Manual Eaton 34003991EN/EB

118 pages 2.98 mb
Download

Go to site of 118

Summary
  • Eaton 34003991EN/EB - page 1

    www.eaton.com Net w ork Management Card User manual Network Management Ca rd – User Manual 34003991EN/EB Page 1/118 ...

  • Eaton 34003991EN/EB - page 2

    Network Management Ca rd – User Manual 34003991EN/EB Page 2/118 Contents 1 EATON NET WORK SOLUTION 5 1.1 G ENERAL P RESENTATION 5 1.1.1 Connecting the U PS to the Ethernet net work 6 1.1.2 Protection of the co mputers/servers 6 1.1.3 Supervision of the UP Ss over the network 7 1.1.4 Connection 7 1.2 P RESENTATION OF THE N ETWORK M ANAGEMENT C ARD ...

  • Eaton 34003991EN/EB - page 3

    Network Management Ca rd – User Manual 34003991EN/EB Page 3/118 4.3.1 Email Notification 43 4.3.2 E-mail Message Set tings 45 4.4 C ONFIGURATION 47 4.4.1 Network settings 48 4.4.2 System 50 4.4.3 Notified Applications 52 4.4.4 Central shutdo wn configuration 54 4.4.5 A ccess control 55 4.4.6 Date and time 57 4.4.7 Firmware upload 59 4.5 E NVIRONM ...

  • Eaton 34003991EN/EB - page 4

    Network Management Ca rd – User Manual 34003991EN/EB Page 4/118 7.4 JBUS TABLE 91 7.4.1 Data for Pulsar 700 / 1000 / 1500 91 7.4.2 Data for Pulsar M 2200 / 3000 93 7.4.3 Data for Pulsar MX 4000 / 5000 / 1 0000 and EX 5 / 7 / 11 RT 95 7.4.4 Data for Pulsar MX frame 15 / 20 97 7.4.5 Sensor data 102 7.4.6 Other data 105 8 APPENDICES 106 8.1 T ABLES ...

  • Eaton 34003991EN/EB - page 5

    Network Management Ca rd – User Manual 34003991EN/EB Page 5/118 1 EATON Netw o rk Solution 1.1 General Presentation EATON Network Solution : - Provides informat ion on events concerning the supply of power to the c omputers connec ted to y our computer network, - Carries out auto matic shutdown of comp uter sy stems, - Monitors and cont rols all ...

  • Eaton 34003991EN/EB - page 6

    Network Management Ca rd – User Manual 34003991EN/EB Page 6/118 1.1.1 Connecting the UPS to the Ethernet network This function can be performed t hrough network Cards inserted in the U PS (Network Management Card). A lso a software "agent" running on a nearby PC that is called the Network Management Proxy can be used. The Network Manage ...

  • Eaton 34003991EN/EB - page 7

    Network Management Ca rd – User Manual 34003991EN/EB Page 7/118 1.1.3 Supervision of the UPSs over the netw ork Depending on y our needs, y ou can either use: Your Internet browser to monitor eac h UPS, as Manage ment Proxy and Management Card inc ludes a Web server Your company ’s standard Network Management Sy stem (HP-Openview, CA Unicenter, ...

  • Eaton 34003991EN/EB - page 8

    Network Management Ca rd – User Manual 34003991EN/EB Page 8/118 1.1.4.1 How to connect UPS / agent / network: Insert the optional card in the UPS and connect the UP S to the computer network. Start the UPS, then the computers. 1.1.4.2 Setting up the protec tion: Set up the Network Management Card (se e user manual). Install and configure the prot ...

  • Eaton 34003991EN/EB - page 9

    Network Management Ca rd – User Manual 34003991EN/EB Page 9/118 Network Management Ca rds are com patible with the "Enterprise Power Management" supervisi on syst em, with the MGE Office Protect ion Syste ms network protection sy stem and with Po werware Netwatch. Network Shutdo wn Module Enterprise Po wer Manager Management-Pac 2 1.2.2 ...

  • Eaton 34003991EN/EB - page 10

    Network Management Ca rd – User Manual 34003991EN/EB Page 10/118 1.3 Technical data 1.3.1 Hardware characteristics Dimensions Dimensions (L x l x H) 132 x 66 x 42 mm Weight (gr) 70 g Storage Storage temperature -10 ° C to 70 ° C A mbient conditions Operating temperature 0 ° C to 40 ° C A mbient humidit y 90 % RH max without co ndensation ROHS ...

  • Eaton 34003991EN/EB - page 11

    Network Management Ca rd – User Manual 34003991EN/EB Page 11/118 1.3.4 Administration Up to 35 workstations( in TCP co nnected mode) or u p to 100(in UDP broa dcasted mode) prote cted by Network Shutdown Modules - Central or l ocal configuration . Up to 5 browsers connected at t he same time (3 in SS L). Minimum recomme nded browser versions : In ...

  • Eaton 34003991EN/EB - page 12

    Network Management Ca rd – User Manual 34003991EN/EB Page 12/118 ◗ Recording of events and measurements in the card log ◗ Possibility of shutting down the installation in the event of a thres hold being exceeded or on opening / clos ure of a dry conta ct ◗ Connection to the ca rd with straight CA T5 RJ45 network cables (maxi mum card/sensor ...

  • Eaton 34003991EN/EB - page 13

    Network Management Ca rd – User Manual 34003991EN/EB Page 13/118 1.3.8 Default parameters Function Parameter Default value Possible value Network IP address 166.99.16.16 Network IP address Subnet mask 255.255.0.0 Network IP address Gateway A ddress 0.0.0.0 Network IP address BOOTP/DHCP Enabled A ctive / Deactivated Firmware Upload Enabled A ctive ...

  • Eaton 34003991EN/EB - page 14

    Network Management Ca rd – User Manual 34003991EN/EB Page 14/118 2 Installation 2.1 Unpacking and check on contents The installation kit co ntents: ◗ A Network Management Card (661 02) ◗ A serial communication cable for configura tion (34003918 ) ◗ Installation manual (34003905) 2.2 Indications ...

