Manual Emerson Process Management 8732

190 pages 9.44 mb
Download

Go to site of 190

Summary
  • Emerson Process Management 8732 - page 1

    www .rosemount.com Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 Integral Mount or Remote Mount Magnetic Flowmeter System with F OUNDATION ™ fieldbus ...

  • Emerson Process Management 8732 - page 2

    ...

  • Emerson Process Management 8732 - page 3

    Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Integral Mount or Remote Mount Magnetic Flo wmeter System with F OUNDATION ™ fieldb us NOTICE Read this manual before working with the prod uct. For personal and system safety , and for optimum product performance, make sure you thoroughly understand the cont ...

  • Emerson Process Management 8732 - page 4

    ...

  • Emerson Process Management 8732 - page 5

    Reference Manual 00809-0100- 4663, Rev BA January 2010 TOC -1 Rosemount 8732 SECTION 1 Introduction System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 Service Support . ...

  • Emerson Process Management 8732 - page 6

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 TOC -2 Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7 Tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7 Flow Units . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 8732 - page 7

    Reference Manual 00809-0100- 4663, Rev BA January 2010 TOC -3 Rosemount 8732 SECTION 6 Maintenance and Troubleshooting Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1 Installation Check and Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2 Diagnostic Messages . . . . . . ...

  • Emerson Process Management 8732 - page 8

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 TOC -4 APPENDIX D Digital Signal Processing Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1 Procedures . . . . . . . . . . . ...

  • Emerson Process Management 8732 - page 9

    Reference Manual 00809-0100- 4663, Rev BA January 2010 TOC -5 Rosemount 8732 APPENDIX F Resource Block Definition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-1 Parameters and Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-1 Resource Block Errors . . . . . . . . . . . . . . ...

  • Emerson Process Management 8732 - page 10

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 TOC -6 ...

  • Emerson Process Management 8732 - page 11

    Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Section 1 Introduction System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 1- 1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-2 Service Support . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 8732 - page 12

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 1-2 SAFETY MESSAGES Procedures and instr uctions in this man ual may require special p recautions to ensure the safety of th e personnel pe rforming the opera tions. Refer to the safety messages listed at the beginni ng of each section before performing any operations. SERVICE SU ...

  • Emerson Process Management 8732 - page 13

    Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Section 2 Inst allation Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1 T ransmitter Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 2-2 Pre-Inst allation . . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 8732 - page 14

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 2-2 TR A N S M I T T E R SYMBOLS Caution symbol — check product document ation for details Protective conductor (grou nding) terminal PRE-INSTALLATION Before installing the Rosemount 8732 Ma gnetic Flowmeter T ransmitter , there are several pre-inst allation steps that should b ...

  • Emerson Process Management 8732 - page 15

    Reference Manual 00809-0100- 4663, Rev BA January 2010 2-3 Rosemount 8732 Figure 2-1. Rosemount 8732 Dimensional Drawing ENVIRONMENT AL CONSIDERATIONS T o ensure maximum transmitter life, avoid temperature extremes and vibration. T ypical proble m ar ea s inc lude: • high-vibration lines with in tegra lly moun ted transmitters • warm-climate in ...

  • Emerson Process Management 8732 - page 16

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 2-4 Surface Mounting T o surface mount the transmitte r: 1. Attach the 8732 to the mountin g location using the mounting screws. Identify O ptions and Configurations The st andard application of the Rosemount 8732 inclu des a F OUNDATION fieldbus output. Be sure to iden tify op t ...

  • Emerson Process Management 8732 - page 17

    Reference Manual 00809-0100- 4663, Rev BA January 2010 2-5 Rosemount 8732 1. Disconnect power to the tran smitter . 2. Remove electronics cover . 3. Remove display if applicable. 4. Identify the location of each switch (see Figure 2- 2). 5. Change th e set tin g of th e de sir ed switch e s with a sm all scr ewd r iver . 6. Replace the electronics ...

  • Emerson Process Management 8732 - page 18

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 2-6 Conduit Cables Run the ap propriate si ze cable throug h the conduit connections in your magnetic flowmeter system. Run the po wer cable from the power source to the transmitter . Do not run power cables and output sig nal cables in the same conduit. For remote mount inst all ...

  • Emerson Process Management 8732 - page 19

    Reference Manual 00809-0100- 4663, Rev BA January 2010 2-7 Rosemount 8732 Requirement s for 12-42 V DC Power Su pply Units powe red with 12- 42 V DC may dr aw up to 1 amp of curren t. As a resu lt, the input powe r wire must meet cert ain gauge requiremen ts. Figure 2-4 shows the supply curren t for each corresponding supply voltage. For combinatio ...

  • Emerson Process Management 8732 - page 20

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 2-8 Figure 2-5. AC T ransmitter Power Connections Connect F OUNDATION fieldbus Wiring The F OUNDATION fieldbus signal provides th e output information from the transmitter . T ransmitter Communication Input The F OUNDATION fieldbus commu nication requires a minimum of 9 V dc and ...

  • Emerson Process Management 8732 - page 21

    Reference Manual 00809-0100- 4663, Rev BA January 2010 2-9 Rosemount 8732 NOTE The number of devices on a fieldbus se gment is limited by the power supply voltage, th e resistance of the cable, an d the amount of current drawn by each device. T ransmitter W iring Connection T o connect the 8732 to the F OUNDATION fieldbus (FF) segment, complete the ...

  • Emerson Process Management 8732 - page 22

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 2-10 Figure 2-7. Ros em o un t 87 32 T ransmitt er Field Wirin g Integrated Power Conditioner and Filter Te r m i n a t o r s 6234 ft (1900 m) max (depending upon ca ble characteristics) Fieldb us Segment (Spur) (T runk) (The power supply , filter , first terminator , and configu ...

  • Emerson Process Management 8732 - page 23

    Reference Manual 00809-0100- 4663, Rev BA January 2010 2-1 1 Rosemount 8732 SENSOR CONNECTIONS This section covers the st eps required to physically install the transmitter including wiring and calibration. Rosemount Sensors T o connect the transmitter to a non-Rosemount sensor , refer to the appropriate wiring dia gram in “Universal Sensor Wirin ...

  • Emerson Process Management 8732 - page 24

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 2-12 Rosemount recommends usin g the combination signal and coil drive for N5 , E5 approved sensors for optimum pe rformance. Remote transmitter inst allations require equal lengths of signal and coil drive cables. Integrally mounted transmitters are factory wired and do not requ ...

  • Emerson Process Management 8732 - page 25

    Reference Manual 00809-0100- 4663, Rev BA January 2010 2-13 Rosemount 8732 Sensor to Remote Mount T ransmitter Connections Connect coil drive and electrode cables as shown in Figure 2-10. Do not connect AC power to the sensor or to terminals 1 and 2 of t he transmitter , or replacement of the electronics board w ill be necessary . Figure 2-1 0. Wir ...

  • Emerson Process Management 8732 - page 26

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 2-14 ...

  • Emerson Process Management 8732 - page 27

    Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Section 3 Configuration Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Local Operator Interface . . . . . . . . . . . . . . . . . . . . . . . . . . p age 3-1 Basic Features . . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 8732 - page 28

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 3-2 Figure 3-1. Local Operator Interface Keypad Dat a Entry The LOI keypad does not have nu merical keys. Numerical data is en tered by the following proced ure. 1. Access the appropriate function . 2. Use the RIGHT ARRO W key to move to the value to change. 3. Use the UP and DOW ...

  • Emerson Process Management 8732 - page 29

    Reference Manual 00809-0100- 4663, Rev BA January 2010 3-3 Rosemount 8732 T able V alue Example Setting the TUBE SIZE: 1. Press the DOWN arrow to access the menu. 2. Select line size from the B asic set-up menu. 3. Press the UP or DOWN arrow to increa se/decreas e (incrementally) the tube size to the next value. 4. When you reach the desi red size, ...

