    OWNER'S OPERATING MANUAL FN Series TM Rackmount UPS Plus ® Parallel or N+1 Redundant 3kVA to 24kVA Hardwire models with a 208-240Vac Input and 120Vac & 240Vac Outputs Uninterruptible Power Supply Models: FN3KRM-2, -2TX & -2TXI FN4KRM-2, -2TX & -2TXI FN5KRM-2, -2TX, & -2TXI FN6KRM-2, -2TX & -2TXI FALCON ® Electric, Inc., 5 ...

  • Falcon FN3KRM-2 - page 2

    FN Rackmount Series Parallelable and N+1 Redundant UPS Features.. . . . 3 FN -2TXI Double-Conversion On-line UPS Block Diagram. . . . . 3 Important Safety Instructions (READ FIRST) .... .4 Chapter 1. Introduction 1.1 Manual Overview. .... ..5 1.2 Brief FN Overview. .... ..5 Chapter 2. FN UPS Circuit Descriptions Galvanically Isolated Output. . . . ...

  • Falcon FN3KRM-2 - page 3

    3 FN Series TM Parallelable and N+1 Redundant UPS Features FN -2TXI Model Double Conversion On-line UPS Block Diagram Parallel Mode and N+1 Redundant Mode Operation True Double Conversion On-Line Sinewave Design Output Galvanic Isolation LCD Display with Advanced Monitoring Remote Emergency Power Off (REPO) Option Input Power Factor Correction Wide ...

  • Falcon FN3KRM-2 - page 4

    IMPORTANT SAFETY INSTRUCTIONS, SAVE THESE INSTRUCTIONS RETAIN THIS USER MANUAL! This manual contains important instructions which must be followed during the installation, operation and maintenance of the FN Series UPS, battery banks transformer box and options. Please read all instructions before operating this equipment and save this manual for f ...

  • Falcon FN3KRM-2 - page 5

    5 1.0 INTRODUCTION Manual Overview This user manual has been written to provide basic information about Falcon FN Series -2TXI rackmount models. The FN Series is a rugged, double conversion, "on-line" UPS. It has galvanic output isolation config- ured for single or dual voltage output(s). The FN Series provides continuous power conditioni ...

  • Falcon FN3KRM-2 - page 6

    6 g. One Local Maintenance Bypass Switch. The switch is located on the transformer module rear panel and provides a manual means of placing the UPS into bypass mode to allow for servicing to be performed on the UPS and battery modules. 2.0 FN RACKMOUNT UPS CIRCUIT DESCRIPTIONS Galvanically Isolated Output The FN -2TXI output isolation transformer m ...

  • Falcon FN3KRM-2 - page 7

    Battery Packs FN rackmount battery modules utilize flame retardant batteries. They consist of (20) 12V, 7AH valve-regulat- ed, sealed lead acid (VRLA) batteries in each module (Yuasa NP7-12). See replacement instructions on page 34. To maintain the optimum battery life, the UPS should be installed in an environment with an ambient temperature of 68 ...

  • Falcon FN3KRM-2 - page 8

    8 3.0 UNPACKING THE UPS AND BATTERY BANK Due to their size and weight the FN rackmount UPS, battery and transformer modules are packaged inside shipping cartons that are secured to a shipping pallet. Removal of the UPS, transformer and battery bank modules should never be attempted by one person. Upon unpacking the UPS, transformer or battery bank, ...

  • Falcon FN3KRM-2 - page 9

    9 4.0 PRE-INSTALLATION DETAILS Falcon Electric, Inc. is not responsible for shipping damage or for filing shipping damage claims. Visually inspect the equipment for freight damage. If any equipment has been damaged during shipment, retain the shipping pallet and packing materials for inspection by the carrier, and immediately file a claim for “sh ...

  • Falcon FN3KRM-2 - page 10

    4.2 UPS Input Power Requirements a. VERIFY THE PROPER UPS INPUT POWER IS AVAILABLE (for each UPS installed) FN3KRM-2TXI Input -- Hardwire, 208-240Vac, 50/60Hz, 20A, single-phase, 2 wire plus ground FN4KRM-2TXI Input -- Hardwire, 208-240Vac, 50/60Hz, 30A, single-phase, 2 wire plus ground FN5KRM-2TXI Input -- Hardwire, 208-240Vac, 50/60Hz, 30A, singl ...