  • Eaton 34003991EN/EB - page 15

    Network Management Ca rd – User Manual 34003991EN/EB Page 15/118 Ethernet port LED Colour A ctivit y Description ACT Green ◗ Off ◗ Card not connected t o the netw ork. ◗ On ◗ Card connected to the network but without activity ◗ Flashing ◗ Port is active in rece iving / transmission 100M Orange ◗ Off ◗ Port operating at 10 Mbits/s. ...

  • Eaton 34003991EN/EB - page 16

    Network Management Ca rd – User Manual 34003991EN/EB Page 16/118 2.4 Sensor installation (option) The Environment sensor is available as a n option on the Net work Management Card and is availa ble from MGE Office Protection Sy stems (reference 668 46). The sensor allo ws remote monitoring of the UPS's environ ment through regular measure me ...

  • Eaton 34003991EN/EB - page 17

    Network Management Ca rd – User Manual 34003991EN/EB Page 17/118 3 Configuration 3.1 Configure IP parameters Once the card has start ed: Connect one end of the cable (3400 3918) to the Service port . If the environment sensor was prev iously connected, the card must be restart ed in order to acce ss the configurat ion menu. Connect the other en d ...

  • Eaton 34003991EN/EB - page 18

    Network Management Ca rd – User Manual 34003991EN/EB Page 18/118 3.1.1 Your network is equipped with a DHCP serv er The card is configure d by default with this service activat ed. The card automatical ly collects IP paramete rs. To know the IP para meters, ty pe 2, the next menu is display ed: ----------- ------------------------- -------------- ...

  • Eaton 34003991EN/EB - page 19

    Network Management Ca rd – User Manual 34003991EN/EB Page 19/118 3.1.2 Your network is not equipped with a DHCP server In the main menu enter 2, then 2 again . The menu is d isplayed: Follow the instruct ions and ente r the static IP para meters. A t the end of the menu, wait for the "Done" message to be display ed indicating that the I ...

  • Eaton 34003991EN/EB - page 20

    Network Management Ca rd – User Manual 34003991EN/EB Page 20/118 4 Supervision and a dministration by browser ◗ On a computer equ ipped with a Web browser (Internet Explorer, FireF ox or Netscape reco mmended), enter the address initialised previously in the Installation chapter (e. g. http://166.99 .16.16.) T he "UPS properties" home ...

  • Eaton 34003991EN/EB - page 21

    Network Management Ca rd – User Manual 34003991EN/EB Page 21/118 4.2 UPS 4.2.1 UPS properties page This page is automatica lly ref reshed every 10 sec onds. From this page, acces s to the ma in UPS information is ava ilable thanks to the combo b ox (see scree n copy below). The different choice s are the following ones: “UPS Status”: (chose n ...

  • Eaton 34003991EN/EB - page 22

    Network Management Ca rd – User Manual 34003991EN/EB Page 22/118 4.2.1.1 "UPS" zone: general information on the UPS. Indication of the picture and generic na me of the UPS range Computer room: Custo mised name of y our sy stem. You can change th is name on th e "System" page. UPS status icon : The various icons showing the st ...

  • Eaton 34003991EN/EB - page 23

    Network Management Ca rd – User Manual 34003991EN/EB Page 23/118 UPS without auto matic by pass Note: In case of loss of commu nication with the UPS , all the ele ments of the sy noptic are grey . The various elements of the sy noptic are the followin g ones: ◗ A C Normal Input : In tolerances Out of tolerances ◗ A C Normal Flow : A C to DC c ...

  • Eaton 34003991EN/EB - page 24

    Network Management Ca rd – User Manual 34003991EN/EB Page 24/118 ◗ Battery : Remaining capacity > 50% Remaining capacity < 50% Battery to be checked (battery test result) ◗ Battery Output Flow : DC to AC convert er powered by battery DC to AC convert er not powered by battery ◗ DC to AC Convert er Input flow : Energy flow present No e ...

  • Eaton 34003991EN/EB - page 25

    Network Management Ca rd – User Manual 34003991EN/EB Page 25/118 ◗ A C A utomatic By pass Flow : Energy flow present No energy flow ◗ A C A utomatic By pass Status : Powered Not powered Internal failure ◗ A C M anua l Bypass Flow : Energy flow present No energy flow ◗ A C M anua l Bypass Stat us : Open Closed ◗ A C Output Flow : Energy ...

  • Eaton 34003991EN/EB - page 26

    Network Management Ca rd – User Manual 34003991EN/EB Page 26/118 ◗ UPS measurements : ◗ Boxes showing measure ments appear when sy noptic elements are hovered by the pointer. See exa mple below. These measurements are available for AC to DC converte r, Battery , DC to AC converter and a utomatic by pass. The measurements available in t hese b ...

  • Eaton 34003991EN/EB - page 27

    Network Management Ca rd – User Manual 34003991EN/EB Page 27/118 4.2.1.2 "UPS status" zone: Es sential informat ion ◗ "Active sources": (a vailable on paralle l or modular UPS) x UPS + y UPS redundant : x indicates the m inimal number of UPS necessary to power the load, y indicates the number of UPS in redu ndancy . A n alar ...

  • Eaton 34003991EN/EB - page 28

    Network Management Ca rd – User Manual 34003991EN/EB Page 28/118 4.2.1.3 Viewing the modules ◗ Click on "UPS Modu les" scroll lis t to view the information about the UPS mo dules. ◗ A ctive sources: x UPS + y UPS redundant : x indicates the m inimal number of UPS necessary to power the load, y indicates the number of UPS i n redunda ...

  • Eaton 34003991EN/EB - page 29

    Network Management Ca rd – User Manual 34003991EN/EB Page 29/118 ◗ The Status can take the next forms: or when the module is working proper ly with no alarm . when the module ha s at least one alar m (level Warning) active. when the module ha s at least one alar m (level Critical) act ive. when the module ha s a communication fault. When the mo ...

  • Eaton 34003991EN/EB - page 30

    Network Management Ca rd – User Manual 34003991EN/EB Page 30/118 4.2.1.4 Viewing the alarms Click on "A larm Table" scroll list to vie w the list of current alarms. The table of managed alar ms is included in the appendix . The level of the a larms appears like belo w: Critical Warning Unknown ◗ A larm table for standard UPS ...