  • Emerson Process Management 8732 - page 30

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 3-4 T able 3-2. LOI Menu T re e Dia g C o n t r o ls Ba s i c D i a g A dv a nc ed D i a g Va r i a b l e s Tr i m s St a t u s E mpt y P i pe Pro c e s s No ise G r ound/W i r i ng El e c Te m p Se lf T e st A O L oop T es t Pu lse Ou t T e st E mpt y P i pe El e c Te m p G r ou ...

  • Emerson Process Management 8732 - page 31

    Reference Manual 00809-0100- 4663, Rev BA January 2010 3-5 Rosemount 8732 DIAGNOSTIC MESSAGES The following error messages ma y appear on the LOI screen. See T able 6-4 on page 6-5 for potential causes and corrective actions for these errors: • Electronics Failure • Coil open circuit • Digital trim failure • Auto zero failure • Auto trim ...

  • Emerson Process Management 8732 - page 32

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 3-6 Analog Output – The a nalog outpu t variab le provides the analog value for the flow rate. The analog outp ut refers to th e industry st andard output in th e 4–20 mA range. The analog output and 4- 20 mA loop can be verified using the Analog Feedback diagnostic capabilit ...

  • Emerson Process Management 8732 - page 33

    Reference Manual 00809-0100- 4663, Rev BA January 2010 3-7 Rosemount 8732 Measured Reverse T ot al Measured reverse tot al provides the outp ut reading of th e tota lizer . This value is the amount of process fluid that has p assed through the flowmeter in the reverse direction since the tot alizer was la st reset. This value is only totalized when ...

  • Emerson Process Management 8732 - page 34

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 3-8 Options for Flow Rate Units Special Unit s The Rosemount 8732 provides a selection of standard unit configurations that meet the needs of most applications (see “Flow Unit s” on page 3-7). If your application has special needs an d the st andard co nfigu rations do not ap ...

  • Emerson Process Management 8732 - page 35

    Reference Manual 00809-0100- 4663, Rev BA January 2010 3-9 Rosemount 8732 Base V olume Unit Base volume unit is the unit from which the conver sion is being made. Set this variable to the appr op r iate op tio n. Conversion Nu mb er The special unit s conversion number is used to convert ba se un its to special units. For a str aight conversion of ...

  • Emerson Process Management 8732 - page 36

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 3-10 PV URV (Upper Range V alue) The upper range value (UR V), or analog output range, is preset to 30 ft/s at the factory . The units that appear will be the same as thos e selected under the units parameter . The URV (20 mA poin t) can be set fo r both forw ard or revers e flow ...

  • Emerson Process Management 8732 - page 37

    Reference Manual 00809-0100- 4663, Rev BA January 2010 3-1 1 Rosemount 8732 Calibration Number The tube calibratio n number is a 16-digit number us ed to identify flowtube sensors calib rated at the Rosemount fa ctory . T he calibration number is also printed inside the flowtube sensor terminal block or on the flowtube sensor name plate. The number ...

  • Emerson Process Management 8732 - page 38

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 3-12 ...

  • Emerson Process Management 8732 - page 39

    Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Section 4 Operation Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Advanced Configuration . . . . . . . . . . . . . . ...

  • Emerson Process Management 8732 - page 40

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-2 Empty Pipe Detection T urn the empty pipe diagnostic on or of f as req uired by the application. For more detai ls on the empty pipe diagnostic, see Appendix C: Diagnostics. Electronics T emperature Out of Range T urn the electronics temper ature diagno stic on or of f as req ...

  • Emerson Process Management 8732 - page 41

    Reference Manual 00809-0100- 4663, Rev BA January 2010 4-3 Rosemount 8732 EP T rigger Level Limits: 3 to 2000 Configure the thre shold limit that the empty p ipe value mu st exceed bef ore the diagnostic alert activates. De fault from the factory is s et to 100. For more detail on this parameter s ee Appendix C: Diagnos tics. EP Count s Limits: 5 t ...

  • Emerson Process Management 8732 - page 42

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-4 8714i Result s Review the result s of the most recently performed 8714i Meter V erification test. Information in this section details th e measurements taken and i f the meter p assed the ve rification test. For more details on these results and what they mean, see Appendix C ...

  • Emerson Process Management 8732 - page 43

    Reference Manual 00809-0100- 4663, Rev BA January 2010 4-5 Rosemount 8732 Sensor Calibration Result Displays the result of the sensor ca libration verification test as p ass or fail. For more detai ls on this parameter see App end ix C: Diagnostics. Coil Circuit Result Displays the result of the coil circuit test as pass or fail. For more det ails ...

  • Emerson Process Management 8732 - page 44

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-6 Re-Signature Meter Have the transmitter measure and stor e the sensor signature values. These values will then be used as the baselin e for the meter veri fication test. Use this when connecting to older Rosemount or competitors’ se nsors or installing the magnetic flowmete ...

  • Emerson Process Management 8732 - page 45

    Reference Manual 00809-0100- 4663, Rev BA January 2010 4-7 Rosemount 8732 Measurement s View the me asured values t aken during the meter veri fication process. These values are comp ared to the signature values to determine if the test p asses or fails. V alues are shown for the Coil Resistance, Coil Signature, and Electrod e Resistance. Coil Resi ...

  • Emerson Process Management 8732 - page 46

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-8 Diagnostic V ariables From this menu, all of the diagnostic variable values can be reviewed. This information can be used to get more in formation about the tran smitter , sensor , and process, or to get more det ail about an alert that may have activated. Empty Pipe V alue R ...

  • Emerson Process Management 8732 - page 47

    Reference Manual 00809-0100- 4663, Rev BA January 2010 4-9 Rosemount 8732 8714i Result Displays the results of the 8714i Me ter V erification test as p ass or fail. For more detai ls on this parameter see App end ix C: Diagnostics. Simulated V elocity Displays the test velocity used to ve rify transmitter calibration. For more details on this p ara ...

  • Emerson Process Management 8732 - page 48

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-10 Electronics T rim Electronics trim is the function by whic h the factory calibrates the transmitter . This procedure is rarely needed by customers. It is only necessary if you suspect the Rosemount 8732E is no longer accu rate. A Rosemount 8714 Calibration S t andard is requ ...

  • Emerson Process Management 8732 - page 49

    Reference Manual 00809-0100- 4663, Rev BA January 2010 4-1 1 Rosemount 8732 Auto Zero The auto zero function initializes th e transmitter for use with the 37 Hz coil drive mode only . Run this function on ly with the transmitter and sensor installed in the process. The sensor mu st be filled with process fluid at zero flow . Before running the auto ...

  • Emerson Process Management 8732 - page 50

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-12 ADVANCED CONFIGURATION In addition to the basic configuration op tions and the diagnostic information and controls, the 8 732 has many advanced functions that can also be configured as req u ire d by th e ap plic ation. DET AILED SETUP The det ailed setup function provides a ...

  • Emerson Process Management 8732 - page 51

    Reference Manual 00809-0100- 4663, Rev BA January 2010 4-13 Rosemount 8732 Cal Min Sp an The PV minimum span is the minimum flow range that must separate the minimum and maximum configure d PV Range values. Reverse Flow Enable or disable the transmitte r ’s ability to read reverse flow . Reverse Flow allows the transm itter to read negative flow ...

  • Emerson Process Management 8732 - page 52

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-14 Control When ON is selected, the Rosemoun t 8732 E output is derived using a running average of the indivi dual flow in puts. Signal processing is a sof tware algorithm that examines th e quality of the electrode signal against user-specified tolerances. Th is average is upd ...

  • Emerson Process Management 8732 - page 53

    Reference Manual 00809-0100- 4663, Rev BA January 2010 4-15 Rosemount 8732 For example, if the number of samples se lected is 100, then the response time of the system is 10 seconds. In some cases this may be unacceptable. By setting the time limit, you can forc e the 8732E to clear the value of the running aver age and re-e stablish the output and ...