  • Falcon FN3KRM-2 - page 11

    4.4 UPS Output Rating Details a. VERIFY THE LOAD TO BE CONNECTED DOES NOT EXCEED THE UPS OUTPUT RATING for the single or combined paralleled UPS units. (1) FN3KRM-2TXI Not N+1 Hardwire, 120/240Vac, 2,100W, split-phase, 3 wire plus ground (2) FN3KRM-2TXI Not N+1 4,200W N+1 2,100W (3) FN3KRM-2TXI Not N+1 6,300W N+1 4,200W (4) FN3KRM-2TXI Not N+1 8,40 ...

  • Falcon FN3KRM-2 - page 12

    4.6 Output Transformer Module Hardwire Terminal Block Wiring Details 12 4.7 UPS Module Hardwire Terminal Block Wiring Details ...

  • Falcon FN3KRM-2 - page 13

    4.8 System Installation Wiring Diagram (single rackmount UPS system) 4.9 System Installation Wiring Diagram (typical multiple parallel UPS units, Rackmount) 13 4.10 UPS & Transformer Modules Communications Bus Cabling Use one UA88385 parallel communications bus cabling kit for each UPS to be connected to the system output trans- former module o ...

  • Falcon FN3KRM-2 - page 14

    4.11 External Battery Charger Option Installation Wiring Detail (Typical UPS unit with optional FN6KBC-5A-2, for use with external battery banks only) FN6KBC-5A-2 5 Amp External Battery Charger Module FN6KBC-5A-2 Battery Charger Module Terminal Block Wiring Details Battery Charger Module/UPS System Wiring Diagram 14 ...

  • Falcon FN3KRM-2 - page 15

    2. When the LCD is in the “Display Programmed Settings” mode, depressing the Function Button will return the LCD to normal mode. The LCD display will also return to “Normal Mode” automatically after 30 seconds of button inactivity. Previous Page/Change Setting Button 1. When the LCD display is in “Normal Mode”, repeated pressing of this ...

  • Falcon FN3KRM-2 - page 16

    Next Page Button 1. When the LCD display is in “Normal Mode”, repeated pressing of this button will sequence down through the input/output/battery parameters and readings. 2. When the UPS is displaying “OFF” or “BPS”, depressing the “Next Page” and “Function” buttons at the same time will place the UPS into “Programming Mode? ...

  • Falcon FN3KRM-2 - page 17

    5.4 LCD Display Overview LCD Display 5.5 LCD Icon Descriptions 1. Bypass input is out of tolerance, UPS failed to transfer to bypass, or bypass input is out of tolerance when the UPS is in Economy/Green Mode. 2. Utility loss or the utility input is out of tolerance. 3. UPS lost inverter output and transferred to bypass. 4. Battery voltage is out of ...

  • Falcon FN3KRM-2 - page 18

    Er04 -- Error code 04 indicates the UPS inverter has malfunctioned. Contact Falcon Service. Er05 -- Error code 05 indicates the UPS batteries are weak or dead and must be replaced. Call Falcon Service upon receiving the message for further instructions. Er06 -- Error code 06 indicates the UPS output has a short circuit connected to it. Remove the c ...

  • Falcon FN3KRM-2 - page 19

    6.0 OPERATION The following sections outline the operation and programming of the FN -2TXI UPS models. Please read and understand them completely prior to connecting any equipment to the UPS output. 6.1 How to start up the UPS with utility power present 1. Verify the UPS input wiring is correct and connected to a live circuit. 2. Turn on the UPS an ...

  • Falcon FN3KRM-2 - page 20

    If the UPS passes the self-test, “OK” is displayed. If the UPS fails the self-test, “FAIL” is displayed alternately with an error code. Please note the error code and contact Falcon Service. The UPS is now turned on and in on-line inverter mode. Using an AC volt meter, verify the UPS input voltage measurement. 20 ...

  • Falcon FN3KRM-2 - page 21

    6.2 How to start up the UPS without utility power present (Cold Start) 1. Press the “On” button for 6 seconds to awaken the UPS. The UPS will beep twice and display G below. Immediately upon G being displayed, press the “On” button for another 6 seconds. The UPS will beep twice again and sequence through H and I. After depressing the “On? ...

