  • Campbell Serial I/O Interface SDM-SIO4 - page 1

    SDM-SIO4 4-Channel Serial I/O Interface User Guide Issued 17.3.97 Copyright  1997 Campbell Scientific Ltd. ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 2

    ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 3

    Guarantee This equipment is guaranteed against defects in materials, workmanship, and software. This guarantee applies for twelve months from date of deliv ery. We will repair or replace products which prove to be defective during the guarantee period provided they are returned to us prepaid. The guaran tee will not apply to: • Equipment which ha ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 4

    ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 5

    i Contents Section 1. Introduction ..................................................... 1-1 1.1 What is the SDM-SIO4? .................................................................................1-1 1.2 Specifications .................................................................................................1-3 1.2.1 Serial Ports ....... ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 6

    ii 5.2.6 Command 5: Status ............................................................................. 5-4 5.2.7 Command 6: Flush Transmit Buffer.................................................... 5-5 5.2.8 Command 7: Activate Command Line ................................................ 5-5 5.2.9 Command 8: Poll Tx Buffers for Data ............ ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 7

    1- 1 Section 1. Introduction The SDM-SIO4 has four configurable serial RS232 ports which allow it to be connected to intelligent serial sensors, display boards, printers or satellite links. It can also be used in many other applications where the data is transferred in a serial fashion. This device is designed to send data to and receive data from ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 8

    SDM-SIO4 4-Channel Serial I/O Interface User G uide 1-2 Switches - Go to 1 if command line active To Other Ports To Other Ports 1 PORT Handshak e Control Tx Buffe r Rx B uffer Command Line Control Datalogge r Command Control CRC/SIG Driver Format Driver & User Strings CRC/SIG Driver Filter Driver Converted Data Buffer 1 0 0 K K K Handshake Line ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 9

    Section 1 . Introduction 1- 3 1.2 Specifications 1.2.1 Serial Ports The SDM-SIO4 has four serial ports which can be configured independently to use different serial data formats and baud rates (from 25 to 115,200 baud). These ports are 0-5V logic or ±5V for RS232 and are configured similar to a PC ‘AT’ style DTE serial port. Handshaking, to co ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 10

    SDM-SIO4 4-Channel Serial I/O Interface User Guide 1- 4 1.2.2 SDM Port This serial port is to connect to the SDM port of the datalogger, e.g. via C1, C2 and C3 on a CR10X. The port is a set of screw terminals marked C1, C2, C3, I/O, +12 and G. C3 is the Synchronous Device Enable line, C1 is the Data line, C2 is the Clock line and I/O is a special-p ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 11

    Section 1 . Introduction 1- 5 1.2.6 Other Key Features • An internal lithium battery which retains configuration information (estimated life 10 years) • A built-in system watchdog which will reset the processor in the event of a crash caused by transients, etc. • A multi-tasking operating system allowing concurrent transmission and receipt of ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 12

    ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 13

    2- 1 Section 2. Installation and Hardware Set-Up The SDM - SIO4 is designed to be mounted on an enclosure chassis plate using the two mounting holes in the tabs on the side of the case . Before installation, it is necessary to set up the address of the SDM-SIO4 and also the mode of operation of each serial port. These settings are determined by jum ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 14

    SDM-SIO4 User Guide 2- 2 2.2 Selecting RS232 or 5V Logic for Each Port The output voltage levels of each serial port can be set to either: • Logic level output: +5V (high) / 0V (low) or • RS232 output: +5V (high) / -5V (low) (compatible with RS232 driver requirements). The logic level output is used when driving a logic level compatible device, ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 15

    Section 2. Installation and Hardware Set-Up 2- 3 • Electrical noise causing possible loss or corruption of serial data. • Electrical noise being transferred back to the datalogger causing errors on analogue measurements. • Long term damage in the form of corrosion caused by current flowing along electro-chemical gradients. If it is not possib ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 16

    ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 17

    3-1 Section 3. Understanding How the SDM-SIO4 Handles Data For simple applications the SDM-SIO4 can be configured and controlled from the datalogger alone, using the datalogger program instruction P113 (CR10X and CR7 dataloggers only). Future developments will include support for other dataloggers. More complicated applications require configuratio ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 18

    SDM-SIO4 User Guide 3-2 The hex. number must always be t wo ASCII characters. Control characters can be entered for all commands in a similar way: • ^M is carriage return, ^J line feed etc. • ^^ means ^ • "" means " • ]] means ] • && means & • &0d means line feed • &hex,hex used to enter 2-character ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 19