  • Emerson Process Management 8732 - page 54

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-16 Sensor T ag Sensor tag is the quickest and shortest way of identifying an d distinguishing between sensors. Sensors can be t agged according to the re quirements of your application. The t ag may be up to eight characters long. DSP Sof tware Rev This function displays the s ...

  • Emerson Process Management 8732 - page 55

    Reference Manual 00809-0100- 4663, Rev BA January 2010 4-17 Rosemount 8732 Electrode T ype Electrode type enables you to select t he electrode type for your magnetic transmitter system. This variable only needs to b e changed if you ha ve replaced electrodes or if you have replaced your sensor . Options for this value are: • S tandard • S td &a ...

  • Emerson Process Management 8732 - page 56

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-18 Block Mode: T arget Operator requested m ode for the functi on bl ock. Only one selection may be made. Options include: Auto Use this mode when all configuratio n changes to the block are complete and the transmitter is ready to be returned to service. OOS Out of service mod ...

  • Emerson Process Management 8732 - page 57

    Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Section 5 Sensor Inst allation Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1 Sensor Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 5-3 Sensor Mounting . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 8732 - page 58

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-2 Explosions could resu lt in death or serious injury: Installation of this transmitter in an explosiv e environment must be in accordance with the appropriate local, national, and international standards, codes, and prac tices. Please review the approvals section of the 8732 r ...

  • Emerson Process Management 8732 - page 59

    Reference Manual 00809-0100- 4663, Rev BA January 2010 5-3 Rosemount 8732 SENSOR HANDLING Handle all part s carefully to prevent damage. Whenever possible, transport the system to the installa tion site in the original shipping cont aine rs. PTFE-lined sensors are shipped with end cover s that protect it from both mechanical damage and normal unres ...

  • Emerson Process Management 8732 - page 60

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-4 SENSOR MOUNTING Physical mounting of a sensor is similar to installing a typical section of pipe. Conventional tools, equip ment, and accessories (bolt s, gaskets, and grounding hard ware) are required. Up stream/Downstream Piping T o ensure specification accurac y ov er wide ...

  • Emerson Process Management 8732 - page 61

    Reference Manual 00809-0100- 4663, Rev BA January 2010 5-5 Rosemount 8732 Figure 5-4. Incline or Decline Orientation Horizontal installation should be restri cted to low piping sections that are normally full. Orient the electr ode plan e to within 45 degrees of horizont al in horizontal inst allations. A deviation of more than 45 degrees of horizo ...

  • Emerson Process Management 8732 - page 62

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-6 The electrodes in the Rosemount 871 1 are properly oriented wh en the top of the sensor is either vertica l or horizo ntal, as shown in Figure 5-6. Av oid any mounting orient ation that positions the to p of the sensor at 45 degre es from the vertical or hori zo ntal positio ...

  • Emerson Process Management 8732 - page 63

    Reference Manual 00809-0100- 4663, Rev BA January 2010 5-7 Rosemount 8732 INST ALLATION (FLANGED SENSOR) The followin g section shou ld be used as a guide in t he installation of the flange-type Rosemount 870 5 and Rose mount 8707 High-Signal Sensors. Refer to page 5-10 for installation of the wafer-type Rosemo unt 87 1 1 Sensor . Gasket s The sens ...

  • Emerson Process Management 8732 - page 64

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-8 NOTE Do not bolt one side at a time. T ighten each sid e si multaneously . Example: 1. Snug left 2. Snug righ t 3. T ighten left 4. T ighten right Do not snug and tighten the up stream side and then snug and tighten the downstream side. Failu re to alternate between the upstr ...

  • Emerson Process Management 8732 - page 65

    Reference Manual 00809-0100- 4663, Rev BA January 2010 5-9 Rosemount 8732 Figure 5-10. Flange Bolt T orquing Sequence T able 5-2. Flange Bolt T orque and Bolt Load S pecifications for Rosemount 8705 PTFE/ETFE liner Size Code PN10 PN 16 PN 25 PN 40 Line Size (Newton-meter) (N ewton) (Newton-m eter) (Newton) (New ton-meter) (Newton ) (Newton-meter) ( ...

  • Emerson Process Management 8732 - page 66

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-10 INSTALLATION (W AFER SENSOR) The following section should be use d as a guide in the installation of t he Rosemount 871 1 Sensor . Refer to page 5-7 for inst allation of the flange-type Rosemount 8705 and 8707 High-Signal sensor . Gasket s The sensor requires a gasket at eac ...

  • Emerson Process Management 8732 - page 67

    Reference Manual 00809-0100- 4663, Rev BA January 2010 5-1 1 Rosemount 8732 3. Place the sensor between the flanges. Make sure that the ce ntering rings are properly placed in the stu ds. The studs should be aligned with the markings on the rings tha t correspond to the flange you are using. 4. Insert the remaining studs, washers, and nu ts. 5. Tig ...

  • Emerson Process Management 8732 - page 68

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-12 INST ALLATION (SANIT ARY SENSOR) Gasket s The sensor requires a gasket at each of its connections to a djacent devices or piping. The gasket material selected must be compatible with the process fluid and operating co nditions. Gaskets are supplied with a ll Rosemount 8721 S ...

  • Emerson Process Management 8732 - page 69

    Reference Manual 00809-0100- 4663, Rev BA January 2010 5-13 Rosemount 8732 NOTE Consult factory for installations requirin g cathodic protection or situations where ther e are high cu rrents or high pot ential in the pro cess. The sensor case should alwa ys be earth groun ded in accordance with national and local electrica l codes. Failure t o do s ...

  • Emerson Process Management 8732 - page 70

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-14 Figure 5-14. Grounding with Grounding Rings or Lining Protectors Figure 5-15. Grounding with Grounding Rings or Lining Protectors Grounding Ring s or Lining Prote ctors Grounding Rings or Lining Prote ctors ...

  • Emerson Process Management 8732 - page 71

    Reference Manual 00809-0100- 4663, Rev BA January 2010 5-15 Rosemount 8732 Figure 5-16. Grounding with Grounding Electrodes ...

  • Emerson Process Management 8732 - page 72

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-16 PR OCESS LEAK PR OTECTION (OPTIONAL) The Rosemount 8705 and 8707 High- Signal Sensor housing is fabricated from carbon steel to perform two sepa rate functions. First, it provides shielding for the sensor magnetics so that external disturbances cannot interfere with th e ma ...

  • Emerson Process Management 8732 - page 73

    Reference Manual 00809-0100- 4663, Rev BA January 2010 5-17 Rosemount 8732 Relief V alves The first optional configuration, identif ied by the W1 in the model number option code, uses a completely welded coil housing. This configuration doe s not provide sep arate electrode comp artments with externa l el ectrod e a ccess. This optional housing con ...

  • Emerson Process Management 8732 - page 74

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-18 Figure 5-19. Housing Configuration — Sealed Electrode Compartmen t (O ption Code W3) If necessary , capture any process fluid lea kage, connect the appropriate piping to the d rainports, and p rovide for proper disp osal (see Figure 5-19). Fused Glass Seal Sealed Electrode ...

  • Emerson Process Management 8732 - page 75

    Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Section 6 Maintenance and T roubleshooting Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 6-1 Inst allation Check and Guide . . . . . . . . . . . . . . . . . . . . . . page 6-2 Diagnostic Messages . . . . . . . . . . . . ...

  • Emerson Process Management 8732 - page 76

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 6-2 INST ALLATION CHECK AND GUIDE Use this guide to check new installatio ns of Rosemount magnetic flowmeter systems that appear to malfunction. Before Y ou Begin Tr a n s m i t t e r Apply power to your system before ma king the following transmitt er checks. 1. V erify that the ...

