Manual Hamilton Sundstrand Company ACT2000

45 pages 1.13 mb
Download

Go to site of 45

Summary
  • Hamilton Sundstrand Company ACT2000 - page 1

    ACT2000 Oper a tions Manual ACT2000 All-Electric Actuator SD-6008-03 ...

  • Hamilton Sundstrand Company ACT2000 - page 2

    ...

  • Hamilton Sundstrand Company ACT2000 - page 3

    This manual provides installation , maint enance, and operating instructio ns for the ACT2000 All-Electric Actuator. Every attempt has been made to provide sufficient information in this manual for the proper operation and preventive maintenance of t he actuator. It is recommended tha t the user read this manual in its entirety. Operating the ACT20 ...

  • Hamilton Sundstrand Company ACT2000 - page 4

    ACT2000 II ...

  • Hamilton Sundstrand Company ACT2000 - page 5

    ACT2000 T able of Content s Table of Contents .............................................................................................................. .......................... i 1 INTRODUCTIO N ................................................................................................................... .......... 1-1 1.1 Application . ...

  • Hamilton Sundstrand Company ACT2000 - page 6

    ACT2000 List of Figures Figure 1-1: ACT20 00 Pin Mount ed ....................................................................................1-1 Figure 1-2: ACT2000 Flange Mounted ..............................................................................1-1 Figure 1-3: ACT2000 Cut-Away View ..................................................... ...

  • Hamilton Sundstrand Company ACT2000 - page 7

    ACT2000 1 INTRODUCTION This publication covers operation, inst allation and m aintenance instructions for the ACT2000 Actuators manufactu red by Precision Engine Controls Corpo ration. 1.1 Application The ACT2000 All-Electric Actuator is d esigned to meet general industria l motion control requirements for high tempera ture hazardous location s. Ty ...

  • Hamilton Sundstrand Company ACT2000 - page 8

    ACT2000 1.3 Main Housing Assembly The main housing assem bly contains a main housing, motor cover, extension rod bearing, and associated seals. See Figure 1-3. The main housing assembly is the primary structural system component a nd supports all the b earings, motor control electronics, motor cover, and mountin gs, which forms the explo sion-proof ...

  • Hamilton Sundstrand Company ACT2000 - page 9

    ACT2000 1.4 Brushless DC Motor Assembl y A brushless DC motor powers the ACT2000 linear drive mechanism. Th e DC motor contains a stator and roto r. See Figure 1-3 Motor Stator The motor stator is attach ed to the main housing by a pre-load ed wave spring and screws. Thermistors are embedded in the stator winding s to monitor winding temperatures. ...

  • Hamilton Sundstrand Company ACT2000 - page 10

    ACT2000 1.7 Linear Drive Mechanism The Linear Drive Mechanism converts the rot ary motion of the Motor Assembly to linear actuator motion. T he core of the mechanica l drive system is the linea r ball screw drive containing a screw shaft, ball bearing fitted nut, exte nsion rod and main duplex thrust bearings. Screw Shaft The thrust bearings, mot o ...

  • Hamilton Sundstrand Company ACT2000 - page 11

    ACT2000 1.9 Identification Plate A product identificatio n plate is attached to the actuator housing assembly. Figure 1-4 shows a typical identif ication plate. The identification plate lists model de signation, product part number, revision and unit serial number. Hazardous area operation, ce rtification and electrical wiring interf ace informatio ...

  • Hamilton Sundstrand Company ACT2000 - page 12

    ACT2000 I NTENTIONALLY B LANK 1-6 ...

  • Hamilton Sundstrand Company ACT2000 - page 13

    ACT2000 2-1 2 FUNCTIONAL DESCRIPTION AND OPERA TION This section describes system fu nctions employed in the ACT2000 Electric Actuator. 2.1 System Description The ACT2000 is a closed loop servo system containing motor control electr onics (MCE) and a brushless DC motor driven ball scr ew actuator. The actuator closes its own control loop on an inte ...

  • Hamilton Sundstrand Company ACT2000 - page 14

    ACT2000 ACTUATOR DRIVER ASSY CONTROL INTERFACE MTR CURRENT MTR CURRENT RTN POWER INTERFACE REVERSE POLARITY PROTECTION 120V ACTUATOR POWER (80 - 160 VDC) RED GREEN + - INPUT TERMINATION 4-20mA OUTPUT BROWN DEMAND DEMAND RTN BLACK VIOLET GRAY ORANGE RUN RUN RTN RESET RESET RTN FAULT ALARM FAULT RTN OVERTEMP ALARM OVERTEMP RTN BRUSHLESS DC MOTOR RESO ...

