Manual Ingersoll-Rand X41

85 pages 3.01 mb
Download

Go to site of 85

Summary
  • Ingersoll-Rand X41 - page 1

    Ingersoll Rand System Automation X4I Application & Compressor Interconnect Guide More Than Air. Answers. Online answer s: http://ww w.air. irco.com Befor e instal ling or startin g this un it for t he fir st time, this manual should be st udied carefully to obtain a working knowledge of the uni t and/or the duties to be performed while operatin ...

  • Ingersoll-Rand X41 - page 2

    2 SECTION 1 — TABLE OF CONTENTS SECTION 1 — TABLE OF CONTE NTS................................ 2 SECTION 2 — IN TRODUCTIO N ........................................ 4 SECTION 3 — SAFETY ..................................................... 4 INSTALLATION ............................................................... 4 OPERATION ........... ...

  • Ingersoll-Rand X41 - page 3

    3 X4I Interco nnect To In gersoll R and Press ure Swi tch Controlle d Compressor s .................................. Continue d UP6 5-15 SD 3P H 50Hz 1o f2 .................................. 59 UP6 5-15 SD 3P H 50Hz 2o f2 .................................. 60 SSR M15-22c 20-30HP XF EP HP HXP 50-60Hz 1o f2 .......................................... ...

  • Ingersoll-Rand X41 - page 4

    SECTION 2 — INTRODUCTION The X 4I is a spec iali zed con troll er d esig ned to prov ide safe, reliab le, and energy -effici ent control of y our compresse d air syste m. The X4I is ca pable of contr olling up to four positive displacement air compre ssors. The compre ssors ma y have electr o-pneu matic or microproce ssor based cont rols. The X4I ...

  • Ingersoll-Rand X41 - page 5

    5 • Carry out the following op erations before opening or removing any access panels or car rying out any work on t he X4I: i. Isol ate the X4 I from th e main electrical pow er supply. Lock t he isolator in th e “OFF” positio n and re move the fuse s. ii. Attac h labels to the is olator switch an d to th e unit stati ng “WORK IN PROGR ESS ...

  • Ingersoll-Rand X41 - page 6

    SECTION 4 — INSTALLATION It is recommended t hat installation and commissioning be carr ied out by a n author ized and tr ained pr oduct supplier. UNIT LOCATION The X4I can be mounted on a wall using conventional bolts. The X4I ca n be located r emotel y from the compressors as long as it is wit hin 330 feet (100 meters) of cable length. The X4I ...

  • Ingersoll-Rand X41 - page 7

    POWER SUPPLY 7 A fuse d switching isolator must be i nstalle d to the mai n incoming power supply, ext ernal to th e X4 I. T he is olat or must be fitted wi th a pr operly si zed fuse t o provi de adeq uate p rote ction to th e po wer sup ply c able u sed ( in accordanc e with local electric al and safety regulati ons). 1 VOLTAGE SELECT 23 4 X04 1 ...

  • Ingersoll-Rand X41 - page 8

    PRESSURE SENSOR CO NNECTION The pre ssure sensor connects t o terminal X05 of the X4I terminal P CB using a shield ed 18 AWG maximum 2- conductor cable no more than 330 feet (100 meters) in length. The transducer threads are BPT. It is the equiva lent o f ¼” NPT. Pressure Sensor Wir ing and Locat ion Wire pol arity is im portant. IR-PCB INTE RFA ...

  • Ingersoll-Rand X41 - page 9

    Consult the air compressor manua l or your air compressor supplier/ specialist for details be fore installing the X 4I. Each air compressor must be e quipped w ith an online/offl ine pre ssure regulat ion system ca pable of accep ting a re mote lo ad/un load sign al thro ugh a vo lt free switching contact or a single electro -mechanic al pressure s ...

  • Ingersoll-Rand X41 - page 10

    RUN INPU T 0V RUN READY ALARM +V MAIN (LINE) CONTACTOR C04 Run Signal Circuit The RUN input will accept 12V to 250V AC (50/60Hz) only. DC cannot be used. Do n ot con ne ct a vo lta ge g rea ter th an 2 50V to th is input. 12V to 250Vac must be applied t o the “run” ter minals when the compressor motor is running. This input can be connecte d to ...

