    USER'S MANUAL - Analog Control Edition FX 3G /FX 3U /FX 3UC SERIES PROGRAMMABL E CONTROLLERS FX 3U -4AD-ADP Voltag e / Curre nt Inpu t FX 3UC -4AD FX 3U -4AD-PT-ADP FX 3U -4AD-PTW -ADP Temperature Sensor Input FX 3U -4AD FX 3U -4AD-TC-ADP FX 3U -4AD-PNK-A DP FX 3G -2AD-BD Voltag e / Curre nt Outpu t FX 3U -4DA-ADP FX 3U -4DA FX 3G -1DA-BD Volt ...

  • Mitsubishi Electronics MELSEC-F - page 2

    ...

  • Mitsubishi Electronics MELSEC-F - page 3

    (1) Safety Precautions (Read these precautions before use.) Before installation, operation, maintenance or inspection of this product, thoroughly read through and understand this manual and all of the associated manuals. Also, take care to handle the module properly and safely. This manual classifies the safety precautions into two categories: and ...

  • Mitsubishi Electronics MELSEC-F - page 4

    (2) Safety Precautions (Read these precautions before use.) 2. WIRING PRECAUTIONS 3. STARTUP AND MAINTENANC E PRECAUTIONS • Make sure to cut off all phases of the po wer su pply exter nally before attempting wiring work . Failure to do so may ca use electric shock or damages to th e product. • Connect the DC power supp ly wiring to th e dedicat ...

  • Mitsubishi Electronics MELSEC-F - page 5

    1 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G /FX 3U /FX 3UC Series Programmable Controllers User's Manual [Analog Control Edition] Foreword This manual describes the "analog" function of the MELSEC-F FX Series programmable controllers and should be read and understood before attempting to install or u ...

  • Mitsubishi Electronics MELSEC-F - page 6

    2 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Outline Precautions • This manual provides information for the use of the FX 3U Series Programmable Controllers. The manual has been written to be used by trained and competent personnel. The definition of such a person o r persons is as follows; 1) Any engineer who is respon ...

  • Mitsubishi Electronics MELSEC-F - page 7

    3 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents Table of Contents SAFETY PRECAUTIONS .................................................... ........................................... ... (1) Common Items 1. Introduction A-1 1.1 Outline and Features of Analog Control .......................................... ...

  • Mitsubishi Electronics MELSEC-F - page 8

    4 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents 4.4 Temperature Sensor Input .................................................................................................. .......A-39 4.4.1 FX 3U -4AD-PT-ADP ....... ........... .............. .............. .............. ........... .............. .... ...

  • Mitsubishi Electronics MELSEC-F - page 9

    5 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents FX 3U -4AD (4-channel Analog Input) FX 3UC -4AD (4-channel Anal og Input) 1. Outline B-3 1.1 Outline of Functions ...................................................................................................... ...............B-3 1.2 Setup Procedure Befo ...

  • Mitsubishi Electronics MELSEC-F - page 10

    6 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents 5.4.11 BFM #28: Over-scale status ................. .............. ................. .............. .............. .............. ... ........B-36 5.4.12 BFM #29: Error status ............ .............. .............. .............. .............. ........... ...

  • Mitsubishi Electronics MELSEC-F - page 11

    7 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents FX 3U -4AD-ADP (4-chann el anal og Input) 1. Outline C-3 1.1 Outline of Functions ...................................................................................................... .............. C-3 1.2 Setup Procedure Before Starting Operation .......... ...

  • Mitsubishi Electronics MELSEC-F - page 12

    8 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents FX 3G -2AD-BD (2-chann el anal og Input) 1. Outline D-3 1.1 Outline of Functions ...................................................................................................... .............. D-3 1.2 Setup Procedure Before Starting Operation ........... ...

  • Mitsubishi Electronics MELSEC-F - page 13

    9 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents FX 3U -4DA (4-channel Analog Output) 1. Outline E-3 1.1 Outline of Functions ...................................................................................................... ...............E-3 1.2 Setup Procedure Before Starting Operation ............... ...