    Section 3. Understanding How the SDM- SIO4 Handles Data 3-3 See Section 5 – ‘P rogramming the Datalogger’. Filter Strings These are used to defin e how to filter incoming data from a port into a format the datalogger can use. This is done by having a user-defined filter s tring pre-stored in the battery-backed memory of the SDM-SIO4. These st ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 20

    SDM-SIO4 User Guide 3-4 • i[ ] Scan until any ASCII ch aracters entered between the brack ets are encountered. The maximum number of characters bet ween the brackets is 255. Note that this filter does n ot remove the matche d character from the buffer. • n n Discard ‘n’ bytes . ‘n’ can be in the range of 0-255. • N n Read ‘n’ byte ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 21

    Section 3. Understanding How the SDM- SIO4 Handles Data 3-5 2. n8 discards everyt hing up to 12.65V. 3. F converts the number t o Campbell Scient ific floating poi nt. If a valid number is not found -99999 is sent to t he datalogger. 4. i[c] waits for the trigger character ‘c’ of ‘current’. 5. n8 discards everyt hing up to 12mA. 6. F conver ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 22

    SDM-SIO4 User Guide 3-6 • Convert a locati on sent into a 16-bit bi nary word. If this option is selected an extra ASCII character/delimiter can be added to the end of the 16-bit word sent. See Section 5 – ‘P rogramming the Datalogger’. 3.3.2 Output Format Strings These allow either j ust long strings to be sent from the SD M-SIO4 or a comb ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 23

    Section 3. Understanding How the SDM- SIO4 Handles Data 3-7 Table 4 Fixed Strings Currently Allocated String number String (enclo sed in quotes) 256 ‘+0000000000123.45670000000000CrLf’ 257 ‘Voltage’ 258 ‘Amps’ 259 ‘Watts ’ 260 ‘Joules’ 261 ‘Temperature’ 262 ‘Pressure’ 263 ‘Speed’ 264 ‘Power’ 265 ‘Depth’ 266 ? ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 24

    SDM-SIO4 User Guide 3-8 z273 – This outputs the fixed string ‘C rLf (carriage return line feed)’. *Table 1 Program 01: 2 Execution Interval (seconds) ;get battery voltag e. 1: Batt Voltage (P10) 1: 2 Loc [ Batt_v ] ;get panel temperat ure. 2: Internal Temperature (P17) 1: 1 Loc [ Temp_C ] ;send batter y voltage and temper ature to port 2 on t ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 25

    4-1 Section 4. Programming the SDM-SIO4 This section gives both the basic commands and advanced command line options which allow testing and advanced configuration of the SDM-SIO4. 4.1 Command Line Operation and Structure To use the command line mode, connect a computer to port 1 of the SDM-SIO4. The computer should run a termi nal emulation progra ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 26

    SDM-SIO4 User Guide 4- 2 Control characters can be entered for all commands in a similar way: • ^M is carriage return, ^J line feed etc. • ^^ means ^ • "" means " • ]] means ] • && means & • &0d means line feed • &hex,hex used to enter 2-character hex. codes (0-9, A-F) 4.3 Basic Commands fltst [strin ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 27

    Section 4. Programming the SDM- SIO4 4-3 because they are compiled. exit This command exits the command lin e and returns port 1 of the SDM-SIO4 to normal operation. 4.4 Advanced Commands version This returns t he internal EPROM part number, signature and the stri ng signature if good or 0 if bad. This will give the same signature as Campbell Scien ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 28

    SDM-SIO4 User Guide 4- 4 WD n WDERR n WDADDR n WD n is a count of the number of watchdog resets, W DERR is the number of the last task that crashed and WDADDR is the address at which the crash was found. NC 0-9 This is t he number of SDM commands the datalogger s ent to the SDM-SIO4 t hat the SDM-SIO4 did not recognise. This counter may be i ncreme ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 29

    Section 4. Programming the SDM- SIO4 4-5 testio [test#] This is used by Camp bell Scientific for test purpo ses. Each test command is carried out for 2 seconds. Tes t# can be in the range 0-255; only five test numbers are currently valid, as s hown below. testio returns test 0 DTR,RTS,IO =LOW test1 DTR=HIGH,RTS,IO=LOW test2 DTR=LOW,RTS=HIGH,IO=LOW ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 30

    ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 31

    5-1 Section 5. Programming the Datalogger The datalogger instruction specific to the SDM-SIO4 is P113 (CR7 and C R10/10X only). (Please check with Campbell Scientific to see if your version of the operating system supports this.) The instruction has the following format: Parameter No. Description 01 Reps (number of adjacent addressed SDM-SIO4s) 02 ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 32

    SDM-SIO4 User Guide 5-2 5.1.5 Parameter 7 — Values per Rep This determines how many values to send or receive, starting from the specified input location (paramet er 8). Data can be either 4-byte floati ng point values or single bytes , determined by the SDM-SIO4 command number. Some commands require no input or out put of values; for thes e comm ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 33

    Section 5. Programming the Datalogger 5-3 5.2.1 Understandi ng Parameter Options and Retur ned Val ues In the following examples, ‘ x ’ indicates a s ingle digit from 0 t o 9. When the command requires or returns values, each digit, or combination of digits, can s ignify either a value, flag or s etting. Using Command 5 as an exampl e: Number o ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 34

    SDM-SIO4 User Guide 5-4 5.2.3 Command 2: Signatures This command gets the SDM-SIO4 EPROM signature and the string memory area signature; the two values are written into consecutive input locations . If the signatures are zero t hen there could be corrupt data. Values per repetition = 2 5.2.4 Command 3: Flush all Receive Buffers Stored data in th e ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 35

    Section 5. Programming the Datalogger 5-5 If any of these four digits is greater than zero then data is available. Values per repetition = 2 5.2.7 Command 6: Flush Transmit Buffer This command flushes the SDM-SIO4 transmit bu ffer of data it is waiting to send . Values per repetition = 0 5.2.8 Command 7: Activate Command Line This command si mulate ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 36

    SDM-SIO4 User Guide 5-6 5.2.12 Command 67: Get Return Code This command gets the return error code and places it into a specified location. Command 67 is us ed in conjunction wit h command 321 and provides a singl e return code value which indicates if the command was success ful or not. See Secti on 5.6 for the return codes. Values per repetition ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 37

    Section 5. Programming the Datalogger 5-7 P65 Bulk load 1:102 f 2:108 l 3:116 t 4:115 s 5:116 t 6:32 ascii space 7:50 2 8:53 5 9:1 First location to store the first lot of 8 characters. P65 Bulk load 1:32 ascii space 2:34 “ 3:102 f 4:102 f 5:67 C 6:99 c 7:34 “ 8:0 9:9 First location to store second lot of characters. ;execute the command line s ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 38

    SDM-SIO4 User Guide 5-8 ;set flag one so that set-up will only be done once. P86 11 ;end of set-up. P95 If you use the RAMTEST command you will have to wait a minimum of 6 s econds for it to compl ete before you try to execute another P113. Some Dataloggers do not support P65 Bulk Load. In that case you would have to use a P30 Instruction for each ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 39

    Section 5. Programming the Datalogger 5-9 Second Value Returned CTS status (0=CTS low, 1=CTS high) | DSR status (0=DSR low, 1=DSR high) | | RI status (see below) | | | DCD status (0=DCD low, 1=DCD high) | | | | x x x x For the RI (Ring Indicator): 0 = no trailing edge seen since last read 1 = trailing edge seen since last read Third Value Returned ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 40

    SDM-SIO4 User Guide 5-10 Break reset: 0 Do nothing 1 Reset line break count to zero Framing reset: 0 Do nothing 1 Reset framing error count to zero Overrun reset: 0 Do nothing 1 Reset overrun error count to zero Parity reset: 0 Do nothing 1 Reset parity error count t o zero 5.2.18 Command 1027: ‘Manual ’ Handshake Mode In this mode, the datalog ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 41

    Section 5. Programming the Datalogger 5-11 First Command Option (Paramet er 5) Handshake mode | Stop bits + parity | | Data length | | | Baud rate | | | | x x x x Handshake Mode: 0 Leave as set previously 1 DTR always set, set RTS when data is availab le to transmit, only transm it if CTS is set 2 DTR always set, RTS always set, o nly transmit if C ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 42

    SDM-SIO4 User Guide 5-12 5.2.20 Command 2054: Set Up Receive Filter This command clears al l buffers relevant to t he mode number and restarts the filter. Values per repetition = 0 With the string filter typ e the SDM-SIO4 buffers are not cleared. First Command Option (Paramet er 5) Input mode | String number or character code | | | | x x x x Input ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 43