  • Ingersoll-Rand X41 - page 11

    OUTPUT FUNCTIONS 11 The X4I will control the IR-PCB load/unload relay output s based on t he active syst em load an d unload pre ssure setpoi nts. The IR-PCB load/unload re lay contact s can be used for compr essor cont rollers that have electr o- mechani cal pressure switch loa d/unload re gulation. IR-PCB Internal Output Circuits The C01 and C02 ...

  • Ingersoll-Rand X41 - page 12

    compressor number) with an a dditional wir e. Use a 7- conductor shield ed cable in this instanc e. Compressor s that use ele ctronic pre ssure dete ction but are not equipped wit h a remot e pressure control enable f eature will no t autom atically rev ert to local control i f the X4I i s stopped or experie nces a fa ult or loss of power. Load/Unl ...

  • Ingersoll-Rand X41 - page 13

    AUX ILIAR Y OUT PUT (O PTION ) The X4 I is equipp ed with a rem ote relay contact o utput a t terminals 33 and 34 (X08). 13 The function of t he output is menu select able and ca n be adapte d for differ ing application re quirement s. X08 33 34 R6 Auxiliary Output Circui t The remote output relay con tacts are rated for 240V “CE” / 115 V “U ...

  • Ingersoll-Rand X41 - page 14

    Compressor #1 IR-PCB DRIP LEG PRESSURE TR ANSDUCER RECEIVER Compressor #3 IR-PCB Compressor #4 IR-PCB Compressor #2 IR-PCB PRESSURE TRA NSDUCER CAB LE 2 Conductor Cable, 18 Gau ge Stranded Earth Shielded No Greater Th an 33 0 FT (1 00 M) 24VDC Control Voltag e X4I X05 CONNE CT OR PT CONNECTOR 25 +VDC Pin #3 26 Signal Pin #1 Reference X4I Op era tio ...

  • Ingersoll-Rand X41 - page 15

    X4I Interconnect To Ingersoll Rand Unigy & Nirvana 20-40 HP Compressors Refer to the X4I Overview Drawing fo r the X4I Compressor 2 t hrough 4 X01 to IR-P CB terminal connect ions For Unigy Compressors:: All Unigy Phase 1 compressors “MUST” be conv erted to Phase 2 or higher. Contact Techni cal Support Services for the CCN's requi red ...

  • Ingersoll-Rand X41 - page 16

    +24VDC DI-4 EN 12 14 13 10 D13 17 NO 0V 5 +24VDC 11 SA1 HATS E-STOP DI-2 9 VFD/FIX Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt rol circuit diagram. +VDC Load Enable Load/Unload VFD ...

  • Ingersoll-Rand X41 - page 17

    Unigy Phase 1 Unigy Phase 1 2of2 Page 17 ...

  • Ingersoll-Rand X41 - page 18

    Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt rol circuit diagram. SA1 HATS E-STOP VFD/FIX +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LO ...

  • Ingersoll-Rand X41 - page 19

    Unigy Phase 2/3 Unigy Phase 2/3 2of2 Page 19 ...

  • Ingersoll-Rand X41 - page 20

    Remote VFD / F IXED Remote LOAD / UNLOAD Remote LOAD ENABLE 33 32 18 12 +24VDC 6 NC COM 20 C 4 SAFE 37 Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt rol circuit diagram. +VDC Load En ...

  • Ingersoll-Rand X41 - page 21

    Nirvana 15 - 30KW (20-40HP) Nirvana 15 - 30KW (20-40HP) 2of2 Page 21 ...

  • Ingersoll-Rand X41 - page 22

    X4I Interconnect To Ingersoll Rand In tellisys Redeye Controlled Compressors Refer to the X4I O verview Drawing for the X4I Compres sor 2 through 4 X01 t o IR-PCB terminal co nnections For Redeye Intellis ys Controlled Machines: The ‘MASTER CONTROL’ setting of the Intell isys controller must be set to ‘ON’ The 'SEQUENCER' setting ...

  • Ingersoll-Rand X41 - page 23

    +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD UNL GND D11 D12 +20V V 1 2 3 4 5 6 2 1 LED 5 VFD LED 2 LOAD LED 1 SEQ LED 4 READY LED 3 RUN C03 C01 C02 C04 C05 IR-PCB 1 2 3 4 5 6 V1 X4I COMPRESSO R #1 X01 TERMINAL Refer to the X 4 I Over v iew Draw ing for the X4I Compressor 2 through 4 terminal connect ...

  • Ingersoll-Rand X41 - page 24

    SSR Redeye FV SSR Redeye FV 2of3 Page 24 ...

