Manual MGE UPS Systems EPS 8000

54 pages 0.99 mb
Download

Go to site of 54

Summary
  • MGE UPS Systems EPS 8000 - page 1

    EPS 8000 UPS Single Module Users Manual www.mgeups.com ...

  • MGE UPS Systems EPS 8000 - page 2

    IMPORT ANT SAFETY INSTRUCTIONS SA VE THESE INSTRUCTIONS – This manual contains important instructions for all EPS 8000 UPS Single Module that must be followed during operation of the equipment. W ARNING: Opening enclosures expose hazardous voltages. Always refer service to qualified personnel only . A TTENTION: L'ouverture des cabinets expos ...

  • MGE UPS Systems EPS 8000 - page 3

    EPS 8000 UPS Single Module Users Manual For service call 1-800-523-0142 86-132217-00 A02 06/03 Copyright © 2003 MGE UPS SYSTEMS, Inc. All rights reserved. Printed in U.S.A. MGE UPS SYSTEMS, Inc. 1660 Scenic Avenue Costa Mesa, CA 92626 (714) 557-1636 page iii Users Manual ...

  • MGE UPS Systems EPS 8000 - page 4

    EPS 8000 UPS Single Module page iv EPS 8000 UPS Single Module Users Manual W arranty Information Wa rranty The liability of MGE UPS SYSTEMS, Inc. hereunder is limited to replacing or repairing at MGE UPS SYSTEMS, Inc.’s factory or on the job site at MGE UPS SYSTEMS, Inc.’ s option, any part or parts which are defective, including labor , for a ...

  • MGE UPS Systems EPS 8000 - page 5

    How T o Use This Manual page v Users Manual How T o Use This Manual This manual is designed for ease of use and easy location of information. To quickly find the meaning of terms used within the text, look to the Glossary . To quickly find a specific topic, look at the T able of Contents. This manual uses Note lines and icons to convey important in ...

  • MGE UPS Systems EPS 8000 - page 6

    CAUTION RECORD ALL SERIAL NUMBERS FOR THE SINGLE MODULE UPS SYSTEM. THESE SERIAL NUMBERS WILL BE REQUIRED IF YOUR SYSTEM NEEDS SER VICE. KEEP THIS MANUAL IN A PLACE WHERE YOU CAN REFERENCE THE SERIAL NUMBERS IF SER VICE IS REQUIRED! UPS UNIT SERIAL NUMBER: _____________________________________________ MBP CABINET SERIAL NUMBER: ____________________ ...

  • MGE UPS Systems EPS 8000 - page 7

    page c i Users Manual Contents section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page Important Safety Instructions . . . . . . . . . . . . . . . . .Inside Front Cover W arranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ivi Revision History . . . . . . ...

  • MGE UPS Systems EPS 8000 - page 8

    Section 2 Operation section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2.0 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1 2.1 Status Screen Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1 2.2 Settings Selection Screen . . . . . ...

  • MGE UPS Systems EPS 8000 - page 9

    Contents page c iii Users Manual Figures figure description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-1 EPS 8000 System, S-M Configuration, 1 GCC per Module . . . . . . .1-2 1-2 Circuit Breaker Locations on the EPS 8000. (Q4S not shown) . . . .1-3 1-3 Circuit Breaker Locations on the Maintenance Bypass ...

  • MGE UPS Systems EPS 8000 - page 10

    (This page left blank intentionally) EPS 8000 UPS Single Module page c iv ...

  • MGE UPS Systems EPS 8000 - page 11

    1.0 Scope This manual provides User instructions for operating the EPS 8000 UPS Single Module system (S-M). Descriptions include section descriptions, a general overview of system internal components, circuit breaker diagrams, descrip- tions for front panel displays and control indicators. Please read this manual before installing the EPS 8000 equi ...

  • MGE UPS Systems EPS 8000 - page 12

    1.3 General Description EPS 8000 is a family of compact, high-efficiency uninterruptible power systems. Standard power ratings for single- module systems range from 555 to 800 kV A. EPS 8000 UPS are optimized for compatibility with non-linear computer-type loads. Computer-aided UPS diagnostics and modular construction assures that any required serv ...

