Summary
  • SPX Cooling Technologies SS-NC-08A - page 1

    / Mar le y NC Class Stainless Crossflow Cooling T ower / Pr od uct S pec ifica tio ns ...

  • SPX Cooling Technologies SS-NC-08A - page 2

    Specifications / Base Base 4 Thermal P erformance 4 P erformance W arranty 5 Design Loading 5 Construction 6 Mec hanical Equipment 7 Fill, Louvers and Drift Eliminator s 8 Hot W ater Distribution System 9 Casing, F an Dec k and Fan Cylinder 9 Access 1 0 Cold W ater Collection Basin 1 0 Specifications / Options Conv enience and Saf ety Options Guard ...

  • SPX Cooling Technologies SS-NC-08A - page 3

    Mar ley / NC Class Stainless Cooling T ower / 3 NC Class Stainless Steel towers are factory assembled, crossflo w cooling tow ers, designed to ser ve air conditioning and refrigeration systems as well as light to medium industrial process loads on clean water . The y ev olve from a factor y-assembled concept of to wers pioneered by Marle y some 50 ...

  • SPX Cooling Technologies SS-NC-08A - page 4

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Base 4 1.0 Base: 1.1 Pro vide an induced draf t, crossflow type, factory assembled, film fill, industrial dut y , st ainless steel cooling tow er situated as shown on the plans. The limiting ov erall dimensions of the tower shall be _____ wide, _____ l ...

  • SPX Cooling Technologies SS-NC-08A - page 5

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Base 5 2.0 Ther mal P erfor mance and Efficiency: 2.1 The tow er shall be capable of cooling _____ m 3 /h of water from ____ °C to _____ °C at a design entering air wet- bulb temperature of _____ C and its thermal rating shall be Certified by the Coo ...

  • SPX Cooling Technologies SS-NC-08A - page 6

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Base 6 designed for 2.4kP a live load or a 91kg concentrated load. Guardrails, where specified, shall be capable of with- standing a 890N concentrated live load in any direction, and shall be designed in accordance with OSHA guidelines. 5.0 Constr ucti ...

  • SPX Cooling Technologies SS-NC-08A - page 7

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Base 7 5.3* The tow er shall include all design and material modifications necessar y to meet the fire rating requirements of Factory Mutual. The product proposed shall be listed in the FM Approval Guide, latest edition. *Standard on models NC8301 thru ...

  • SPX Cooling Technologies SS-NC-08A - page 8

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Base 8 LOUVER S DRIFT ELIMINA T OR separ ate from fill on some models FILL 7.0 Fill, Louvers and Dr ift Eliminators: 7.1 Fill shall be film t ype, thermof ormed of 0.40mm thic k PV C, with louvers formed as part of eac h fill sheet. Fill shall be susp ...

  • SPX Cooling Technologies SS-NC-08A - page 9

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Base 9 8.0 Hot W ater Distribution Syst em: 8.1 T wo st ainless steel open basins (one abov e eac h bank of fill) shall receive hot water piped to eac h cell of the tow er . These basins shall be inst alled and sealed at the factor y , and shall be equ ...

  • SPX Cooling Technologies SS-NC-08A - page 10

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Base 10 10.0 Access: 10.1 A large st ainless steel, rectangular access door shall be located on both end panels for entr y into the cold water basin. Doors shall provide access to the fan plenum area to facili- tate inspection and allow maintenance to ...

  • SPX Cooling Technologies SS-NC-08A - page 11

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Options 11 Conv enience and Saf ety Options Guardr ail and Ladder: 11.2 Add the following paragraph in the Access section: The top of the tow er shall be equipped with a sturdy guardrail, complete with kneerail and toeboard, designed according to OSHA ...

  • SPX Cooling Technologies SS-NC-08A - page 12

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Options 12 ACCESS DOOR PLA TFORM GU ARDRAIL LADDER LADDER EXTENSION ...

  • SPX Cooling Technologies SS-NC-08A - page 13

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Options 13 Access Door Platfor m: 11.2 Add the following paragraph in the Access section: There shall be an access platform at the base of the tow er extending from the vertical lad- der to the endwall access door . The platform shall be galvanized ste ...

  • SPX Cooling Technologies SS-NC-08A - page 14

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Options 14 Control Options Fan Motor Starter Control Panel: 6.4 Add the following paragraph in the Mechanical Equipment sec- tion: Each cell of the cooling to wer shall be equipped with a UL listed control system in a IP1 4 or IP56 out- door enclosure ...

  • SPX Cooling Technologies SS-NC-08A - page 15

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Options 15 Vibr ation Limit Switc h: 6.5 Add the following paragraph in the Mec hanical Equipment section: A single-pole, double-throw vibration limit switch in a IP56 housing shall be installed on the mec hanical equipment support for wiring into the ...