  • Mitsubishi Electronics MELSEC-F - page 14

    10 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents 5.4.17 BFM #50: Setting of output corrective function by load resistance (only in voltage ou tput mode)/BFM #51 to #54: L oad resistance values ... ........... ............ .....E-33 5.4.18 BFM #60: Status automatic transfer function set ting ........ ....... ...

  • Mitsubishi Electronics MELSEC-F - page 15

    11 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents FX 3U -4DA-ADP (4-chann el anal og Output) 1. Outline F-3 1.1 Outline of Functions ...................................................................................................... ............... F-3 1.2 Setup Procedure Before Starting Operation ....... ...

  • Mitsubishi Electronics MELSEC-F - page 16

    12 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents FX 3G -1DA-BD (1-channel analog Output) 1. Outline G-3 1.1 Outline of Functions ...................................................................................................... .............. G-3 1.2 Setup Procedure Before Starting Operation ........... ...

  • Mitsubishi Electronics MELSEC-F - page 17

    13 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents FX 3U -3A-ADP (2-channel analog Input, 1-channel analog output) 1. Outline H-3 1.1 Outline of Functions ...................................................................................................... .............. H-3 1.2 Setup Procedure Before Starti ...

  • Mitsubishi Electronics MELSEC-F - page 18

    14 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents 6. Troubleshooting H-34 6.1 PLC Version Number Check .................................................................................................. ... H-34 6.2 Wiring Check ................................................................................. ...

  • Mitsubishi Electronics MELSEC-F - page 19

    15 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents FX 3U -4AD-PT-ADP (4-channel Platinum Resistan ce Thermometer Data Input) 1. Outline I-3 1.1 Outline of Functions ...................................................................................................... ...... .......... I-3 1.2 Setup Procedure ...

  • Mitsubishi Electronics MELSEC-F - page 20

    16 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents FX 3U -4AD-PTW-ADP (4-channel Platinum Resistan ce Thermometer Data Input) 1. Outline J-3 1.1 Outline of Functions ...................................................................................................... ............... J-3 1.2 Setup Procedure B ...

  • Mitsubishi Electronics MELSEC-F - page 21

    17 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents FX 3U -4AD-PNK-ADP (4-cha nnel Resistance Thermometer Data Input) 1. Outline K-3 1.1 Outline of Functions ...................................................................................................... ...............K-3 1.2 Setup Procedure Before Star ...

  • Mitsubishi Electronics MELSEC-F - page 22

    18 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents FX 3U -4AD-TC-ADP (4-c hannel Thermocouple Data Input) 1. Outline L-3 1.1 Outline of Functions ...................................................................................................... ............... L-3 1.2 Setup Procedure Before Starting Opera ...

  • Mitsubishi Electronics MELSEC-F - page 23

    19 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents PID Instruction (FNC 88) 1. Outline M-3 1.1 Outline of functi on ....................................................................................................... ................ M-3 1.2 Basic Operation Expressions in PID Instruction (Reference)....... ...

  • Mitsubishi Electronics MELSEC-F - page 24

    20 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Table of Contents MEMO ...

  • Mitsubishi Electronics MELSEC-F - page 25

    A-1 1 Introduction 1.1 Outline and Features of Analog Control FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 1. Introduction This manu ...

  • Mitsubishi Electronics MELSEC-F - page 26

    A-2 1 Introduction 1.1 Outline and Features of Analog Control FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 1.1 Outline and Features of Analog Control 1.1.1 Analog input control Input the voltage/current signal from a flowmeter, pressure sensor, etc. to the PLC to monitor the condition of the workpiece or equipm ...

  • Mitsubishi Electronics MELSEC-F - page 27

    A-3 1 Introduction 1.1 Outline and Features of Analog Control FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 1.1.2 Analog output contr ...

  • Mitsubishi Electronics MELSEC-F - page 28

    A-4 1 Introduction 1.1 Outline and Features of Analog Control FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 1.1 Outline and Features of Analog Control 1.1.3 Temperature se nsor input control Use the PLC to check the workpiece/machine tem perature measured with a thermocouple or platinum resistance thermome ter s ...

  • Mitsubishi Electronics MELSEC-F - page 29

    A-5 2 Descri ption of Anal og Products 2.1 Types of Analog Products FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 2. Description of A ...