  • MGE UPS Systems EPS 8000 - page 13

    Introduction page 1 — 3 Users Manual 1.4 Specifications, Circuit Breakers and Powerflow Diagrams 1.4.1 Circuit Breakers EPS 8000 UPS circuit breakers (except the battery disconnect circuit breaker QF1) are located behind the doors of the Input/Output cabinet. Following is a brief description of the available circuit breakers and contacts, and the ...

  • MGE UPS Systems EPS 8000 - page 14

    Figure 1-3: Circuit Breaker Locations on the Maintenance Bypass Cabinet. Figure 1-4: Circuit Breaker Locations on the Q4S Cabinet. Introduction EPS 8000 UPS Single Module page 1 — 4 BYP ASS INPUT A, B, C NEUTRAL GROUND BYP ASS INPUT CB Q4S GROUND BYP ASS INPUT A, B, C NEUTRAL Q5N OUTPUT A, B, C Q3BP Q4S (optional) ...

  • MGE UPS Systems EPS 8000 - page 15

    Introduction page 1 — 5 Users Manual 1.4.2 Power Flow Diagrams 1.4.2.1 Normal Operation During normal operation, power flows from the main AC input source (mains 1) into the UPS rectifier/battery charger section. The rectifier/battery charger converts the AC voltage to DC, maintains the charge of the battery , and feeds the DC power to the invert ...

  • MGE UPS Systems EPS 8000 - page 16

    1.5 Single Module Indicators and Controls Single Module indicators and controls are located in three places on the UPS cabinet: on the front panel, behind a drop-down cover just below the front panel, and inside the cabinet doors, see Figure 1-7. In battery cabinets and auxiliary cabinets, the controls are located behind the cabinet doors. The foll ...

  • MGE UPS Systems EPS 8000 - page 17

    Introduction page 1 — 7 Users Manual 1.5.1 Front Panel The UPS front panel, includes the emergency power off (EPO) pushbutton, the audible alarm, four LEDs that serve as system status indicators, the “inverter on” pushbutton, and the “inverter off” pushbutton. See Figure 1-8. Figure 1-8: Front Panel Indicators and Control Display . EPO On ...

  • MGE UPS Systems EPS 8000 - page 18

    AC input (mains 2) source, the static switch transfers the load to the inverter output. If the inverter cannot synchronize to the bypass AC input (mains 2) source, the load must be forced to transfer using the hidden panel (see section 2.1 1, Forced Tr ansfers). Inverter off (item 7) This gray pushbutton is used to stop the inverter . When it is pr ...

  • MGE UPS Systems EPS 8000 - page 19

    Introduction page 1 — 9 Users Manual 1.5.2.2 Alphanumeric Display Pushbuttons Descriptions of the function of the alphanumeric display settings pushbuttons. ø Settings This pushbutton is used to select the display language and adjust the LCD screen contrast for optimal viewing. ˘ Selection Depending on the displayed message, the “ ˘ ” key ...

  • MGE UPS Systems EPS 8000 - page 20

    Ø On/off This pushbutton is reserved for future use. ° Confirmation/V erify Depending on the displayed message, this pushbutton may serve to indicate confir- mation, positive response, and other functions. 1.5.2.3 Numbered Lights During normal operation, the green LED #1 will be on, indicating that the UPS core controller communicates with the di ...

  • MGE UPS Systems EPS 8000 - page 21

    Introduction page 1 — 11 Users Manual 1.5.3.1 LED Alphanumeric Indicators Fourteen alphabetically labeled LEDs provide detailed information on UPS status as follows: A : Emergency shutdown This red LED indicates that the emergency power off (EPO) or remote emergency power of f (REPO) has been activated. See section 2.12.1, Emergency Shutdown. B : ...

  • MGE UPS Systems EPS 8000 - page 22

    I : Battery discharged This orange LED indicates that the battery has reached the end of its autonomy , shutting down the inverter . J : Inverter desynchronized This orange LED indicates that the inverter is not synchronized with the bypass AC input (mains 2). K :T ransfer fault This red LED indicates a transfer fault, which may be one or more of t ...