  • Ingersoll-Rand X41 - page 25

    SSR Redeye SD SSR Redeye SD 3of3 Page 25 ...

  • Ingersoll-Rand X41 - page 26

    X4I Interconnect To Ingersoll Rand Intellisys SE Controlled Compressors Refer to the X4I O verview Drawing for the X4I Compres sor 2 through 4 X01 t o IR-PCB terminal co nnections For All SE Intellisys Controlled Machines: The 'SEQUENCER' setting of the Intelli sys controller must be set to 'ON'. Auto Restart must be turned &apo ...

  • Ingersoll-Rand X41 - page 27

    E-STOP 110VAC 1M 0VAC Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt rol circuit diagram. +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD ...

  • Ingersoll-Rand X41 - page 28

    SE UP SE UP 2of2 Page 28 ...

  • Ingersoll-Rand X41 - page 29

    Remote Load/Unload (was Remote Start) Remote Load/Unload (was Remote Start) 1 9 10 11 E-STOP J5 7 11 12 13 14 J5 J5 J1 110VAC 1M 0VAC Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt ro ...

  • Ingersoll-Rand X41 - page 30

    SE ESA SE ESA 2of2 Page 30 ...

  • Ingersoll-Rand X41 - page 31

    1M 0VAC Remote Load/Unload (was Remote Start) Remote Load/Unload (was Remote Start) 34 33 32 110VAC E-STOP J5 36 6 5 4 3 J5 J5 J1 42 Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt rol ...

  • Ingersoll-Rand X41 - page 32

    SE DSA SE DSA 2of2 Page 32 ...

  • Ingersoll-Rand X41 - page 33

    X4I Interconnect To Ingersoll Rand In tellisys SG Controlled Compressors Refer to the X4I O verview Drawing for the X4I Compres sor 2 through 4 X01 t o IR-PCB terminal co nnections For SG Intellisys Controll ed Machines: The 'SEQUENCER' setting of the Intellisys controller must be set to 'ON'. Auto Restart must be turned ' ...

  • Ingersoll-Rand X41 - page 34

    1M 0VAC Remote Load/Unload Remote Load Enable 3 2 1 110VAC E-STOP P1 1 25 26 27 28 P2 P1 P3 2 Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt rol circuit diagram. 1ATS +VDC Load Enable ...

  • Ingersoll-Rand X41 - page 35

    SG SSR SG SSR 2of2 Page 35 ...

  • Ingersoll-Rand X41 - page 36

    Guidance o nly; connection s may diff er with date, mo del, type, variant, s pecial, cus tom or conc ession builds. This information is int en ded to be used in conjunct ion with the compressor’s orig inal control circuit d iagram. 1M 0VAC Remote Load/Unload Remote Load Enable 3 2 1 110VAC E-STOP P1 1 25 26 27 28 P2 P1 P3 2 1ATS +VDC Load Enable ...

  • Ingersoll-Rand X41 - page 37

    SG Sierra SG Sierra 2of2 Page 37 ...

  • Ingersoll-Rand X41 - page 38

    X4I Interconnect To Ingersoll Rand Pr essure Switch Controlled Compressors Refer to the X4I Overview Drawing for the X4I Compressor 2 t hrough 4 X01 to IR-PCB terminal connec tions For All Compressors: Compressors to be connected must have automatic Start / Stop capability . Drawing Notes For Pressure Switch Controller Machines: Ensure each compres ...

  • Ingersoll-Rand X41 - page 39

    KM1 0 VAC KM1 Re lay Contact P To TM2 Relay To KM1 Co ntact To KM2 Contact Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt rol circuit diagram. +VDC Load Enable Load/Unload VFD/fixed I ...

  • Ingersoll-Rand X41 - page 40

    SSR UP5 11-22 SD SSR UP5 11-22 SD 2of2 Page 40 ...

  • Ingersoll-Rand X41 - page 41

    KM1 0 VAC KM1 Relay Contact KM1 Relay Contact TM3 Relay Contact Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt rol circuit diagram. +VDC Load Enable Load/Unload VFD/fixed IN NO C NC N ...

  • Ingersoll-Rand X41 - page 42

    SSR UP5 22-37 SD SSR UP5 22-37 SD 2of2 Page 42 ...

  • Ingersoll-Rand X41 - page 43

    Guidance only; co nnections may di ffer with date, mode l, type, variant, special, cus tom or concess i on builds. This informatio n is intended to be used in conjunctio n with the comp ressor’s original c ontrol circuit diagram. M 0 VAC +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD UNL GND D11 D12 ...

