    1 18004 04/03/2007 Rev. C CG2 & MA2 Series Clean Agent FE-241 & HF C-227ea Owner’s Manual & Installation Instructions For all sizes 25 cubic feet to 1500 cubic feet Read and comply with all instructions, warnings and limitations before installing, servicing or removing this device. ...

  • Fireboy- Xintex, LTD CG2 - page 2

    2 This owner’s manual and i nstallation instru ctions pamphlet is provided in English. Additional copies in English are availabl e at no charge by contacting the manufacturer, distributor or dealer. Co pies in the language of desti nation are available upon request for an additio nal fee. Fireboy-Xintex reserves the right to change features witho ...

  • Fireboy- Xintex, LTD CG2 - page 3

    3 General Information Fireboy Automatic (CG series) and Manual/Automatic (MA) se ries Fire Extinguishing Systems are manufactured for a broad range of ap plications, including marine, industrial, and comm ercial uses. This booklet is intended to outline the proper installation of the sy stem for mari ne applications; most applications are similar. ...

  • Fireboy- Xintex, LTD CG2 - page 4

    4 WARNING: • Never install a Fireboy system on the underside of a h atch cover or on an access door that may open or separate in an expl osion • Never install the actuator of a Fireboy sy stem in close proximity to exhaust manifolds or turbocha rgers. Radiated heat may cause premature actuation • Never install the actuator of a Fireboy system ...

  • Fireboy- Xintex, LTD CG2 - page 5

    5 Volume Approximate Protected Diameter Total Height Age nt Weight Shipping Weight Model Number ft^3 m^3 in cm in cm lbs kgs lbs kgs U.S.C.G. # CG2-550-FE241 550 15.6 7.2 18 24.7 63 18.6 8.5 49 22.1 162.029/185/0 CG2-600-FE241 600 17 7.2 18 24.7 63 20.3 9.2 50 22.9 162.029/185/0 CG2-650-FE241 650 18.4 7.2 18 24.7 63 22 10 52 23.6 162.029/185/0 CG2- ...

  • Fireboy- Xintex, LTD CG2 - page 6

    6 Volume Approximate Protected Diameter Total Height Age nt Weight Shipping Weight Model Number ft^3 m^3 in cm in cm lbs kgs lbs kgs U.S.C.G. # CG2-300-227 300 8.5 7.2 18 15.1 38 13 5.9 35 15.9 162.029/210/0 CG2-325-227 325 9.2 7.2 18 15.1 38 14 6.4 36 16.4 162.029/210/0 CG2-350-227 350 10 7.2 18 15.1 38 15.1 6.9 37 16.9 162.029/210/ 0 CG2-375-227 ...

  • Fireboy- Xintex, LTD CG2 - page 7

    7 Marine Installation Instructions Before Installation 1. Check the system for damage during sh ipment. 2. Check the pressure gauge to be sure the gauge pointer lies within the green zone at 70°F (2 1°C). The correct weig ht is shown on the nameplate for the appropriate model. 3. Select an interior location not directly subject to weather or seaw ...

  • Fireboy- Xintex, LTD CG2 - page 8

    8 Accommodating Diesel Engines 1. Failure to install an Automa tic Engine Shutdown in any compartment containing a diesel engine and a Fir eboy system impedes the fire extinguisher and may prevent fire extinguishment. 2. Automatic Engine Shutdown units are available through your Fireboy- Xintex distributor, dealer or retailer in three, five and eig ...

  • Fireboy- Xintex, LTD CG2 - page 9

    9 WARNING: • An electrical short may result in electrical burn, injury or fire • Before attempting to wire the indicato r lamp, turn off all electrical current to the ignition switch • All Fireboy wiring must comply with the American Boat and Yacht Council Standard E9-9, titled Direct Cu rrent Electrical Systems for Boats, available from ABYC ...

  • Fireboy- Xintex, LTD CG2 - page 10

    10 If the engine compartment is equipped with a powe red ventilation system, U.S. Coast Guard Rule 162.029 requires that the ground conne ction of the ventilation system be connected to the Fireboy system. Failure to connect a po wered ventilation system in the manner described belo w impedes fire extinguisher and may prev ent fire extinguishment. ...

  • Fireboy- Xintex, LTD CG2 - page 11

    11 NOTE: Never push the cable at the T-handle end. Cable m ay jam and become inoperable. Fixing a jammed cable: 1. Turn the T-handle and threaded metal rod counter clo ckwise ½ turn until the jam releases . 2. If necessary, use a pair of pliers to carefully twist the threaded metal rod until the jam releases. 3. Pull the cable from the “S” hoo ...