  • MGE UPS Systems EPS 8000 - page 23

    Introduction page 1 — 13 Users Manual Return to float voltage (pushbutton #2) This pushbutton can be used during a battery charge cycle to force the rectifier/battery charger back to the float voltage level. Security pushbutton (key) This pushbutton must be pressed simultaneously with any of the following three pushbuttons. This helps guard again ...

  • MGE UPS Systems EPS 8000 - page 24

    (This page left blank intentionally) EPS 8000 UPS Single Module page 1 — 14 ...

  • MGE UPS Systems EPS 8000 - page 25

    Users Manual Operation page 2 —1 2.0 Scope This section describes procedures for normal operation of EPS 8000 Single Module systems. Including interactive front panel display , settings for language configuration, alarms message displays, voltage, current, battery measure- ments, with before and after start-up checks, emergency shutdown using EPO ...

  • MGE UPS Systems EPS 8000 - page 26

    Operation EPS 8000 UPS Single Module page 2 —2 2.2 Settings Selection Screen The settings selection screens allow the user to configure the display language and set the contrast of the LCD display . To access the settings selection screen, press the settings pushbutton, and follow the steps. See Figure 2-2. Figure 2-2: Settings Selection Display ...

  • MGE UPS Systems EPS 8000 - page 27

    page 2 —3 Users Manual The most serious alarms are stored in the fault log, and may be viewed by following the steps shown in Figure 2-3. To reset the alarms, press the “clear fault log” pushbutton. See section 1.5.2.2 Alphanumeric Display Pushbuttons. Figure 2-3: Sequential Alarm Messages for Viewing the Fault Log. 2.4 Sensor Measurements Th ...

  • MGE UPS Systems EPS 8000 - page 28

    EPS 8000 UPS Single Module page 2 —4 Operation 2.5 V oltage Measurements To display voltage measurements, press the “V” key on the keyboard. See Figure 2-5. Figure 2-5: V oltage Measurement Displays. Select voltage measurements by pressing the ◊ pushbutton INPUT VAB VBC VCA V RMS BYPASS VAN VBN VCN V RMS BYPASS VAB VBC VCA V RMS INV. VAN VB ...

  • MGE UPS Systems EPS 8000 - page 29

    page 2 —5 Users Manual 2.6 Current Measurements To display current measurements, press the “A” key on the keyboard. See Figure 2-6. Figure 2-6: Current Measurements Displays. Operation Select current measurements by pressing the Å pushbutton INPUT I1 I2 I3 A RMS BYPASS I1 I2 I3 A RMS I LOAD / IN = Å Å Å Å Å Å Å INV. I1 I2 I3 A RMS LOA ...

  • MGE UPS Systems EPS 8000 - page 30

    2.7 Power Frequency Measurements To display power or frequency measurements, press the “W .Hz” key on the keyboard. See Figure 2-7. Figure 2-7: Power and Frequency Measurements Displays. Operation EPS 8000 UPS Single Module page 2 —6 Select power and frequency measurements by pressing the „ pushbutton. FREQ. INP. BYP. INV. HZ LOAD P1 P2 P3 ...

  • MGE UPS Systems EPS 8000 - page 31

    Operation page 2 —7 Users Manual 2.8 Battery Measurements To display battery voltage, current, ambient temperature, and time available or remaining, press the battery key on the keyboard. see Figure 2-8. Figure 2-8: Battery Measurements Displays. Select battery measurements by pressing the "battery" pushbutton. UBAT. V AVAILABLE BAT.TIM ...

  • MGE UPS Systems EPS 8000 - page 32

    Operation EPS 8000 UPS Single Module page 2 —8 2.9 LCD Messages This section presents the most common alarm messages that appear on the LCD (the alphanumeric section of the “hidden” panel), and explains their meaning. LOAD IS PROTECTED UPS IS ON LINE This is the normal display message. There are no alarms or problems, and the load is being su ...

  • MGE UPS Systems EPS 8000 - page 33

    Operation page 2 —9 Users Manual 2.9.2 Secondary Alarms The presence of these alarms is indicated by a flashing exclamation mark (!) on the general alarm message. Press the “alarm” pushbutton to view these messages. EMERGENCY SHUTDOWN REPO ON ! This message indicates that the UPS has been shut down because a remote emergency power off (REPO) ...