  • Ingersoll-Rand X41 - page 44

    SSR UP6 15-30 FV SSR UP6 15-30 FV 2of2 Page 44 ...

  • Ingersoll-Rand X41 - page 45

    Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt rol circuit diagram. 1M 0 VAC +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD UNL GND D11 ...

  • Ingersoll-Rand X41 - page 46

    SSR UP6 15-30 SD SSR UP6 15-30 SD 2of2 Page 46 ...

  • Ingersoll-Rand X41 - page 47

    Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt rol circuit diagram. 1M 0 VAC +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD UNL GND D11 ...

  • Ingersoll-Rand X41 - page 48

    SSR UP6 40-50 FV SSR UP6 40-50 FV 2of2 Page 48 ...

  • Ingersoll-Rand X41 - page 49

    Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt rol circuit diagram. 1M 0 VAC +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD UNL GND D11 ...

  • Ingersoll-Rand X41 - page 50

    SSR UP6 40-50 SD SSR UP6 40-50 SD 2of2 Page 50 ...

  • Ingersoll-Rand X41 - page 51

    Guidance only; co nnections may di ffer with date, mode l, type, variant, special, cus tom or concess i on builds. This informatio n is intended to be used in conjunctio n with the comp ressor’s original c ontrol circuit diagram. +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD UNL GND D11 D12 +20V V 1 ...

  • Ingersoll-Rand X41 - page 52

    UP6 5-15 FV 1PH 60Hz UP6 5-15 FV 1PH 60Hz 2of2 Page 52 ...

  • Ingersoll-Rand X41 - page 53

    +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD UNL GND D11 D12 +20V V 1 2 3 4 5 6 2 1 LED 5 VFD LED 2 LOAD LED 1 SEQ LED 4 READY LED 3 RUN C03 C01 C02 C04 C05 IR-PCB 1 2 3 4 5 6 V1 X4I COMPRESSOR #1 X01 TERMINAL Refer to the X4I Overv iew Drawing for the X4I Co mpressor 2 through 4 terminal connectio n ...

  • Ingersoll-Rand X41 - page 54

    UP6 5-15 FV 3P H 60Hz UP6 5-15 FV 3PH 60Hz 2of2 Page 54 ...

  • Ingersoll-Rand X41 - page 55

    0 VAC 110VAC PS ST CR Contact HATS 1M To 1M Contac t To CR Relay To HM To EDV To 1M/1S/2M Contacts To TD Relay Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt rol circuit diagram. +VDC ...

  • Ingersoll-Rand X41 - page 56

    UP6 5-15 SD 3PH 60Hz UP6 5-15 SD 3PH 60Hz 2of2 Page 56 ...

  • Ingersoll-Rand X41 - page 57

    Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt rol circuit diagram. +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD UNL GND D11 D12 +20V ...

  • Ingersoll-Rand X41 - page 58

    UP6 5-15 FV 3P H 50Hz UP6 5-15 FV 3PH 50Hz 2of2 Page 58 ...

  • Ingersoll-Rand X41 - page 59

    Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt rol circuit diagram. +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD UNL GND D11 D12 +20V ...

  • Ingersoll-Rand X41 - page 60

    UP6 5-15 SD 3PH 50Hz UP6 5-15 SD 3PH 50Hz 2of2 Page 60 ...

  • Ingersoll-Rand X41 - page 61

    KM1 0 VAC TM2 Contact P To TM2 Relay To KM2 Contact +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD UNL GND D11 D12 +20V V 1 2 3 4 5 6 2 1 LED 5 VFD LED 2 LOAD LED 1 SEQ LED 4 READY LED 3 RUN C03 C01 C02 C04 C05 IR-PCB 1 2 3 4 5 6 V1 X4I COMPRESSO R #1 X01 TERMINAL Refer to the X4 I Overview Drawing for ...

  • Ingersoll-Rand X41 - page 62

    SSR M15-22c 20-30HP XF EP HP HXP 5 0-6 0Hz SSR M15-22c 20-30HP XF EP HP HXP 50-60Hz 2of2 Page 62 ...