  • Eaton 34003991EN/EB - page 31

    Network Management Ca rd – User Manual 34003991EN/EB Page 31/118 ◗ A larm table for modular UPS ...

  • Eaton 34003991EN/EB - page 32

    Network Management Ca rd – User Manual 34003991EN/EB Page 32/118 4.2.1.5 Viewing the “Abou t your UPS” window Click on "A bout your UPS" scroll list to v iew the informati on about the U PS and the card. ...

  • Eaton 34003991EN/EB - page 33

    Network Management Ca rd – User Manual 34003991EN/EB Page 33/118 4.2.2 On-line help On-line contextual he lp in Engli sh is available at the top of each page by clicking on the He lp link, which is a lway s located on the top r ight corner. T he navigation menu of the on-line he lp is identical to that of the card's pa ges. The Help page alw ...

  • Eaton 34003991EN/EB - page 34

    Network Management Ca rd – User Manual 34003991EN/EB Page 34/118 4.2.3 UPS control Click on the "UPS C ontrol" section in the menu The parameters of t his menu can on ly be modified aft er entering the "Login " and "Pass word". The following screen is proposed automatical ly: The default login an d password are : adm ...

  • Eaton 34003991EN/EB - page 35

    Network Management Ca rd – User Manual 34003991EN/EB Page 35/118 UPS configuration may prev ent the shutdown and resta rt comma nds from being properly run. Read the UP S user manual for more information. This page enables tr iggering of startup and shutdo wn sequence s for the UPS main output and cont rolled outlets. ◗ The status of each o utp ...

  • Eaton 34003991EN/EB - page 36

    Network Management Ca rd – User Manual 34003991EN/EB Page 36/118 "Immediate On" : A sequence to switch on output p ower is launc hed immediately . The output is r e-powered and the systems supplied sta rt up correctly . "Delayed, safe power down": This is the same switch off sequence as for the "Safe power do wn" com ...

  • Eaton 34003991EN/EB - page 37

    Network Management Ca rd – User Manual 34003991EN/EB Page 37/118 4.2.4 UPS weekly schedule programming Click on the "Weekly schedule" section of the menu . UPS configuration may prev ent the shutdown and resta rt comma nds from being properly run. Read the UP S user manual for more information. The weekly schedule enables the admin istr ...

  • Eaton 34003991EN/EB - page 38

    Network Management Ca rd – User Manual 34003991EN/EB Page 38/118 4.2.5 Shutdown parameters This page enables v iewing and configurat ion of UPS operat ing parameters in batt ery mode and for power restoration. Click on the "Shutdo wn paramete rs" section in the men u to see the list of para meters. When you tick the Show advance d param ...

  • Eaton 34003991EN/EB - page 39

    Network Management Ca rd – User Manual 34003991EN/EB Page 39/118 For the main outlet ( "Master" by def ault) The first shutdow n criteria initiates the re start of the shutdow n sequence . ◗ If remaining time is under (0 to 9 9999 seconds, 180 by default) is the minimum remaining backup time from w hich the shutdown seq uence is launc ...

  • Eaton 34003991EN/EB - page 40

    Network Management Ca rd – User Manual 34003991EN/EB Page 40/118 4.2.6 Measurements Click on " Meas urements " in the menu ◗ The next windo w shows the me asurements for a mon o phases UPS. The following meas urements are saved and time-sta mped (env. 430): ◗ "AC Normal : Voltage" : Value of the uti lity voltage supply ing ...

  • Eaton 34003991EN/EB - page 41

    Network Management Ca rd – User Manual 34003991EN/EB Page 41/118 4.2.7 Event log ◗ Click on "Event Log ". in the menu ◗ "Save log" enables a ll saved values to be opened or saved in CSV format . (compatible with Excel ty pe spreadsheets) ◗ "Clear log" enables de letion of all records. The ad ministrator must en ...

  • Eaton 34003991EN/EB - page 42

    Network Management Ca rd – User Manual 34003991EN/EB Page 42/118 4.2.8 System log ◗ Click on "System l og". in the m enu ◗ "Save log" enables a ll saved values to be opened or saved in CSV format . (compatible with Excel ty pe spreadsheets) ◗ "Clear log" enables de letion of all records. The ad ministrator must ...

  • Eaton 34003991EN/EB - page 43

    Network Management Ca rd – User Manual 34003991EN/EB Page 43/118 4.3 Notification 4.3.1 Email Notification The card offers the possibility of redirecting UPS alarms to an e-mail server. The format of thes e e-mails is compatible with mobi le telephone transf er sy stems using text messages (SMS) . ...

  • Eaton 34003991EN/EB - page 44

    Network Management Ca rd – User Manual 34003991EN/EB Page 44/118 ◗ Recipient List: On the left side of t his page, up to four recipients can be configured to receive e-mails fro m the card. Each addressee has its o wn trigger event s, selected from the r ight side of the page , for which an e-m ail is sent. The card’s log indicates e-mail tra ...

  • Eaton 34003991EN/EB - page 45

    Network Management Ca rd – User Manual 34003991EN/EB Page 45/118 4.3.2 E-mail Message Settings This page enables c ustomisation of the content of the messages received by recipients of e-ma ils sent by the card. Customisation is c ommon to th e four recipients that can be notified (see E-mail notificati on ). ◗ Sender (59 characters maxi mum) i ...

  • Eaton 34003991EN/EB - page 46

    Network Management Ca rd – User Manual 34003991EN/EB Page 46/118 The body of the e-mail sent is compos ed of: - Message text, whic h is free text . - The date and ti me of the event, as save d in the log. - URL of the card, enab ling a direct link with the card to be established. - Attac hments, as configured for the e- mail recipients .- duplica ...

  • Eaton 34003991EN/EB - page 47

    Network Management Ca rd – User Manual 34003991EN/EB Page 47/118 4.4 Configuration The parameters of t his menu can on ly be modified aft er entering the "Login " and "Pass word". The following screen is proposed automatical ly: The default login an d password are : admin/admin Each field accepts up to 10 chara cters max. A ft ...

