  • Minuteman UPS - page 1

    User's Manual ...

  • Minuteman UPS - page 2

    1 © Copyright Para Systems, Inc., 2002 User's Manual 1 . Introduction 2 2 . Controls and Indicators 4 3. Installation 6 4 . Operation 9 5 . T roubleshooting 1 1 6 . Replacing the Battery 12 7 . Obtaining Service 15 8 . Specifications 16 9 . Configurable Parameters & Settings 17 10 . Limited Product W arranty 19 1 1 . Declaration of Confor ...

  • Minuteman UPS - page 3

    2 IMPORT ANT SAFETY INSTRUCTIONS SA VE THESE INSTRUCTIONS ! NOTICE: This equipment has been tested and found to comply with the limits for a Class B computing device in accordance with the specifications in Subpart J of Part 15 of FCC Rules and the Class B limits for radio noise emissions from digital apparatus set out in the Radio Interference of ...

  • Minuteman UPS - page 4

    3 ! Re-orient the receiving antenna ! Relocate the computer with respect to the receiver ! Move the computer away from the receiver ! Plug the computer into a different outlet so that the computer and receiver are on different branch circuits. ! Shielded communications interface cables must be used with this product. W ARNING: Risk of electrical sh ...

  • Minuteman UPS - page 5

    4 FRONT P ANEL English Para Systems Life Support Policy As a general policy , Para Systems Inc. (Para Systems) does not recommend the use of any of its products in life support applications where failure or malfunction of the Para Systems product can be reasonably expected to cause failure of the life support device or to significantly affect its s ...

  • Minuteman UPS - page 6

    5 Press and release the ON/OFF/T est Button after 1 beep to turn the UPS ON or OFF (see section 4). English SWF On-Line/On-Battery/Boost/Buck LED Overload LED Weak/Bad Battery LED Site Wiring Fault LED On/Off/T est Button On-Line On-Battery The On-Line/On-Battery/Boost and Buck (green) LED illuminates in a steady state when the UPS is on and supply ...

  • Minuteman UPS - page 7

    6 English REAR P ANEL 1 5 2 3 6 7 9 INST ALLA TION PLACEMENT 8 4 1. The RJ-45/RJ-1 1 modular connectors are used for 10 Base-T network/single line telephone surge protection. (see section 3) 2. The communications port is for UPS monitoring and control. (see section 4) 3. The output receptacles are NEMA 5-15R type. 4. Rating/Serial number label. 5. ...

  • Minuteman UPS - page 8

    7 English INST ALLA TION Be sure to read the installation placement and all the cautions before installing the UPS. Place the UPS in the final desired location and complete the rest of the installation procedure. USE CAUTION: The UPS is heavy . Use the appropriate number of personnel when installing the UPS. Install the UPS in a temperature control ...

  • Minuteman UPS - page 9

    8 English CHARGING THE BA TTER Y The SmartSine UPS will charge the internal batteries whenever the UPS is connected to an AC source. It is recommended that the UPS's batteries be charged for a minimum of 4 hours before use. The UPS may be used immediately , however , the “ON Battery” runtime may be less than normally expected. CAUTION! If ...

  • Minuteman UPS - page 10

    9 English TURNING THE UNIT ON/OFF ON / OFF / T est Button SELF TEST English Press and release the ON/OFF/T est Button after one beep to turn the UPS ON and supply power to the load. The load is immediately powered while the UPS runs a five-second self test. Press and release the ON/OFF/T est Button after one beep to turn the UPS OFF . The UPS will ...

  • Minuteman UPS - page 11

    10 COMMUNICA TIONS PORT The communications port is a standard DB9 female with both RS232 and simulated contact closure capability . The SmartSine UPS will poll the port and activate the port for RS232 or contact closure in accordance with the type of cable it finds connected to the port. T o change the port configuration requires the UPS be turned ...

  • Minuteman UPS - page 12

    11 English Possible Cause Symptom What T o Do Press and release the On/Off/ T est button to start UPS On/Of f/T est button not pushed UPS will not turn on Reset circuit breaker by pressing the plunger back in. If the AC circuit breaker trips after UPS starts up, reduce the load on the UPS UPS operates in battery mode only , even though there is nor ...

  • Minuteman UPS - page 13

    12 REPLACING THE BA TTER Y The SmartSine UPS has an easy to replace hot-swappable batteries. Please read all of the Warnings and Cautions before attempting to service the batteries. NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will not be backed up. English W ARNING! This Uninterrupti ...

