    Air Conditioning Clinic Psychrometry One of the Fundamental Series TRG-TRC001-EN ...

  • Trane trg-trc001-en - page 2

    Comment Card We want to as sure t hat our ed ucationa l material s meet y our ever-changing reso urce dev elopment needs. Please t ake a moment to comment o n the effe ctivenes s of th is Air C onditionin g Clinic . Give the comp leted card to the presente r or drop i t in the ma il. Thank you! Psychrometry One of the Fundamental Seri es TRG-TRC001 ...

  • Trane trg-trc001-en - page 3

    Crop to width of 7.75 ” NO POST AGE NECESSA RY IF MAILED IN THE UNITED ST A TES BU SI NESS REP L Y MAIL FIRST -CLASS MAIL LA CROSSE, WI PERMIT NO. 11 POST AG E WILL BE P AID BY ADDRESSEE THE TRANE COMP ANY Attn: Applications Engineerin g 3600 P ammel Creek Road La Crosse WI 54601-9985 NO POST AGE NECESSA RY IF MAILED IN THE UNITED ST A TES BU SI ...

  • Trane trg-trc001-en - page 4

    Psychrometry One of the Fundamental Series A publication of The T rane Company— W orldwide Applied Systems Group ...

  • Trane trg-trc001-en - page 5

    Preface © 1999 American Standard Inc. All rights reserved TRG-TRC001-EN ii The T rane Company believes that it is incumbent on manufacturers to serve the industry by regularly disseminating information gathered through laboratory research, testing programs, and field experience. The T rane Air Conditioning Clinic series is one means of knowledge s ...

  • Trane trg-trc001-en - page 6

    TRG-TRC001-EN iii Contents period one The Psychrometric Chart ................................... 1 Properties of Air ......................................................... 2 Constructing a Simple Psychrometric Chart .............. 8 Effect of Sensible Heat and Moisture Changes ....... 15 period two Air Mixtures ................................. ...

  • Trane trg-trc001-en - page 7

    iv TRG-TRC001-EN ...

  • Trane trg-trc001-en - page 8

    TRG-TRC001-EN 1 notes period one The Psychrometric Chart Psychrometry is the science dealing with the physical laws of air – water mixtures. When designing an air conditioning system, the temperature and moisture content of the air to be conditioned, and the same properties of the air needed to produce the desired air conditioning effect, must be ...

  • Trane trg-trc001-en - page 9

    2 TRG-TRC001-EN notes period one The Psychrometric Chart Properties of Air At first glance, the psychrometric chart appears to be an imposing network of lines. When properly used, however , it provides valuable information about the properties of air . During this session, the psychrometric chart and its use in solving many air conditioning problem ...

  • Trane trg-trc001-en - page 10

    TRG-TRC001-EN 3 period one The Psychrometric Chart notes Dry-bulb temperatures are read from an ordinary thermometer that has a dry bulb. Wet-bulb temperatures are read from a thermometer whose bulb is covered by a wet wick. The difference between the wet-bulb temperature and the dry- bulb temperature is caused by the cooling effect produced by the ...

  • Trane trg-trc001-en - page 11

    4 TRG-TRC001-EN notes period one The Psychrometric Chart The third property , dew-point temperature , is the temperature at which moisture leaves the air and condenses on objects, just as dew forms on grass and plant leaves. When the dry-bulb, wet-bulb, and dew-point temperatures are the same, the air is saturated . It can hold no more moisture. Wh ...

  • Trane trg-trc001-en - page 12

    TRG-TRC001-EN 5 period one The Psychrometric Chart notes The fourth property , relative humidity , is a comparison of the amount of moisture that a given amount of air is holding, to the amount of moisture that the same amount of air can hold, at the same dry-bulb temperature. Relative humidity is expressed as a percentage. For example, if the rela ...