  • Eaton 34003991EN/EB - page 48

    Network Management Ca rd – User Manual 34003991EN/EB Page 48/118 4.4.1 Network settings Click on "Network" in the menu. This menu enables the administ rator to configure the network parameters of the card and a uthorisation of the remote upgrade of the embe dded sys tem. ◗ IP Address: The IP a ddress of t he card (e.g.: 166.99.22.252 ...

  • Eaton 34003991EN/EB - page 49

    Network Management Ca rd – User Manual 34003991EN/EB Page 49/118 If the hostname is not used, the IP address supplied by the DHCP server must be fixed to maint ain connection with the clients installed on the stations to be protected. Note 2: During the first connect ion, if the DHCP query is not successful, the NMC starts with the follo wing IP ...

  • Eaton 34003991EN/EB - page 50

    Network Management Ca rd – User Manual 34003991EN/EB Page 50/118 4.4.2 System Click on " System " in the menu. This menu enables the customisat ion of the information o n the UPS propert ies pages. ◗ UPS Contact: Th is text field is limited to 49 characters. Enter the name of the person responsib le for UPS administration at IT networ ...

  • Eaton 34003991EN/EB - page 51

    Network Management Ca rd – User Manual 34003991EN/EB Page 51/118 ◗ Factory Reset button: enables re storation of the defau lt configuration of al l the card’s para meters. TCP/IP parameters: IP addres s, subnet mask, gat eway and BootP/DH CP value are maintained if the "Keep TCP/IP parameters" option is selected. Security of this op ...

  • Eaton 34003991EN/EB - page 52

    Network Management Ca rd – User Manual 34003991EN/EB Page 52/118 4.4.3 Notified Applications Click on " Notified Appl ications " in the menu. Security : The administrator has to ente r his/her login/pass word in order to vie w this information . This menu enables : ◗ The addition of the su pervision sta tions receiving traps and confi ...

  • Eaton 34003991EN/EB - page 53

    Network Management Ca rd – User Manual 34003991EN/EB Page 53/118 application) or Central (coming from the card). The Central sh utdown configuration is available by clicking on the Configura tion link. ◗ Shutdown duration: the shutdown durat ion necessary to properly shutdown the computer. ◗ Shutdown after : the time availa ble to the user fr ...

  • Eaton 34003991EN/EB - page 54

    Network Management Ca rd – User Manual 34003991EN/EB Page 54/118 4.4.4 Central shutdown configuration Click on "Notified A pplications" in the menu, then "Config uration". This page is used to define either the "s hutdown" or the "notification" set tings used by the Network Shutdown Modules that connect to ...

  • Eaton 34003991EN/EB - page 55

    Network Management Ca rd – User Manual 34003991EN/EB Page 55/118 4.4.5 Access control Click on " Access Control " in the menu. To access this page , the login and pass word are sy stematically requested if they have not already been entered. This menu enables co nfiguration of the different parameters enabling secure access to the card ...

  • Eaton 34003991EN/EB - page 56

    Network Management Ca rd – User Manual 34003991EN/EB Page 56/118 ◗ SSL Ac cess: When selected, access to the Web interface is made in secure mo de (https). Connections with Ne twork Shutdo wn Modules stay in standard mode (s ecure TCP) SSL Security Implementation: SSL     version 3.0 TLS     version 1.0 Method   ? ...

  • Eaton 34003991EN/EB - page 57

    Network Management Ca rd – User Manual 34003991EN/EB Page 57/118 4.4.6 Date and time Click on " Date and Time " in the menu. This menu enables initialisation of the da te and time of the ca rd in three differe nt way s. The date format is a lway s of y ear/month/day type ◗ Set manually : Enables initialisation of the date and ti me of ...

  • Eaton 34003991EN/EB - page 58

    Network Management Ca rd – User Manual 34003991EN/EB Page 58/118 ◗ Synchronize with NT P server: Enables co nnection with a time server, either available on the co mpany ’s internal network or on the Web. This ser ver communicates G MT time. The IP addres s or hostname of the time server must be entered, and the ti me zone of y our geographic ...

  • Eaton 34003991EN/EB - page 59

    Network Management Ca rd – User Manual 34003991EN/EB Page 59/118 4.4.7 Firmware upload Click on " Firmware Upload " in t he menu. This menu enables a new firmw are version to be uploade d To upload a ne w version of the card's firmware, select the file to be loaded using the "Browse…" butt on and click Upload. Do not in ...

  • Eaton 34003991EN/EB - page 60

    Network Management Ca rd – User Manual 34003991EN/EB Page 60/118 4.5 Environment Sensor (option ) The environment sens or (66846) is an o ption that enables te mperature and hu midity to be measured, and indicat ion of the position of two external conta cts. It is connected with a standard network cable to the Card Settings port of the Network Ma ...

  • Eaton 34003991EN/EB - page 61

    Network Management Ca rd – User Manual 34003991EN/EB Page 61/118 4.5.2 Environment Status For both measure ments, a graduated gauge proposes the following functions : The cursor indicates the current value. Two red zones to the left and rig ht represent the high a nd low thre sholds that can be set on the Envir onment Settings page. When the meas ...

  • Eaton 34003991EN/EB - page 62

    Network Management Ca rd – User Manual 34003991EN/EB Page 62/118 4.5.3 Environment Settings The environment sens or measures temperature, humidity and gives the stat us of the 2 contac ts (used for door, alarms or generator unit). The temperature an d humidity thresholds can be adjust ed and can trigger notification and corr ect shutdown of the p ...

  • Eaton 34003991EN/EB - page 63

    Network Management Ca rd – User Manual 34003991EN/EB Page 63/118 The low alarm disappe ars when the value returns above the Low threshold + Hysteres is value Input #1 and Input #2 : Enter an i dentifier correspondin g to the acquired contact (e.g.: rack door, air condition ing, generator unit, etc.). Max. lengt h is 28 characters. when closed and ...