    Section 5. Programming the Datalogger 5-13 Output Mode: 0 No output format st ring 1 Convert location t o ASCII floating poi nt. Add character/delimit er between values if enabled. The last value will not have a d elimiter after it. 2 Convert location t o ASCII hex pair. Add character/del imiter between values if enabled. The last v alue will not h ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 44

    SDM-SIO4 User Guide 5-14 5.2.22 Command 2305: Transmit Byte(s) By using P 113 command 2305 it is pos sible to tr ansmit either one or t wo bytes from the command options. If any command opt ion is se t to 999 then the byte wi ll not be sent. The number range for each command option is 0-255 and 999. An example of its use is below: 1:SDM-SIO4 (P113) ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 45

    Section 5. Programming the Datalogger 5-15 ;set ser ial mode to DTR, RTS alw ays set, ignor e CTS, 1 stop bi t no parity, ;8 bit data le ngth, 9600 baud and no handshake delay. 2: SDM-SIO4 (P113) 1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 2049 Command 5: 3146 1st Parameters 6: 0 2nd Parameters 7: 0 Values per Rep 8: 0000 Loc [ _________ ] 9 ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 46

    SDM-SIO4 User Guide 5-16 *Table 2 Program 02: 0.0000 Execution Interval (seconds) *Table 3 Subroutines End Program The normal configuration would i nclude setting t he speed and serial data format by calling the dat alogger instruct ion with command 2049 and the relevant parameters. For the majority of se nsor applications where data is returned in ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 47

    Section 5. Programming the Datalogger 5-17 ^J^M – this is a way of entering control characters fo r carriage return/linefeed into a string The following program example works as follows: 1. The first P113 sets up a s imple filter to search for floating point numbers. 2. The first parameter of this co mmand is used to tran smit a string which will ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 48

    SDM-SIO4 User Guide 5-18 ;get data from SDM -SIO4 and put into locat ions 1 and 2. 3: SDM-SIO4 (P113) 1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 4 Command 5: 0 1st Parameters 6: 0 2nd Parameters 7: 2 Values per Rep 8: 1 Loc [ number ] 9: 1.0 Mult 10: 0.0 Offset ;At zero minut es into a 10 minute inte rval set t he output ;so that the d ata ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 49

    Section 5. Programming the Datalogger 5-19 Example CR10X Program without Polling or Interrupts This simpl e program is an example for sens ors that send data at random intervals. If no data was available when the datalogger asked for it then -99999 will be put into locations 1 and 2. An IF THEN structure could be us ed in the datalogger program to ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 50

    SDM-SIO4 User Guide 5-20 ;end of set up. 5: End (P95) ;get the two fl oating point values from the SDM-SIO4. 6: SDM-SIO4 (P113) 1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 4 Command 5: 0 1st Parameters 6: 0 2nd Parameters 7: 2 Values per Rep 8: 1 Loc [ Voltage ] 9: 1.0 Mult 10: 0.0 Offset ;Only set the out put flag when the volt age is ;grea ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 51

    Section 5. Programming the Datalogger 5-21 x – this filter marks the start o f the data set. In this case the da ta set is two floating point numbers. f – this filter searches for the first ASC II floating point number to convert. f – this filter searches for the second ASC II floating point number to convert. *Table 1 Program 01: 2 Execution ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 52

    SDM-SIO4 User Guide 5-22 ;if value returned from poll is >=1 then data must be a vailable. 7: IF (X<=>F) (P89) 1: 2 X Loc [ poll ] 2: 3 >= 3: 1 F 4: 30 Then Do ;get voltages i nto locations 3 and 4 if poll was true. 8: SDM-SIO4 (P113) 1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 4 Command 5: 0 1st Parameters 6: 0 2nd Parameters 7: ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 53

    Section 5. Programming the Datalogger 5-23 – see ‘SDM Port’ i n Section 1 for details . This should be connected t o control port 8 for this example. A typical filter that could b e used is as follows: fltst 200 "t[d ata]A5xff" This filter works as follows: t[data] – this filter waits for an exact string match before it starts the ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 54