  • Trane trg-trc001-en - page 13

    6 TRG-TRC001-EN notes period one The Psychrometric Chart Finally , humidity ratio describes the actual weight of water in an air – water vapor mixture. In other words, if one pound of air were wrung completely dry , comparing the weight of the water to the weight of the dry air would yield its humidity ratio. Humidity ratio can be expressed as po ...

  • Trane trg-trc001-en - page 14

    TRG-TRC001-EN 7 period one The Psychrometric Chart notes For example, let's assume that the summer design conditions are 95 °F dry bulb and 78 °F wet bulb. What is the relative humidity , humidity ratio, and dew point? Only one point on the psychrometric chart represents air with both of these conditions. This point is located where the vert ...

  • Trane trg-trc001-en - page 15

    8 TRG-TRC001-EN notes period one The Psychrometric Chart Notice that the point of intersection falls between two relative humidity curves: 40% and 50%. By interpolation, the relative humidity at this condition is approximately 47%. Constructing a Simple Psychrometric Chart T o better understand the psychrometric chart and show why the lines interse ...

  • Trane trg-trc001-en - page 16

    TRG-TRC001-EN 9 period one The Psychrometric Chart notes These saturation points can be plotted on a chart with dry-bulb temperature along the horizontal axis and humidity ratio along the vertical axis. When several saturation points are plotted, the curve created resembles the relative humidity curves of the psychrometric chart. In fact, this curv ...

  • Trane trg-trc001-en - page 17

    10 TRG-TRC001-EN notes period one The Psychrometric Chart Another fact about saturated air should be discussed before we proceed. Assume a volume of moist air has the initial conditions indicated in column D of the table. The air has a 90 °F dry-bulb temperature and a 60 °F dew point. A wet-bulb thermometer shows the wet-bulb temperature to be 70 ...

  • Trane trg-trc001-en - page 18

    TRG-TRC001-EN 11 period one The Psychrometric Chart notes Additionally , the dew-point temperature does not change as the dry-bulb temperature changes, provided that the moisture content of the air remains the same. Merely heating the air does not change its moisture content. Therefore, as the air is heated, its condition will move horizontally alo ...

  • Trane trg-trc001-en - page 19

    12 TRG-TRC001-EN notes period one The Psychrometric Chart Additional curves can be added to the chart to represent relative humidity conditions that are less than 100%. The curves shown are at 10% intervals and represent humidity conditions ranging from completely saturated air to completely dry air . When air is completely dry , its relative humid ...

  • Trane trg-trc001-en - page 20

    TRG-TRC001-EN 13 period one The Psychrometric Chart notes T o complete this basic chart, the wet-bulb temperature lines must be added. Once again, at a saturated condition the wet-bulb, dry-bulb and dew-point temperatures are equal. Therefore, the wet-bulb temperature lines start at the saturation curve. T o observe what happens to wet-bulb tempera ...

  • Trane trg-trc001-en - page 21

    14 TRG-TRC001-EN notes period one The Psychrometric Chart The psychrometric chart now defines these five properties of air: dry-bulb temperature (vertical lines), humidity ratio and dew-point temperature (horizontal lines), relative humidity (curved lines) and wet-bulb temperature (diagonal lines). Remember: if any two of these five air conditions ...

  • Trane trg-trc001-en - page 22

    TRG-TRC001-EN 15 period one The Psychrometric Chart notes Effect of Sensible Heat and Moisture Changes When either the sensible heat content or the moisture content of air changes, the point on the psychrometric chart that represents the original air condition moves to a position that represents the new condition of temperature and/or humidity . Fo ...

  • Trane trg-trc001-en - page 23

    16 TRG-TRC001-EN notes period one The Psychrometric Chart On the other hand, if moisture is added to air without changing the dry-bulb temperature, the air condition moves upward along a dry-bulb temperature line. Finally , if moisture is removed from the air without changing its dry-bulb temperature, the air condition moves downward along a dry-bu ...