  • Eaton 34003991EN/EB - page 64

    Network Management Ca rd – User Manual 34003991EN/EB Page 64/118 4.5.4 Log The two environ ment sensor measurements : Temperature and Humidity are recorded at an interva l defined by the Environment log interv al in the System settings pa ge. By default, this peri od is 300 seconds. Each measurement is dated and stored in the log of the U PS’s ...

  • Eaton 34003991EN/EB - page 65

    Network Management Ca rd – User Manual 34003991EN/EB Page 65/118 5 Server protection 5.1 Set-up of the shutdown pa rameters The protection appl ication : Network Shutdown Module or Netwatc h, on protected server boot, subscribes itself automatically to notified applications list a nd sends its essent ial data: ◗ IP Address or host name of the s ...

  • Eaton 34003991EN/EB - page 66

    Network Management Ca rd – User Manual 34003991EN/EB Page 66/118 Start of the shutdo wn sequence Delay before shutdown Utility failure Remaining autono my 100% Shutdown after : If remaining time und er UPS Shut off Card param eters UPS parameters Shutdown duration Battery capacity 0% Shutdown if remainig capacity under t 5.1.1.1 Backup time befor ...

  • Eaton 34003991EN/EB - page 67

    Network Management Ca rd – User Manual 34003991EN/EB Page 67/118 5.1.1.3 Shutdown when backu p time is less than When the Network Management Card detect s that the percenta ge of backup ti me remaining is less than the value set, the shutdown seq uence is started. 5.1.1.4 Shutdown duration Duration (in seconds) required f or the syst em protected ...

  • Eaton 34003991EN/EB - page 68

    Network Management Ca rd – User Manual 34003991EN/EB Page 68/118 5.1.2 Controlled outlets Certain UPS models are equipped with controlled outlets (generally 2) which are alway s dependant on the U PS's main outlet. Shutdown of the mai n outlet syst ematically causes shutdown of the progra mmable outlets. The following notati ons are used to ...

  • Eaton 34003991EN/EB - page 69

    Network Management Ca rd – User Manual 34003991EN/EB Page 69/118 5.1.3.2 Sequential startup It is possible to de lay outlet power-on to reduce inrus h currents on startup or to sequence the startup of seve ral devices. Controlled outlet start up after a given t ime is based on start up of the main outlet. 5.2 The different server and UPS shutdown ...

  • Eaton 34003991EN/EB - page 70

    Network Management Ca rd – User Manual 34003991EN/EB Page 70/118 Shutdown duration Start shutdown main output Utility failure Utility Battery capa city under : NSM 2 on output 1 NSM 1 on main output Main output Utility restor e Start shutdown output 1 Output 1 Shutdown duration output 1 Battery capacity under : (output 1) 5.2.3 Case of power rest ...

  • Eaton 34003991EN/EB - page 71

    Network Management Ca rd – User Manual 34003991EN/EB Page 71/118 5.3 Shutdown management with 2 NMC bo ards Certain UPS can have 2 NMC boa rds in order to: ◗ Increase the nu mber of protected serv ers, ◗ Protect 2 groups of serv er connect ed to different net works physically separated. 5.3.1 Shutdown Duration A s described in the 5.1.1.4 par ...

  • Eaton 34003991EN/EB - page 72

    Network Management Ca rd – User Manual 34003991EN/EB Page 72/118 6 Configuration via R S232 ◗ Use the cord supplie d with the c ard. ◗ Connect the card to a computer equipped with a hy perterminal ty pe emulator. The seria l link must be set at 96 00 baud, 8 bits, no parity , 1 stop bit , and without flo w control. ◗ Check that UPS po wer i ...

  • Eaton 34003991EN/EB - page 73

    Network Management Ca rd – User Manual 34003991EN/EB Page 73/118 6.1 Choice 1: Restart / Reset Use this function to rest art the c ard; two choices are possible 1 : Hardware Reset: E quivalent to a restar t of the electrica l power supply . 2 : Restart application : Restarts only the application part. ----------- ------------------------- ------- ...

  • Eaton 34003991EN/EB - page 74

    Network Management Ca rd – User Manual 34003991EN/EB Page 74/118 6.2.2 Choice 2: Modify Network settings Enables the modificati on of network para meters For each of the fol lowing questions, y ou can press <Ret urn> to select the value shown in braces, or you can ente r a new value. Should this target obtain IP setti ngs from the net work? ...

  • Eaton 34003991EN/EB - page 75

    Network Management Ca rd – User Manual 34003991EN/EB Page 75/118 6.3 Choice 3: Lost password / Set Login Password to De fault In the even the login or password is lost , choice 3 enab les the return to the defa ult password: ----------- ------------------------- -------------------------- --------------- EATON NETWORK MA NAGEMENT CA RD ---------- ...

  • Eaton 34003991EN/EB - page 76

    Network Management Ca rd – User Manual 34003991EN/EB Page 76/118 6.4 Choice 4: Return to Default Configuration Enables restoratio n of the default configurat ion of all the card’s parameters ----------- ------------------------- -------------------------- --------------- EATON NETWORK MA NAGEMENT CA RD ----------- ------------------------- ---- ...

  • Eaton 34003991EN/EB - page 77

    Network Management Ca rd – User Manual 34003991EN/EB Page 77/118 7 Industrial Network Management Card (INMC op tion) 7.1 Presentation 7.1.1 Overview 7.1.2 Functions The Industrial Net work Manage ment Card (INMC) prov ides the s ame functions than the NMC card describe d in the previous section of th is docume nt. The adding function c onsists to ...

  • Eaton 34003991EN/EB - page 78

    Network Management Ca rd – User Manual 34003991EN/EB Page 78/118 7.1.3 Technical characteristics Functions Parameters Default values Possible values JBUS/MODBUS communication - Baud rate - Parity - Slave number - 9600 bauds - without parity - Slave nr 1 - 1200, 2400, 4800, 9600 - Without parity , even parity - 1 to FF (hexadec imal) RS232 link - ...

  • Eaton 34003991EN/EB - page 79

    Network Management Ca rd – User Manual 34003991EN/EB Page 79/118 7.2 Installation 7.2.1 RS232 link configuration and c onnection Set the SA2 switche s like below: The next figure sho ws the details of the connection in RS232 mode: ...