  • SPX Cooling Technologies SS-NC-08A - page 16

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Options 16 in quantities and locations as indicated on the drawings. An overflo w and drain connection shall be provided in eac h cell of the cooling tower . The basin floor shall slope tow ard the drain to allow complete flush out of debris and silt w ...

  • SPX Cooling Technologies SS-NC-08A - page 17

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Options 17 cold-water temperature. The application must be able to handle ver y cold water while VFD is in a by -pass mode. Operator controls shall be mounted on the front of the enclosure and shall consist of start and stop control, bypass/VFD selecti ...

  • SPX Cooling Technologies SS-NC-08A - page 18

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Options 18 shall be operated as a st and- alone sys- tem without the need for a BMS system. Operator controls shall be mounted on the front of the enclosure and shall consist of st art and stop control, bypass/ VFD selector switc h, Auto/Manual selecto ...

  • SPX Cooling Technologies SS-NC-08A - page 19

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Options 19 Inlet Flow Contr ol V alves: 8.2 : Add the following to the end of the paragraph: Heavy-duty flow -regulator valv es shall be provided at the hot water inlet connections. These valv es shall be disc-t ype, with cast iron bodies and st ainles ...

  • SPX Cooling Technologies SS-NC-08A - page 20

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Options 20 box whic h is self supporting . The inlet at tenuation will not be allow ed to impact the thermal performance ef fi- ciency of the basic tower configuration. Outlet Sound At tenuation 1.4 Add the following paragraph under Base: The cooling t ...

  • SPX Cooling Technologies SS-NC-08A - page 21

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Options 21 Ultra Low-Noise F an 1.4 Replace paragraph 6.1 with the fol- lowing: Fan(s) shall be propeller -type, incorporating wide-chord for ward- swept FRP blades and galvaniz ed hubs. Blades shall be individually adjustable. Maximum f an tip speed s ...

  • SPX Cooling Technologies SS-NC-08A - page 22

    Specifications Specification V alue Mar ley / NC Class Stainless Cooling T ower / Specifications: Options 22 ______ psf, as well as a ______ seismic load. The fan dec k and hot water basin cov ers shall be designed for 50 psf live load or a 200 lb. concentrated load. Guardrails, where specified, shall be capable of withst anding a 200 lb. con- cent ...

  • SPX Cooling Technologies SS-NC-08A - page 23

    ...

  • SPX Cooling Technologies SS-NC-08A - page 24

    In the interest of techno logical progr ess, all products are subject to design and/or material change without notice. ©2008 SPX Cooling T echnologies uk_SP EC- S S-N C -08A SPX C OO LIN G TEC H NO L O G I ES U K L TD. G R EGO RY’S BAN K WOR CESTE R WR3 8AB U N ITE D K I NG DO M +44 (0) 1905 7 20 200 info.uk@spx.com spxcooling.com ...

Manufacturer SPX Cooling Technologies Category Humidifier

Documents that we receive from a manufacturer of a SPX Cooling Technologies SS-NC-08A can be divided into several groups. They are, among others:
- SPX Cooling Technologies technical drawings
- SS-NC-08A manuals
- SPX Cooling Technologies product data sheets
- information booklets
- or energy labels SPX Cooling Technologies SS-NC-08A
All of them are important, but the most important information from the point of view of use of the device are in the user manual SPX Cooling Technologies SS-NC-08A.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals SPX Cooling Technologies SS-NC-08A, service manual, brief instructions and user manuals SPX Cooling Technologies SS-NC-08A. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product SPX Cooling Technologies SS-NC-08A.

A complete manual for the device SPX Cooling Technologies SS-NC-08A, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use SPX Cooling Technologies SS-NC-08A by users. Manuals are usually written by a technical writer, but in a language understandable to all users of SPX Cooling Technologies SS-NC-08A.

A complete SPX Cooling Technologies manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual SPX Cooling Technologies SS-NC-08A - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the SPX Cooling Technologies SS-NC-08A, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the SPX Cooling Technologies SS-NC-08A, that we can find in the current document
3. Tips how to use the basic functions of the device SPX Cooling Technologies SS-NC-08A - which should help us in our first steps of using SPX Cooling Technologies SS-NC-08A
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with SPX Cooling Technologies SS-NC-08A
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of SPX Cooling Technologies SS-NC-08A in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning SPX Cooling Technologies SS-NC-08A?

Use the form below

If you did not solve your problem by using a manual SPX Cooling Technologies SS-NC-08A, ask a question using the form below. If a user had a similar problem with SPX Cooling Technologies SS-NC-08A it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)