    PRODUCT DATA 63-2675-03 TB7100A1000 MultiPRO™ Multispeed and Multipurpose Thermostat FOR CONVENTIONAL, HEAT PUMP, FAN COIL AND PTAC SYSTEMS APPLICATION The TB7100A1000 Mu ltiPRO™ Multispeed and Multipurpose Thermostat is an effortless, seven-day programmable or non- programmable thermostat that provides universal system compatibility , precise ...

  • Honeywell TB7100A1000 - page 2

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 2 ORDERING INFORMATION When purchasing replacement and modernizat io n products from your TRADELINE® whol esaler or distributor , refe r to the TRADELINE® Catalog or price sheets for complete ordering number . If you have additional questions, need further information, or ...

  • Honeywell TB7100A1000 - page 3

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 3 63-2675—03 NOTE: Alkaline batteries keep calendar and time if lithium battery is no longer fun ctional. Resistance Characteristics of Remote Sensors: C7189U Remote Indoor Sensor: 10K ohm NTC. C7772 Flush-Mount Remote Indoor Sensor: 20 K ohm NTC. TR21 W all-Mount Remote Indoor Sensor ...

  • Honeywell TB7100A1000 - page 4

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 4 Fig. 4. C71 89U Indoor Sensor d imensions in in. (mm). MERCURY NOTICE If this control is replaci ng a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly . Contact your local waste management author ity for instr ...

  • Honeywell TB7100A1000 - page 5

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 5 63-2675—03 Fig. 7. Install wallplate. WIR ING CAUTION Electrical Shock Hazard. Can cause electrical shock or eq uipment damage. Disconnect power supply before connecting wiring. IMPORT ANT — All wiring must agree with applicabl e codes, ordinances and regulations. — Use 18 gauge ...

  • Honeywell TB7100A1000 - page 6

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 6 T able 5. T erminal Designation Description s. NOTES: 1. When used in a single-transformer system, leave metal jumper wire in place between Rc and R. If used on a two-transfo rmer system, remove met al jumper wire between Rc and R. 2. Common wire is optional when thermost ...

  • Honeywell TB7100A1000 - page 7

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 7 63-2675—03 Fig. 13. T ypical hookup of heat-only sys tem. Fig. 14. T ypica l hookup of hea t-only system with fan . Fig. 15. T ypical ho okup of cool-onl y system. Heat Pump System Wiring Fig. 16. T ypi cal hookup of singl e-stage heat pump w ith no auxiliary heat (1H/1C). Fig. 17. ...

  • Honeywell TB7100A1000 - page 8

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 8 Fan Coil System Wiring Fig. 18. T ypica l wiring of 4 pipe fan coi l. Fig. 19. T ypical wiring of 2 pipe fan coil wi th reheat. Fig. 20. T ypic al wiring of 2 pipe fan coil with out reheat. PT AC System Wiring Fig. 21. T ypical hookup of PT AC with HI and LO fan speeds (1 ...

  • Honeywell TB7100A1000 - page 9

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 9 63-2675—03 Fig. 22. T ypical hoo kup of PT AC with HI and LO fan speed s (2H/1C). POWER THE THERMOSTAT Y ou can choose from three methods to power the thermostat: • Batteries only (AAA alkaline). • 24 V ac direct connection only . • 24 V ac direct connection with battery backu ...

  • Honeywell TB7100A1000 - page 10

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 1 0 Wire Indoor Sensor CAUTION Electrical Interference (Noise) Hazard. Can cause erratic system operation. Keep wiring at least one foot away from large inductive loads such as motors, li ne starters, lighting ballasts and large power distribution panels. 1. Check Installer ...

  • Honeywell TB7100A1000 - page 11

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 11 63-2675—03 Fig. 29. Setting calend ar when thermostat is first powered. Fig. 30. Setting time when thermostat is first powered. INSTALLER SETUP Advanced Settings The thermostat has advanced settings to match the HV AC system. These set tings can be adjust ed to match specific needs ...

  • Honeywell TB7100A1000 - page 12

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 1 2 INSTALLER SETUP NUMBERS (ISU), SETTINGS, AND T ESTS (T ABLE 6) Use the Installer System T est to test the heatin g, cooling and fan. Refer to th e latter portion of T able 6. CAUTION Equipment Damage Hazard . Minimum compressor off tim e is byp assed during Installer Sy ...

  • Honeywell TB7100A1000 - page 13

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 13 63-2675—03 0310 De adband 3°F (2°C) 2 (1.5)—2°F (1.5°C) 3 (2.0)—3°F (2.0°C) 4 (2.5)—4°F (2.5°C) 5 (3.0)—5°F (3.0°C) 6 (3.5)—6°F (3.5°C) 7 (4.0)—7°F (4.0°C) 8 (4.5)—8°F (4.5°C) 9 (5.0)—9°F (5.0°C) Only shown if Automa tic Changeover selected (ISU 03 ...

