    DESCRIPTION YORK Sunline 2000 Heat Pumps are convertible single package units with a common cabinet and common roof curb for the 3, 4 and 5 ton sizes. The units were designed for residential and light commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame. All units are self--contained and assembled on rigid ...

  • York SUNLINE 2000 2000 - page 2

    SYSTEM PROTECTION -- Crankcase heaters and internal compressor protection are standard on all compressors. Every unit has a liquid line filter--drier , low pressure switch, high pressure switch and high temperature switch to protect all system components. A suction line freezestat is supplied on all three--phase units to protect against loss of cha ...

  • York SUNLINE 2000 2000 - page 3

    036-21564-003-A-1005 Unitary Products Group 3 MODELS BCH 036 048 060 SUPPL Y AIR BLOWER CENTRIFUGAL BLOWER (Dia. x Wd. in.) 12 x 10 12 x 10 12 x 10 F AN MOTOR HP (DIRECT -DRIVE) 1 2 3 4 1 F AN MOTOR HP (BEL T -DRIVE) 1.5 1.5 1.5 INDOOR COIL ROWS DEEP 4 3 3 FINS PER INCH 16 15 15 F ACE AREA (Sq. Ft.) 4.3 5.1 5.1 OUTDOOR FA N PROPELLER DIA. (in.) 22 ...

  • York SUNLINE 2000 2000 - page 4

    036-21564-003-A-1005 4 Unitary Products Group COOLING CAP ACITIES - 3 TON (BCH036) Air On Indoor Coil T emperature of Air on Outdoor Coil 85 ° F9 5 ° F To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH CFM WB ° F Entering Dry Bulb, ° F Entering Dry Bulb, ° F 86 83 80 7 ...

  • York SUNLINE 2000 2000 - page 5

    036-21564-003-A-1005 Unitary Products Group 5 COOLING CAP ACITIES - 4 TON (BCH048) Air On Indoor Coil T emperature of Air on Outdoor Coil 85 ° F9 5 ° F To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH CFM WB ° F Entering Dry Bulb, ° F Entering Dry Bulb, ° F 86 83 80 7 ...

  • York SUNLINE 2000 2000 - page 6

    036-21564-003-A-1005 6 Unitary Products Group COOLING CAP ACITIES - 5 TON (BCH060) Air On Indoor Coil T emperature of Air on Outdoor Coil 85 ° F9 5 ° F To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH CFM WB ° F Entering Dry Bulb, ° F Entering Dry Bulb, ° F 86 83 80 7 ...

  • York SUNLINE 2000 2000 - page 7

    036-21564-003-A-1005 Unitary Products Group 7 HEA TING CAP ACITIES BCH036 CFM RET . AIR CAP OUTDOOR AIR TEMPERATURE, ° F (72% RH) ° F & K W - 1 0 0 1 02 03 04 05 06 0 1750 55 MBH 13.1 16.4 23.5 29.1 30.2 41.7 47.0 48.2 KW 2.9 3.0 3.2 3.3 3.5 3.7 3.8 3.9 70 MBH 1 1.9 15.0 21.5 26.7 27.7 38.2 43.1 44.1 KW 3.0 3.1 3.4 3.4 3.6 3.8 3.9 4.1 80 MBH ...

  • York SUNLINE 2000 2000 - page 8

    036-21564-003-A-1005 8 Unitary Products Group SUPPL Y AIR BLOWER PERFORMANCE - BCH036 & 048 with Belt-Drive MODEL BCH AIR FLOW CFM Available External S tatic Pressure - IWG* 0.20 0.30 0.40 0.50 0.60 0.70 0.80 RPM W atts RPM W atts RPM W atts RPM Watt s RPM W atts RPM W atts RPM W atts 048 2000 843 860 880 925 919 1005 956 1065 993 1 145 1030 1 ...

  • York SUNLINE 2000 2000 - page 9

    036-21564-003-A-1005 Unitary Products Group 9 SUPPL Y AIR BLOWER PERFORMANCE - BCH036, 048 & 060 with Direct-Drive SUPPL Y AIR BLOWER PERFORMANCE - BCH060 with Belt-Drive MODEL BCH AIR FLOW CFM Available External S tatic Pressure - IWG* 0.20 0.30 0.40 0.50 0.60 0.70 0.80 RPM W atts RPM W atts RPM W atts RPM Watt s RPM W atts RPM W atts RPM W at ...

