Manual Raypak Y-200

40 pages 7.37 mb
Download

Go to site of 40

Summary
  • Raypak Y-200 - page 1

    INST ALLA TION & OPERA TING INSTR UCTIONS Catalog No. 5000.62H Effective: 09-28-09 Replaces: 1 1-25-08 P/N 241 125 Rev . 9 Y -200 Series Electr onic Boiler Sequencer & Outdoor R eset Contr ol System ...

  • Raypak Y-200 - page 2

    2 is a registered trademark of Underwriters Laboratories Inc. ® Rev . 9 reflects the following: Changes to: C-UL Listed Mark on page 1. ...

  • Raypak Y-200 - page 3

    3 IMPORT ANT SAFETY INSTRUCTIONS 4 INTRODUCTION 4 Concept of Operation 4 Y -200 Controller Configurations 5 Y -200 Options 5 INST ALLA TION 6 Mechanical Installation 6 Electrical Installation 6 Controller Field Wiring 8 Communication Field Wiring 9 Air T emperature Sensor Installation 9 W ater T emperature Sensor Installatio n 10 Power T est 1 1 In ...

  • Raypak Y-200 - page 4

    4 Y–200 SERIES ELECTRONIC BOILER CONTROL SAFETY INSTR UCTIONS Thank you for selecting the Raypak Y–200 Series Electronic Boiler Control. It is our sincere hope that you will enjoy its outstanding design, ease of use and energy-saving features. Please R e gister Before proceeding any further , please take a moment to complete the enclosed user r ...

  • Raypak Y-200 - page 5

    5 Y -200 Controller Configur ation s Y -200 Options M odel No. D escription Y -241 4-St age Controller - Includes main controller assembly , air temperature sen- s or assembly (P/N 068634), water temperature assembly (P/N 068635) and one (1) stage contact board. Main controller includes one (1) mounted auxiliary contacts board. Y -281 8-St age Cont ...

  • Raypak Y-200 - page 6

    6 INST ALLA TION If the controller was not mounted on the boiler by the factory , care should be taken to select a suitable mounting location. The controller should be mounted on a solid and permanent base. The unit should be readily accessible for maintenance and installation purposes, and should be mounted so that the display is at a height and l ...

  • Raypak Y-200 - page 7

    7 P ower to the Controller • Observe (follow proper) polarity . • Observe proper wire colors while making electrical connections. • Provide an external surge suppressor capable of maintaining system integrity . • Provide overload prot ection and a disconnect means for equipment serviceability as required by local and state code. • Conduit ...

  • Raypak Y-200 - page 8

    8 N otes: 1 . T ighten terminal strip clamping screws to 2.5 in- lbs. Breakage from over-torquing is not covered under warranty . 2 . Use stranded copper conductors only . For supply connections, use wires sized on the basis of 60°C (140°F) ampacity and rated a minimum 90°C (194°F). 3. Install disconnect for each control unit. Fig. 3: Wiring Di ...

  • Raypak Y-200 - page 9

    9 Communication (RS485) Wiring R equir ed f or Optional Slav e Unit(s) Y -304 Slav e Cable Installation from System Control Module • Y -304 slave cable or equivalent shielded commu- nications cable (Belden #9842, Belden #8132 or Alpha 3492C) must be used. Maximum cable length 100 ft. Correct polarity must be observed. Make use of wire color codin ...

  • Raypak Y-200 - page 10

    10 Wa ter T emperature Sensor Installation Hydronic Heating Applications • Hydronic installations may require outdoor reset function. See page 1 1, and screen 02. • Ensure shielded cable length does not exceed 300 feet. Use 18 AWG shielded wire for sensor con- nections. • Must be installed in properly-sized conduit with no other wiring. • L ...

  • Raypak Y-200 - page 11

    11 Domestic Hot Wa ter Suppl y Applications • Outdoor reset function should be disabled. See screen 06 and 24. P ow er T est Check P ower Utilizing a V olt-ohm meter (VOM) monitor the following on the controller for proper voltage levels. Check at the T erminal Block (TB-1). Fig. 7: Domestic Hot W ater Supply From T o Indication TB pin 1 TB pin 2 ...