  • Hamilton Sundstrand Company ACT2000 - page 15

    ACT2000 2.2.1 Power The ACT2000 operates on nominal 12 0 VDC, user-provided input voltag e via the four-wire power harness. Refer to Figure 2-2 for typical connection. Refer to section 6 for specif ication values. Primary power wires. • +120 VDC is connected to the RED wire. • The 120 VDC return wire is GREEN. Redundant power wires: • +120 VD ...

  • Hamilton Sundstrand Company ACT2000 - page 16

    ACT2000 Run Command The RUN command is a user provided discrete input to the ACT2000 which allows the actuator to track po siti on demand. The + 24 VDC signal shall be provided on the VIOLET wire. The sig nal return shall be pr ovided on the WHITE/VIOLET wire. Reset Command The RESET command is a user provided discr ete input to the ACT2000, which ...

  • Hamilton Sundstrand Company ACT2000 - page 17

    ACT2000 Motor Current Feedback The ACT2000 provides motor curren t feedback to t he user. This internally generated feedback signal is pr oportional to actua tor load. 4mA represents no load on the actuator. The motor current feedback is provid ed on the BLUE wire. The motor cu rrent feedback return is provided on the W HITE/BLUE wire. The expected ...

  • Hamilton Sundstrand Company ACT2000 - page 18

    ACT2000 2.3 Basic Operation and S t ate Description The basic operation of the ACT2000 is described in the following sect ions. The Power-Up mode section covers the P ower Up/Reset and the Set-Up states. The Run Mode section covers the Home/Dead Band, Holding Motor Current and the Run states. SET-UP POWER UP/RESET HOME DEADBAND RUN HOLDING MOTOR CU ...

  • Hamilton Sundstrand Company ACT2000 - page 19

    ACT2000 • If the ACT2000 receives a discre te RUN command, the firmware program will transition to the HOME DEAD BAND state. • If the ACT2000 receives a discrete R ESET command, the firmware progr am will continuously re set. The actuator will not function and will re main in the power-up/reset state. WARNING: Property Damage Hazard – Al ways ...

  • Hamilton Sundstrand Company ACT2000 - page 20

    ACT2000 When the mechanical stop is found (actuator velocity less 0. 05 inches per second), the MCE will apply the maximum homing force. Once the maximum homing force is applied, the firmware program will transition to the HOLDING MOTOR CURRENT state. Holding Motor Current State In the HOLDING MOTOR CURRENT state, the MCE applies a constant HOLDING ...

  • Hamilton Sundstrand Company ACT2000 - page 21

    ACT2000 2-9 If any of the health param eters are out of the normal operating range, the MCE outputs a discrete FAULT alarm to the user’s contro ller. The actuator firmware also captures the fau lt data in the EEPROM. If the motor or electronics temperature is above the normal operation range, t he MCE outputs a separate OVERTEMP alarm. The actuat ...

  • Hamilton Sundstrand Company ACT2000 - page 22

    ACT2000 This FAULT does not cl ear without RESET command. Unregulated Voltage Lo w The MCE signals a FAULT if the reference voltage drops b elow minimum f or ten (10) seconds. Should the voltage re turn to acceptabl e level, the FAULT signal is cleared. +/- 14V High/Low The MCE signals a FAULT if the internal ± 14 VDC power supplie s exceed operat ...

  • Hamilton Sundstrand Company ACT2000 - page 23

    ACT2000 2-11 2.8 ACT2000 Set-Up Parameters The ACT2000 employs several variables to define its functiona lity. These variables are called set -up parameters. These par ameters are downloaded through the RS232 interf ace to the ACT2000 u sing ActWiz soft ware. See ActWiz Software Manual for further deta ils. The user can define set up any of the fol ...

  • Hamilton Sundstrand Company ACT2000 - page 24

    ACT2000 2-12 Table 2-1 lists the set-up parameters and factory d efault settings. Parameter Factory Setting Part Number Per Drawing Actuator Type Stand Alone Command So urce Analog Home Retract Span 5.9 inches Stop Position 0.1 inches Interpolation Table Linear Position Loop Constant 20 Current Loop PID Constants Proportional 2.0 Integral 200 Deriv ...

