    1 359AA V DIRECT OR NON - - DIRECT VENT 4- -W A Y M U L TI P O I S E CONDENSING GAS FURNACE Installation Instructions SPECIAL VENTING REQUIREMENTS FOR INST ALLA TIONS IN CANADA Installation in Canada must confor m to the requirements of CSA B149 code. Vent systems must be composed of pipe, fittings, cements, and primers listed to ULC S636. The spec ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 2

    2 Required Notice for Massachusetts Installations IMPOR T ANT The Commonwealth of Massachusetts r equires compliance with regulation 248 CMR as follows: 5.08: Modifications to NFP A- - 54, Chapter 10 2) Revise 10.8.3 by adding the follo wing additional requirements: a. For all side wall horizontally vented gas f ueled equipmen t installed in every ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 3

    3 NOTE : Read the entire instruction manual before starting the installation. NOTE : Please retain these instructions with the furnace after installation for future reference. SAFETY CONSIDERA TIONS FURNACE RELIABILITY HAZARD Failure to follow this warning could result in personal injury , death or property damage. Improper installation or misappli ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 4

    4 SAFE INST ALLA TION REQUIREMENTS FIRE, EXPLOSION, AND ASPHYXIA TION HAZARD Failure to follow this warning could result in personal injury or death. Improper adjustment, alteration, service, maintenance or installation could cause persona l injury , death and/or property damage. Installation or repairs made by unqualified persons could result in h ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 5

    5 Frozen W ater Pipe Hazard W A TER DAMAGE T O PROPERT Y HAZARD Failure to follow this caution m ay result in property damage. Do not leave your home unattended for long periods during freezing weather without turning off water supply and draining water pipes or otherwise protecting against the risk of frozen pipes and resultant damage. CAUTION ! Y ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 6

    6 V ent Pipes MUST be supported Horizontally and V er tically *8 ″ (203.2mm) Min. 20 ′ (6.1m) Max. in same atmospheric zone *8 ″ (203.2mm) Min. 20 ′ (6.1m) Max. in same atmospheric zone Coupling on ends of exhaust pipe. T otal pipe & c oupling out- side structure = 8 ″ (203.2mm) Aluminum or non - -rust ing shield recommended. (See Ven ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 7

    7 Furnace Installation Considerations The installation of the furnace for a given application will dictate the position of the furnace, the airflow , ductwork connections, vent and combustion air piping. Consideration m ust be given to the following: Condensate T rap and Drain Lines The supplied condensate trap must be attached to the furnace side ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 8

    8 AIR INT AKE VENT H G E F TOP AIR INT AKE (KO) (AL TERNA TE) LEFT SIDE VENT 7 2 1 / 4 6 11 / 16 1 1 / 4 ELECTRICAL 4 13 / 16 1 1 / 16 1 11 / 16 17 5 / 16 24 1 / 16 19 13 / 16 28 3 / 4 29 7 / 8 TRAP (KO) UPFLOW/HORIZONTAL 1 7 / 8 21 5 / 8 24 13 1 / 4 4 7 / 8 TRAP (KO) (COU NTERFLOW) 13 11 / 16 31 11 / 16 1 3 / 8 THERMOST A T GAS A FRONT B D 23 1 / ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 9

    9 Minimum One Inlet an d One Outlet Air Sup ply is Required M a yb ei na n yC o m b i n a t i o nS h o w n Inlet Air Opening Must be Within1 2 in. (304.8mm) of oor Outlet Air Opening Must be Within12 in. (304.8mm) of ceiling (1) 1 Square Inch per 4000 BTUH (2) 1 Square Inch per 2000 BTUH This installation NOT approved in Canada Gas V ent Gable V ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 10

    10 d. V ertical duct openings or openings directly communic- ating with the outdoors require 1 squar e inch of free area per 4,000 BTUH (5.5 cm 2 /kW) for combined in- put of all gas appliances in the space ( see Ta b l e 1 ) . 3. When one permanent outdoor opening is used, the opening requires: a. 1 sq. in of free area per 3,000 BTUH (7 cm 2 /kW) ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 11