  • Falcon FN3KRM-2 - page 22

    6.5 How to display readings 1. The bypass input voltage is displayed immediately after the UPS and Bypass circuit breakers are turned on and has sequenced up to inverter mode as shown in I1. Depressing the “Next Page” button will change to display the utility frequency as shown in J below. The “b” denotes the reading is for the bypass. The ...

  • Falcon FN3KRM-2 - page 23

    Depress the “Next Page” button. The arrow next to the battery icon indicates the reading is for the battery voltage. Depress the “Next Page” button. The degree C symbol indicates the reading is for the internal UPS temperature. Depressing the “Next Page” button again will return the display to reading I1. 23 ...

  • Falcon FN3KRM-2 - page 24

    24 6.6 How to Display Programmed Settings 1. The UPS must be turned on and operating in on-line inverter mode prior to attempting to read the “programmed settings”. 2. Depress the “Function” button and the following first function parameter will be displayed: The first function status displayed will be the audible alarm buzzer status. It is ...

  • Falcon FN3KRM-2 - page 25

    Note: The following functions are a continuation from the previous page. These functions can only be displayed and must have their settings changed using another programming method referenced later in the manual. As the other programming method requires turning the UPS off to perform, they are accessible here as a convenient reference while the UPS ...

  • Falcon FN3KRM-2 - page 26

    26 Fixed or constant frequency output mode: In normal mode the UPS output frequency will automatically be set to the utility frequency and is synchronized with that frequency. When set to cf50Hz mode, the UPS inverter output frequency will always be 50Hz. When set to cf60Hz mode, the UPS inverter output frequency will always be 60Hz. Setting the UP ...

  • Falcon FN3KRM-2 - page 27

    6.7 How to Change the Programmed Settings Note: The UPS must be placed into Off / Bypass mode prior to attempting to change the following parameter settings. 1. To enter programming mode depress the “On” and “Next Page” buttons at the same time and hold them down until the UPS sounds two beeps. The audible alarm status parameter setting wil ...

  • Falcon FN3KRM-2 - page 28

    The next parameter displayed shows the “bypass input voltage acceptable window” setting. The voltage window can be set to “Lo” (184-260Vac) or “Hi” (195-260Vac), which is shown below. To change the settings, depress the “Previous Page/Change Setting” button. To change to the alternate setting, press the button again. All setting cha ...

  • Falcon FN3KRM-2 - page 29

    29 The following V1, V2, V3 and V4 show the operational status setting of the UPS. This function may be set to one of four modes. “Normal”: which indicates none of the other modes are set. The Economy/Green Mode: indicates the UPS will automatically transfer to bypass mode to save energy, should the output load drop below 10% of the UPS output ...

  • Falcon FN3KRM-2 - page 30

    30 The next parameter displayed shows the UPS unit address. If only one UPS is being used, the address should be set to “d0” as shown. If multiple parallel UPS units are connected on a parallel configu- ration of 6, 12, 18 or 24kVA, or 6, 12, 18kVA N+1 operation, the units would be addressed “d0”, “d1”, “d2” and “d3”. See the pa ...

  • Falcon FN3KRM-2 - page 31

    31 6.8 How to Use the Maintenance Bypass Switch Located on the Rear Panel IMPORTANT: Improper use of the internal Maintenance Bypass Switch will void the equipment warranty. The following instructions must be followed whenever this switch is used. 1. Press the”Off/Bypass” button for 5 seconds to place the UPS into bypass mode. 2. On the rear of ...

  • Falcon FN3KRM-2 - page 32

    7.0 COMMUNICATIONS All FN models are provided with the following communication ports: RS-232 port with standard DB-9F serial port connector located on the UPS module rear panel. Two advanced communications option slots are provided on the rear panel of the UPS module. Unless an advanced communications option board has been previously purchased and ...

  • Falcon FN3KRM-2 - page 33

    The supplied Falcon RS-232 interface cable pin designations are as follows: The computer RS-232 Port settings should be set to the following: 7.3 Optional Remote Emergency Power Off (REPO) A two-pin REPO connector (green connector) is located on the UPS module rear panel. The connector is shipped with no jumper wire installed, and is a normally ope ...

  • Falcon FN3KRM-2 - page 34

    UA88382 USB Interface Option Card This option card supports the connection of (1) USB interface cable for use with UPSilon remote monitoring, management and unattended O/S shutdown software. UA88383 Dry Contact Interface Option Card This card provides dry contact closure signals for UPS on bypass, utility normal, inverter on, low battery, abnormal ...

