Connector STATUS Required for 700W, 750W and 800W p o w er levels Systems that require more then 16A of +12V current to the basebo ard ...

  • SSI America ERP2U - page 17

    SSI ERP2U Power Supply Design Guide, V2.31 - 17 - 2. If 240VA limiting is not a requirement for the power s upply than all +12V outputs are common and ma y have the same wire c olo r. 6.1.5 Serial ATA Power Connector STATUS Optional This is a required conn ecto r for systems with serial AT A devices. The detailed requirements for the serial ATA con ...

  • SSI America ERP2U - page 18

    SSI ERP2U Power Supply Design Guide, V2.31 - 18 - 1 SMBus Clock White/Green Stripe 2 SMBus Data White/Yellow Stripe 3 SMBAlert 4 ReturnS Black/White Stripe 5 3.3RS Orange/White Stripe 6.2 Grounding STATUS Required The ground of the pins of the power assembly wire h arn es s provid es the power return path. The wire ha rness ground pins shall be con ...

  • SSI America ERP2U - page 19

    SSI ERP2U Power Supply Design Guide, V2.31 - 19 - +12V1 0 A 16 A 18 A +12V2 0 A 16 A 18 A +12V3 0.9 A 14 A +12V4 0.1 A 8 A 13 A -12 V 0 A 0.5 A +5 VSB 0.1 A 2.0 A 1. Maximum continuous total DC output power should not exceed 550 W. 2. Maximum continuous combined load on +3.3 VD C and +5 VDC outputs shall not exceed 140 W. 3. Maximum Peak total DC o ...

  • SSI America ERP2U - page 20

    SSI ERP2U Power Supply Design Guide, V2.31 - 20 - 4. Peak power and current loading shall be supported for a minimum of 10 second. 5. Maximum combined current for the 12 V outputs shall be 45 A. 6. Maximum 12V combined peak current shall be 54 A. 7. The 3.3V and 5V may be supply by the mod ule or DC/DC converters powered from +12V in the cage. Tabl ...

  • SSI America ERP2U - page 21

    SSI ERP2U Power Supply Design Guide, V2.31 - 21 - Table 18: 800 W Load Ratings Voltage Minimum Continuous Maximum Continuou s Peak +3.3 V 7 0.8 A 24 A +5 V 7 0.5 A 30 A +12V1 0 A 16 A 18 A +12V2 0 A 16 A 18 A +12V3 0.9 A 16 A 18 A +12V4 0.1 A 16 A 18 A -12 V 0 A 0.5 A +5 VSB 0.1 A 3.0 A 3.5 A 1. Maximum continuous total DC output power should not e ...

  • SSI America ERP2U - page 22

    SSI ERP2U Power Supply Design Guide, V2.31 - 22 - Table 19: Voltage Regulation Limits Parameter MIN NOM MAX Units Tolerance +3.3 V +3.14 +3.30 +3.47 V rm s +/-5% +5 V +4.75 +5.00 +5.25 V rms +/-5% +12V1,2,3,4 +11. 40 +12.00 +12.60 V rms +/-5% -12 V -10.80 -12.20 -13.20 V rms +/-10% +5 VSB +4.75 +5.00 +5.25 V rms +/-5% STATUS Optional Some system ap ...

  • SSI America ERP2U - page 23

    SSI ERP2U Power Supply Design Guide, V2.31 - 23 - Required The power supply shall be stable a nd meet all requirem ents, except dynamic loa ding requirements, with the following capacitive loading ranges. Note: Up to 10,000 μ F of the +12V capacitive loading may be on the +12V1 out put. Table 22: Capacitve Loading Conditions Output MIN MAX Units + ...

  • SSI America ERP2U - page 24

    SSI ERP2U Power Supply Design Guide, V2.31 - 24 - 6.9 Redundancy The power sub-system ma y have different levels of redundancy dependi ng upon the availability requirements of the system. The Required, Reco mmen ded, and Optional items are broken down here. To be redunda nt each item must be in the hot swap power supply module. STATUS Required The ...

  • SSI America ERP2U - page 25

    SSI ERP2U Power Supply Design Guide, V2.31 - 25 - may be removed, then replaced with a g ood po wer supply, however, hot swap needs to work with ope ratio nal as well as failed power supplies. The newl y inserted power su pply may get turned on by inserting the sup ply into the system or by system management recognizing an inserted su pply and expl ...

  • SSI America ERP2U - page 26

    SSI ERP2U Power Supply Design Guide, V2.31 - 26 - Table 25: Turn On/Off Timing Item Description MIN MAX UNITS T sb_on_delay Delay from AC being applied to 5 VSB being within regulation. 1500 ms T ac_on_delay Delay from AC being applied to all output volt ages being within regulation. 2500 ms T vout_holdup Time all output voltages stay within regula ...