    11 T able 2 – Minimum Space V olume for 100% Combustion and V entilation Air fr om Indoors - - Ft 3 (M 3 ) Other Than Fan - - - Assisted T otal (1,000 Btuh) Fa n - - - assisted T otal (1,000’s Btuh) ACH 30 40 50 50 75 100 125 0.60 1,050 (29.7) 1,400 (39.2) 1,750 (49.0) 1,250 (35.0) 1,875 (52.5) 2,500 (70.0) 3,125 (87.5) 0.50 1,260 (35.3) 1,680 ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 12

    12 good judgement of the installer . Manufacturer does NOT take responsibility for modifications made to existing equipment. CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation, could result in carbon monoxide poisoning or death: The following ste ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 13

    13 Applicable ASTM Standards for V ent Mate rials Materials Sch. 40 Pipe SDR Pipe Cell Core Pipe Fittings Primer Solvent Cement ABS D1527 __ F628 D2468 & D2661 --- --- D2235 PVC D1785 D2241 F891 D2466 & D2665 F656 D2564 CPVC F441 F442 --- --- F438 --- --- F493 ABS to PVC --- --- --- --- --- --- --- --- --- --- D3138 NOTE : 1. In Canada, all ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 14

    14 T able 3 – Pipe Diameter T able PIPE DIAMETER T ABLE 359AA V MODEL 60,000 BTUH F urnaces 10 ′ (3.0 M) & (3) 90 ° elbows with 1.5 ″ (13 mm) PVC pipe 40 ′ ( 1 2 . 1M )&( 5 )9 0 ° elbows with 2 ″ (51 mm) PVC pipe or 70 ′ ( 2 1 . 3M )&( 5 )9 0 ° elbows with 3 ″ (76 mm) PVC pipe 80,000 BTUH F urnace 40 ′ ( 1 2 . 1M )&am ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 15

    15 12 inches (30 cm) for appliean ces >10,000 Btuh(3 kW) and < 100,000 Btuh(30kW), 36 inches (91cm) for appliances > 100,000 Btuh(30kW) A06675 Fig. 7 - - Direct V ent T ermination Clearance 359AAV ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 16

    16 Fig. 8 - - Other than Dir ect V ent T ermination Clearance 359AAV ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 17

    17 Condensate Drain T rap This furnace removes both sensible and latent heat from the products of combustion. Removal of the latent heat results in condensation of the water vapor . The condensate is removed from the furnace through the drains i n the plastic transition and the vent fitting. The drains connect to the externally mounted condensate d ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 18

    18 INLET EXHAUST IN ON OFF V E N T AIR FLOW Street Elbow 1 / 2 ″ CPVC (Loose parts bag ) Casing Grommet Black Rubbe r 5 / 8 ″ ID (Loose parts bag ) Drain T ee Drain Conn ector Black PVC 3 / 4 ″ PVC X 1 / 2 ″ CPVC (Loose parts bag ) Drain Line V ent T ee 3 / 4 ″ PVC or 1 / 2 ″ CPVC (Field supplied) Drain T ube Black Rubber 1 / 2 ″ ID & ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 19

    19 INLET EXHAUST IN ON OFF V E N T Casing Grommet Black Rubbe r 5 / 8 ″ ID (Loose parts bag ) Drain Conn ector Black PVC 3 / 4 ″ PVC X 1 / 2 ″ CPVC (Loose parts bag ) Drain Line Vent T ee 3 / 4 ″ PVC or 1 / 2 ″ CPVC (Field supplied) Drain T ube Black Rubber 1 / 2 ″ ID & Clamps 3 / 16 ″ ID Rubber T ube Coupling & Clamps (Option ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 20