  • Trane trg-trc001-en - page 24

    TRG-TRC001-EN 17 period one The Psychrometric Chart notes Put all of these changes together on one chart and they show the direction the air condition will move when the dry-bulb temperature or moisture content is altered. In actual practice, however , both the dry-bulb temperature and moisture content of the air generally change simultaneously . W ...

  • Trane trg-trc001-en - page 25

    18 TRG-TRC001-EN notes Before an air conditioning problem can be analyzed on the psychrometric chart, the conditions of the air to be cooled or heated must be known. The air entering the cooling coil may be 100% recirculated ( A ), 100% outdoor ( B ), or a mixture of the two ( C ). 3VFKURPHWU SHULRGWZR $LU0L[WXUHV Figure 31 VXSSO VXSSO ID ...

  • Trane trg-trc001-en - page 26

    TRG-TRC001-EN 19 period two Air Mixtures notes If outdoor air B is mixed with recirculated air A , the conditions of the resulting mixture are found somewhere on a straight line connecting the two points. If the mixture is half and half, this condition falls on the midpoint of the line between A and B . If more than half of the mixture is recircula ...

  • Trane trg-trc001-en - page 27

    20 TRG-TRC001-EN notes period two Air Mixtures The outdoor air quantity in this example constitutes 25% of the mixture, while the recirculated air makes up the remaining 75%. The next step is to determine the dry-bulb temperature of the air mixture. This is done by multiplying the dry-bulb temperature of each air condition by its percentage and sum ...

  • Trane trg-trc001-en - page 28

    TRG-TRC001-EN 21 period two Air Mixtures notes Returning to the psychrometric chart, point C , at which the 83.75 °F dry-bulb temperature falls on the line from A to B , represents the conditions of the air mixture: 83.75 °F DB and approximately 70 °F WB. Because the recirculated air quantity constitutes a larger percentage (75%) of the mixture, ...

  • Trane trg-trc001-en - page 29

    22 TRG-TRC001-EN notes period three Sensible Heat Ratio This period is devoted to understanding the term sensible heat ratio and how it is represented on the psychrometric chart. The ratio of sensible heat gain to total heat gain is one of the most important factors affecting air conditioning system requirements. If only sensible heat is removed fr ...

  • Trane trg-trc001-en - page 30

    TRG-TRC001-EN 23 period three Sensible Heat Ratio notes Conversely , if only latent heat is removed, the line moves vertically downward along a constant dry-bulb temperature line. This results in a lower moisture content or humidity ratio. If both sensible and latent heat are removed from the air , the resulting air condition will be to the left an ...

  • Trane trg-trc001-en - page 31

    24 TRG-TRC001-EN notes period three Sensible Heat Ratio Imagine conditioned supply air as a sponge. As it enters a room, it absorbs heat and moisture. The amount of heat and moisture absorbed depends on the temperature and humidity of the supply air . This “sponge,” the supply air , must be cool enough to pick up the room's excess sensible ...

  • Trane trg-trc001-en - page 32

    TRG-TRC001-EN 25 period three Sensible Heat Ratio notes When the required amount of sensible and latent heat are not properly removed from the room, the desired room conditions cannot be maintained. For example, if too much sensible heat and not enough latent heat are removed, the room feels cold and damp. On the psychrometric chart, room condition ...

  • Trane trg-trc001-en - page 33

    26 TRG-TRC001-EN notes period three Sensible Heat Ratio This relationship between the conditions and quantity of the supply air can be described using the analogy of maintaining a constant temperature within a container of water . In this illustration, the container of water is capable of absorbing heat. The amount of heat it absorbs is called heat ...

  • Trane trg-trc001-en - page 34

    TRG-TRC001-EN 27 period three Sensible Heat Ratio notes The sensible heat ratio , abbreviated as SHR, refers to the comparison of sensible heat gain to total heat gain (sensible heat plus latent heat). Once this ratio is known, an SHR line can be drawn on the psychrometric chart. A scale around the right and top edges of the chart gives the SHR val ...