  • Emerson Process Management 8732 - page 77

    Reference Manual 00809-0100- 4663, Rev BA January 2010 6-3 Rosemount 8732 DIAGNOSTIC MESSAGES Problems in the magnetic flo wmeter system are u sually indicated by incorr ect output readings from the syste m, error me ssages, or failed te st s. Consider all sources in identifyin g a pr ob lem in you r sys te m. T able 6-1. Rosemount 8732 Basic Diagn ...

  • Emerson Process Management 8732 - page 78

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 6-4 T able 6-2. Rosemount 8732 Advanced Diagnos tic Messag es (Suite 1 - Option Cod e D01) T able 6-3. Rosemount 8732 Advanced Diagnos tic Messag es (Suite 2 - Option Cod e D02) Message Potential Cause Corrective Action Grounding/Wiring Fault Improper installation of wiring See ? ...

  • Emerson Process Management 8732 - page 79

    Reference Manual 00809-0100- 4663, Rev BA January 2010 6-5 Rosemount 8732 TR A N S M I T T E R T ROUBL ESHOOTING T able 6-4. Advanced T roubleshooting–Rosemount 8 732 Symptom Potential Cause Corrective Action Does not appear to be within rated accuracy T ransmitter , control system, or other receiving device not configured properly Check all conf ...

  • Emerson Process Management 8732 - page 80

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 6-6 Meter output is unstable Medium to low conductivity flu ids (10– 25 microsiemens/cm) combined with cable vibration or 60 Hz interference Eliminate cable vibration: • Integral mount • Move cable to lower vibration run • Tie down cable mechanically • Trim electrode an ...

  • Emerson Process Management 8732 - page 81

    Reference Manual 00809-0100- 4663, Rev BA January 2010 6-7 Rosemount 8732 QUICK T ROUBL ESHOOTING Step 1: W iring Errors Th e most common magmeter problem is wiring between the se nsor and the transmitte r in remote moun t inst allations. The signal wire and coil drive wire must be twis ted shielded ca ble: 20 AWG twisted shield ed cable for the el ...

  • Emerson Process Management 8732 - page 82

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 6-8 T o test the sensor , a multimeter cap able of measuring conductance in nanosiemens is pref erred. Nanosiemen s is the reciprocal of resistance. or T able 6-5. Sensor T est T est Sensor Location Required Equipment Measuring at Connections Expected Value Potential Cause Correc ...

  • Emerson Process Management 8732 - page 83

    Reference Manual 00809-0100- 4663, Rev BA January 2010 6-9 Rosemount 8732 Figure 6-1. Sensor Cir cuit Diagram Step 4: Uninst alled Sensor T est s An uninstalle d sensor can also be used for sensor troubleshooting. T o interpret the result s, the hazardous locatio n certification for the sensor must be known. Applicable code s for the Rosemount 8705 ...

  • Emerson Process Management 8732 - page 84

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 6-10 Figure 6-2. 45° Elec trode Plane T o insure accuracy of re sistance re adings, zero out multimeter by shorting and touching the leads together . T able 6-6. Uninstalled Rosemoun t 8705 / 8707 Flanged Sensor T ests Measuring at Connections Hazardous Location C ertifications ...

  • Emerson Process Management 8732 - page 85

    Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Appendix A Reference Dat a Functional Specificat ions . . . . . . . . . . . . . . . . . . . . . . . . . p age A-1 Foundation™ fieldbus S pecifications . . . . . . . . . . . . . . . page A-4 Performan c e Specific at io ns . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 8732 - page 86

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 A-2 Figure A-2. Ap parent Power DC Supply Current Requirements Units powe red by 12 -4 2 V DC po wer sup ply may dr aw up to 1 amp of current steady state. Figure A-3. DC Current Requirements Inst allation Coordination Installatio n (overvoltage) Category II Power Consumption 10 ...

  • Emerson Process Management 8732 - page 87

    Reference Manual 00809-0100- 4663, Rev BA January 2010 A-3 Rosemount 8732 Enclosure Ra tin g NEMA 4X CSA T ype 4X, IEC 60529, IP66 (transmitter), Pollution Degree 2 Output Sign al Manchester-encoded digit al signal that conforms to IEC 1 158-2 and ISA 50.02 ...

  • Emerson Process Management 8732 - page 88

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 A-4 F OUNDATION ™ FIELDBUS SPECIFICATIONS Schedule Entries Seven (7) Links T wenty (20) Virtual Communications Relationship s (VCRs) One (1) predefined (F6, F7 ) Nineteen (19) configurable (see T able 1) T able A-1. Block Information Reverse Flow Detects and report s reverse fl ...

  • Emerson Process Management 8732 - page 89

    Reference Manual 00809-0100- 4663, Rev BA January 2010 A-5 Rosemount 8732 8732E transmitters and other manufacture r ’s sensors can be calibrated at known process conditions or at the Ro semount NIST -T raceab le Flow Facility . T ransmitters calibrated on site require a two-step procedure to match a known flow rate. This procedure can be fo und ...

  • Emerson Process Management 8732 - page 90

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 A-6 Optional high accuracy is ±0.15% of ra te ±1.0 mm/sec from 0.04 to 13 ft/s (0.01 to 4 m/s); above 13 ft/s (4 m/s), the system has an accuracy of ±0.18% of rate. Rosemount 8732E with 8721 Senso r: S tan dard system accuracy is ±0.5% of rate from 1 to 39 ft/s (0.3 to 12 m/s ...

  • Emerson Process Management 8732 - page 91

    Reference Manual 00809-0100- 4663, Rev BA January 2010 A-7 Rosemount 8732 St ability ±0.1% of rate over six months Ambient T emperature Effect ±0.25% change over operating temper ature range EMC Compliance EN61326-1 1997 + A1/A2/A3 (Industria l) electromagnetic compatibility (EMC) for process and laborato ry apparatus. PHYSICAL SPECIFICATIONS Mat ...

  • Emerson Process Management 8732 - page 92

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 A-8 ...

  • Emerson Process Management 8732 - page 93

    Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Appendix B Approval Information Product Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age B-1 Approved Manufacturing Locations . . . . . . . . . . . . . . . . . p age B-1 European Directive Information . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 8732 - page 94

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-2 Rosemount 8721 Sanitary Magmeter Sensors in line sizes of 1 1 / 2 in. and larger: Module A Conformity Assessment All other Rosemount 8705/8707/87 1 1/8721 Sensors — in line sizes of 1 in. and less: Sound Engi neering Practi ce Sensors that are SEP are outside the scope of P ...

  • Emerson Process Management 8732 - page 95

    Reference Manual 00809-0100- 4663, Rev BA January 2010 B-3 Rosemount 8732 HAZARDOUS LOCATIONS PRODUCT APPROVALS OFFERING The Rosemount 8700 Series mag netic flowmeters offer many different hazardous locations certifications. The table below provides an overview of the available hazardous are a approv al options. Equivalent hazard ous locations cert ...

  • Emerson Process Management 8732 - page 96

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-4 T able B-3. A TEX Approvals Offering T able B- 4. IECEx Approva ls Offering T ransmitter 8732E 8712D (1) (1) Remote T ransmitter On ly 8712H (1) Sensor 8705 8707 871 1 8705 8707 871 1 8707 A TEX Category Hazardous Area Approval Code Non-Hazardous T rans: L VD and EMC NA - NA ...

  • Emerson Process Management 8732 - page 97

    Reference Manual 00809-0100- 4663, Rev BA January 2010 B-5 Rosemount 8732 HAZARDOUS LOCATION CERTIFICATIONS Equivalent Hazardous Loc ation Certification s for sensor an d transmitte r must match in integrally-mounted magnetic flowmeter systems. Remote-mounted systems do not require matched hazardou s location certification o ption codes. T ransmitt ...

  • Emerson Process Management 8732 - page 98

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-6 North American Certifications Factory Mutual ( FM) NOTE For intrinsically safe (IS) outputs on the 8732E output option code B must be selected. IS outputs for Class I, Division 1, Groups A, B, C, D. T emp Code – T4 at 60°C NOTE For the 8732E transmitters with a local opera ...