  • York SUNLINE 2000 2000 - page 10

    036-21564-003-A-1005 10 Unitary Products Group HEA TER / CFM LIMIT ATIONS HEA TER SIZE NOM. KW VOL TAGE 1 UNIT MODEL SIZE, NOMINAL TONS 345 MINIMUM SUPPL Y AIR CFM 5 7 10 15 20 30 208 / 230-1-60 1,100 1,100 1,200 1,200 1,300 2 - 1,300 1,300 1,300 1,300 1,300 2 - 1,600 1,600 1,600 1,600 1,600 1,600 5 7 10 15 20 30 208 / 230-3-60 1,100 1,100 1,200 1, ...

  • York SUNLINE 2000 2000 - page 11

    036-21564-003-A-1005 Unitary Products Group 11 ELECTRICAL DA T A - Basic Unit (Direct-Drive) MODEL BCH POWER SUP - PL Y VOL TAGE LIMIT ATIONS (SEE NOTE 1) COMPRESSOR OUTDOOR FA N MOTOR, FLA SUPPL Y AIR BLOWER MOTOR, FLA MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, (SEE NOTE 2) AMPS MAX. HACR BREAKER SIZE, AMPS MIN. MAX. RLA LRA 036 208/230-1-60 208/23 ...

  • York SUNLINE 2000 2000 - page 12

    036-21564-003-A-1005 12 Unitary Products Group MODEL BCH POWER SUPPL Y HEA TER ACCESSORY MODEL NUMBER SUPPL Y AIR BLOWER MOTOR FLA ELECTRIC HEA TERS MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE 1 AMPS MAX. SIZE HACR 2 BREAKER AMPS KW ST AGES TO T A L AMPS 048 208-1-60 2CE04510506 2CE04510706 2CE0451 1006 2CE0451 1506 2CE04512006 5.0 4.0 5.6 8.0 1 1.9 1 ...

  • York SUNLINE 2000 2000 - page 13

    036-21564-003-A-1005 Unitary Products Group 13 ELECTRICAL DA T A - Basic Unit (Belt-Drive) MODEL BCH POWER SUP - PL Y VOL TAGE LIMIT ATIONS (SEE NOTE 1) COMPRESSOR OUTDOOR FA N MOTOR, FLA SUPPL Y AIR BLOWER MOTOR, FLA MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, (SEE NOTE 2) AMPS MAX. HACR BREAKER SIZE, AMPS MIN. MAX. RLA LRA 036 208/230-1-60 208/230- ...

  • York SUNLINE 2000 2000 - page 14

    036-21564-003-A-1005 14 Unitary Products Group MODEL BCH POWER SUPPL Y HEA TER ACCESSORY MODEL NUMBER SUPPL Y AIR BLOWER MOTOR FLA ELECTRIC HEA TERS MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE 1 AMPS MAX. SIZE HACR 2 BREAKER AMPS KW ST AGES TO T A L AMPS 048 208-1-60 2CE04510506 2CE04510706 2CE0451 1006 2CE0451 1506 2CE04512006 8.6 4.0 5.6 8.0 1 1.9 1 ...

  • York SUNLINE 2000 2000 - page 15

    036-21564-003-A-1005 Unitary Products Group 15 CLEARANCES Front 24" Back 12" (Less Economizer) 36" (With Economizer or Fixed Air/Motorized Air Damper) Left Side (Filter Access) 24" (Less Economizer) 36" (With Economizer) Right Side (OD Coil) 24" Below Unit 1 2 0" Above Unit 2 72" (For Outdoor Air Discharge) N ...

  • York SUNLINE 2000 2000 - page 16

    036-21564-003-A-1005 16 Unitary Products Group UNIT DIMENSIONS - CONT'D. ( B C H-3 ,4&5T O N ) REAR VIEW SIDE SUPPL Y AND RETURN AIR DUCT OPENINGS 17 1 2 3 11 1 2 4 5 8 17 1 2 11 1 2 7 7 8 6 1 2 DUCT COVERS - Units are shipped with all air duct openings covered. For side duct applications; 1.Remove and discard the supply and return air duc ...