  • Mitsubishi Electronics MELSEC-F - page 30

    A-6 2 Descri ption of Anal og Products 2.1 Types of Analog Products FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 2.1 Types of Analog Products 2.1.2 Special adapter The analog special adapter uses PLC devices to send/receive data to/from the PLC. 1. FX 3U Series PLC • Connect the special adapter(s) to the left ...

  • Mitsubishi Electronics MELSEC-F - page 31

    A-7 2 Descri ption of Anal og Products 2.1 Types of Analog Products FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 3. FX 3UC -32MT-LT( ...

  • Mitsubishi Electronics MELSEC-F - page 32

    A-8 2 Descri ption of Anal og Products 2.1 Types of Analog Products FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 2.1 Types of Analog Products 2.1.3 Special function block The special function block uses buffer memory (BFM) to send/receive data to/from the PLC. 1. FX 3U Series PLC • Connect the special functio ...

  • Mitsubishi Electronics MELSEC-F - page 33

    A-9 2 Descri ption of Anal og Products 2.2 List of Analog Product Models FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 2.2 List of An ...

  • Mitsubishi Electronics MELSEC-F - page 34

    A-10 2 Descri ption of Anal og Products 2.2 List of Analog Product Models FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 2.2 List of Analog Product Models 2.2.3 Special function block Type No. of channels Range Resolution Function Refer- ence Voltage/current i nput FX 3U -4AD *1 4ch Voltage: -10V to +10V DC 0.32m ...

  • Mitsubishi Electronics MELSEC-F - page 35

    A-11 2 Descri ption of Anal og Products 2.2 List of Analog Product Models FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP Voltage/curre ...

  • Mitsubishi Electronics MELSEC-F - page 36

    A-12 3 System Configuration Drawing s of Analog Products 3.1 FX3U Series PLC FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 3.1 FX3U Series PLC 3. System Configuration Drawings of Analog Products This section shows drawings to describe the configuration of analog units for the FX 3U /FX 3UC /FX 3G Series PLC. 3.1 ...

  • Mitsubishi Electronics MELSEC-F - page 37

    A-13 3 System Configuration Drawing s of Analog Products 3.1 FX3U Series PLC FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 3.1.2 Conn ...

  • Mitsubishi Electronics MELSEC-F - page 38

    A-14 3 System Configuration Drawing s of Analog Products 3.2 FX3UC Series PLC FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 3.2 FX3UC Series PLC 3.2 FX 3UC Series PLC 3.2.1 Connection of special adapters 1. FX 3UC (D, DSS) Series PLC European terminal bl ock European terminal bl ock European terminal bl ock Euro ...

  • Mitsubishi Electronics MELSEC-F - page 39

    A-15 3 System Configuration Drawing s of Analog Products 3.2 FX3UC Series PLC FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 2. FX 3UC ...

  • Mitsubishi Electronics MELSEC-F - page 40

    A-16 3 System Configuration Drawing s of Analog Products 3.2 FX3UC Series PLC FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 3.2 FX3UC Series PLC 3.2.2 Connection of special function blocks 1. FX 3UC (D, DSS) Series PLC • For a detailed description of special function block connectability and system configurati ...

  • Mitsubishi Electronics MELSEC-F - page 41

    A-17 3 System Configuration Drawing s of Analog Products 3.2 FX3UC Series PLC FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 2. FX 3UC ...

  • Mitsubishi Electronics MELSEC-F - page 42

    A-18 3 System Configuration Drawing s of Analog Products 3.3 FX3G Series PLC FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 3.3 FX3G Series PLC 3.3 FX 3G Series PLC 3.3.1 Connection of expansion boards, special adapters 1. FX 3G Series PLC (14-point, 24-point type) and represent the connecting positions. For a de ...

  • Mitsubishi Electronics MELSEC-F - page 43

    A-19 3 System Configuration Drawing s of Analog Products 3.3 FX3G Series PLC FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 2. FX 3G S ...