  • MGE UPS Systems EPS 8000 - page 34

    Operation EPS 8000 UPS Single Module page 2 —10 UPS INPUT PROBLEM CHECK FREQUENCY ! This message indicates that the main AC input (mains 1) frequency is out of tolerance. The rectifier/battery charger has shut down and the inverter is operating from its battery source. UPS INPUT PROBLEM CHECK VOLTAGE ! This message indicates that the main AC inpu ...

  • MGE UPS Systems EPS 8000 - page 35

    Operation page 2 —11 Users Manual Q1 UPS INPUT CB OPEN ! This message indicates that the input isolation circuit breaker is open or has tripped. It must be closed for rectifier/battery charger start-up. INVERTER OVERLOAD CHECK P.F. AND KW This message indicates that the inverter is in an overload condition, usually due to excessive real power (kW ...

  • MGE UPS Systems EPS 8000 - page 36

    Q5N UPS OUTPUT ISOL. SWITCH OPEN ! This message indicates that the optional UPS isolation circuit breaker Q5N is open. The load is not supplied unless the maintenance bypass circuit breaker Q3BP is closed. Q3BP MAINT. BYPASS SWITCH CLOSED ! This message indicates that the optional maintenance bypass circuit breaker Q3BP is closed. The system is set ...

  • MGE UPS Systems EPS 8000 - page 37

    Operation page 2 —13 Users Manual 2.10 Preparations Before Start-up Preparing before start-up uses a check list to powering up the EPS 8000 UPS. Reference the EPS 8000 Shared Systems Users Manual 86-132216-00, and Installation Manual for Single module and Shared Systems 86-132215- 00, in conjunction with this start-up procedure, to utilize inform ...

  • MGE UPS Systems EPS 8000 - page 38

    2.10.2 Start-up The following start-up procedure should be performed during the initial start-up following installation of the system, and this sequence should be followed any time that the EPS 6000 UPS is being restarted from an off condition (i.e., after the UPS has been powered down by removing the upstream AC input power and opening all the cir ...

  • MGE UPS Systems EPS 8000 - page 39

    Operation page 2 —15 Users Manual NOTE: I f the transfer conditions are not satisfied (bypass AC input sources is out of tolerance) a forced transfer is required. Refer to section 2.12 Forced T ransfers. 2.10.3 Checks After Start-up After initial start-up of the system, normal operation should be tested. At the minimum, the following tests should ...

  • MGE UPS Systems EPS 8000 - page 40

    2.1 1.2 Normal Shutdown To shut down the UPS, press the “inverter off” pushbutton on the module front panel for 3 seconds. T o restart, press the “inverter on” pushbutton. Note that the transfer will occur only if the inverter is synchronized to the bypass; otherwise, a forced transfer is needed, see section 2.12 Forced T ransfers. To isola ...

  • MGE UPS Systems EPS 8000 - page 41

    Operation page 2 —17 Users Manual configuration, close all the battery disconnect circuit breakers. 8. Automatic restart of the UPS is the normal configuration; the UPS inverter will start automatically and resume normal operation. If your EPS 6000 has been programmed NOT to automatically restart, start the inverter by pressing the “inverter on ...

  • MGE UPS Systems EPS 8000 - page 42

    2.12 Forced T ransfers This section describes the normal transfer conditions and the procedures to be followed when issuing forced transfers. CAUTION: Opening Q4S with the inverter stopped in a UPS without maintenance bypass will disconnect the attached load. 2.12.1 Uninterrupted T ransfer Conditions To transfer the load between the UPS module outp ...

  • MGE UPS Systems EPS 8000 - page 43

    Users Manual Maintenance Maintenance page 3 —1 3.0 Scope This section describes maintenance of the EPS 8000, including safety instructions, preventive maintenance, isolation for maintenance, information about replacement parts, and troubleshooting LCD alarm messages. 3.1 Safety Instructions W ARNING: D C input power to the inverter is normally fr ...

  • MGE UPS Systems EPS 8000 - page 44

    3.3 Preventive Maintenance The following preventive maintenance routines should be considered the minimum requirements; your installation and site may require additional preventive maintenance to assure optimal performance from your installed EPS 8000 and associated equipment. These routines should be performed twice a year (more often if required) ...