  • Raypak Y-200 - page 12

    12 Installation V erification Procedur e R e gister J Before proceeding any further , please verify that the user registration form has been completed and mailed. Mechanical Installa tion J V erify that the mechanical installation has been completed in accordance with the instructions. Outdoor Air T emperature Sensor J V erify that all Outdoor Air ...

  • Raypak Y-200 - page 13

    13 Control Scr eens T o access programming mode: Press and hold the " MODE" button for 4 seconds. When in Program mode, cursor is blinking on first settable parameter . U P/DOWN arrows change parameter . LEFT/RIGHT arrows move to next selectable parameter . T able E: Control Screens NO TE: Once programming is finished, go to Sc r ee n 28 ...

  • Raypak Y-200 - page 14

    14 Manual Ov er ride Internal switches have been provided on each of the stage modules that can be used to manually override the microcontroller . See switch SW1 on each stage board, page 15. Boiler/Sta g e Off Dela y 15 0 to 600 seconds; sets the time interval between sequential boiler start-ups. 0 to 600 seconds; sets time interval between sta g ...

  • Raypak Y-200 - page 15

    15 Circuit Boar d Layout Main Circuit Board d r a o B y r a i l i x u A d r a o B y a l e R e g a t S - 4 1 SW3 Reset Switch Manual Override Switch Manual Override Switch Fig. 8: Circuit Board Layout ...

  • Raypak Y-200 - page 16

    16 K eypad Nor mal Mode M ove to next screen Not active except in special modes Move to previous screen Not active except in special modes T o access programming mode: Press and hold "MODE" button for 4 seconds. If no button is pressed while in PROGRAM mode for 30 seconds, screen returns to normal mode Increase selected parameter Move to ...

  • Raypak Y-200 - page 17

    17 Control Scr een Displays & Prog r amming 1 0 C N I K A P Y A R Y - S ER I E S V ER XX . X X X e r a w t f o s f o r e b m u n n o i s r e V n o i t a c i f i t n e d i t c u d o r P This is the initial screen displayed after system st art-up, provided that there are no faults. IN I T I A L S E T P O I NT ° F 0 2 M M - D D- YY H H M M X XX . ...

  • Raypak Y-200 - page 18

    18 Control Band: 3 0 D N A B L O R T N O C XX . X ° F *C Band is a range of temperature above and below the target temperature. Range: 1°F to 10°F (.5°C to 5.5°C) Default value is 3°F Screen number Fahrenheit or Celsius NO TE: The above settings are recommended at initial installation. For maximum performance and system efficiency , these set ...

  • Raypak Y-200 - page 19

    19 4 0 F F O T E S F F O Press "MODE" to select "OFF" or "ALL" or "FULL WEEK" "OFFSET" screen Screen number 4 0 L L A T E S F F O —— — X : H H M M + X X . X ° F There are six offset adjustment s allowed for each calendar day . Screen number " ALL " means every day has the same param ...

  • Raypak Y-200 - page 20

    20 Holiday: SE T T I N G H O L I DA Y 0 5 H OL #X X X X — X X — X X Thirty two holidays are selectable (01-32) Month: 01 thru 12 Day: 01 thru 31 Ye ar: 01 to 99; Below 01 is Repeating Holiday (RH) setting RS T R A T I O X . X X : 1 0 6 XX X . X @ 7 0 X X X . X @ X X Default: System temperature at 70°F (21.1°C) 140°F @ 70°F (60°C @ 21.1°C) ...

  • Raypak Y-200 - page 21

    21 Fig. 10: System to Outdoor T emperature T yp ical Reset Ratio Setpoint at Design T emp: T emp@ T emp@ Radiation D esign C ond. 70°F 40°F 20°F 0°F - 20°F St a nding 190 105 0.3:1 0.6:1 0.8:1 1.1:1 Convection or Basebo ard 200 105 0. 3:1 0.5:1 0.7:1 0.9:1 Fan coil Heating 190 10 5 0.3:1 0.6:1 0.8:1 1.1:1 Fan Coil Heat and Coo l 140 105 0 .9:1 ...