  • Minuteman UPS - page 14

    13 BA TTER Y REPLACEMENT PROCEDURE PLEASE READ THE CAUTIONS BEFORE A TTEMPTING TO REPLACE THE BA TTERIES Hot-swappable batteries mean that the batteries can be replaced without powering down the whole UPS system. NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will not be backed up. T o ...

  • Minuteman UPS - page 15

    14 English 8. Disconnect the positive (red) wire from the battery positve terminal. 9. Using the pull tab, pull the batteries out far enough to get to the battery negative (black) wire. DO NOT pull the batteries out by pulling the battery jumper wires. 10. Disconnect the battery negative (black) wire from the battery negative terminal. 1 1. Using t ...

  • Minuteman UPS - page 16

    15 IF THE UPS REQUIRES SERVICE 1.Use the TROUBLESHOOTING section to eliminate obvious causes. 2.V erify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem. 3.Call your dealer for assistance. If you cannot reach your dealer , or if they cannot resolve the problem call or fax MINUTEMAN T echnical Support at th ...

  • Minuteman UPS - page 17

    16 English Default 120V AC / User selectable at 1 10, 120, 127V AC 3-6 years, depending on discharge cycles and ambient temp 700V A 500W 1000V A 700W 2000V A 1400W 1400V A 1000W 500 J 0 ns (instantaneous) normal mode; <5 ns common mode <5% 0 to 40 degrees C (+32 to 104 degrees F) Normal and common mode EMI/RFI suppression 2-12V7Ah 2-12V12Ah 2 ...

  • Minuteman UPS - page 18

    17 (These items may require optional software or hardware) English English Function Factory Default Description User Choices Set inverter output voltage Shut- down T ype Set audible alarm state Enable/ Disable auto restart Battery life in days Battery install date UPS ID SmartSine Date of manufacture 1826 Enabled Enabled UPS output 120V AC Up to 64 ...

  • Minuteman UPS - page 19

    18 English The SmartSine UPS has a removable receptacle panel. The receptacle panel can be configured with one locking receptacle and two duplex receptacles. This will allow the user to customize the output receptacles for their specific applications. MINUTEMAN will only use UL or CE approved receptacles. Here is one example that could be used: one ...

  • Minuteman UPS - page 20

    19 LIMITED PRODUCT W ARRANTY Para Systems Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase. For equipment sites within the United States and Canada, this warranty covers repair or replacement of d ...

  • Minuteman UPS - page 21

    20 English EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL P ARA SYSTEMS BE LIABLE FOR DIRECT , INDIRECT , SPECIAL, INCIDENT AL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT , EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically , Para Systems is not liable for any costs, such as lost profits or revenue, loss of equipment, ...

  • Minuteman UPS - page 22

    21 English DECLARA TION OF CONFORMITY Application of Council Directive(s): 89/336/EEC, 7/23/EEC Standard(s) to which Conformity is declared: EN50091-2, EN60555-2, EN61000-3, EN50091-1 Manufacturer’s Name: Para Systems, Inc. (Minuteman UPS) Manufacturer’s Address: 1455 LeMay Drive Carrollton, T exas 75007 USA T ype of Equipment: Uninterruptible ...

  • Minuteman UPS - page 23

    24 English Notes: 22 ...

  • Minuteman UPS - page 24

    Para Systems, Inc. 1455 Lemay Dr . Carrollton, TX 75007 Phone: 1-972-446-7363 Fax: 1-972-446-901 1 Internet: minutemanups.com UPS Sizing: sizemyups.com PN - 34000196 Rev . 0 ...

Manufacturer Minuteman Category Power Supply

Documents that we receive from a manufacturer of a Minuteman UPS can be divided into several groups. They are, among others:
- Minuteman technical drawings
- UPS manuals
- Minuteman product data sheets
- information booklets
- or energy labels Minuteman UPS
All of them are important, but the most important information from the point of view of use of the device are in the user manual Minuteman UPS.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Minuteman UPS, service manual, brief instructions and user manuals Minuteman UPS. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Minuteman UPS.

Similar manuals

A complete manual for the device Minuteman UPS, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Minuteman UPS by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Minuteman UPS.

A complete Minuteman manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Minuteman UPS - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Minuteman UPS, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Minuteman UPS, that we can find in the current document
3. Tips how to use the basic functions of the device Minuteman UPS - which should help us in our first steps of using Minuteman UPS
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Minuteman UPS
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Minuteman UPS in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Minuteman UPS?

Use the form below

If you did not solve your problem by using a manual Minuteman UPS, ask a question using the form below. If a user had a similar problem with Minuteman UPS it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)