  • Trane trg-trc001-en - page 35

    28 TRG-TRC001-EN notes period three Sensible Heat Ratio Assume that room design conditions ( A ) are 78 °F DB and 65 °F WB, and that the sensible heat ratio is calculated as 0.80. That is, sensible heat gain represents 80% of the total (sensible plus latent) heat gain. The SHR line is found by aligning the index point with the 0.80 marking on the ...

  • Trane trg-trc001-en - page 36

    TRG-TRC001-EN 29 period three Sensible Heat Ratio notes Sensible-heat-ratio lines for other conditions are drawn in the following manner . Assume that room design conditions are 80 °F DB and 60% RH, and that the SHR is calculated as 0.60. First, line up the index point with the 0.60 marking on the sensible-heat-ratio scale and draw a line. Next, d ...

  • Trane trg-trc001-en - page 37

    30 TRG-TRC001-EN notes period four Air Quantity Next, we will determine the flow rate of supply air necessary to maintain a given set of design room conditions. Before proceeding, one more set of curves on the psychrometric chart must be identified. These curved lines represent the changes in dry-bulb and wet-bulb temperatures as air passes through ...

  • Trane trg-trc001-en - page 38

    TRG-TRC001-EN 31 period four Air Quantity notes T o demonstrate how the required supply airflow is determined, assume that a room’s sensible heat gain is 80,000 Btu/hr and its latent heat gain is 20,000 Btu/ hr . First, divide the sensible heat gain by the total heat gain. The resulting sensible heat ratio (SHR) is 0.80. The second step is to det ...

  • Trane trg-trc001-en - page 39

    32 TRG-TRC001-EN notes period four Air Quantity Plot the outdoor air B (95 °F DB, 78 °F WB) and indoor air A (78 °F DB, 65 °F WB) conditions on the psychrometric chart. Then calculate the mixed-air conditions using the method learned in Period 2. Locate the mixed air conditions C on the psychrometric chart (82.25 °F DB, 68.6 °F WB). Next, est ...

  • Trane trg-trc001-en - page 40

    TRG-TRC001-EN 33 period four Air Quantity notes The third step is to determine the required supply air conditions. This is where the coil curves are used. Using the curvature of the nearest coil line as a guide, draw a curve from the mixed-air condition C until it intersects the SHR line. Point D , at which this curve crosses the SHR line, represen ...

  • Trane trg-trc001-en - page 41

    34 TRG-TRC001-EN notes period four Air Quantity With the supply air conditions known, the next step is to calculate the specific quantity of air (cfm or cubic feet per minute) needed to satisfy the room heat gains. The required supply airflow is determined using the following formula, where the sensible heat gain is expressed in Btu/hr and the two ...

  • Trane trg-trc001-en - page 42

    TRG-TRC001-EN 35 period four Air Quantity notes For this example, the supply airflow is calculated as follows: The cooling coil must cool and dehumidify 3,430 cfm of air from the entering condition C to the supply air condition D to maintain the desired room conditions. %WXKU  Õ  ) ¤? ...

  • Trane trg-trc001-en - page 43

    36 TRG-TRC001-EN notes period four Air Quantity Some designers prefer to set the supply air temperature at 55 °F or use a 20 °F temperature differential (Room DB – Supply DB) without regard for the actual sensible heat ratio of the room. Using our same example, let’ s examine how this has the potential for creating a problem. Assume that the ...

  • Trane trg-trc001-en - page 44

    TRG-TRC001-EN 37 notes period five T ons of Refrigeration The psychrometric chart can also be used to determine the total load on the refrigeration equipment, expressed in Btu per hour or tons of refrigeration . One ton equals 12,000 Btu/hr . Another property of air , enthalpy , must now be defined. Enthalpy describes the total amount of heat energ ...

  • Trane trg-trc001-en - page 45

    38 TRG-TRC001-EN notes period five T ons of Refrigeration Using the previous example for calculating supply airflow , the first step is to determine the enthalpies of the air entering and leaving the cooling coil. This is accomplished by lining up three points on the chart, including the entering-air condition and identical points on the two enthal ...