  • Raypak Y-200 - page 22

    22 T he selection of the correct ratio depends on the initial temperature Set Point set on screen 02 and the desired system water temperature. If the building is too cold, increase the ratio value. After changing the r atio, wait several days and evaluate the comfort level before making another change. Advanced Prog r amming F eat ur e Line 2 may b ...

  • Raypak Y-200 - page 23

    23 Wa ter T emper a tur e: 8 0 P M E T R E T A W M AX : X XX . X M I N : X X X. X Displays the maximum water temperature for the boiler . Range is determined by s creen number 23. Factory default is 180°F (82.2°C) Maximum. S creen number Displays the minimum water temperature for the b oiler . Range is determ i ned by s creen number 23. Factory d ...

  • Raypak Y-200 - page 24

    24 System Monitor : 1 1 R O T I N O M M E T S Y S M A S T E R PB SS S B S SS A A A S creen number This screen is only a display . T ot al # of stages available is set on screen 24. P= SYSTEM PUMP MODULE Rule: Always on before boiler . Always off af ter last boiler off + programmed delay , or outdoor sensor reading is above cut off temperature setti ...

  • Raypak Y-200 - page 25

    25 Auxiliar y Delay: 3 1 Y A L E D X U A XX X SEC Screen number Auxiliar y Delay When CFH signal is "ON" the relay contact of the A1 Auxiliary module stays closed. When the CFH signal changes to "OFF", the contacts of the relay stay closed as long as the delay is set up. The AUX contacts operate on a delay after CFH. AUX turnoff ...

  • Raypak Y-200 - page 26

    26 Boiler/Stage Of f Delay: BO I L R / S T G O F F D L Y 1 5 C E S X X X C E S X X X Screen number Boiler T ur n-Of f Delay In a multiple boiler system: The boiler Turn-Of f Delay sets the amount of delay before each additional boiler is turned off. This delay starts when the preceding boil- er is turned off. The Boiler T urn-Off Delay range is fro ...

  • Raypak Y-200 - page 27

    27 IN LE T O U T L E T D ELT A 1 7 X X X .X XXX . X X XX . X Screen number Current boiler inlet or system temperature* Current boiler outlet or system temperature* Boiler or System delta.* A U TO L EA D — — L AST 18 1 0 0— 04 4 # XX # X X Screen number Run time If manual lead change hours L ead boiler Last boiler Auto or Manual (Displayed in ...

  • Raypak Y-200 - page 28

    28 Pass wor d: 9 1 D R O W S S A P AAA Screen number Used by maintenance personnel to change settings. 0 2 P U — T E S T I N U MA S T ER P B S B S B S S S A A A Screen number In display mode shows AAA or current password. T o enter the password: 1. Push the mode key . The cursor under the first A should start flashing. 2. Change the first letter ...

  • Raypak Y-200 - page 29

    29 System T est: W A T E R TE M P L IM I TS 23 MA X : X X X . X M I N : X X X . X Screen number Maximum programmable setting is 235°F (1 12.7°C). Factory default value is 210°F(98.8°C). Minimum programmable setting is 40°F (4.4°C). Factory default value is 105°F (40.5°C). 1 2 T S E T M E T S Y S N OT AC T I V E S creen number or ACTIVE SE T ...

  • Raypak Y-200 - page 30

    30 Master Unit: 4 2 R E T S A M SN S : X R E L A Y : X A U X : X Screen number 0, 1, 2 or 4 Number of temp. sensors. 1 thru 8 Number of staging contact s in use. See screen 25. 0, 1, 2 or 3 Number of auxiliary boards in use. If SNS:0 This unit is a slave unit (No sensors required or active) If SNS:1 W ater (System) - T urn outdoor reset ratio to &q ...

  • Raypak Y-200 - page 31

    31 Slav e Unit: S ee Staging T able S L A VE S CON NE CT E D 2 5 #X X Screen number Number of slaves connected: 01 thru 04 6 2 S K R O W N O L OF F Screen number OFF ON F ACT O RY D EFA U L TS 27 NO Screen number Press MODE button to get into program mode. Press UP arrow key to select YES. Press MODE button to load Factory Defaults and to exit prog ...