  • Hamilton Sundstrand Company ACT2000 - page 25

    ACT2000 3 INST ALLA TION The purpose of this sectio n is to aid personnel in the installation, pla cement, and environmental considerations to be ob served for the ACT2000 and asso ciated equipment. 3.1 Inspection The ACT2000 should be inspe cted immediately after unpacking. Check for damage, paying particular atten tion to the external lead wire s ...

  • Hamilton Sundstrand Company ACT2000 - page 26

    ACT2000 3-2 Figure 3-1: ACT2000-590P Envelop e ...

  • Hamilton Sundstrand Company ACT2000 - page 27

    ACT2000 3-3 Figure 3-2: ACT2000-200F Envelo pe ...

  • Hamilton Sundstrand Company ACT2000 - page 28

    ACT2000 Note: The cl evis can be rotate d to any orientati on to support i nstallation. To rotate, loosen the four retaining s crews and rotate to desired angle. Screw p attern can be i ndexed ± 45 degre es to provid e additional adjustment . Torque the four retaining screws to 117-138 in-lbs. WARNING: Explosion Hazard – Do not remove the clevis ...

  • Hamilton Sundstrand Company ACT2000 - page 29

    ACT2000 WARNING: 94/9/EC (ATEX) Compliance – Special Condi tions for Safe Use: Two special factory -sealed unions are mounted on the equipment to en sure the electrical connection to the network and to provide the feedback signal to the user. The installation of t hese devices and the f inal connections to the conduit shall comply with the re qui ...

  • Hamilton Sundstrand Company ACT2000 - page 30

    ACT2000 Note: For proper operation of the actuator, the voltage betwee n the control inputs and the negative te rminal of the power supply should be below 200 VDC. The discrete inputs and output s are 24 VDC and are ele ctrically isolated up to 500 VAC. The recommended wiring is a fourteen -conductor shielded cab le containing twisted-pair wires wi ...

  • Hamilton Sundstrand Company ACT2000 - page 31

    ACT2000 WARNING: Property Damage Hazard – Serial inputs are not electric ally isolated. Fai lure to properly isolate the user serial interface could result in actuator or computer damage. Use separate co nduits for power and signal wiring. Close proximity to power lines may cause signal interferen ce. Shock Hazard – The serial in puts are not e ...

  • Hamilton Sundstrand Company ACT2000 - page 32

    ACT2000 Power Harness Electrical Hook-Up POWER SUPPLY ACT2000 Digital Harness Electrical Hook-Up PWR (RED) PWR [AUX] (WHT/RED) PWR RTN (GRN) PWR RTN [AUX] (WHT/G RN) Shield No Connection DEMAND (BR N) DEMAND RTN (WHT/BRN ) Shield No Connection RUN (VIO) RUN RTN (WHT/VIO) Shield No Connection RESET (GRY) RESET RTN (WHT/GRY) Shield No Connection MTR ...

  • Hamilton Sundstrand Company ACT2000 - page 33

    ACT2000 Table 3-4 shows the fa ctory wiring and refer ence signals for the ACT2000 signal harness. Note: The serial wiring is segregated from the ot her wires. Wire Color Function AWG Signals WHITE/ORANGE/YELLOW Serial/RX In 20 ± 12 V WHITE/ORANGE/BLUE Serial/TX Out 20 ± 12 V WHITE/ORANGE/GREEN Serial Return 20 0 V BLACK OVER TEMP Alarm 20 0 / 24 ...

  • Hamilton Sundstrand Company ACT2000 - page 34

    ACT2000 Power Supply Requirem ents A battery power system is recommended, Table 3 -5 lists the power supply requirements. Voltage: 120VDC nominal 80VDC minimum 160VDC maximum Max Ripple: 4 VAC RMS or 12VAC p-p Max Current: 20 AMPS Typical Continuous Cu rrent: <1 AMP Typical Transi ent Current: +20 A <60ms +10A <600 ms -5A <100 ms *Outpu ...

  • Hamilton Sundstrand Company ACT2000 - page 35

    ACT2000 4 TROUBLESHOOTING The information contained in this se ction is intende d to aid maintenance technicians in troublesho oting and isolating cause s of malfunctions in th e ACT2000. Most electrical fault isolation of the actuat or can be accomplished by using an external oscilloscope and digital voltmeter (DVM). The ACT2000 is comprised of hi ...

  • Hamilton Sundstrand Company ACT2000 - page 36

    ACT2000 Table 4-1 ACT20 00 Initial Installati on Troublesho oting Chart Symptom Prob able Causes Corrective Actio n Actuator Inoperative - FAULT alarm Power Wires not connected No or low 120 VDC power Ensure RED and GREEN wires correctly connected to Actuator Ensure 120 VDC Primary System Power at Actuator Actuator Inoperative - NO FAULT alarm No R ...