  • Honeywell TB7100A1000 - page 14

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 1 4 0 3 4 9 A u t o F a n R e s e t 0 0 — I n a c t i v e 1—Reset back to Auto after 2 hours 2—Reset back to Auto after 4 hours The timer will be set after the user selects the constant fan speed. Fan will be set to Auto automatically when time out. The start time is ...

  • Honeywell TB7100A1000 - page 15

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 15 63-2675—03 NOTE: Press the Done button to exit the Installer System T est. MAIN SCREEN Fig. 33. Main screen selections. Fig. 34. Main screen display . 0700 T emperature Display Offset 0 -3 (-1.5)— -3°F (-1.5°C) -2 (-1.0)— -2°F (-1.0°C) -1 (-0.5)— -1°F (-0.5°C) 0 (0.0)? ...

  • Honeywell TB7100A1000 - page 16

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 1 6 PROGRAMMING T able 7 shows default program settings. T able 7. Energy-saving Default Program Settings. Fan Settings Auto: Fan runs only w hen heating/ cooling system is on. See the Fan Schedule section for more info rmation. On: Fan runs continuously . System Settings H ...

  • Honeywell TB7100A1000 - page 17

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 17 63-2675—03 OPERATION Fan Sequence Operations (ISU 347, 348, 349) If heat pump or conventional app lication modes a re enabled in ISU 170, then ISU 347 is not available for fan ramp algorithm. The fan operates as a default ON/AUTO selection that works the same way as our CommercialP ...

  • Honeywell TB7100A1000 - page 18

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 1 8 a If Installer Setup (0170) System T ype is set to 2 pipe Fan Coil (8) or 2 pipe Fan Coil w/Aux Heat (9), the Y terminal will be u sed for cooling and heating. If Installer Setup (0170) System T ype is set to 4 pipe Fan Coil (7), the Y terminal will be used fo r c oolin ...

  • Honeywell TB7100A1000 - page 19

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 19 63-2675—03 Special Programmabl e Mode Functions Installer Setup 160 allows the thermostat to be configured for either a mode with a programmable 7 d ay schedule or as a non-programmable thermostat. Preoccupancy purge (ISU 185) This feature is available only when the thermostat is c ...

  • Honeywell TB7100A1000 - page 20

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 2 0 Replace the batteries as follows: 1. Remove the thermostat from the base by pulling it straight out. (See Fig. 39.) 2. Install two new AA alkaline batteries with proper polar- ization. NOTES: — Always use AA alkaline batteries. — All programming (Schedule, Date and ...

  • Honeywell TB7100A1000 - page 21

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 21 63-2675—03 — Users cannot make changes to the temperature setpoint or any schedule, system, or fan settings. — The only features availabl e are HOLIDA Y and OVERRIDE. — T o unlock the screen, see Advanced Settings secti on. T emperature Recovery The thermostat is equi pped wi ...

  • Honeywell TB7100A1000 - page 22

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 2 2 Fig. 41. 20 K ohm sensor resistance versus temperature. TEMPERA TURE (DEGREES) o F 30 40 50 60 70 80 90 100 110 0 10 20 30 40 RESIST ANCE (OHMS) 20K OHM A T 77 o F (25 o C) 80K 70K 60K 50K 40K 30K 20K 10K o C M5874A ...

  • Honeywell TB7100A1000 - page 23

    TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 23 63-2675—03 T ROUBLESHOOTING (T ABLE 12) T able 12. T rou bleshooting. Symptom Possible Cause Action Display does not come on. Thermostat is not being powered. Ch eck for 24 V ac between C and Rc. Check that AAA batteries are installed cor rectly and are good. T emperature se ttings ...

  • Honeywell TB7100A1000 - page 24

    Automation and Co ntrol Solutions Honeywell Internation al Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Dri ve North 35 Dynamic Drive Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9 customer.honeywell.com TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT ® U.S. Registered T rademark © 201 1 Honeywell International Inc. 63- ...

Manufacturer Honeywell Category Thermostat

Documents that we receive from a manufacturer of a Honeywell TB7100A1000 can be divided into several groups. They are, among others:
- Honeywell technical drawings
- TB7100A1000 manuals
- Honeywell product data sheets
- information booklets
- or energy labels Honeywell TB7100A1000
All of them are important, but the most important information from the point of view of use of the device are in the user manual Honeywell TB7100A1000.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Honeywell TB7100A1000, service manual, brief instructions and user manuals Honeywell TB7100A1000. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Honeywell TB7100A1000.

Similar manuals

A complete manual for the device Honeywell TB7100A1000, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Honeywell TB7100A1000 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Honeywell TB7100A1000.

A complete Honeywell manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Honeywell TB7100A1000 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Honeywell TB7100A1000, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Honeywell TB7100A1000, that we can find in the current document
3. Tips how to use the basic functions of the device Honeywell TB7100A1000 - which should help us in our first steps of using Honeywell TB7100A1000
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Honeywell TB7100A1000
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Honeywell TB7100A1000 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Honeywell TB7100A1000?

Use the form below

If you did not solve your problem by using a manual Honeywell TB7100A1000, ask a question using the form below. If a user had a similar problem with Honeywell TB7100A1000 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)