  • York SUNLINE 2000 2000 - page 17

    036-21564-003-A-1005 Unitary Products Group 17 ROOF CURB DIMENSIONS B C H-3 ,4&5T O N COMPRESSOR AND OUTDOOR COIL END OF UNIT DUCT SIZES: Supply Air = 19" x 19" Return Air = 19" x 19" 82 1 4 40 3 4 BACK APPROXIMA TE CENTER OF GRA VITY 44 7 8 FRONT 19 3 4 CENTER OF GRA VITY CORNER CORNER CORNER OPTIONS / ACCESSORIES Electric ...

  • York SUNLINE 2000 2000 - page 18

    FIELD--INST ALLED ACCESSORIES SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZER -- Includes a slide--in/plug--in damper assembly with fully modulating spring return motor actuator capable of introducing up to 100% outdoor air , one outdoor air electronic enthalpy sensor and a rainhood with filters. The rainhood is painted to match the basic unit and must ...

  • York SUNLINE 2000 2000 - page 19

    036-21564-003-A-1005 Unitary Products Group 19 TYPICAL APPLICATIONS TYPICAL ROOF-TOP INST ALLA TION ROOF JACK INST ALLA TION ROOF CURB INST ALLA TION SLAB ON GROUND INST ALLA TION FIELD-SUPPLIED DISCONNECT SWITCH TO POWER SUPPL Y CONTROL WIRING TO INDOOR THERMOST A T ROOF CURB SUPPL Y AIR DUCT RETURN AIR DUCT CONDENSA TE TRAP ...

  • York SUNLINE 2000 2000 - page 20

    GENERAL DESCRIPTION Units shall be factory--assembled, single packaged Heat Pumps, designed for outdoor mounted inst allation. Units shall have minimum SEER ratings of 10.0. They shall have built in field convertible duct connections for down discharge supply/return or horizontal discharge supply/return, and be available with factory installed opti ...

  • York SUNLINE 2000 2000 - page 21

    (1) -- Loss--of--charge/Low--pressure switch. (2) -- High--pressure switch. If any of the above safety devices trip, an LED (light emitting diode) indicator shall illuminate. C. Unit shall incorporate “AUTO RESET” compressor over--temperature, over--current protection. D. Unit shall operate with conventional thermostat designs and have a low vo ...

  • York SUNLINE 2000 2000 - page 22

    6. THERMOST A TS -- Multiple models available from A.C.O., M.C.O., Electronic or Electrical Mechanical ver - sions. 7. ANTI--RECYCLE TIMER -- Assures 5--minute off--time between compressor cycles. 8. ELECTRIC HEA T -- Slide--in design, provides single point power and ranges from 5 to 30 KW . OTHER F ACTOR Y INST ALLED OPTIONS 1. HIGH PERFORMANCE BE ...

  • York SUNLINE 2000 2000 - page 23

    036-21564-003-A-1005 Unitary Products Group 23 ...

  • York SUNLINE 2000 2000 - page 24

    8QLWDU3URGXFWV*URXS < RUN'ULYH1RUPDQ2. 6XEMHFWWRFKDQJHZLWKRXWQRWLFH3ULQWHGLQ86$ &RSULJKWE< RUN,QWHUQDWLRQDO&RUSRUDWLRQ$OO5LJKWV5HVHUYHG $? ...

Manufacturer York Category Heat Pump

Documents that we receive from a manufacturer of a York SUNLINE 2000 2000 can be divided into several groups. They are, among others:
- York technical drawings
- SUNLINE 2000 2000 manuals
- York product data sheets
- information booklets
- or energy labels York SUNLINE 2000 2000
All of them are important, but the most important information from the point of view of use of the device are in the user manual York SUNLINE 2000 2000.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals York SUNLINE 2000 2000, service manual, brief instructions and user manuals York SUNLINE 2000 2000. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product York SUNLINE 2000 2000.

Similar manuals

A complete manual for the device York SUNLINE 2000 2000, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use York SUNLINE 2000 2000 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of York SUNLINE 2000 2000.

A complete York manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual York SUNLINE 2000 2000 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the York SUNLINE 2000 2000, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the York SUNLINE 2000 2000, that we can find in the current document
3. Tips how to use the basic functions of the device York SUNLINE 2000 2000 - which should help us in our first steps of using York SUNLINE 2000 2000
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with York SUNLINE 2000 2000
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of York SUNLINE 2000 2000 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning York SUNLINE 2000 2000?

Use the form below

If you did not solve your problem by using a manual York SUNLINE 2000 2000, ask a question using the form below. If a user had a similar problem with York SUNLINE 2000 2000 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)