  • Eaton 34003991EN/EB - page 80

    Network Management Ca rd – User Manual 34003991EN/EB Page 80/118 7.2.2 RS485 link configuration and c onnection 7.2.2.1 RS485 connection The EIA RS485 link, 2 wires or 4 wires, must be polarized at a unique point of the link and must be adapted at b oth ends for a good worki ng. Normally , the master of the network set s the polarity of the line. ...

  • Eaton 34003991EN/EB - page 81

    Network Management Ca rd – User Manual 34003991EN/EB Page 81/118 The settings of the RS485 link are made through the SA 1 switches: SA1 description: 1: reserved 2: reserved 3: link termination between T- to R- (2 wires configurati on) if set to ON 4: connection T- to R- (2 wires configurat ion) if set to ON 5: connection T+ to R+ (2 wires conf ig ...

  • Eaton 34003991EN/EB - page 82

    Network Management Ca rd – User Manual 34003991EN/EB Page 82/118 7.2.2.2 RS485 link configura tion for 2 wires conn exion Set the SA2 switche s like below to set the RS485 mode: Set the SA1 switche s to select t he two wires configura tion with no ter mination: ...

  • Eaton 34003991EN/EB - page 83

    Network Management Ca rd – User Manual 34003991EN/EB Page 83/118 Set the SA1 switche s to select t he two wires configura tion with te rmination: The next figure gives a ty pical bus structure in the t wo wires conf iguration: ...

  • Eaton 34003991EN/EB - page 84

    Network Management Ca rd – User Manual 34003991EN/EB Page 84/118 7.2.2.3 RS485 link configura tion for 4 wires conn exion Set the SA2 switche s like below: Set the SA1 switche s to select t he four wires configurat ion with no termination: ...

  • Eaton 34003991EN/EB - page 85

    Network Management Ca rd – User Manual 34003991EN/EB Page 85/118 Set the SA1 switche s to select t he four wires configurat ion with termi nation: The next figure gives a ty pical bus structure in the four wires configurati on: ...

  • Eaton 34003991EN/EB - page 86

    Network Management Ca rd – User Manual 34003991EN/EB Page 86/118 7.2.3 Configuration of the JBUS/MODBUS communication parameters ◗ Use the cord supplie d with the c ard. ◗ Connect the card to a computer equipped with a Hy per terminal ty pe emulator. The serial link must be set at 9600 baud, 8 bits, no parity , 1 stop bit, and without flow co ...

  • Eaton 34003991EN/EB - page 87

    Network Management Ca rd – User Manual 34003991EN/EB Page 87/118 ◗ The next menu appears : ----------- ------------------------- -------------------------- --------------- EATON NETWORK MA NAGEMENT CA RD ----------- ------------------------- -------------------------- --------------- 1 : Reset 2 : Network conf iguration 3 : Set Login Pass word ...

  • Eaton 34003991EN/EB - page 88

    Network Management Ca rd – User Manual 34003991EN/EB Page 88/118 Setting Jbus config uration : Set Slave number : 0x7 Set the Baud Rate [1: 38400, 2: 1 9200, 3: 9600, 4: 4800 , 5: 2400, 6: 1200] :3 Set data format [1 : 8 bits, 2: 7 bits] :1 Set stop bit [1: 1 b its, 2: 2 bits] :1 Set Parity [1: None, 2: Even, 3: Odd] :1 Wait during the ne w setti ...

  • Eaton 34003991EN/EB - page 89

    Network Management Ca rd – User Manual 34003991EN/EB Page 89/118 7.2.3.6 Choice 6: Display Jbus frames Enables the display of the Jbus f rames: Recv : 01 01 00 00 00 64 3d e1 Send : 01 81 02 c1 91 Recv : 01 03 00 62 00 64 e5 ff Send : 01 03 c8 00 00 00 00 00 00 00 00 00 00 00 00 00 ... Recv : 01 01 00 00 00 64 3d e1 Send : 01 81 02 c1 91 Recv : 0 ...

  • Eaton 34003991EN/EB - page 90

    Network Management Ca rd – User Manual 34003991EN/EB Page 90/118 7.3 Additional Web pages The INMC card Jbus parameters could be set through the next page: ...

  • Eaton 34003991EN/EB - page 91

    Network Management Ca rd – User Manual 34003991EN/EB Page 91/118 7.4 JBUS table 7.4.1 Data for Pulsar 700 / 1000 / 1500 7.4.1.1 Status table Status description Status to 0 Status to 1 Word (hex) Bit Load protected no y es 40 0 UPS coupled no y es 40 1 Unit general alarm no y es 40 2 UPS in backup no y es 40 4 Battery low warning no y es 40 5 Low ...

  • Eaton 34003991EN/EB - page 92

    Network Management Ca rd – User Manual 34003991EN/EB Page 92/118 7.4.1.2 Measurements tab le Description of the physical quantity Word (hex) Unit I output 109 A U output 1 24 V U battery 12D V Output active po wer 136 W Output apparent po wer 137 VA % output load level 139 % Power factor (Cos PH I) 13D - Mains 1 frequency 13E Hz Output frequency ...

  • Eaton 34003991EN/EB - page 93

    Network Management Ca rd – User Manual 34003991EN/EB Page 93/118 7.4.2 Data for Pulsar M 2200 / 3000 7.4.2.1 Status table Status description Status to 0 Status to 1 Word (hex) Bit Load protected no y es 40 0 UPS coupled no y es 40 1 Unit general alarm no y es 40 2 UPS in backup no y es 40 4 Battery low warning no yes 40 5 Low battery no y es 40 6 ...

  • Eaton 34003991EN/EB - page 94

    Network Management Ca rd – User Manual 34003991EN/EB Page 94/118 7.4.2.2 Measurements tab le Description of the physical quantity Word (hex) Unit I mains 2 106 A I output 109 A U mains 2 11E V U output 124 V U battery 12D V Output active po wer 136 W Output apparent po wer 137 V A % output load level 139 % Power factor x 100 13D - Mains 1 frequen ...