  • Mitsubishi Electronics MELSEC-F - page 44

    A-20 3 System Configuration Drawing s of Analog Products 3.3 FX3G Series PLC FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 3.3 FX3G Series PLC 3.3.2 Connection of special function blocks • For a detailed description of the connectable special function blocks and system configuration: → Refer to the FX 3G Ser ...

  • Mitsubishi Electronics MELSEC-F - page 45

    A-21 4 Comparison of Pe rformance Spe cifications 4.1 Analog Input FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 4. Comparison of Per ...

  • Mitsubishi Electronics MELSEC-F - page 46

    A-22 4 Comparison of Pe rformance Spe cifications 4.1 Analog Input FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 4.1 Analog Input 4.1.2 FX 2N -2AD *1. For FX 2N -2AD, combined use of the vol tage and current inputs is not possi ble. *2. Use the adju stment volume to adjust FX 2N -2AD. *3. Adjustment of the offse ...

  • Mitsubishi Electronics MELSEC-F - page 47

    A-23 4 Comparison of Pe rformance Spe cifications 4.1 Analog Input FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 4.1.3 FX 3U -4AD *1. ...

  • Mitsubishi Electronics MELSEC-F - page 48

    A-24 4 Comparison of Pe rformance Spe cifications 4.1 Analog Input FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 4.1 Analog Input 4.1.4 FX 2N -4AD *1. Adjustment of the offset or gain value will not aff ect the resolution. *2. The offset and the gain shoul d satisfy the following condition: 1V ≤ (Gain - Offset ...

  • Mitsubishi Electronics MELSEC-F - page 49

    A-25 4 Comparison of Pe rformance Spe cifications 4.1 Analog Input FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 4.1.5 FX 3UC -4AD *1 ...

  • Mitsubishi Electronics MELSEC-F - page 50

    A-26 4 Comparison of Pe rformance Spe cifications 4.1 Analog Input FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 4.1 Analog Input 4.1.6 FX 2NC -4AD *1. Adjustment of the offset or gain value will not affect the resoluti on. In the direct indi cation mode, however, the offset/gain cannot be a djusted. *2. The off ...

  • Mitsubishi Electronics MELSEC-F - page 51

    A-27 4 Comparison of Pe rformance Spe cifications 4.1 Analog Input FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 4.1.7 FX 2N -8AD *1. ...

  • Mitsubishi Electronics MELSEC-F - page 52

    A-28 4 Comparison of Pe rformance Spe cifications 4.1 Analog Input FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 4.1 Analog Input 4.1.8 FX 3G -2AD-BD Specifications FX 3G -2AD-BD Voltage input Current inpu t Number of input points 2ch Analog inp ut range 0V to 10V DC (Input resistance: 198 .7 k Ω ) 4mA to 20mA ...

  • Mitsubishi Electronics MELSEC-F - page 53

    A-29 4 Comparison of Pe rformance Spe cifications 4.2 Analog Output FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 4.2 Analog Output 4 ...

  • Mitsubishi Electronics MELSEC-F - page 54

    A-30 4 Comparison of Pe rformance Spe cifications 4.2 Analog Output FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 4.2 Analog Output 4.2.2 FX 2N -2DA *1. Use the adju stment volume to adjust the FX 2N -2DA. *2. Adjustment of the offset or gain value will cha nge the resolution . Specifications FX 2N -2DA Voltage ...

  • Mitsubishi Electronics MELSEC-F - page 55

    A-31 4 Comparison of Pe rformance Spe cifications 4.2 Analog Output FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 4.2.3 FX 3U -4DA *1 ...

  • Mitsubishi Electronics MELSEC-F - page 56

    A-32 4 Comparison of Pe rformance Spe cifications 4.2 Analog Output FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 4.2 Analog Output 4.2.4 FX 2N -4DA *1. Adjustment of the offset or gain value will not aff ect the resolution. *2. The offset and the gain shoul d satisfy the following condition:1 1V ≤ (Gain - Off ...

  • Mitsubishi Electronics MELSEC-F - page 57

    A-33 4 Comparison of Pe rformance Spe cifications 4.2 Analog Output FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 4.2.5 FX 2NC -4DA * ...