    20 EXHAUST AIR FLOW INLET IN ON OFF V E N T Casing Grommet Black Rubbe r 5 / 8 ″ CPVC (Loose parts b ag) Drain Conn ector Black PVC 3 / 4 ″ PVC X 1 / 2 ″ CPVC (Loose parts bag ) Drain Line V ent T ee 3 / 4 ″ PVC or 1 / 2 ″ CPVC (Field supplied) Drain T ube Corrugated 5 / 8 ″ I D&C l a m p s Relief T ube Black Rubbe r 3 / 16 ″ ID S ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 21

    21 Elbow T ube Black Rubber 1 / 2 ″ ″ ID (13 mm) & Clamps (Loose Parts Bag) AIR FLOW OFF ON AIR FLOW 25 - - 24 - - 69 Single Pressure Switch Detail Dual Pressure Switch T ee Trap White PVC (loose parts bag) Flexible T ubing Connector , 3 / 16 ″ (5 mm) OD (loose parts bag) EXHAUS T Cut Here Drain T ube Black, 5 / 8 ″ (16 mm) ID Corrugate ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 22

    22 AIR FLOW OFF ON Drain Connector Black PVC 3 / 4 ″ CPVC (Loose parts bag) T rap Connection “Clamp ears” Pointed OUT Preassemble & insert into furnace Single Pressure Switch Detail Dual Pressure Switch T ee Trap White PVC (loose parts bag) Drain T ube Corrugated Black, 5 / 8 ″ (16 mm) WA R N I N G Move Caps to top of trap Drain T ube B ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 23

    23 T rap Connection “Clamp ears” Pointed OUT Preassemble & insert into furnace AIR FLOW IN ON OFF V E N T Relief T ube Black Rubber 3 / 16 ″ ID Plastic Caps Y ellow o r black Ve n t D r a i n &C l a m p s Single Pressure Switch Detail Dual Pressure Switch T ee T rap White PVC (loose parts bag) Cap and Clamp Open End Flexible T ubing C ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 24

    24 AIR FLOW IN ON OFF V E N T Relief T ube Black Rub ber 3 / 16 ″ ID 2 5 -- 2 4 -- 8 8 Single Pressure Switch Detail Dual Pressure Switch T ee T rap White PVC (loose parts ba g) WA R N I NG Move Caps to top of trap Flexible T ubing Connector 3 / 16 ″ OD (Loose Par ts Bag) Elbow T ube Black Rubber 1 / 2 ″ ID & Clamps (Loose Parts B ag) EXH ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 25

    25 Cut Here Drain T ube Corrugate d 5 / 8 ″ ″ ID & Clamps Cut at straight section Leave room fo r clamp IN ON OFF V E N T Relief T ube Rub ber T ube 3 / 16 ″ ID T rap Connection “Clamp ears” Pointed OUT Preassemble & insert into furnace Single Pressure Switch Detail Dual Pressure Switch Te e Tr a p White PVC (loose parts ba g) WA ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 26

    26 IN ON OFF V E N T AIR FLOW Coupling & Clamps (Optional) Drain T ube Corrugate d, 5 / 8 ″ ID & Clamps Cut at straight section Relief T ube Black R ubber 3 / 16 ″ ID Single Pressure Switch Detail Dual Pressure Switch Te e Tr a p White PVC (loose parts ba g) Flexible T ubing Connector 3 / 16 ″ OD (Loose Parts Bag) Barbed Coupli ng 1 / ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 27

    27 before operation. V erify all condensate drain connections are securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system. Open T ee Te e T r a p Condensate Tr a p Evaporator Coil Drain Line (Optional) Main Drain Line INLET EXHAUST IN ON OFF V E N T Representative drawing onl y , ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 28

    28 Rubber Coupling &C l a m p s 90 ° Elbow Combustion Blower V ent Fitting &C l a m p s V ent Extension Pipe (Side Panel Exit) V ent Pipe (T op Panel Exit) V ent Pipe Rotate downward 5 ° to 10 ° NOTE: Built- - in channel will be angled 5 ° to 10 ° also. SIDE VIEW NOTE: The 90 ° elbow is approved for use inside the furnace ONL Y . Te e ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 29