  • Trane trg-trc001-en - page 46

    TRG-TRC001-EN 39 period five T ons of Refrigeration notes Realize that 4.5 is not a constant! It is the product of density of air and the conversion factor of 60 minutes per hour . The density of air at “standard” conditions (69.5 °F DB dry air at sea level) results in the value 4.5. Air at other conditions and elevations will cause this facto ...

  • Trane trg-trc001-en - page 47

    40 TRG-TRC001-EN notes period five T ons of Refrigeration The psychrometric chart can also be used to determine the sensible and latent components of the coil’s refrigeration load. First, draw a right triangle though the coil entering and leaving air conditions. The vertical leg represents the amount of moisture removed by the coil, i.e., latent ...

  • Trane trg-trc001-en - page 48

    TRG-TRC001-EN 41 period five T ons of Refrigeration notes By determining the enthalpy values for these three points, the same equation can be used to calculate both the sensible and the latent portions of the coil’ s refrigeration load.  ÕFIPÕ ¤  ? ...

  • Trane trg-trc001-en - page 49

    42 TRG-TRC001-EN notes period six Psychrometric Analyses Now we will look at a few ways that the psychrometric chart can help us analyze air conditioning systems. For simplicity , we will limit our examples to systems serving a single zone. In the previous example, the sensible heat ratio was based on full load or design load conditions . It must b ...

  • Trane trg-trc001-en - page 50

    TRG-TRC001-EN 43 period six Psychrometric Analyses notes For example, assume that at full load the room is subject to an 80,000 Btu/hr sensible heat gain and a 20,000 Btu/hr latent heat gain. The full-load sensible heat ratio is 0.80. At other times during the day , clouds block the sun and reduce the solar heat gain, and some of the lights are tur ...

  • Trane trg-trc001-en - page 51

    44 TRG-TRC001-EN notes period six Psychrometric Analyses In response to the reduction in room sensible heat gain, the coil capacity is throttled, raising the supply air temperature from D to D’ to balance the new room sensible heat gain. This new supply air temperature is dictated by the equation: Since the supply airflow and the desired room dry ...

  • Trane trg-trc001-en - page 52

    TRG-TRC001-EN 45 period six Psychrometric Analyses notes This is the manner in which a constant-volume, variable-temperature system with a modulating coil performs. It provides a constant quantity of air to the room and responds to part-load conditions by varying the supply air temperature. This is performed by modulating the flow of the cooling fl ...

  • Trane trg-trc001-en - page 53

    46 TRG-TRC001-EN notes period six Psychrometric Analyses Using the part-load conditions from the previous example, the room’s sensible heat gain is reduced from 80,000 Btu/hr to 47,000 Btu/hr while the latent heat gain remains the same. Sensing the reduction in dry-bulb temperature due to the lower sensible heat gain, the room thermostat assumes ...

  • Trane trg-trc001-en - page 54

    TRG-TRC001-EN 47 period six Psychrometric Analyses notes This supply air mixes with room air along the part-load 0.70 SHR line from E to A , arriving at the desired room conditions A . Now , if the room’ s latent heat gain were also changed, the resulting room conditions would not fall exactly on A , but on the appropriate SHR line that runs thro ...

  • Trane trg-trc001-en - page 55

    48 TRG-TRC001-EN notes period six Psychrometric Analyses varying the supply air temperature as the two airstreams mix downstream of the air handler . The face-and-bypass dampers are controlled by the room dry-bulb thermostat. The cooling coil is allowed to “run wild,” causing the air that does pass through it to be cooled more at partial airflo ...

  • Trane trg-trc001-en - page 56

    TRG-TRC001-EN 49 period six Psychrometric Analyses notes This supply air E mixes with room air along the part-load 0.70 SHR line, arriving at the resulting new room conditions A’ . While the quantity and temperature of supply air are suitable to absorb the room’s sensible heat gain, they are unable to completely absorb the latent heat gain. The ...