  • Emerson Process Management 8732 - page 99

    Reference Manual 00809-0100- 4663, Rev BA January 2010 B-7 Rosemount 8732 European Certifications E1 A TEX Flameproof Hydrogen gas group 8732 - Certificate No.: KEMA 07A TEX0073 X II 2G Ex de [ia] IIC T6 (-50 °C  Ta  +60 °C) with LOI T6 (-20 °C  Ta  +60 °C) V max = 250 V AC or 42 V DC 0575 ED A TEX Flameproof 8732 - Certificate No.: ...

  • Emerson Process Management 8732 - page 100

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-8 INSTALLATION INSTRUCTIONS: The cable and conduit entry devices and the closing elements shall be of a certified increased safety type, suitable for the conditions of use and correctly installed. At ambient temperatures above 50 °C, the flow meter shall be used with heat resi ...

  • Emerson Process Management 8732 - page 101

    Reference Manual 00809-0100- 4663, Rev BA January 2010 B-9 Rosemount 8732 SPECIAL CONDITIONS FOR SAFE USE (KEM 07.0038X): If the Rosemount 8732 Flow Transmitter is used integrally with the Rosemount 8705 or 871 1 Sensors, it shall be assured that the mechani cal contact areas of the Sensor and Flow T ransmitter comply with the r equirements for fl ...

  • Emerson Process Management 8732 - page 102

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-10 North American Certifications Factory Mutual ( FM) N0 Division 2 Approval for Non-Flammable Flui ds (All Sensors) Class I, Division 2, Groups A, B, C, D T emp Code – T5 (8705/871 1 at 60°C) T emp Code – T3C (8707 at 60°C) Dust-Ignition proof Class II/III, Division 1, G ...

  • Emerson Process Management 8732 - page 103

    Reference Manual 00809-0100- 4663, Rev BA January 2010 B-1 1 Rosemount 8732 SPECIAL CONDITIONS FOR SAFE USE (X): The relation between ambient temperatur e, process temperature and temperature class is to be taken from the table under (15-description) above. - (See T able 13) The e lectrical data is to be taken from the summary under (15-elec trical ...

  • Emerson Process Management 8732 - page 104

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-12 T able B-7. Electrical Data Ro semount 8732 Flow T ransmitter Power supply: 250 V AC, 1 A or 42 Vdc, 2,5 A, 20 W maximum Foundation fieldbus output: 30 V DC, 30 mA, 1 W maximum Rosemount 8705 and 8711 Sensors Coil excitation circuit: 40 V DC (pulsed), 0,5 A, 20 W maximum Ele ...

  • Emerson Process Management 8732 - page 105

    Reference Manual 00809-0100- 4663, Rev BA January 2010 B-13 Rosemount 8732 T able B-8. Relation between ambient temperature, pr ocess temperature, and temperatur e class (1) T able B-9. Relation between the maximum ambient temperature, the maximum pr oc es s temperature, and the temperature class (2) (1) This table is applicable for CD and KD optio ...

  • Emerson Process Management 8732 - page 106

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-14 1.5 in. sensor size 149°F (65°C) 297°F (147°C) 160°F (71°C) 88°F (31°C) 55°F (1 3°C) 140°F (60°C) 307°F (153°C) 171°F (77°C) 97°F (36°C) 66° F (19°C) 131°F (55°C) 318°F (159°C) 181°F (83°C) 108°F (42°C) 77°F (25°C) 122°F (50°C) 329°F (165°C) ...

  • Emerson Process Management 8732 - page 107

    Reference Manual 00809-0100- 4663, Rev BA January 2010 B-15 Rosemount 8732 Figure B-1. A T EX Installation (1 of 6) ...

  • Emerson Process Management 8732 - page 108

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-16 Figure B-2. A T EX Installation (2 of 6) ...

  • Emerson Process Management 8732 - page 109

    Reference Manual 00809-0100- 4663, Rev BA January 2010 B-17 Rosemount 8732 Figure B-3. A T EX Installation (3 of 6) ...

  • Emerson Process Management 8732 - page 110

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-18 Figure B-4. A T EX Installation (4 of 6) ...

  • Emerson Process Management 8732 - page 111

    Reference Manual 00809-0100- 4663, Rev BA January 2010 B-19 Rosemount 8732 Figure B-5. A T EX Installation (5 of 6) ...

  • Emerson Process Management 8732 - page 112

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-20 Figure B-6. A T EX Installation (6 of 6) ...

  • Emerson Process Management 8732 - page 113

    Reference Manual 00809-0100- 4663, Rev BA January 2010 B-21 Rosemount 8732 Figure B-7. FM Certified I.S. Output (1 of 4) ...

  • Emerson Process Management 8732 - page 114

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-22 Figure B-8. FM Certified I.S. Output (2 of 4) ...

  • Emerson Process Management 8732 - page 115

    Reference Manual 00809-0100- 4663, Rev BA January 2010 B-23 Rosemount 8732 Figure B-9. FM Certified I.S. Output (3 of 4) ...

  • Emerson Process Management 8732 - page 116

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-24 Figure B-10. FM Certified I.S. Output (4 of 4) ...

  • Emerson Process Management 8732 - page 117

    Reference Manual 00809-0100- 4663, Rev BA January 2010 B-25 Rosemount 8732 Figure B-1 1. CSA Certified I.S. Output (1 of 2) ...

  • Emerson Process Management 8732 - page 118

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-26 Figure B-12. CSA Certified I.S. Output (2 of 2) ...

  • Emerson Process Management 8732 - page 119

    Reference Manual 00809-0100- 4663, Rev BA January 2010 B-27 Rosemount 8732 Figure B-13. CSA Installation ...

  • Emerson Process Management 8732 - page 120

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-28 Figure B-14 . Factory Mu tual Hazardous Locations ...

  • Emerson Process Management 8732 - page 121

    Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Appendix C Diagnostics Diagnostic A vailabil ity . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age C-1 Licensing and Enabling . . . . . . . . . . . . . . . . . . . . . . . . . . . page C-2 T unable Empty Pipe Detection . . . . . . . . . . . . . . . ...

  • Emerson Process Management 8732 - page 122

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 C-2 LICENSING AND ENABLING All non-basic diagnostics must be licensed by order ing option code D01, D02, or both. In the event that a diagno stic optio n is not ordered, advanced diagnostics can be license d in the field through the use of a license key . T o obtain a license key ...

  • Emerson Process Management 8732 - page 123

    Reference Manual 00809-0100- 4663, Rev BA January 2010 C-3 Rosemount 8732 Empty Pipe V alue Reads the current Empty Pipe V alue. This is a read-only value. This number is a unitless number and is calculated based on multiple inst allation and process variables such as sensor type, line size, p rocess fluid propertie s, and wiring. If the Empty Pipe ...

  • Emerson Process Management 8732 - page 124

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 C-4 T r oubleshooting Empty Pipe The following actions can be t aken if Empty Pipe detection is unexpe cted. 1. V erify the sensor is full. 2. V erify that the sensor has no t been installed with a measurement electrode at the top of the pipe . 3. Decrease the sensitivity by sett ...

  • Emerson Process Management 8732 - page 125

    Reference Manual 00809-0100- 4663, Rev BA January 2010 C-5 Rosemount 8732 T r oubleshooting Ground/Wiring Fault The transmitter detected high leve ls of 50/60 Hz noise caused by improper wiring or poor process grounding . 1. V erify that the transmitter is earth grou nded. 2. Connect ground rings, groundin g electrode, lining protector , or groundi ...

  • Emerson Process Management 8732 - page 126

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 C-6 High Process Noise Parameters The High Process Noise diagno stic has tw o read -only p arameters. It does no t have any configurable par ameters. This diagnostic requires that flow be present in the pipe and the velocity be > 1 ft/s. 5 Hz Signal to Noise Ratio Reads the cu ...