  • Fireboy- Xintex, LTD CG2 - page 12

    12 6. Pull cable to full extension. 7. Screw ferrule on to cable (approximately 4-5 turns maximum). 8. Slide o-ring onto c able shaft. 9. Screw red T-handle onto cable sha ft (Do not obstruct cross hole in T- handle). 10. Push red T-handle into ferrule to seat o-ring. 11. Align holes in ferrule and T-handle. 12. Temporarily install pull pin. 13. Al ...

  • Fireboy- Xintex, LTD CG2 - page 13

    13 3. Push the cable end through the hole on the cylinder manifold far enough to allow the flexible strand to be bent. 4. Place “S” hook through the hole in the MA lever. 5. Gently pull cable sheath back into manifold, aligning the groove in sheath with slot in the manifold. 6. Insert the wire retaining clip provided around the groove in the ca ...

  • Fireboy- Xintex, LTD CG2 - page 14

    14 1. A loud sound similar to small arms fire. 2. A loud sound of rushing air. 3. An extinguished indicator lamp. 4. A stalled engine. When actuation occurs 1. Immediately shutdown all engines, powered ventilation, and electrical systems. 2. Extinguish all smoking materials. 3. Do not open the engine compartment. After actuation 1. Before inspectin ...

  • Fireboy- Xintex, LTD CG2 - page 15

    15 Inspect manual discharge cabl e annually when inspe cting the fire extinguisher. 1. Do not remove the pull pin on the T-handle when disconnecting the manual discharge cable fro m the fire extinguisher manifold. 2. Remove the wire retaining clip secu ring the cable located at the sl ot in the top of the manifold. 3. C arefully push the cable from ...

  • Fireboy- Xintex, LTD CG2 - page 16

    16 Automatic Engine Shutdown/Override System is required for u se with Fireboy systems in diesel powered cr aft. Returning Fireboy-Xintex Equipment No product may be returned for credit or repair withou t a written “Returned Material Authorization” (RMA) form. Pu rchaser must call or email Fireboy-Xintex 616-735-9380 or fireboy@fireboy-xintex . ...

  • Fireboy- Xintex, LTD CG2 - page 17

    17 NOTE: Detroit Diesel engines may require Auto matic Engine Shutdown system s with time delay. Fireboy accessories are av ailable from y our Fireboy-Xintex distributor, dealer or retailer. ...

  • Fireboy- Xintex, LTD CG2 - page 18

    18 3 YEAR LIMITED WARRANTY This Warranty is in lieu of all ot her expressed of implied Wa rranties Seller warrants title, materials, and workmanship on equipment, except components manufactured by others for whic h the Seller assigns, as permitted, the original manufacturer’ s warranty. Seller’s warranty shall b e for a period of (3) three year ...

Manufacturer Fireboy- Xintex, LTD Category Fire Extinguisher

Documents that we receive from a manufacturer of a Fireboy- Xintex, LTD CG2 can be divided into several groups. They are, among others:
- Fireboy- Xintex, LTD technical drawings
- CG2 manuals
- Fireboy- Xintex, LTD product data sheets
- information booklets
- or energy labels Fireboy- Xintex, LTD CG2
All of them are important, but the most important information from the point of view of use of the device are in the user manual Fireboy- Xintex, LTD CG2.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Fireboy- Xintex, LTD CG2, service manual, brief instructions and user manuals Fireboy- Xintex, LTD CG2. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Fireboy- Xintex, LTD CG2.

A complete manual for the device Fireboy- Xintex, LTD CG2, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Fireboy- Xintex, LTD CG2 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Fireboy- Xintex, LTD CG2.

A complete Fireboy- Xintex, LTD manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Fireboy- Xintex, LTD CG2 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Fireboy- Xintex, LTD CG2, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Fireboy- Xintex, LTD CG2, that we can find in the current document
3. Tips how to use the basic functions of the device Fireboy- Xintex, LTD CG2 - which should help us in our first steps of using Fireboy- Xintex, LTD CG2
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Fireboy- Xintex, LTD CG2
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Fireboy- Xintex, LTD CG2 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Fireboy- Xintex, LTD CG2?

Use the form below

If you did not solve your problem by using a manual Fireboy- Xintex, LTD CG2, ask a question using the form below. If a user had a similar problem with Fireboy- Xintex, LTD CG2 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)