  • Trane trg-trc001-en - page 57

    50 TRG-TRC001-EN notes period six Psychrometric Analyses At part load, when the SHR of the room is reduced from 0.80 to 0.70, the V A V system responds by reducing the quantity of 56.5 °F air supplied to the room to match the reduced sensible heat gain. The part-load sensible heat gain of 47,000 Btu/hr and the constant supply air temperature, 56.5 ...

  • Trane trg-trc001-en - page 58

    TRG-TRC001-EN 51 period six Psychrometric Analyses notes The psychrometric chart is a visual tool that helps designers find solutions to many common HV AC problems by plotting conditions on the chart. T oday , many of these same problems can be quickly solved by computers, which can often eliminate the need for a graphical solution altogether . Sti ...

  • Trane trg-trc001-en - page 59

    52 TRG-TRC001-EN notes Let’ s review some of the main concepts from this clinic on psychrometry . The lines of the psychrometric chart represent five physical properties of air: dry bulb, wet bulb, dew point, humidity ratio, and relative humidity . If any two of these properties are known, the remaining properties can be determined from the chart ...

  • Trane trg-trc001-en - page 60

    TRG-TRC001-EN 53 period seven Review notes In Period T wo, a method was discussed to determine the resulting properties of an air mixture. By plotting the conditions of the outdoor air and recirculated air , and using the percentage of outdoor air , the resulting condition of the air mixture was calculated and plotted on a straight line from A to B ...

  • Trane trg-trc001-en - page 61

    54 TRG-TRC001-EN notes period seven Review After determining the entering air conditions for the coil and the slope of the SHR line, the coil curves were used to find the required supply air conditions. This point ( D ) was established by the intersection of the coil curve and the SHR line. By knowing the design room conditions A and the required s ...

  • Trane trg-trc001-en - page 62

    TRG-TRC001-EN 55 period seven Review notes The resulting psychrometric chart plot represents the changes that a volume of air undergoes as it travels through a typical air conditioning system. In this illustration, recirculated air A is mixed with outdoor air B , producing a mixed air condition C . This air mixture passes through the cooling and de ...

  • Trane trg-trc001-en - page 63

    56 TRG-TRC001-EN notes period seven Review For more information, refer to the following references: ■ T rane Air Conditioning Manual ■ ASHRAE Handbook—Fundamentals ■ Fundamentals of Thermodynamics and Psychrometrics, ASHRAE self- directed learning course ■ Psychrometrics: Theory and Practice, ASHRAE Visit the ASHRAE Bookstore at www .ashr ...

  • Trane trg-trc001-en - page 64

    TRG-TRC001-EN 57 Questions for Period 1 1 Given air conditions of 80 °F DB and 60% RH, find the humidity ratio and dew-point temperature. 2 Given air conditions of 85 °F DB and a humidity ratio of 90 grains/lb, find the relative humidity and wet-bulb temperature. 3 Given air conditions of 74 °F WB and 60% RH, find the dry-bulb temperature and hu ...

  • Trane trg-trc001-en - page 65

    58 TRG-TRC001-EN Quiz Questions for Period 4 9 Given a room with a 42,000 Btu/hr sensible heat gain and a 56,000 Btu/hr total heat gain (excluding ventilation heat gain); and indoor design conditions of 80 °F DB and 50% RH: a Determine the sensible heat ratio. b Draw the SHR line. 10 Given a room with an 80,000 Btu/hr sensible heat gain, a 20,000 ...

  • Trane trg-trc001-en - page 66

    TRG-TRC001-EN 59 1 93 grains/lb, 64.8 °F DP 2 49.5% RH, 70.5 °F WB 3 85 °F DB, 110 grains/lb 4 41% RH, 64 °F WB 5 56 °F DP , 32% RH 6a 95 °F × 0.20 = 19 °F 80 °F × 0.80 = 64 °F Mixed-Air T emperature = 19 °F + 64 °F = 83 °F b See Figure 90. c 69.4 °F WB 7a 95 °F × 0.15 = 13.5 °F 78 °F × 0.85 = 66.3 °F Mixed-Air T emperature = 1 ...