  • Emerson Process Management 8732 - page 127

    Reference Manual 00809-0100- 4663, Rev BA January 2010 C-7 Rosemount 8732 1. Tu rn on the Digital Signal Process ing (DSP) technolo gy and follow the setup procedure (r efer to Appen dix D: Digital Signal Process ing). This will minimize the level of damp ing in the flow measurement and control loop while also stabilizing the reading to minimize va ...

  • Emerson Process Management 8732 - page 128

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 C-8 The transmitter continuously mon itors signal amp litu des over a wide rang e of frequencies. For the high process noise diagnostic, the transmitter specifically looks at the signal amplitude at fr eque ncies of 2.5 Hz, 7.5 Hz, 32.5 Hz, and 42.5 Hz. The transmitter uses the v ...

  • Emerson Process Management 8732 - page 129

    Reference Manual 00809-0100- 4663, Rev BA January 2010 C-9 Rosemount 8732 8714i Meter V erification T est Parameters The 8714i has a multitude of paramete rs that set the test criteria, test conditions, and scope of the calibration verification test. T est Conditions for the 8714i Meter V erification There are th ree possible test conditions that t ...

  • Emerson Process Management 8732 - page 130

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 C-10 Empty Pipe Set the test criteria for the Empty Pipe condition. The factor y default for this value is set to three percent with limit s configurable between one and te n percent. 8714i Meter V erification T est Scope The 8714i Meter V erification can be used to verify the en ...

  • Emerson Process Management 8732 - page 131

    Reference Manual 00809-0100- 4663, Rev BA January 2010 C-1 1 Rosemount 8732 Viewing the 8714i Meter V erification Res ults Depending on the method us ed to view the results, they will be display ed in either a menu structure , as a method, or in th e repor t format. When using the 375 Field Communicator , each individ ual component can be viewed as ...

  • Emerson Process Management 8732 - page 132

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 C-12 Actual V elocity Displays the velocity measured by the transmitte r during the transmitter calibration v erification proc ess. V elocity Deviat ion Displays the deviation in the actual velocity compared to th e simulated velocity in terms of a percentage. This percen tage is ...

  • Emerson Process Management 8732 - page 133

    Reference Manual 00809-0100- 4663, Rev BA January 2010 C-13 Rosemount 8732 Optimizing the 8714i Meter V erification The 8714i Meter V erification diagnostic can be optimized by setting the test criteria to the desired leve ls necessary to meet the co mpliance requ irements of the application. The following examples below will provide some guidance ...

  • Emerson Process Management 8732 - page 134

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 C-14 T r oubleshooting the 8714i Meter V erification T est In the event that the 8714i Meter V eri fi cation test fails, the following step s can be used to determin e the appropriate co urse of action. Begin by reviewing the 8714i results to deter mine the specific test that fai ...

  • Emerson Process Management 8732 - page 135

    Reference Manual 00809-0100- 4663, Rev BA January 2010 C-15 Rosemount 8732 Electrode Circuit Resist ance The Electrode Circuit Resist ance is a measurement of the electro de circuit health. This value is used as a baseline to determine if the electrode circuit is still operating correctly w hen the 8714i Meter V erification diagnostic is initiated. ...

  • Emerson Process Management 8732 - page 136

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 C-16 ROSEMOUNT MAGNETIC FLOWMETER CALIBRATION V ERIFICATION REPORT Calibration V erification Report Parameters User Name: _________________________________________ ____ Calibration Conditions: □ Internal □ External T ag #:_____________________________ _____________________ T ...

  • Emerson Process Management 8732 - page 137

    Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Appendix D Digit al Signal Processing Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page D-1 Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age D-2 SAFETY MESSAGES Instructions and proc ...

  • Emerson Process Management 8732 - page 138

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 D-2 PROCEDURES If the output of your Ro semount 8732 is unstable , first check the wiring and grounding associated with the magnetic flowmeter system. Ensure that the following conditions are met: • Ground straps ar e attached to the adjacent flange or gr ound ring? • Groundi ...

  • Emerson Process Management 8732 - page 139

    Reference Manual 00809-0100- 4663, Rev BA January 2010 D-3 Rosemount 8732 This software techn ique, known as signal proc essing, “qua lifies” individual flow signals based on historic flow infor ma tion and three user-definable paramete rs, plus an on/off c ontrol. These p arameters are: 1. Number of samples: The n umber of samples function set ...

  • Emerson Process Management 8732 - page 140

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 D-4 x : Input flow signal from sensor . o : Average flow signals and tra nsmitter output, determined by the “number of samples” parameter . T olerance band, determined by the “perce nt limit” parameter . – Upper va lue = average flow + [(per cent limit/100) average flow ...

  • Emerson Process Management 8732 - page 141

    Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Appendix E Universal Sensor W iring Diagrams Rosemount Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age E-3 Brooks Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age E-6 Endress And Hauser Sensors . . . . . ...

  • Emerson Process Management 8732 - page 142

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-2 T able E-1. Sensor Cross References Rosem ount T ransmitter Sensor Manufa cturer Page Number Rosemount Rosemount 8732 Rosemount 8705, 8707, 871 1 page E-3 Rosemount 8732 Rosemount 8701 page E-4 Brooks Rosemount 8732 Model 5000 page E-6 Rosemount 8732 Model 7400 page E-7 Endre ...

  • Emerson Process Management 8732 - page 143

    Reference Manual 00809-0100- 4663, Rev BA January 2010 E-3 Rosemount 8732 ROSEMOUNT SENSORS Rosemount 8705/8707/871 1/8721 Sensors to Rosemount 8732 T ransmitter Connect coil drive and electrode cables as shown in Figure . Figure E-1. Wiring Diagra m to a Rosemount 8732 T ransmitter T able E-2. Rosemo unt 8705/8707/871 1/8721 Sensor Wiring Connecti ...

  • Emerson Process Management 8732 - page 144

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-4 Rosemount 8701 Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-2 on page E-4. Figure E-2. Wiring Diagra m for Rosemount 8701 Sensor and Rosemount 8732 T ransmitter T able E-3. Rosemount 8701 Sensor Wiring Connections 2 1 19 ...

  • Emerson Process Management 8732 - page 145

    Reference Manual 00809-0100- 4663, Rev BA January 2010 E-5 Rosemount 8732 Connecting Sensors of Other Manufacturers Before connecting another manufacture r ’s sensor to the Rosemount 8732 transmitter , it is necessary to perform the following functions. 1. Turn of f the AC power to the se nso r and transmitt er . Failure to do so could result in ...

  • Emerson Process Management 8732 - page 146

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-6 BROOKS SENSORS Connect coil drive and electrode cables as shown in Figure E-3. Model 5000 Sensor to Rosemount 8732 T r ansmitter Figure E-3. Wiring Diagra m for Brooks Sensor Model 5000 an d Rosemount 8732 T able E-4. Brooks Model 5000 Sensor Wiring Connections BROOKS MODEL 5 ...

  • Emerson Process Management 8732 - page 147

    Reference Manual 00809-0100- 4663, Rev BA January 2010 E-7 Rosemount 8732 Model 7400 Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-4. Figure E-4. Wiring Diagra m for Brooks Sensor Model 7400 an d Rosemount 8732 T able E-5. Brooks Model 7400 Sensor Wiring Connections BROOKS MODEL 7400 ROSEMOUNT 8 ...

  • Emerson Process Management 8732 - page 148

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-8 ENDRESS AND HAUSER SENSORS Connect coil drive and electrode cables as shown in Figure E-5. Endress and Hauser Sensor to Rosemount 8732 T r ansmitter Figure E-5. Wiring Diagra m for Endress and Hauser Sensors and Rosemount 8732 T able E-6. Endres s and Hauser Sensor Wiring Con ...