  • SSI America ERP2U - page 27

    SSI ERP2U Power Supply Design Guide, V2.31 - 27 - Figure 4: Turn On/Off Timing AC Input Vout PWOK 5VSB N# PSO T sb_on_dela y T AC_on_dela y T pwok_on T vout_holdup T pwok_holdup T pson_on_dela y T sb o n de l ay T pwok_on T pwok_off T pwok _off T pwok_low T pson_pwok T sb_vout AC turn on/off cycle PSON turn on/off cycle Tsb_holdup ...

  • SSI America ERP2U - page 28

    SSI ERP2U Power Supply Design Guide, V2.31 - 28 - 7 Protection Circuits STATUS Required Protection circuits inside the power supply shall cause only the power supply’s m ain outputs to shutdown. If the power supply latches off due to a protection circuit tri pping, an AC cycle OFF for 15 s and a PSON # cycle H IGH for 1 s must be able to reset th ...

  • SSI America ERP2U - page 29

    SSI ERP2U Power Supply Design Guide, V2.31 - 29 - 7.3 Over Voltage Protection STATUS Required The power supply over voltage protection shall be loca lly sensed in the hot swa p modules. The power supply shall shutdown and latch off after an over voltage conditi on occurs. This latch shall be cleared by toggling the PSON # signal or by an AC power i ...

  • SSI America ERP2U - page 30

    SSI ERP2U Power Supply Design Guide, V2.31 - 30 - 8 Control and Indicator Functions The following sections define the input and output si gnals from the power supply. Signals that can be defined as low true use the following co nventio n: signal # = low true 8.1 PSON# STATUS Required The PSON # signal is required to remotely turn on/off the power s ...

  • SSI America ERP2U - page 31

    SSI ERP2U Power Supply Design Guide, V2.31 - 31 - 8.2 PWOK (Power OK) STATUS Required PWOK is a power OK signal and will be pulled HIGH by the pow er supply to indicate that all the outputs are within the regulation limits of the power supply. When any output voltag e falls belo w regulation limits or when AC powe r has been removed for a time suff ...

  • SSI America ERP2U - page 32

    SSI ERP2U Power Supply Design Guide, V2.31 - 32 - PDB addressing A0/A1 0/0 0/1 1/0 1/1 Power supply PSMI device B0h B2h B4h B6h 8.5 Field Replacement Un it (FRU) Signals STATUS Optional The FRU device in the power supply shall derive its power off of the 5VSB out put on the system side of the or’ing device and grounded to ReturnS. The Write Contr ...

  • SSI America ERP2U - page 33

    SSI ERP2U Power Supply Design Guide, V2.31 - 33 - FRU File ID {Not required} PAD Bytes {Added as necessary to allo w for 8-byte offset to next area} 8.5.2.2 MultiRecord Area Implement as defined by the IPMI FRU document. The follo wing record types sh all be used on this power sup ply: • Power Supply Information (Record Type 0x00) • DC Output ( ...

  • SSI America ERP2U - page 34

    SSI ERP2U Power Supply Design Guide, V2.31 - 34 - available. The AMBER LED shall turn ON to indicate t hat the power supply has failed, shutdown due to over current, or shutdown due to over temperature. Refer to Table 35: LED Indicators for conditions of the LED(s). Table 34: LED Indicators POWER SUPPLY CONDITION Power Supply LED(s) AMBER GREEN No ...

  • SSI America ERP2U - page 35

    SSI ERP2U Power Supply Design Guide, V2.31 - 35 - 9 MTBF STATUS Recommended The power module shall have a minimu m MTBF at continuo us operation of 1) 50,000 hours at 100% load and 45 ° C, as calculated by Bellcore RPP, or 2) 100,000 hours demonstrated at 100 % load and 5 0 ° C. The power cage shall have a minimum MTBF at continuous op erat ion o ...

Manufacturer SSI America Category Power Supply

Documents that we receive from a manufacturer of a SSI America ERP2U can be divided into several groups. They are, among others:
- SSI America technical drawings
- ERP2U manuals
- SSI America product data sheets
- information booklets
- or energy labels SSI America ERP2U
All of them are important, but the most important information from the point of view of use of the device are in the user manual SSI America ERP2U.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals SSI America ERP2U, service manual, brief instructions and user manuals SSI America ERP2U. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product SSI America ERP2U.

A complete manual for the device SSI America ERP2U, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use SSI America ERP2U by users. Manuals are usually written by a technical writer, but in a language understandable to all users of SSI America ERP2U.

A complete SSI America manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual SSI America ERP2U - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the SSI America ERP2U, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the SSI America ERP2U, that we can find in the current document
3. Tips how to use the basic functions of the device SSI America ERP2U - which should help us in our first steps of using SSI America ERP2U
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with SSI America ERP2U
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of SSI America ERP2U in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning SSI America ERP2U?

Use the form below

If you did not solve your problem by using a manual SSI America ERP2U, ask a question using the form below. If a user had a similar problem with SSI America ERP2U it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)