  • Eaton 34003991EN/EB - page 95

    Network Management Ca rd – User Manual 34003991EN/EB Page 95/118 7.4.3 Data for Pulsar MX 4000 / 5000 / 10000 and EX 5 / 7 / 11 RT 7.4.3.1 Status table Status description Status to 0 Status to 1 Word (hex) Bit Load protected no y es 40 0 UPS coupled no y es 40 1 Unit general alarm no yes 4 0 2 UPS in backup no yes 40 4 Battery low warning no y es ...

  • Eaton 34003991EN/EB - page 96

    Network Management Ca rd – User Manual 34003991EN/EB Page 96/118 7.4.3.2 Measurements tab le Description of the physical quantity Word (hex) Unit I mains 1 10 0 A I mains 2 10 6 A I output 109 A I battery 10E A U mains 2 11 E V U output 124 V U battery 12D V Output active po wer 136 W Output apparent po wer 137 V A % output load level 139 % Power ...

  • Eaton 34003991EN/EB - page 97

    Network Management Ca rd – User Manual 34003991EN/EB Page 97/118 7.4.4 Data for Pulsar MX frame 15 / 20 7.4.4.1 Status table Status description Status to 0 Stat us to 1 W ord (hex) Bit Load protected no y es 40 0 UPS coupled no y es 40 1 Unit general alarm no y es 40 2 UPS in backup n o y es 40 4 Battery low warning no y es 40 5 Low battery no ye ...

  • Eaton 34003991EN/EB - page 98

    Network Management Ca rd – User Manual 34003991EN/EB Page 98/118 7.4.4.2 Modular fault table Description du Status Status to 0 Status to 1 Word (hex) Bit General alarm A bsent Present 61 0 Fan failure A bsent Present 61 1 Internal communicati on fault A bsent Present 61 2 Inverter thermal overloa d A bsent Present 61 3 Inverter fault A bsent Pres ...

  • Eaton 34003991EN/EB - page 99

    Network Management Ca rd – User Manual 34003991EN/EB Page 99/118 Description du Status Status to 0 Status to 1 Word (hex) Bit General alarm A bsent Present 65 0 Fan failure A bsent Present 65 1 Internal communicati on fault A bsent Present 65 2 Inverter thermal overloa d Absent Present 65 3 Inverter fault A bsent Present 65 4 Inverter fuse blown ...

  • Eaton 34003991EN/EB - page 100

    Network Management Ca rd – User Manual 34003991EN/EB Page 100/118 7.4.4.3 Measurements tab le Description of the physical quantity Word (hex) Unit I1 (I phase 1) mains 1 100 A I2 (I phase 2) mains 1 101 A I3 (I phase 3) mains 1 102 A I1 (I phase 1) mains 2 106 A I2 (I phase 2) mains 2 107 A I3 (I phase 3) mains 2 108 A I1 (I phase 1) output 109 A ...

  • Eaton 34003991EN/EB - page 101

    Network Management Ca rd – User Manual 34003991EN/EB Page 101/118 Description of the physical quantity Word (hex) Unit U mains 1 (phase 1) 150 V U mains 1 (phase 2) 151 V U mains 1 (phase 3) 152 V Nominal voltage of batt ery element 213 V ...

  • Eaton 34003991EN/EB - page 102

    Network Management Ca rd – User Manual 34003991EN/EB Page 102/118 7.4.5 Sensor data 7.4.5.1 Status table Status description Status to 0 Status to 1 Word (hex) Bit Input 1 alarm no y es 45 5 Input 2 alarm no y es 45 6 A larm : hum idity too low no yes 45 4 A larm : hum idity too high no yes 45 3 A larm : temperatu re too low no y es 45 2 A larm : ...

  • Eaton 34003991EN/EB - page 103

    Network Management Ca rd – User Manual 34003991EN/EB Page 103/118 7.4.5.2 Measurements tab le Description of the physical quantity Word (hex) Unit Temperature measure 180 ° C / ° F Maximum temperat ure 181 ° C / ° F Maximum temperat ure date (MSB) in Unix t imestamp 18 2 Maximum temperat ure date (LSB) in Unix timestamp 183 Minimum temperat u ...

  • Eaton 34003991EN/EB - page 104

    Network Management Ca rd – User Manual 34003991EN/EB Page 104/118 7.4.5.3 Read of the personal ization table Description Wor d (hex) Uni t High threshold te mperature (° C) 32C 0 Low threshold tem perature (° C) 32D 0 Temperature hy steresis (° C) 32E 0 Offset temperature 32F 0 High threshold hum idity (%) 330 0 Low threshold hum idity (%) 331 ...

  • Eaton 34003991EN/EB - page 105

    Network Management Ca rd – User Manual 34003991EN/EB Page 105/118 7.4.6 Other data Information descript ion Word (hex) Example Manufacturer name 1A0 « MGE Office Protecti on Systems » Product name 1A8 « Pulsar » UPS model 1B0 « 700 » Serial number 1B8 « AN2E49 008 » ...

  • Eaton 34003991EN/EB - page 106

    Network Management Ca rd – User Manual 34003991EN/EB Page 106/118 8 Append ices 8.1 Tables of alarms and events 8.1.1 Table of alarms List of time dated alarms Alarm on A larm o ff Battery fuse blown Battery fuse OK No Battery Battery present Battery temperature fault Ba ttery temperature OK Battery charger fault Battery charger OK Battery fault ...

  • Eaton 34003991EN/EB - page 107

    Network Management Ca rd – User Manual 34003991EN/EB Page 107/118 Inverter overload I nverter l oad OK Inverter over temperature Inverter tempera ture OK Inverter short circu it Inverter OK Inverter thermal overloa d Inverter load OK Load not protect ed - On A utomatic Bypa ss Load protected - Return fro m By pass Load short circuit Load OK Load ...

  • Eaton 34003991EN/EB - page 108

    Network Management Ca rd – User Manual 34003991EN/EB Page 108/118 If the UPS is modular UPS, for each modu le: Battery fuse blow n Battery fuse OK No Battery Battery prese nt Battery temperature fault Battery temperature OK Battery charger fault Ba ttery charger OK Low battery Battery OK Charger temperature fault Charger temperature OK M A X char ...