  • Emerson Process Management 8732 - page 149

    Reference Manual 00809-0100- 4663, Rev BA January 2010 E-9 Rosemount 8732 FISCHER AND PORTER SENSORS Connect coil drive and electrode cables as shown in Figure E-6. Model 10D1418 Sensor to Rosemount 8732 T r ansmitter Figure E-6. Wiring Diagra m for Fischer and Porter Sensor Model 10D1418 an d Rosemount 8732 T able E-7. Fischer and Porter Model 10D ...

  • Emerson Process Management 8732 - page 150

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-10 Model 10D1419 Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-7. Figure E-7. Wiring Diagra m for Fischer and Porter Sensor Model 10D1419 and Rosemoun t 8732 T able E-8. Fischer and Porter Model 10D141 9 Sensor Wiring Connec ...

  • Emerson Process Management 8732 - page 151

    Reference Manual 00809-0100- 4663, Rev BA January 2010 E-1 1 Rosemount 8732 Model 10D1430 Sensor (Remote) to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-8. Figure E-8. Wiring Diagra m for Fischer and Porter Sensor Model 10D1430 (Remote) and Rosemount 8732 T able E-9. Fischer and Porter Model 10D1430 (Re ...

  • Emerson Process Management 8732 - page 152

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-12 Model 10D1430 Sensor (Integral) to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-9. Figure E-9. Wiring Diagra m for Fischer and Porter Sensor Model 10D1430 (Int eg ra l) an d Rosemount 8732 T able E-10. Fischer and Porter Model 10D ...

  • Emerson Process Management 8732 - page 153

    Reference Manual 00809-0100- 4663, Rev BA January 2010 E-13 Rosemount 8732 Model 10D1465 and Model 10D1475 Sensors (Integral) to 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-10. Figure E-10. Wiring Diagram for Fischer and Porter Sensor Model 10D1465 and Model 10D1475 (Integral) an d Rosemount 8732 T able E-1 1. Fi ...

  • Emerson Process Management 8732 - page 154

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-14 Fischer and Porter Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-1 1. Figure E-1 1. Generic Wiring Diagram for F ischer and Porter Sensors and Rosemount 873 2 T able E-12. Fischer and Porter Generic Sensor Wiring Connecti ...

  • Emerson Process Management 8732 - page 155

    Reference Manual 00809-0100- 4663, Rev BA January 2010 E-15 Rosemount 8732 FOXBORO SENSORS Connect coil drive and electrode cables as shown in Figure E-12. Series 1800 Sensor to Rosemount 8732 T r ansmitter Figure E-12. Wiring Diagram for Foxboro Series 1800 and Rosemount 8732 T able E-13. Foxboro Generi c Sensor Wiring Connections ROSEMOUNT 8732 T ...

  • Emerson Process Management 8732 - page 156

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-16 Series 1800 (V ersion 2) Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-13. Figure E-13. Wiring Diagram for Foxboro Series 1 800 (V ersion 2) and Rosemount 8732 T able E-14. Foxboro Generi c Sensor Wiring Connections FOXBO ...

  • Emerson Process Management 8732 - page 157

    Reference Manual 00809-0100- 4663, Rev BA January 2010 E-17 Rosemount 8732 Series 2800 Sensor to 8732 T ransmitter Connect coil drive and electrode cables as shown in Figure E-14. Figure E-14. Wiring Diagram for Foxboro Series 2800 and Rosemount 8732 T able E-15. Foxboro Series 2800 Sensor Wiri ng Connections ROSEMOUNT 8732 T RANSMITTER Coil Connec ...

  • Emerson Process Management 8732 - page 158

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-18 Foxboro Sensor to 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-15 . Figure E-15. Generic Wiring Diagram for F oxboro Sen sors and Rosemount 8732 T able E-16. Foxboro Sensor Wiring Connections Electrodes Coils Ground ROSEMOUNT 8732 TR A N S ...

  • Emerson Process Management 8732 - page 159

    Reference Manual 00809-0100- 4663, Rev BA January 2010 E-19 Rosemount 8732 KENT V ERIFLUX VTC SENSOR Connect coil drive and electrode cables as shown in Figure E-16. V eriflux VTC Sen sor to 8732 T ransmitter Figure E-16. Wiring Diagram for Kent V e riflux VTC Sensor and Rosemount 8732 T able E-17. Kent V eriflux VTC Sensor Wiring Connections Elect ...

  • Emerson Process Management 8732 - page 160

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-20 KENT SENSORS Connect coil drive and electrode cables as shown in Figure E-17. Kent Sensor to Rosemount 8732 T r ansmitter Figure E-17. Generic Wiring Diagram for Ke nt Sensors an d Rosemount 8732 T able E-18. Kent Se nsor Wiring Connections Coils Electrodes SCR OUT ROSEMOUNT ...

  • Emerson Process Management 8732 - page 161

    Reference Manual 00809-0100- 4663, Rev BA January 2010 E-21 Rosemount 8732 KROHNE SENSORS Connect coil drive and electrode cables as shown in Figure E-18. Krohne Sensor to Rosemount 8732 T r ansmitter Figure E-18. Generic Wiring Diagram for Krohne Sensor s and Rosemount 8732 T able E- 19. Krohne Sen sor Wiring Connections Electrodes Coils Coil Shie ...

  • Emerson Process Management 8732 - page 162

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-22 T AYLOR S ENSORS Connect coil drive and electrode cables as shown in Figure E-19. Series 1 100 Sensor to Rosemount 8732 T r ansmitter Figure E-19. Wiring Diagram for T aylo r Series 1 100 Sensors and Rosemount 8732 T able E-20. T aylor Series 1 100 Sensor Wiring Connections ...

  • Emerson Process Management 8732 - page 163

    Reference Manual 00809-0100- 4663, Rev BA January 2010 E-23 Rosemount 8732 T aylor Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-20. Figure E-20. Generic Wiring Diagram for T aylor Sensors and Rosemount 8732 T able E-21. T aylor Sensor Wiring Connections Electrodes Coils Green ROSEMOUNT 8732 T R ...

  • Emerson Process Management 8732 - page 164

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-24 Y AMATAKE HONEYWELL SENSORS Connect coil drive and electrode cables as shown in Figure E-21. Y amatake Honeywell Sensor to Rosemount 8732 T r ansmitter Figure E-21. Generic Wiring Diagram for Y amatake Honeywell Sensors and Rosemount 8732 T able E- 22. Y amata ke Honeywell S ...

  • Emerson Process Management 8732 - page 165

    Reference Manual 00809-0100- 4663, Rev BA January 2010 E-25 Rosemount 8732 Y OKOGAWA SENSORS Connect coil drive and electrode cables as shown in Figure E-22. Y okogawa Sensor to Rosemount 8732 T r ansmitter Figure E-22. Generic Wiring Diagram for Y okogawa Sensors and Rosemount 8732 T able E-23. Y okogawa Sensor Wiring Connections Electrodes Coils ...

  • Emerson Process Management 8732 - page 166

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-26 GENERIC MANUFACTURER SENSORS Generic Manufacturer Sensor to Rosemount 8732 T r ansmitter Identify the T erminal s First check the sensor manufacture r ’s manual to identify the appropr iate terminals. Otherwise, perform the following procedure. Identify coil and electrode ...

  • Emerson Process Management 8732 - page 167

    Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Appendix F Resource Block Parameters and Descriptions . . . . . . . . . . . . . . . . . . . . . . p age F-1 Resource Block Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age F-5 Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 8732 - page 168

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 F-2 BLOCK_ALM 36 The block alarm is used for all co nfigur ation, hardware, connection failure, or system problems in the block. The cau s e of the alert is entered in the subcode field. The first alert to become active wi ll set the active status in the status parameter . As soo ...

  • Emerson Process Management 8732 - page 169

    Reference Manual 00809-0100- 4663, Rev BA January 2010 F-3 Rosemount 8732 FREE_SP ACE 24 This p arameter re presents the percent of memory available for further configuration (zero in a preconfigured device) . FREE_TIME 25 This parameter represents the percent of t he block processing time that is free to process additional blocks. GRANT_DENY 14 Op ...