  • Ingersoll-Rand X41 - page 63

    KM1 0 VAC KM1 Contact P To 2TR Relay To KM2 Contact +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD UNL GND D11 D12 +20V V 1 2 3 4 5 6 2 1 LED 5 VFD LED 2 LOA D LED 1 SEQ LED 4 READY LED 3 RUN C03 C01 C02 C04 C05 IR-PCB 1 2 3 4 5 6 V1 X4I COMPRESSOR #1 X01 TERMINAL Refer to the X4I O verview Drawing for ...

  • Ingersoll-Rand X41 - page 64

    M37-50 M37-50 2of2 Page 64 ...

  • Ingersoll-Rand X41 - page 65

    110VAC CR Contact HATS CR Contact PUSH STOP PULL START 1M 0 VAC +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD UNL GND D11 D12 +20V V 1 2 3 4 5 6 2 1 LED 5 VFD LED 2 LOAD LED 1 SEQ LED 4 READY LED 3 RUN C03 C01 C02 C04 C05 IR-PCB 1 2 3 4 5 6 V1 X4I COMPRESSOR # 1 X01 TERMINAL Refer to the X4I O verview ...

  • Ingersoll-Rand X41 - page 66

    EP 20-30 ESP FV EP 20-30 ESP FV 2of2 Page 66 ...

  • Ingersoll-Rand X41 - page 67

    110VAC CR Contact HATS CR Contact PUSH STOP PULL START 1M 0 VAC +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD UNL GND D11 D12 +20V V 1 2 3 4 5 6 2 1 LED 5 VFD LED 2 LOAD LED 1 SEQ LED 4 READY LED 3 RUN C03 C01 C02 C04 C05 IR-PCB 1 2 3 4 5 6 V1 X4I COMPRESSOR # 1 X01 TERMINAL Refer to the X4I O verview ...

  • Ingersoll-Rand X41 - page 68

    EP 20-30 ESP S D EP 20-30 ESP SD 2of2 Page 68 ...

  • Ingersoll-Rand X41 - page 69

    X4I Interconnect To Ingersoll Rand Inte llisys SGN / SGNe Controlled Compressors Refer to the X4I O verview Drawing for the X4I Compres sor 2 through 4 X01 t o IR-PCB terminal co nnections For SGN/SGNe Intellisys Controlled Machines: The SI1 interface (CCN: 42 425710) must be used to allow the SG N/SGNe Controller to be sequenced/controlled by the ...

  • Ingersoll-Rand X41 - page 70

    +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD UNL GND D11 D12 +20V V 1 2 3 4 5 6 2 1 LED 5 VFD LED 2 LOAD LED 1 SEQ LED 4 READY LED 3 RUN C03 C01 C02 C04 C05 IR-PCB 1 2 3 4 5 6 V1 X4I COMPRESSO R #1 X01 TERMINAL Refer to the X4I Overv iew Drawing for the X4I Compr essor 2 through 4 terminal connectio ...

  • Ingersoll-Rand X41 - page 71

    Nirvana SGN/SGNe Nirvana SGN/SGNe 2of3 Page 71 ...

  • Ingersoll-Rand X41 - page 72

    Nirvana SGN/SGNe Nirvana SGN/SGNe 3of3 Page 72 ...

  • Ingersoll-Rand X41 - page 73

    +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD UNL GND D11 D12 +20V V 1 2 3 4 5 6 2 1 LED 5 VFD LED 2 LOAD LED 1 SEQ LED 4 READY LED 3 RUN C03 C01 C02 C04 C05 IR-PCB 1 2 3 4 5 6 V1 X4I COMPRESSO R #1 X01 TERMINAL Refer to the X4 I Overview Drawing for the X4I Compressor 2 through 4 terminal connectio n ...

  • Ingersoll-Rand X41 - page 74

    X4I Interconnect To Ingersoll Rand Intellisys S3 Refer to the X4I Overview Drawing for the X4I Compressor 2 t hrough 4 X01 to I R-PCB terminal connect ions For All S3 Intellisys Controlled Machines: The 'REMOTE CONTROL' sett ing “RC” of the In tellisys cont roller must be set to 'ON'. Auto Restart must be turned 'ON’ ...

  • Ingersoll-Rand X41 - page 75

    KM1 0VAC 3 4 110VAC 1 7 8 X02 X03 X04 2 Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt rol circuit diagram. +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY O ...

  • Ingersoll-Rand X41 - page 76

    Intellisys S3 Intellisys S3 2of2 Page 76 ...