  • Mitsubishi Electronics MELSEC-F - page 58

    A-34 4 Comparison of Pe rformance Spe cifications 4.2 Analog Output FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 4.2 Analog Output 4.2.6 FX 3G -1DA-BD Specifications FX 3G -1DA-BD Voltage output Current output Number of output points 1ch Analog outp ut range 0V to 10V DC (External load: 2k to 1M Ω ) 4mA to 20m ...

  • Mitsubishi Electronics MELSEC-F - page 59

    A-35 4 Comparison of Pe rformance Spe cifications 4.3 Mixed Analog Input/Output FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 4.3 Mix ...

  • Mitsubishi Electronics MELSEC-F - page 60

    A-36 4 Comparison of Pe rformance Spe cifications 4.3 Mixed Analog Input/Output FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 4.3 Mixed Analog Input/Output 4.3.2 FX 2N -5A 1. Analog input Specifications FX 2N -5A Voltage input Current input Number of input poin ts 4ch Analog inp ut range -10V to +10V DC -100mV t ...

  • Mitsubishi Electronics MELSEC-F - page 61

    A-37 4 Comparison of Pe rformance Spe cifications 4.3 Mixed Analog Input/Output FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 2. Anal ...

  • Mitsubishi Electronics MELSEC-F - page 62

    A-38 4 Comparison of Pe rformance Spe cifications 4.3 Mixed Analog Input/Output FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 4.3 Mixed Analog Input/Output 4.3.3 FX 0N -3A *1. Combined use of voltage and current inputs is not possible. *2. Adjustment of the volume (offset or gain) value will change the resolutio ...

  • Mitsubishi Electronics MELSEC-F - page 63

    A-39 4 Comparison of Pe rformance Spe cifications 4.4 Temperature Sensor Input FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 4.4 Temp ...

  • Mitsubishi Electronics MELSEC-F - page 64

    A-40 4 Comparison of Pe rformance Spe cifications 4.4 Temperature Sensor Input FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 4.4 Temperature Sensor Input 4.4.2 FX 3U -4AD-PTW-ADP Specifications FX 3U -4AD-PTW-ADP Centigrade( ° C) Fahrenh eit( ° F) Number of input points 4ch Input signal 3-wire plat inum resist ...

  • Mitsubishi Electronics MELSEC-F - page 65

    A-41 4 Comparison of Pe rformance Spe cifications 4.4 Temperature Sensor Input FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 4.4.3 FX ...

  • Mitsubishi Electronics MELSEC-F - page 66

    A-42 4 Comparison of Pe rformance Spe cifications 4.4 Temperature Sensor Input FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 4.4 Temperature Sensor Input 4.4.4 FX 3U -4AD-TC-ADP Specifications FX 3U -4AD-TC-ADP Centigrade( ° C) Fahrenheit ( ° F) Number of input points 4ch Input signal Thermocouple ty pe K or J ...

  • Mitsubishi Electronics MELSEC-F - page 67

    A-43 4 Comparison of Pe rformance Spe cifications 4.4 Temperature Sensor Input FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 4.4.5 FX ...

  • Mitsubishi Electronics MELSEC-F - page 68

    A-44 4 Comparison of Pe rformance Spe cifications 4.4 Temperature Sensor Input FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 4.4 Temperature Sensor Input 4.4.6 FX 2N -4AD-TC Specifications FX 2N -4AD-TC Centigrade( ° C) Fahrenh eit( ° F) Number of input points 4ch Input signal Thermocouple type K or J JIS C 16 ...

  • Mitsubishi Electronics MELSEC-F - page 69

    A-45 4 Comparison of Pe rformance Spe cifications 4.4 Temperature Sensor Input FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 4.4.7 FX ...

  • Mitsubishi Electronics MELSEC-F - page 70

    A-46 4 Comparison of Pe rformance Spe cifications 4.4 Temperature Sensor Input FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 4.4 Temperature Sensor Input 4.4.8 FX 2N -2LC *1. For FX 2N -2LC, the rated temperature range, digital output val ue, and resolution dep end on the selected sensor and mode. *2. Accuracy i ...

  • Mitsubishi Electronics MELSEC-F - page 71

    A-47 5 Version Numb er 5.1 PLC Main Unit FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ADP 5. Version Number 5.1 PLC Main Unit 5.1.1 Manu ...

