Manual APC PMF3XS-B

24 pages 1.32 mb
Download

Go to site of 24

Summary
  • APC PMF3XS-B - page 1

    Inst allation and Operation Manual APC Brick Panel Product s PMF3XS-B PMJ3XS-B PMP3XS-B PMH3XS-B PMG3XS-B PML3XS-B ...

  • APC PMF3XS-B - page 2

    The Brick Panel Product Surge Protective Devices (SPD) are designed to deliver specification grade performance at the service entrance, branch panels or other critical locations. Th e APC SurgeArrest ® Branch Panel Mount Products have replaceable multi-pha se modules, a display panel w ith surge counter, LED status indicators, and an audible alarm ...

  • APC PMF3XS-B - page 3

    Installation and Operation Ma nual 3 Precautions ........ .............. .............. .............. .............. .............. .............. ... 4 Introduction .. .............. .............. .............. .............. .............. .............. ......... 6 Unpacking and Preliminary I nspection .......................... ............. ...

  • APC PMF3XS-B - page 4

    4 Installation and Operation Manu al Precautions At end-of-life conditions, Surge Protective Devices ( SPDs) can lose their ability to block power system voltage and attemp t to draw excessive current from the line. This SPD is equipped with overcurrent and overtemperature components that will automatically disconnect th e surge suppression element ...

  • APC PMF3XS-B - page 5

    Installation and Operation Ma nual 5 Table 1: SPD Per Phase I 2 tI appar ent I p I th PM_3XS-B 175 kA 2 seconds 17,000 A RMS 40,000 A RMS 220 A CA UTION LOSS OF SURGE SUPPRESSION • Do not energize the SPDs until the electrical system is completely installed, inspected, tested, and all conductors have be en conn ected and functional, including the ...

  • APC PMF3XS-B - page 6

    6 Installation and Operation Manu al Introduction Thank you for choosing the APC SurgeArrest ® PM_3X Series “Brick” Su rge Protective Device. The APC non-modular Surge Protecti ve Device (SPD) is a high-qual ity, high-en ergy surge attenuation system that ha s been designe d to protect sensitive equipment from damaging transient voltage surges ...

  • APC PMF3XS-B - page 7

    Installation and Operation Ma nual 7 D ANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Apply appropriate p ersonal protective equipment (PPE) and foll ow safe electrical wo rk pr act ices. See NFPA 70E. • This equipment must onl y be inst alled and serviced by qualified electrical personnel. • Turn off all power su pplying this equi ...

  • APC PMF3XS-B - page 8

    8 Installation and Operation Manu al Unpacking and Preliminary Inspection Inspect the entire shi pping containe r for damage or sig ns of mishandling before unpacking the device. Remove the packing mate rial and further inspect the device for any obvious shipping damage . If any damage is found and is a result of shipping or handling, immediately f ...

  • APC PMF3XS-B - page 9

    Installation and Operation Ma nual 9 Electrical Voltage Rating Prior to mounting the SPD, verify that th e devi ce has the same voltage rating as the power distribution system in which it is installe d. Compare th e nameplate voltage or model number on the SPD with the namep late of the electrical distribution equipment. The specifier or user of th ...

  • APC PMF3XS-B - page 10

    10 Installation and Operation Manu al Terminals, Wire Size, and Installation Torque Terminals are provided for phase (line), neutral, an d equipment ground connections. The SPD termin als accept a range of 12 AWG (3 mm 2 ) to 2 AWG (34 mm 2 ) copper wire for phase, neutral, and ground conn ectors. Torque connections to the followi ng values. Branch ...

  • APC PMF3XS-B - page 11

    Installation and Operation Ma nual 11 Location of SPD Install Type 2 SPDs on the load side of th e main Overcurrent Protection De vice (OCPD) to comply with NEC Article 28 5 for Type 2 SPDs. Locate the SPD as close as possible to the circuit being ad dressed to minimize the wire length and optimize SPD perfo rmanc e. Avo id long wire runs so th at ...

  • APC PMF3XS-B - page 12

    12 Installation and Operation Manu al Grounding The SPD has leakage current to ground when energized and can present a hazardous touch voltage. The device has SPD elements conne cted from phase to ground. To prevent hazardous touch voltage on the SPD enc losu re during normal operation or during SPD end-of-life , it is critical that there be a robu ...

  • APC PMF3XS-B - page 13

    Installation and Operation Ma nual 13 Installation Conduit Location and Recommendations The recommended conduit entry is at the bottom of the device enclosure. Use a conduit seal that is appropriate for the enclosure rating. Special Enclosure Considerations Removing and Reconnect ing the RJ45 Patch Cables The RJ45 patch cables are marked with match ...