  • Hamilton Sundstrand Company ACT2000 - page 37

    ACT2000 Table 4-2 ACT20 00 In-Service Trou bleshooting Chart Symptom Prob able Causes Corrective Actio n FAULT alarm Various Upload F ault Fi le to ident ify source of f ault OVER TEMP alarm Ambient temperature limit exceeded Electronics or Mo tor winding temperatur e out of r ange Allow actuator to cool and re-start Reduce a mbient temp erature Ch ...

  • Hamilton Sundstrand Company ACT2000 - page 38

    ACT2000 I NTENTIONALLY B LANK 4-4 ...

  • Hamilton Sundstrand Company ACT2000 - page 39

    ACT2000 5 DECOMMISSIONING AND DISPOSAL This section contains recommended ACT2000 decommissioning and disposal practices. It is fo r permanent removal or replacement of the in stalled product, with no intentions of rework, overhaul , or to be used as spares. For removal follow proper lockout /t agout procedures and verify no live electrical circuits ...

  • Hamilton Sundstrand Company ACT2000 - page 40

    ACT2000 I NTENTIONALLY B LANK 5-2 ...

  • Hamilton Sundstrand Company ACT2000 - page 41

    ACT2000 6 ACT2000 GENERAL SPECIFICA TIONS Power Input Nominal Voltage: 120 VDC Minimum Voltage: 80 VDC Maximum Voltage: 160 VDC Maximum Current: 20A Typical Transient Current: +20A < 60ms; +10A < 600 ms; -5A < 100ms Typical Continuous Current: < 1A RUN and RESET Command Input ON Voltage: 12 to 32 VDC; +24 VDC Nominal ON Current: 6.5 mA ...

  • Hamilton Sundstrand Company ACT2000 - page 42

    ACT2000 I NTENTIONALLY B LANK 6-2 ...

  • Hamilton Sundstrand Company ACT2000 - page 43

    ACT2000 7 GLOSSAR Y Term Definition RUN Command A discrete 24 VDC sign al that enables the ACT 2000 extension rod t o move. RESET Command A discrete 24 VD C signal that causes the ACT2000 internal program (firmware) to jump to the be ginning. Controller A user-provided computer t hat executes comm ands to the ACT200 0 and accepts anal og and discre ...

  • Hamilton Sundstrand Company ACT2000 - page 44

    ACT2000 I NTENTIONALLY B LANK 7-2 ...

  • Hamilton Sundstrand Company ACT2000 - page 45

    ACT2000 7-1 ...

Manufacturer Hamilton Sundstrand Company Category Automobile Electronics

Documents that we receive from a manufacturer of a Hamilton Sundstrand Company ACT2000 can be divided into several groups. They are, among others:
- Hamilton Sundstrand Company technical drawings
- ACT2000 manuals
- Hamilton Sundstrand Company product data sheets
- information booklets
- or energy labels Hamilton Sundstrand Company ACT2000
All of them are important, but the most important information from the point of view of use of the device are in the user manual Hamilton Sundstrand Company ACT2000.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Hamilton Sundstrand Company ACT2000, service manual, brief instructions and user manuals Hamilton Sundstrand Company ACT2000. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Hamilton Sundstrand Company ACT2000.

A complete manual for the device Hamilton Sundstrand Company ACT2000, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Hamilton Sundstrand Company ACT2000 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Hamilton Sundstrand Company ACT2000.

A complete Hamilton Sundstrand Company manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Hamilton Sundstrand Company ACT2000 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Hamilton Sundstrand Company ACT2000, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Hamilton Sundstrand Company ACT2000, that we can find in the current document
3. Tips how to use the basic functions of the device Hamilton Sundstrand Company ACT2000 - which should help us in our first steps of using Hamilton Sundstrand Company ACT2000
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Hamilton Sundstrand Company ACT2000
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Hamilton Sundstrand Company ACT2000 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Hamilton Sundstrand Company ACT2000?

Use the form below

If you did not solve your problem by using a manual Hamilton Sundstrand Company ACT2000, ask a question using the form below. If a user had a similar problem with Hamilton Sundstrand Company ACT2000 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (1)

Gerolamo Loddo

Forno Microonde Panasonic K 123 Mf = Libretto di istruzioni = Grazie indirizzo e-mail: gelo45@tiscali.it.