  • Ingersoll-Rand X41 - page 77

    X4I Interconnect To Ingersoll Rand Small Reciprocating Air Compressors Refer to the X4I Overview Drawing for the X4I Compressor 2 t hrough 4 X01 to I R-PCB terminal connect ions For All Compressors: Compressors to be connected must have automatic Start / Stop capability . Drawing Notes For Pressure Switch Controller Machines: Ensure each compressor ...

  • Ingersoll-Rand X41 - page 78

    Guidance only; c onnections may di ff er with date, model, type, variant, spec ia l, custom or concess i on builds. This information is inte nded to be used in conju nction with the compre ssor’s original co ntrol circuit dia gram. UP6RE 7.5–15 175, UP6RX 7.5–15 175 0 VAC 110VAC P M +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RU ...

  • Ingersoll-Rand X41 - page 79

    UP6RE 7.5–15 175 , UP6RX 7.5–15 175 UP6RE 7.5–15 175, UP6RX 7.5–15 175 2of3 Page 79 ...

  • Ingersoll-Rand X41 - page 80

    UP6RE 7.5–15 175 , UP6RX 7.5–15 175 UP6RE 7.5–15 175, UP6RX 7.5–15 175 3of3 Page 80 ...

  • Ingersoll-Rand X41 - page 81

    L2 L1 P HATS M +VDC Load Enable Load/Unload VFD/fixed IN NO C NC NO C NC RUN ALARM READY OUT V SEQ CONT LOAD UNL GND D11 D12 +20V V 1 2 3 4 5 6 2 1 LED 5 VFD LED 2 LOAD LED 1 SEQ LED 4 READY LED 3 RUN C03 C01 C02 C04 C05 IR-PCB 1 2 3 4 5 6 V1 X4I COMPRESSO R #1 X01 TERMINAL Refer to the X4 I Overview Drawing for the X4I Compressor 2 through 4 termi ...

  • Ingersoll-Rand X41 - page 82

    Models 2340, 2475, 2545, 7100, 15T & 3000 Models 2340, 2475, 2545, 7100, 15T & 3000 2of3 Page 82 ...

  • Ingersoll-Rand X41 - page 83

    Models 2340, 2475, 2545, 7100, 15T & 3000 Models 2340, 2475, 2545, 7100, 15T & 3000 3of3 Page 83 ...

  • Ingersoll-Rand X41 - page 84

    KM1 0 VAC KM1 Re lay Contact P To TM2 Relay To KM1 Co ntact To KM2 Contact Guidance only; connections may dif fer with date, model, t ype, variant, sp ecial, custom or conc ession builds. This information is inte nd ed to be use d in conjunc tion with the compresso r ’s origin al co nt rol circuit diagram. +VDC Load Enable Load/Unload VFD/fixed I ...

  • Ingersoll-Rand X41 - page 85

    KM1 0 VAC KM1 Relay Contact P To TM2 Relay To KM1 Contact To KM2 Contact Guidance only; co nnections may di ff er with date, model, ty pe, variant, spec ial, custom or conc ession builds. This information is inte nded to be used in conjunc tion with the compressor’s ori ginal control circuit diagram. +VDC Load Enable Load/Unload VFD/fixed IN NO C ...

Manufacturer Ingersoll-Rand Category Air Compressor

Documents that we receive from a manufacturer of a Ingersoll-Rand X41 can be divided into several groups. They are, among others:
- Ingersoll-Rand technical drawings
- X41 manuals
- Ingersoll-Rand product data sheets
- information booklets
- or energy labels Ingersoll-Rand X41
All of them are important, but the most important information from the point of view of use of the device are in the user manual Ingersoll-Rand X41.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Ingersoll-Rand X41, service manual, brief instructions and user manuals Ingersoll-Rand X41. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Ingersoll-Rand X41.

A complete manual for the device Ingersoll-Rand X41, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Ingersoll-Rand X41 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Ingersoll-Rand X41.

A complete Ingersoll-Rand manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Ingersoll-Rand X41 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Ingersoll-Rand X41, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Ingersoll-Rand X41, that we can find in the current document
3. Tips how to use the basic functions of the device Ingersoll-Rand X41 - which should help us in our first steps of using Ingersoll-Rand X41
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Ingersoll-Rand X41
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Ingersoll-Rand X41 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Ingersoll-Rand X41?

Use the form below

If you did not solve your problem by using a manual Ingersoll-Rand X41, ask a question using the form below. If a user had a similar problem with Ingersoll-Rand X41 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)