  • Mitsubishi Electronics MELSEC-F - page 72

    A-48 5 Version Numb er 5.2 Special adapter FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 5.2 Special adapter 5.1.2 Version check Special data register D8001 contains information for determining the PLC version number. 5.2 Special adapter 5.2.1 Manufacturer's seri al number check method 1. Checking the namep ...

  • Mitsubishi Electronics MELSEC-F - page 73

    A-49 6 Manual Introd uction (Types, Co ntents, and Obtainment) 6.1 How to Use the Manuals FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - A ...

  • Mitsubishi Electronics MELSEC-F - page 74

    A-50 6 Manual Introd uction (Types, Co ntents, and Obtainment) 6.2 Description of Related Manuals FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 6.2 Description of Related Manuals 6.2 Description of Related Manuals The main manuals necessary for the use of analog products are described below. These manuals are cl ...

  • Mitsubishi Electronics MELSEC-F - page 75

    A-51 6 Manual Introd uction (Types, Co ntents, and Obtainment) 6.2 Description of Related Manuals FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD ...

  • Mitsubishi Electronics MELSEC-F - page 76

    A-52 6 Manual Introd uction (Types, Co ntents, and Obtainment) 6.2 Description of Related Manuals FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 6.2 Description of Related Manuals 6.2.3 Manuals of analog units The manuals of various analog units are described below: Manual type Document number Supplied with produ ...

  • Mitsubishi Electronics MELSEC-F - page 77

    A-53 6 Manual Introd uction (Types, Co ntents, and Obtainment) 6.2 Description of Related Manuals FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD ...

  • Mitsubishi Electronics MELSEC-F - page 78

    A-54 7 Generic Na mes and A bbreviations in This Manu al 6.2 Description of Related Manuals FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 6.2 Description of Related Manuals 7. Generic Names and Abbreviations in This Manual 1. Main unit 2. Expansion board and special adapter Abbreviation, generic name Description ...

  • Mitsubishi Electronics MELSEC-F - page 79

    A-55 7 Generic Na mes and A bbreviations in This Manu al 6.2 Description of Related Manuals FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD-PT - ADP J FX 3U -4AD-PTW - ...

  • Mitsubishi Electronics MELSEC-F - page 80

    A-56 7 Generic Na mes and A bbreviations in This Manu al 6.2 Description of Related Manuals FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Common Items 6.2 Description of Related Manuals 4. Peripheral unit 5. Manual Abbreviation, generic name Description Peripheral unit Peripheral unit Generic name for programming softwar e, ...

  • Mitsubishi Electronics MELSEC-F - page 81

    B-1 A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) FX 3G /FX 3U /FX 3UC Series Programmable Contro ...

  • Mitsubishi Electronics MELSEC-F - page 82

    B-2 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) ...

  • Mitsubishi Electronics MELSEC-F - page 83

    B-3 1 Outline 1.1 Outline of F unctions A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 1. Outline ...

  • Mitsubishi Electronics MELSEC-F - page 84

    B-4 1 Outline 1.2 Setup Procedure Before Starting Operation FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 1.2 Setup Procedure Befo re Starting Operation Before starting to use the 4AD, follow the procedure below to set up the system: Specific ations: • Operation environm ent ...

  • Mitsubishi Electronics MELSEC-F - page 85

    B-5 1 Outline 1.3 Conn ectable PLC and Ver sion Number s A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog I ...

  • Mitsubishi Electronics MELSEC-F - page 86

    B-6 2 Specificat ions 2.1 Generic Spe cifications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 2. Specifications This chapter describes the general, power supply, and performance specifications for the 4AD. 2.1 Generic Specifications *1. The criterion is shown in IEC61131-2. * ...

  • Mitsubishi Electronics MELSEC-F - page 87

    B-7 2 Specificat ions 2.2 Power S upply Specifications A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Inp ...

  • Mitsubishi Electronics MELSEC-F - page 88

    B-8 2 Specificat ions 2.4 Inpu t Mode (Char acteri stics) BF M #0 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 2.4 Input Mode (Characteristics) BFM #0 For the 4AD, there are two types of input characterist ics: voltage (-10 to +10V) and current (4 to 20mA, -20 to +20mA) input ...