  • Raypak Y-200 - page 32

    32 8 2 S T L U A F E D R E S U T L U A F E D O N E N O N Screen number Press MODE button to get into program mode. Press UP or DOWN key to select “Setup Defaults”. 8 2 S T L U A F E D R E S U INV O K E D E F A UL T S Screen number If parameters have been changed and original user defaults are required: Press UP or DOWN key to select "Invok ...

  • Raypak Y-200 - page 33

    33 Alar m Call T elephone: A LA R M C A LL TE L E 3 0 X X XX X XX XXX X XX X XX Screen number Used to enter telephone number to be called when a fault occurs. 1 3 D I L L A C M R A L A X X XX X XX XXX X X Screen number Used to identify person or place to be called when a fault occurs. AL A R M CA L L E V E N T S 3 3 A A AA A AA AAA A AA X XX X X X ...

  • Raypak Y-200 - page 34

    34 Press MODE button to get into program mode. Go to screen number 25 and select the number of slaves you wish to use, 01 thru 04. S L A VE S CON NE CT E D 2 5 #X X Go to screen number 24 and select the number of sensors, relays and auxiliaries. 4 2 R E T S A M SN S : X R E L A Y : X A U X : X 0 2 P U - T E S K R O W T E N M A S T E R PB XX X XX XX ...

  • Raypak Y-200 - page 35

    35 Press MODE button to get into program mode. Go to screen number 25 and display should read. S L A VE S CON NE CT E D 2 5 4 2 X X # E V A L S SN S : 0 R E L A Y : X A U X : X Go to screen number 20 and set up your unit operations. 0 2 P U - T E S T I N U SL A V E P B X X XX X X X X XX Ignore screen number 1 1 on the slave units. Screen number Scr ...

  • Raypak Y-200 - page 36

    36 Y -200 Master/Sla ve Diagr am ...

  • Raypak Y-200 - page 37

    37 Sensor R esistance at V arious T emperatures If a sensor error is suspected, perform the following: 1. Examine the wiring, ensuring continuity from con- troller to sensor(s). 2. Using a multimeter , measure resistance of sen- sor(s) and compare the value with the T able M below . 3. If all okay , replace main control board. T able M: Sensor Resi ...

  • Raypak Y-200 - page 38

    38 Y -200 Illustrated P ar ts List Item No. Description Part No. 1-C PC Board As sy , Y -200 008846F 2-C Expansion Board As sy , 4-Stage 008847F 3-C Auxiliary B oard As sy 008848F 4-C T ransfor mer As sy 008705F 5-C LCD Display Assy 008849F 6-C Control Keypad 008850F 7-C Modem Module 010792 8-C Lon Wo rks Module 010791 9-C 4-20 MA/2-10 VDC Module 0 ...

  • Raypak Y-200 - page 39

    39 L IMITED WARRANTY Y-200 Series SCOPE OF WARRANTY : R aypak, Inc. ("Raypak") warrants to the original owner the C ontrol Sys tem to be free from d ef ects in m ateria ls and workmanship under normal use and service for the a p pl ica ble warr an ty p eri od. In a c cordan ce with the t erms of this L imited W arranty, RAYPAK will furnis ...

  • Raypak Y-200 - page 40

    w w w.ray pak .c o m Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468 Litho in U.S.A. ...

Manufacturer Raypak Category Boiler

Documents that we receive from a manufacturer of a Raypak Y-200 can be divided into several groups. They are, among others:
- Raypak technical drawings
- Y-200 manuals
- Raypak product data sheets
- information booklets
- or energy labels Raypak Y-200
All of them are important, but the most important information from the point of view of use of the device are in the user manual Raypak Y-200.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Raypak Y-200, service manual, brief instructions and user manuals Raypak Y-200. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Raypak Y-200.

Similar manuals

A complete manual for the device Raypak Y-200, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Raypak Y-200 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Raypak Y-200.

A complete Raypak manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Raypak Y-200 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Raypak Y-200, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Raypak Y-200, that we can find in the current document
3. Tips how to use the basic functions of the device Raypak Y-200 - which should help us in our first steps of using Raypak Y-200
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Raypak Y-200
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Raypak Y-200 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Raypak Y-200?

Use the form below

If you did not solve your problem by using a manual Raypak Y-200, ask a question using the form below. If a user had a similar problem with Raypak Y-200 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)