  • Eaton 34003991EN/EB - page 109

    Network Management Ca rd – User Manual 34003991EN/EB Page 109/118 Positive DC bus too low Positive DC bus OK Output switch (Q5N) open Output switch (Q5N) closed Normal AC NOK Normal A C OK UPS on battery UPS on normal A C UPS overload UPS returns to nor mal load UPS overtemperature UPS temperature OK Fan fault Fan OK UPS communicatio n failed UPS ...

  • Eaton 34003991EN/EB - page 110

    Network Management Ca rd – User Manual 34003991EN/EB Page 110/118 Inverter fault Inverter OK Inverter overload Inverter load OK Inverter overtemperat ure Inverter temperature OK Inverter short circu it Inverter OK Inverter thermal overloa d Inverter load OK Output switch (Q5N) open Output switch (Q5N) closed Load short circuit Load OK Single wave ...

  • Eaton 34003991EN/EB - page 111

    Network Management Ca rd – User Manual 34003991EN/EB Page 111/118 8.1.3 Table of system alarms Network Management Ca rd startup Send test mail SUCC ESS Send test mail ERROR Send mail to <rec ipient> ERROR <Sensor name> Co mmunication failure <Sensor name> Co mmunication restore d Firmware upgraded Connected NSM list Full, last c ...

  • Eaton 34003991EN/EB - page 112

    Network Management Ca rd – User Manual 34003991EN/EB Page 112/118 8.2 SNMP objects 8.2.1 MGE MIB The NMC card imple ment reduce MGE Office Protecti on Systems MIB, with the objects be llow managed. The entire MIB descr iption is availab le on www.mgeops .com area “ Downloads – Software Do wnload . Le chemin d’accès à la MIB MGE est 1 .3.6 ...

  • Eaton 34003991EN/EB - page 113

    Network Management Ca rd – User Manual 34003991EN/EB Page 113/118 mgoutputFrequency _1 deciHz {7,2,1,3,1,0} mgoutputFrequency _2 deciHz {7,2,1,3,2,0} mgoutputFrequency _3 deciHz {7,2,1,3,3,0} mgoutputLoadPerP hase_1 % {7,2,1,4,1,0} mgoutputLoadPerP hase_2 % {7,2,1,4,2,0} mgoutputLoadPerP hase_3 % {7,2,1,4,3,0} mgoutputCurrent_1 deciA mps {7,2,1,5 ...

  • Eaton 34003991EN/EB - page 114

    Network Management Ca rd – User Manual 34003991EN/EB Page 114/118 If the Environment Sensor is det ected , the following information are managed. upsmgEnvironA mbientTemp 0.1 degré {8,1,0} upsmgEnvironA mbientHumidity 0.1 % {8,2,0} upsmgEnvironmentNu m {8,6,0} upsmgEnvironmentI ndex {8,7,1,1,1 } upsmgEnvironmentCo mFailure 1(yes) 2(no) {8,7,1,2, ...

  • Eaton 34003991EN/EB - page 115

    Network Management Ca rd – User Manual 34003991EN/EB Page 115/118 8.2.2 Table des TRAPS : (1.3.6.1.4.1.705.1.11 ) SNMP traps are sent when alarms ap pears and desappears . Level : 1:informationa l , 2:major, 3:critica l MIB TRA P T rap # Level -upsmgBattery Fault Trap 1 Level 3 -upsmgBattery OK Trap 2 Level 1 -upsmgAt LowBattery Trap 5 L evel 3 - ...

  • Eaton 34003991EN/EB - page 116

    Network Management Ca rd – User Manual 34003991EN/EB Page 116/118 - upsEnvironment Input1Open Trap 62 Level 2 - upsEnvironment Input2Open Trap 64 Level 2 - upsEnvironment Input2Closed Trap 63 Level 2 The level is used to se lect traps to be sent to the supervis or. This adjust ment is available fro m the “Notified applications” page ...

  • Eaton 34003991EN/EB - page 117

    Network Management Ca rd – User Manual 34003991EN/EB Page 117/118 9 Glossary Bootp: Protocol based on UD P used to allocate an IP address corres ponding to an Ethernet card d uring the startup phase . Defined by the RCF 951 Community name: A ccess key to access SNMP agent information DHCP Dy namic Host Configuration Protoc ol This IETF protoco l ...

  • Eaton 34003991EN/EB - page 118

    Network Management Ca rd – User Manual 34003991EN/EB Page 118/118 NMS NET WORK MANA GEMENT STATION (SNMP) The dedicated PC or workstation is used on the company ’s networks to adm inistrate all device s connected to the network. Data are tra nsmitted using the SN MP protocol. Popular NMS sy stems include HP Ope nView, IB M Tivoli, CA Unicenter, ...

Manufacturer Eaton Category Network Card

Documents that we receive from a manufacturer of a Eaton 34003991EN/EB can be divided into several groups. They are, among others:
- Eaton technical drawings
- 34003991EN/EB manuals
- Eaton product data sheets
- information booklets
- or energy labels Eaton 34003991EN/EB
All of them are important, but the most important information from the point of view of use of the device are in the user manual Eaton 34003991EN/EB.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Eaton 34003991EN/EB, service manual, brief instructions and user manuals Eaton 34003991EN/EB. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Eaton 34003991EN/EB.

Similar manuals

A complete manual for the device Eaton 34003991EN/EB, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Eaton 34003991EN/EB by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Eaton 34003991EN/EB.

A complete Eaton manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Eaton 34003991EN/EB - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Eaton 34003991EN/EB, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Eaton 34003991EN/EB, that we can find in the current document
3. Tips how to use the basic functions of the device Eaton 34003991EN/EB - which should help us in our first steps of using Eaton 34003991EN/EB
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Eaton 34003991EN/EB
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Eaton 34003991EN/EB in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Eaton 34003991EN/EB?

Use the form below

If you did not solve your problem by using a manual Eaton 34003991EN/EB, ask a question using the form below. If a user had a similar problem with Eaton 34003991EN/EB it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)