    SDM-SIO4 User Guide 5-24 ;end of IF 6: End (P95) *Table 2 Program 02: 0.0000 Execution Interval (seconds) *Table 3 Subroutines ;interr upt routine for control port 8 1: Beginning of Subroutine (P85) 1: 98 Subroutine 98 ;get voltages i nto locations 3 and 4 2: SDM-SIO4 (P113) 1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 4 Command 5: 0 1st Para ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 55

    Section 5. Programming the Datalogger 5-25 5.4 Outputting Datalogger Data The SDM-SIO4 can be used t o drive displays, printout devices and other output- only systems. In this cas e after the initial configuration (as above) either simple data can be sent us ing commands 0320, 1025 or jus t data stri ngs using 1024 or strings plus formatted dat a s ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 56

    SDM-SIO4 User Guide 5-26 *Table 2 Program 02: 0.0000 Execution Interval (seconds) *Table 3 Subroutines End Program 5.5 Flushing the Input and Output Buffers One importan t aspect of the SDM-SIO4 is that it will contin ue to collect data and store it i n its buffers even if the dat alogger program stops running. C are must be taken to ensure that da ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 57

    6-1 Section 6. Data Error Detection Error detection by checksum, CRC or signatures is a way of detecting errors in data, either transmitted or received. This section gives details on how to use filter strings together w ith datalogger program examples to implem ent error detection methods. 6.1 Error Detection with the SDM-SIO4 Error detection is ca ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 58

    SDM-SIO4 User Guide 6-2 3 CRC16-CCITT-IB M (Tag Receiver). 4 CRC32 st andard. Polynomial x 32 +x 26 +x 23 +x 22 +x 16 +x 12 +x 11 +x 10 +x 8 +x 7 +x 5 +x 4 +x 2 +x+1. 5 CSI Signature (see Appendi x C of the CR10X Manual ). 6 Checksum using modul o 256. 7 Checksum using modulo 8192 (S ee Section 5 of the C R10X Manual). 8-255 For future use. Gn This ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 59

    Section 6. Data Error Detection 6-3 6.2.1 Example of Using Received Data Filters If a sensor transmitted th e following string: Frequency=12.34567HzBB3DCrLf then a user defined filter string would have to be used. The BB3D part of the string is the CRC sent in hex. from the sensor. To produce a filter string to deal with the se nsor output you coul ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 60

    SDM-SIO4 User Guide 6-4 *Table 1 Program 01: 1.0 Execution Interval (seconds) ;test flag 1 – if n ot set tell the SDM-SIO4 to use filter string 100 1: If Flag/Port (P91) 1: 21 Do if Flag 1 is Low 2: 30 Then Do ;tell the SDM-SIO4 to use filter string 100 2: SDM-SIO4 (P113) 1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 2054 Command 5: 9100 1st ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 61

    Section 6. Data Error Detection 6-5 ;if the value in locat ion 1 is greater than zero then ther e must be data ;this ass umes only one sensor is connected to the SDM-SIO4 7: IF (X<=>F) (P89) 1: 1 X Loc [ _________ ] 2: 3 >= 3: 1 F 4: 30 Then Do ;if data is available then get the value and put into locat ion 2 8: SDM-SIO4 (P113) 1: 1 Reps 2 ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 62

    SDM-SIO4 User Guide 6-6 1,2 CRC 16 and CRC16-C CITT 0.159ms/char. 3 CRC 16-CCITT-IBM 0.159ms/char. 4 CRC32 0.369ms/ char. 5 CSI Signature 0.077ms/char. 6 Checksum using modulo 256 0.066ms/char. 7 Checksum using modulo 8192 0.071ms/char. c The time for the differen t data types is shown belo w. Note that this is the time needed to convert the receiv ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 63

    Section 6. Data Error Detection 6-7 5 CSI Signature (CR 10X user manual secti on C-4). 6 Check sum using modulo 256. 7 Check sum using modulo 8192 (C R10X user manual s ection 5-2). 8-255 reserved for future use. Gn This formatter type can b e put into the formatter string to m ark the end of the string and the point at which the signature should b ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 64

    SDM-SIO4 User Guide 6-8 6.3.2 CR10X Program Example A typical CR 10X datalogger program to work with the above format ter is shown below. The program assumes that the SDM-SIO4 is set to address 0, the sensor is connected to port 1 of the SDM-S IO4 and the port setti ngs, baud rate etc have been set. The output from t he SDM-SIO4 is every s econd: * ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 65