  • Falcon FN3KRM-2 - page 35

    8.0 MAINTENANCE T he FN Series UPS requires very little maintenance. The batteries are located inside the battery module and consist of (20) Yuasa 12V, 7AH or equivalent, sealed, VRLA, maintenance-free, lead-acid batteries. Batteries must be kept recharged to prevent excessive self-discharging, which may result in their premature failure. When conn ...

  • Falcon FN3KRM-2 - page 36

    9.0 PARALLEL MODE OPERATION 9.1 How to configure FN rackmount models for transformer module, parallel or N+1 mode operation. Up to (4) like kVA FN model UPS units may be connected to their respective transformer modules and/or in parallel, in single UPS increments, to provide a single 3-24kVA UPS output a true N+1 redundant output. This is accompli ...

  • Falcon FN3KRM-2 - page 37

    10.0 ENVIRONMENTAL 10.1 Recycling the Used Battery Packs NEVER discard the UPS module, the UPS battery module, the transformer module or batteries in the trash. Contact your local recycling or hazardous waste center for information on proper disposal of the used battery pack and batteries. The entire spent battery packs may be returned to the Falco ...

  • Falcon FN3KRM-2 - page 38

    11.0 TECHNICAL SUPPORT In the event your FN Series UPS requires service or should any other technical support be required, write, call, fax or email Falcon Service. Falcon Electric, Inc. 5106 Azusa Canyon Road Irwindale, CA. 91706 Service 800.842.6940 Voice 626.962.7770 Fax 626.962.7720 Email: service@falconups.com WWW.FALCONUPS.COM Please have you ...

  • Falcon FN3KRM-2 - page 39

    39 FALCON ELECTRIC, INC. NEW PRODUCT LIMITED WARRANTY Limited Warranty: Falcon warrants that this product will be free from defects in materials and workmanship for a period of two years from the date of shipment by Falcon. Procedures: Any defective product must be returned to Falcon. No product can be returned without first obtaining a Return Mate ...

  • Falcon FN3KRM-2 - page 40

    40 Falcon Electric, Inc. - 5106 Azusa Canyon Rd. - Irwindale, CA 91706 - 800.842.6940 Fax 626.962.7720 www.falconups.com - email: sales@falconups.com FN Series TM UPS PLUS ® 3kVA - 12kVA ...

  • Falcon FN3KRM-2 - page 41

    41 Falcon Electric, Inc. - 5106 Azusa Canyon Rd. - Irwindale, CA 91706 - 800.842.6940 Fax 626.962.7720 www.falconups.com - email: sales@falconups.com FN Series TM UPS PLUS ® 4kVA - 16kVA ...

  • Falcon FN3KRM-2 - page 42

    FN Series TM UPS PLUS ® 5kVA - 20kVA 42 ...

  • Falcon FN3KRM-2 - page 43

    43 FN Series TM UPS PLUS ® 6kVA - 24kVA Falcon Electric, Inc. - 5106 Azusa Canyon Rd. - Irwindale, CA 91706 - 800.842.6940 - Fax 626.962.7720 www.falconups.com ...

Manufacturer Falcon Category Power Supply

Documents that we receive from a manufacturer of a Falcon FN3KRM-2 can be divided into several groups. They are, among others:
- Falcon technical drawings
- FN3KRM-2 manuals
- Falcon product data sheets
- information booklets
- or energy labels Falcon FN3KRM-2
All of them are important, but the most important information from the point of view of use of the device are in the user manual Falcon FN3KRM-2.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Falcon FN3KRM-2, service manual, brief instructions and user manuals Falcon FN3KRM-2. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Falcon FN3KRM-2.

Similar manuals

A complete manual for the device Falcon FN3KRM-2, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Falcon FN3KRM-2 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Falcon FN3KRM-2.

A complete Falcon manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Falcon FN3KRM-2 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Falcon FN3KRM-2, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Falcon FN3KRM-2, that we can find in the current document
3. Tips how to use the basic functions of the device Falcon FN3KRM-2 - which should help us in our first steps of using Falcon FN3KRM-2
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Falcon FN3KRM-2
5. FAQ - Frequently Asked Questions