    29 EXHAUST INLET GRADE LEVEL SNOW LEVEL OR 8” (203.2mm)* MIN. 20’ (6.1m) MA X *18 in. (457.2mm) Minimum for cold climates [sustained 0 _ F (- 17 _ C) and below for 24 o r more consecutive hours] 8” (203.2mm) MIN. 12 ” (304.8mm) MIN. A07716 Fig. 22 - - Sidewall T ermination with Exterior Risers to Get Above Snow Level or Grad e Level Using E ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 30

    30 V ertical T ermination 1. Fig. 24 shows the pr oper installation and clearances for vertical vent termination. Th e vertical roof termination should be sealed with a plumbing roof boot or equivalent flashing. The inlet of the intake pipe and end of the ex- haust vent must be terminated no less than 12 ″ (305 mm) above the roof or snow accumula ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 31

    31 CONCENTRIC TERMINA TION V ent T ermination Clearances CARBON MONOXIDE POISONING, FIRE AND EXPLOSION HAZARD Failure to follow t his warning could result in personal injury , death, or property damage. Inlet and outlet pipes may NOT be vented directly above each other (standard vent terminals). ! W ARNING 1. Determine termination locations based o ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 32

    32 B PVC Intake/Combustion Air B PVC V ent /Exhaust D A 1 1 / 2 ″ C Model A* B C D** KGAVT0801CVT 38 7 / 8 3 4 1 / 2 21 1 / 8 KGAVT0701CVT 33 3 / 8 2 3 1 / 2 16 5 / 8 * = Dimension will change accordingly as dimension D is lengthened or shortened. **= Dimension D may be lengthened to 60 ″ may also be shortened by cutting the pipes provided in t ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 33

    33 1 ″ (25.4mm) max. Maintain 12 ″ (304.8mm) clearance above highest anticipated snow level or grade whichever is greater . Combustion Air V ent 25- - 22 - - 02 12 ″ (304.8mm) min. Roof Overhang A07736 Fig. 34 - - Concentric V e nt and Combustion- - Air Side T ermina tion 9. Cement the furnace combus tion air and vent pipes to the concentric ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 34

    34 7. Install a manual shut- - of f v alve external to furnace casing and tighten all joints securely . 8. If local codes allow the use of flexible gas appliance con- nectors, always use a new listed connector . Do not use a connector which has previously ser v iced an- other gas appliance. 9. Flexible corrugated metal gas connector may NOT be used ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 35

    35 O N O F F O N O F F O N O F F Use elbows and 3 ″ pipe nipple to connect valve to piping when using right side gas pipe entry . * Union may be installed inside the cabinet when necessary because of clearances. Drip Leg and Union, Union* should be outs ide the cabinet. Manual sh ut - off valve MUST be upstr eam of dripleg, union, and furnac e. P ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 36

    36 T able 6 – Natural Gas Manifold Pr essure (i n wc) 20,000 BTU per B urner* MEAN ELEVA TION FEET ABOVE SEA LEVEL Ft. (M) HEA TING VALU E BTU/CU . FT . 0 to 2000 2001 to 3000† 3001 to 4000 4001 to 5000 5001 to 6000 6001 to 7000 7001 to 8000 (0 to 610) (610.1 to 914)† ( 914.1 to 1219) (1219.1 to 1524) (1524.1 to 1829) (1829.1 to 2134) (2134.1 ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 37

    37 your local gas supplier , then refer to T able 6 for required pressure change and/or orifice change for high altitudes . 3. For operation with Propane gas, gas orifices MUST be changed and manifold pressure MUST be maintained as per T able 7 . Orifices can be or dered through our distribut- or . (See F ig. 38). High Altitude Input Rate = Namepla ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 38

    38 5. Move J- - Box to alternate location and attach using two self tapping screws from bag. 6. Apply two hole plugs from bag at left J - - Box location. Thermostat Thermostat location has an important effect on the operation o f the unit. Follow instructions incl uded with thermostat for correct mounting and wiring. Low voltage connections to furn ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 39