  • APC PMF3XS-B - page 14

    14 Installation and Operation Manu al Wiring Follow the step s listed below when making wi ring connections. 1. Turn off all power supplying this equip ment before working on or i nside any enclosure containing this equipment. 2. Confirm the SPD voltage ra ting and configuration i s the same as th e system voltage and power system co nfiguration to ...

  • APC PMF3XS-B - page 15

    Installation and Operation Ma nual 15 Wiring Diagrams without Integral Switch Figure 3: SIngle-Phase , T hree-Wire, Grou nded Installati on Figure 4: Three-Phase, Three- or Four-Wire, Ground ed Wye Installation Figure 5: Three-Phase, Three- or Four -Wire, High-Leg Delta Installation N 8222-0013-04 SPD A N C Made in U S A / Hecho en E.U.A. / Fabriqu ...

  • APC PMF3XS-B - page 16

    16 Installation and Operation Manu al Operation LED Status Indicators The diagnostic display panel shows the sta tus of the SPD module with diagnostically controlled gree n/red LEDs. If a unit is operating correctly, a ll the phase LEDs will be illumin ated green. To te st the integrity of the diagnostics for each phase, push the button below the p ...

  • APC PMF3XS-B - page 17

    Installation and Operation Ma nual 17 When power is applied to the SPD and one or more of the diagnostic display panel LEDs are red, and one or more modul e LEDs are out, the module sho uld be replaced. Refer to “Maintenance and Tr oubleshooting” on page 19 for prop er troubleshooting procedu res. Audible Alarm Push the alarm enable/disable but ...

  • APC PMF3XS-B - page 18

    18 Installation and Operation Manu al Dry Contacts The SurgeArrest ® series SPDs come standard with dry contacts. The connection for the dry contacts is located on the back of the diagnostic display panel (lower right corner). The dry cont acts are 3-posi tion, Form “C” type with Normally Open, Normally C losed and Common conn ections. In the ...

  • APC PMF3XS-B - page 19

    Installation and Operation Ma nual 19 Maintenance and Troubleshooting Preventive Maintenance Inspect the SPD periodically to main tain reliable system performance and continued transient voltage surge suppression. Periodicall y check the state of the diagnostic displ ay panel LED status ind icators. Routinely use the built-in diagnostics to inspect ...

  • APC PMF3XS-B - page 20

    20 Installation and Operation Manu al Troubleshooting If a module shows two gree n indicator lights and the di splay panel shows a red phase indicator light, follow the Troubl eshooting Flow Chart in Figure 9 below. Replac ement Pa rts The following replacement part s are available. For orderi ng information re fer to the product catalog. • SPD m ...

  • APC PMF3XS-B - page 21

    Installation and Operation Ma nual 21 ...

  • APC PMF3XS-B - page 22

    22 Installation and Operation Manu al ...

  • APC PMF3XS-B - page 23

    Installation and Operation Ma nual 23 ...

  • APC PMF3XS-B - page 24

    APC Worldwide Customer Support Customer support for this or other APC products is available at no charge in the fo llowing ways: • Visit the APC website to access documents in the APC Kn owledge Base and to submit customer support requests. — www.apc.com (Corporate Headquarters) Connect to localized APC Web sites fo r spe cific countries, ea ch ...

Manufacturer APC Category Surge Protector

Documents that we receive from a manufacturer of a APC PMF3XS-B can be divided into several groups. They are, among others:
- APC technical drawings
- PMF3XS-B manuals
- APC product data sheets
- information booklets
- or energy labels APC PMF3XS-B
All of them are important, but the most important information from the point of view of use of the device are in the user manual APC PMF3XS-B.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals APC PMF3XS-B, service manual, brief instructions and user manuals APC PMF3XS-B. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product APC PMF3XS-B.

Similar manuals

A complete manual for the device APC PMF3XS-B, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use APC PMF3XS-B by users. Manuals are usually written by a technical writer, but in a language understandable to all users of APC PMF3XS-B.

A complete APC manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual APC PMF3XS-B - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the APC PMF3XS-B, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the APC PMF3XS-B, that we can find in the current document
3. Tips how to use the basic functions of the device APC PMF3XS-B - which should help us in our first steps of using APC PMF3XS-B
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with APC PMF3XS-B
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of APC PMF3XS-B in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning APC PMF3XS-B?

Use the form below

If you did not solve your problem by using a manual APC PMF3XS-B, ask a question using the form below. If a user had a similar problem with APC PMF3XS-B it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)