  • MGE UPS Systems EPS 8000 - page 45

    Symbols Definition / Meaning @ At. / And/or . +/- Plus or Minus. ≤ Equal to or less than. # Number . °C Degree Celsius. °F Degree Fahrenheit. Ø Phase angle. Ω Ohm; unit of resistance. ®T rade Mark. 2nd Second. A, B, C Normal sequence of phases (clockwise) in three-phase power . AC or ac Alternating current, also implies root-mean-square (rm ...

  • MGE UPS Systems EPS 8000 - page 46

    Carrier The company or individual responsible for delivering goods from one location to another . C Common. CB Circuit breaker . cm Centimeter . dB Decibels. DC Direct current . Conduit A flexible or rigid tube enclosing electrical conductors. C.S.S. Customer Support Service. Current rating The maximum current that a conductor or equipment can carr ...

  • MGE UPS Systems EPS 8000 - page 47

    kV A KiloV olt-Ampere; is equal to 1000 V olt-Ampere. L Line. LCD Liquid-Crystal Display unit. LED Light Emitting Diode. Load protected The attached load is being supplied by the UPS module inverter output, and the battery is available in the event that incoming (utility) power is lost. Load not protected The attached load is being supplied, but th ...

  • MGE UPS Systems EPS 8000 - page 48

    Q3BP Optional maintenance bypass circuit breaker (in single-module UPS system); optional mainte- nance bypass circuit breaker in MBC cabinet (in shared systems). Q4S Control or bypass circuit breaker (in single-module UPS systems); user-supplied bypass AC input circuit breaker supplying the SSC (in shared systems). Q5N Optional UPS isolation circui ...

  • MGE UPS Systems EPS 8000 - page 49

    Glossary page g — 5 Users Manual VV olts VA Vo lt amperes VA V olt-amps, unit for apparent power measurement, equal V x I. V AC or V ac V oltage of AC type. VDC or Vdc V oltage of DC type. ve Battery voltage. Via By way of. ...

  • MGE UPS Systems EPS 8000 - page 50

    (This page left blank intentionally) EPS 8000 UPS Single Module page g — 6 ...

  • MGE UPS Systems EPS 8000 - page 51

    Reorder form 1660 Scenic A venue Costa Mesa, CA 92626 Use this form to order additional copies of this document, or to report any errors, omissions, or other problems you have experienced. NAME __________________________________________________________________________________ COMP ANY ________________________________________________________________ ...

  • MGE UPS Systems EPS 8000 - page 52

    ...

  • MGE UPS Systems EPS 8000 - page 53

    ...

  • MGE UPS Systems EPS 8000 - page 54

    1660 Scenic Avenue, Costa Mesa, California 92626 • (714) 557-1636 www.mgeups.com ...

Manufacturer MGE UPS Systems Category Power Supply

Documents that we receive from a manufacturer of a MGE UPS Systems EPS 8000 can be divided into several groups. They are, among others:
- MGE UPS Systems technical drawings
- EPS 8000 manuals
- MGE UPS Systems product data sheets
- information booklets
- or energy labels MGE UPS Systems EPS 8000
All of them are important, but the most important information from the point of view of use of the device are in the user manual MGE UPS Systems EPS 8000.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals MGE UPS Systems EPS 8000, service manual, brief instructions and user manuals MGE UPS Systems EPS 8000. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product MGE UPS Systems EPS 8000.

A complete manual for the device MGE UPS Systems EPS 8000, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use MGE UPS Systems EPS 8000 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of MGE UPS Systems EPS 8000.

A complete MGE UPS Systems manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual MGE UPS Systems EPS 8000 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the MGE UPS Systems EPS 8000, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the MGE UPS Systems EPS 8000, that we can find in the current document
3. Tips how to use the basic functions of the device MGE UPS Systems EPS 8000 - which should help us in our first steps of using MGE UPS Systems EPS 8000
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with MGE UPS Systems EPS 8000
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of MGE UPS Systems EPS 8000 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning MGE UPS Systems EPS 8000?

Use the form below

If you did not solve your problem by using a manual MGE UPS Systems EPS 8000, ask a question using the form below. If a user had a similar problem with MGE UPS Systems EPS 8000 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)