    39 Installation NOTE : Design and install the air distribution system to comply with Air Conditioning Contractors of America manuals and/or NFP A pamphlets 90A and 90B or other approved methods that conform to local codes and good tr ade practices. 1. When furnace supply ducts carry air outside furnace ar ea, seal return air duct to furnace casing ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 40

    40 A07729 Fig. 42 - - Side Mounted Filter Rack Filter Installation using Optional Filter Rack When installing or removing a bottom mounted filter , slide the two side filter clips to the back of the furnace BEFORE installing or removing. This will allow the filter to clear the front raised edge of the furnace. Insert filter into side clips first an ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 41

    41 Gas Supply Pressure Gas supply pressure should be within minimum and maximum values listed on rating plate ( minimum and maximum p ressures, refer to T able 5). P ressu res are usually set by gas suppliers. Manifold Gas Pressure Adjustment NOTE : Make adjustment to manifold pressure with burners operating. 1. Remove the burner compartment door . ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 42

    42 will lower the temperature rise. A lower blower speed will increase the temperature rise. Changing Blower Speed ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. T urn OFF power to furnace before changing speed taps. ! W ARNING NOTE : The speed taps that the manufacturer sets from the factory for th ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 43

    43 See “User ’s Information Manu al” and the “Service Manual”. SEQUENCE OF OPERA TION & DIAGNOSTICS Following is the normal operating sequence: Cooling (Y) Request: 24V AC signals applied to Y & G terminals of FCB (furnace control board) S Cool motor speed is ener gized after 5 second Cool Fan On Delay time. Y & G signals remo ...

  • Bryant 4-WAY MULTIPOISE 359AAV - page 44

    44 Blower Off Delay Jumper FUSE Diagnos tic Light 24 V AC HUM 11 5 V A C HUM A07733 Fig. 49 - - Control Board Control Board Diagnostic Codes OFF = 24VAC or 115V AC is off, fuse is open Heartbeat = Normal operat ion or no previous Diagnostic Code ON SOLID = Soft Lockout - - - Furnace Control Error (1 hr . delay) If code repeats immediately following ...

Manufacturer Bryant Category Furnace

Documents that we receive from a manufacturer of a Bryant 4-WAY MULTIPOISE 359AAV can be divided into several groups. They are, among others:
- Bryant technical drawings
- 4-WAY MULTIPOISE 359AAV manuals
- Bryant product data sheets
- information booklets
- or energy labels Bryant 4-WAY MULTIPOISE 359AAV
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bryant 4-WAY MULTIPOISE 359AAV.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bryant 4-WAY MULTIPOISE 359AAV, service manual, brief instructions and user manuals Bryant 4-WAY MULTIPOISE 359AAV. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bryant 4-WAY MULTIPOISE 359AAV.

Similar manuals

A complete manual for the device Bryant 4-WAY MULTIPOISE 359AAV, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bryant 4-WAY MULTIPOISE 359AAV by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bryant 4-WAY MULTIPOISE 359AAV.

A complete Bryant manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bryant 4-WAY MULTIPOISE 359AAV - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bryant 4-WAY MULTIPOISE 359AAV, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bryant 4-WAY MULTIPOISE 359AAV, that we can find in the current document
3. Tips how to use the basic functions of the device Bryant 4-WAY MULTIPOISE 359AAV - which should help us in our first steps of using Bryant 4-WAY MULTIPOISE 359AAV
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bryant 4-WAY MULTIPOISE 359AAV
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bryant 4-WAY MULTIPOISE 359AAV in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Bryant 4-WAY MULTIPOISE 359AAV?

Use the form below

If you did not solve your problem by using a manual Bryant 4-WAY MULTIPOISE 359AAV, ask a question using the form below. If a user had a similar problem with Bryant 4-WAY MULTIPOISE 359AAV it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)