  • Trane trg-trc001-en - page 67

    60 TRG-TRC001-EN Answers 8a The SHR line crosses the saturation curve at 56 °F WB (See Figure 92.) b 60 °F DB, 58 °F WB (See Figure 92.) 9a b See Figure 93. ) ) ) ) ) ) ) ) Figure 91 ) ) ) ) ) ) ? ...

  • Trane trg-trc001-en - page 68

    TRG-TRC001-EN 61 Answers 10 58.3 °F WB (See Figure 94.) 11 ) )      6 + 5      6 + 5       Figure 93 SHR 80,000 Btu/hr 80,000 Btu/hr 20,000 Btu/hr + ? ...

  • Trane trg-trc001-en - page 69

    62 TRG-TRC001-EN Answers 12 See Figure 95. 13 a See Figure 96. b c d Refrigeration Load 4.5 7,000 cfm × 33.2 24.2 – () × 283,500 Btu/hr == 283,500 Btu/hr 12,000 Btu/hr/ton   23.6 tons of refrigeration = ...

  • Trane trg-trc001-en - page 70

    TRG-TRC001-EN 63 Answers e f g ) )      6 + 5      6 + 5 ) ) ) ) Figure 96 Airflow (cfm) 156,000 Btu/hr 1.085 78 ° F5 7 ° F – () × ? ...

  • Trane trg-trc001-en - page 71

    64 TRG-TRC001-EN ASHRAE American Society of Heating, Refrigerating and Air -Conditioning Engineers coil curves These represent the changes in dry-bulb and wet-bulb temperatures as air passes through a “typical” cooling coil. constant-volume system A type of air -conditioning system that varies the temperature of a constant volume of air supplie ...

  • Trane trg-trc001-en - page 72

    TRG-TRC001-EN 65 Glossary saturation curve This represents the moisture content that constitutes complete saturation of air at the various dry-bulb temperatures. saturation point The maximum amount of water vapor that one pound of dry air can hold at a given dry-bulb temperature. sensible heat Heat that causes a change in the air’ s dry-bulb temp ...

  • Trane trg-trc001-en - page 73

    The T rane Company Worldwide Applied Systems Group 3600 Pammel Creek Road La Crosse, WI 54601-7599 www .trane.com An American Standard Company Literature Order Number TRG-TRC001-EN File Number E/A V -FND-TRG -TRC001-1099-EN Supersedes ED-FND-TRG-TRC001-199-EN Stocking Location Inland-La Crosse Since The T rane Company has a policy of continuous pro ...

Manufacturer Trane Category Air Conditioner

Documents that we receive from a manufacturer of a Trane trg-trc001-en can be divided into several groups. They are, among others:
- Trane technical drawings
- trg-trc001-en manuals
- Trane product data sheets
- information booklets
- or energy labels Trane trg-trc001-en
All of them are important, but the most important information from the point of view of use of the device are in the user manual Trane trg-trc001-en.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Trane trg-trc001-en, service manual, brief instructions and user manuals Trane trg-trc001-en. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Trane trg-trc001-en.

Similar manuals

A complete manual for the device Trane trg-trc001-en, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Trane trg-trc001-en by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Trane trg-trc001-en.

A complete Trane manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Trane trg-trc001-en - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Trane trg-trc001-en, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Trane trg-trc001-en, that we can find in the current document
3. Tips how to use the basic functions of the device Trane trg-trc001-en - which should help us in our first steps of using Trane trg-trc001-en
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Trane trg-trc001-en
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Trane trg-trc001-en in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Trane trg-trc001-en?

Use the form below

If you did not solve your problem by using a manual Trane trg-trc001-en, ask a question using the form below. If a user had a similar problem with Trane trg-trc001-en it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)