  • Emerson Process Management 8732 - page 170

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 F-4 REST AR T 16 Allows a manual restart to be initiated. Several degrees of restart are possible: 1 Run: Nominal state when not restarting 2 Restart resource: Not used 3 Restart with defaults: Set parameters to default values (see ST AR T_WITH_DEF AUL TS below for which paramete ...

  • Emerson Process Management 8732 - page 171

    Reference Manual 00809-0100- 4663, Rev BA January 2010 F-5 Rosemount 8732 RESOURCE BLOCK ERRORS T able F-2 lists conditions reported in the BLOCK_ERR parameter . Conditions in italics are inactive for the resource block and are given here only for your reference. T able F-2. Resource BLOCK_ERR Conditions MODES The resource bl ock supports two modes ...

  • Emerson Process Management 8732 - page 172

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 F-6 Alarm Detection A block alarm will be generated whenev er the BLOCK_ER R has an error bit set. The types of block error for the reso urce block are defined in T able F-2. A write alarm is generated whene ver the WRITE_LOCK parameter is cleared. The priority of the write alarm ...

  • Emerson Process Management 8732 - page 173

    Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Appendix G T ransducer Block Parameters and Descriptions . . . . . . . . . . . . . . . . . . . . . . p age G-2 Flow-Speci fic Block Configuration V alu es . . . . . . . . . . . . p age G-3 T ransducer Block Errors . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 8732 - page 174

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 G-2 PARAMETERS AND DESCRIPTIONS T able G-1 lists all of the configu rable parameters of the tr ansducer block, indicating the descriptions and ind ex numbers for each parameters. T able G-1. T ransducer Block Parameters Parameter Index Number Definition ALERT_KEY 4 ID number of t ...

  • Emerson Process Management 8732 - page 175

    Reference Manual 00809-0100- 4663, Rev BA January 2010 G-3 Rosemount 8732 FLOW-SPECIFIC BLOCK CONFIGURATION VA L U E S Once the transmitter is in stalled and communication is est ablished, configuration must be completed . Three parameters must be enter ed for proper configur ation: • Sensor calibration number • Engineering units (configured v ...

  • Emerson Process Management 8732 - page 176

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 G-4 T RANSDUCER BLOCK ERRORS The following conditions are reported in the BLOCK_ERR and XD_ERROR paramete rs. Conditions in italics are inactive for the transducer block and are given here only for your r eference. T able G-4. T ransducer BLOCK_ERR and XD_ERR Conditions Condition ...

  • Emerson Process Management 8732 - page 177

    Reference Manual 00809-0100- 4663, Rev BA January 2010 G-5 Rosemount 8732 T RANSDUCER BLOCK DIAGNOSTICS In addition to the BLOCK_ERR an d XD_ERROR parameters, more detailed information on the measu rement status can be obtain ed via DET AILED_ST A TUS. T able G-5 lists the potential erro rs and the possible corrective actions for the given values. ...

  • Emerson Process Management 8732 - page 178

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 G-6 In Auto mode, OUT reflects the value and status quality of the output channels. T R OUBLESHOOTING Refer to T able G-6 to troubleshoot tr ansducer block problems. T able G-6. T roubleshooting Symptom Possible Causes Corrective Action Mode will not leave out of service ( OOS). ...

  • Emerson Process Management 8732 - page 179

    Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Appendix H 375 Field Communicator Operation HandHeld Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . page H-1 Connections and Hardware . . . . . . . . . . . . . . . . . . . . . . . . p age H-2 Basic Features . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 8732 - page 180

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 H-2 CONNECTIONS AND HARDWARE The 375 Field Communicator exch anges information with the transmitter from the control room, the instrument site, or any wiring terminatio n point in the loop. Be sure to install the instrume nts in the loop in accordance with intrinsically safe or n ...

  • Emerson Process Management 8732 - page 181

    Reference Manual 00809-0100- 4663, Rev BA January 2010 H-3 Rosemount 8732 BASIC FEATURES The basic features of the Handh eld Communicator include Action Keys, Function Keys, and Alphanu meric and Shift Keys. Figure H-3. The Handheld Communicator Action Keys The Action Key s As shown in Figure H-3, th e act ion ke ys are the six blue, white, and bla ...

  • Emerson Process Management 8732 - page 182

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 H-4 Function Key Use the four sof tware-defined function keys, located below the LCD, to perform sof tware functions. On any given menu, the label appe aring above a function key indicates the fu nction of that key f or the curren t menu. As you move among menus, dif ferent funct ...

  • Emerson Process Management 8732 - page 183

    Reference Manual 00809-0100- 4663, Rev BA January 2010 H-5 Rosemount 8732 Main Menu The Main Men u pr ov ide s th e follo win g op tio n s: • Offline - The Of fline option provide s access to offlin e configuration dat a and simulation functions. • Online - The Online option checks for a device and if it finds one, brings up the Online Menu. ? ...

  • Emerson Process Management 8732 - page 184

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 H-6 Diagnostic Messages The following is a list of messages us ed by the Ha ndheld Communicator (HC) and their correspo ndi ng descriptions. V ariable parameters within the text of a message are indicated with <variable par ameter> . Reference to the name of another m essag ...

  • Emerson Process Management 8732 - page 185

    Reference Manual 00809-0100- 4663, Rev BA January 2010 H-7 Rosemount 8732 OFF KEY DISABLED Appears when the user attempts to turn the HC off before sending modified data or before completing a method On-line device disconnected with unsent data – RETRY or OK to lose data There is unsent data for a previo usly connected device . Press RETRY to sen ...

  • Emerson Process Management 8732 - page 186

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 H-8 ...

  • Emerson Process Management 8732 - page 187

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Index-1 Rosemount 8732 A Action Keys Handheld Communicator .H - 3 Alphanumeric Keys Handheld Communicator .H - 4 Analog Output Range . . . . . . . . . . . . . 3-10 Zero . . . . . . . . . . . . . . . 3-10 Applications/Configurations . . . 2-4 Auto Zero . . . . . . . . . . . . . . . D-2 B Basic S ...

  • Emerson Process Management 8732 - page 188

    Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 Index-2 Lower Range Value (LRV) . . 3-10 M Mechanical Considerations 2-2 , 2-6 Menu Handheld Communicator .H - 4 Messages Safety . . . . . . . . . . . . . . 1-2 Mode Transducer Block . . . . . . G-5 MODE_BLK Transducer Block . . . . . . G-5 Mounting . . . . . . . . . . . . . . . ...

  • Emerson Process Management 8732 - page 189

    ...

  • Emerson Process Management 8732 - page 190

    Emerson Process Management 00809-0100-4663 Rev BA, 1/10 The Emerson logo is a trade mark and se rvice mar k of Emerson Electric Co. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. PlantWeb is a registered trademark of one of t he Emerson Process Management group of companies. All other marks are the property of thei ...

Manufacturer Emerson Process Management Category Oxygen Equipment

Documents that we receive from a manufacturer of a Emerson Process Management 8732 can be divided into several groups. They are, among others:
- Emerson Process Management technical drawings
- 8732 manuals
- Emerson Process Management product data sheets
- information booklets
- or energy labels Emerson Process Management 8732
All of them are important, but the most important information from the point of view of use of the device are in the user manual Emerson Process Management 8732.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Emerson Process Management 8732, service manual, brief instructions and user manuals Emerson Process Management 8732. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Emerson Process Management 8732.

A complete manual for the device Emerson Process Management 8732, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Emerson Process Management 8732 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Emerson Process Management 8732.

A complete Emerson Process Management manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Emerson Process Management 8732 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Emerson Process Management 8732, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Emerson Process Management 8732, that we can find in the current document
3. Tips how to use the basic functions of the device Emerson Process Management 8732 - which should help us in our first steps of using Emerson Process Management 8732
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Emerson Process Management 8732
5. FAQ - Frequently Asked Questions