    Section 6. Data Error Detection 6-9 *Table 1 Program 01: 1.0 Execution Interval (seconds) ;use form atter st ring 100 to se t up the CRC16 on por t 1 1: SDM-SIO4 (P113) 1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 2304 Command 5: 9100 1st Parameters 6: 0 2nd Parameters 7: 0 Values per Rep 8: 0000 Loc [ _________ ] 9: 1 Mult 10: 0 Offset ;A mi ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 66

    SDM-SIO4 User Guide 6-10 ;use for matter string 102 and out put datalogger location 1 as ASC II floati ng point ;to port 1 and then out put the calculat ed ASCII hex CRC16 6: SDM-SIO4 (P113) 1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 2304 Command 5: 9102 1st Parameters 6: 0 2nd Parameters 7: 1 Values per Rep 8: 0000 Loc [ _________ ] 9: 1 M ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 67

    Section 6. Data Error Detection 6-11 1 8 bit binary 0.155ms 2,3 16 bi t binary 0.216ms 4,5 32 bi t binary 0.334ms 6 ASCII decimal 1.125ms 7 8 bit ASCII hex 0.226ms 8 16 bit ASCII hex 0.355ms 9 32 bit ASCII hex 0.613ms The above timings are preli minary. d With the C RC32 and CRC 16-CCITT there is a extra 0.19ms for an additional calculatio n. This ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 68

    ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 69

    A- 1 Appendix A. ASCII Table American Standard Code for Information Interchange Decimal Values and Characters (X3.4-1968) Dec. Char. Dec. Char. Dec. Char. Dec. Char. 0 CONTROL @ 32 SPACE 64 @ 96 ` 1 CONTROL A 33 ! 65 A 97 a 2 CONTROL B 34 " 66 B 98 b 3 CONTROL C 35 # 67 C 99 c 4 CONTROL D 36 $ 68 D 100 d 5 CONTROL E 37 % 69 E 101 e 6 CONTROL F ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 70

    ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 71

    B- 1 Appendix B. Serial Port Data Transfer Modes This appendix describes the serial port set-up in some detail. Please note that the numerical option codes vary between the command line set-up and the datalogger command set-up. The ones listed below are those for the command line mode. B.1 Baud rates The SDM-SIO4 ports can support 16 baud rates if ...

  • Campbell Serial I/O Interface SDM-SIO4 - page 72

    SDM-SIO4 4-Channel Serial I/O Interface B- 2 B.4 Parity Bits Parity can be enabled and set to either odd or even. 0. No parity set 1. Odd parity set 2. Even parity set B.5 Serial Handshake Modes You can select different kinds of handshaking from none at all, hardware (DTR, CTS etc.) and XON/XOFF. On modes 0 and 1 there is a user-set delay (0..254 x ...

Manufacturer Campbell Category Network Card

Documents that we receive from a manufacturer of a Campbell Serial I/O Interface SDM-SIO4 can be divided into several groups. They are, among others:
- Campbell technical drawings
- Serial I/O Interface SDM-SIO4 manuals
- Campbell product data sheets
- information booklets
- or energy labels Campbell Serial I/O Interface SDM-SIO4
All of them are important, but the most important information from the point of view of use of the device are in the user manual Campbell Serial I/O Interface SDM-SIO4.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Campbell Serial I/O Interface SDM-SIO4, service manual, brief instructions and user manuals Campbell Serial I/O Interface SDM-SIO4. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Campbell Serial I/O Interface SDM-SIO4.

A complete manual for the device Campbell Serial I/O Interface SDM-SIO4, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Campbell Serial I/O Interface SDM-SIO4 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Campbell Serial I/O Interface SDM-SIO4.

A complete Campbell manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Campbell Serial I/O Interface SDM-SIO4 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Campbell Serial I/O Interface SDM-SIO4, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Campbell Serial I/O Interface SDM-SIO4, that we can find in the current document
3. Tips how to use the basic functions of the device Campbell Serial I/O Interface SDM-SIO4 - which should help us in our first steps of using Campbell Serial I/O Interface SDM-SIO4
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Campbell Serial I/O Interface SDM-SIO4
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Campbell Serial I/O Interface SDM-SIO4 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Campbell Serial I/O Interface SDM-SIO4?

Use the form below

If you did not solve your problem by using a manual Campbell Serial I/O Interface SDM-SIO4, ask a question using the form below. If a user had a similar problem with Campbell Serial I/O Interface SDM-SIO4 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)