  • Mitsubishi Electronics MELSEC-F - page 89

    B-9 2 Specificat ions 2.4 Inpu t Mode (Char acteri stics) BF M #0 A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel ...

  • Mitsubishi Electronics MELSEC-F - page 90

    B-10 3 Wiring 2.4 Inpu t Mode (Char acteri stics) BF M #0 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 3. Wiring This chapter describes the 4AD wiring. Observe the following cautions when wiring the 4AD. WIRING PRECAUTIONS • Make sure to cut off all phases of the po wer su p ...

  • Mitsubishi Electronics MELSEC-F - page 91

    B-11 3 Wiring 3.1 Terminal Layout A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 3.1 Terminal Layo ...

  • Mitsubishi Electronics MELSEC-F - page 92

    B-12 3 Wiring 3.2 Cabl e and Terminal Tightenin g Torque FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 3.2 Cable and Terminal Tightening Torque 3.2.1 Power cable (FX 3UC -4AD) The power crossover cable (type "C" shown in the following table) is supplied with the FX 3U ...

  • Mitsubishi Electronics MELSEC-F - page 93

    B-13 3 Wiring 3.2 Cabl e and Terminal Tightenin g Torque A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog I ...

  • Mitsubishi Electronics MELSEC-F - page 94

    B-14 3 Wiring 3.3 Examples of Pow er Supply Circuit FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 3.3 Examples of Power Supply Circuit 3.3.1 FX 3U -4AD Below are shown examples of circuits for using the 24V DC service power supply of the FX 3G /FX 3U Series PLC. 1) Sink input [ ...

  • Mitsubishi Electronics MELSEC-F - page 95

    B-15 3 Wiring 3.3 Examples of Pow er Supply Circuit A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) ...

  • Mitsubishi Electronics MELSEC-F - page 96

    B-16 3 Wiring 3.4 Analo g Input Line FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 3.4 Analog Input Line The analog input type, "voltage input "or "current input", can be selected for each channel. 3.4.1 FX 3U -4AD *1. For FX 3G /FX 3U Series PLC (AC power t ...

  • Mitsubishi Electronics MELSEC-F - page 97

    B-17 3 Wiring 3.5 Grou nding A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 3.4.2 FX 3UC -4AD *1. ...

  • Mitsubishi Electronics MELSEC-F - page 98

    B-18 4 Analog Input 4.1 Analog Inp ut Procedures FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 4. Analog Input This chapter describes the minimum programming necessary to readout the 4AD analog data. Follow the procedure below to confirm that the analog data can be properly rea ...

  • Mitsubishi Electronics MELSEC-F - page 99

    B-19 4 Analog Input 4.1 Analog Inp ut Procedures A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 3 ...

  • Mitsubishi Electronics MELSEC-F - page 100

    B-20 5 Buffer Memory (BFM) 5.1 Assignment of Unit Num bers and Outline of Buffer Memo ry FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 5. Buffer Memory (BFM) This chapter describes the buffer memory incorporated in 4AD. 5.1 Assignment of Unit Numbers and Outline of Buffer Memor ...

  • Mitsubishi Electronics MELSEC-F - page 101

    B-21 5 Buffer Memory (BFM) 5.1 Assignment of Unit Num bers and Outline of Buffer Memo ry A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD ...

  • Mitsubishi Electronics MELSEC-F - page 102

    B-22 5 Buffer Memory (BFM) 5.2 Bu ffer Memory Reading/Wri ting Meth od FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 5.2 Buffer Memory Reading/Writing Method To read or write to the 4AD buffer memory, use t he FROM/TO instructions or buffer memory direct specifications *1 . How ...

  • Mitsubishi Electronics MELSEC-F - page 103

    B-23 5 Buffer Memory (BFM) 5.3 Buffer Mem ory List (BFM) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog I ...

  • Mitsubishi Electronics MELSEC-F - page 104

    B-24 5 Buffer Memory (BFM) 5.3 Buffer Mem ory List (BFM) FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) *1. If powe r failure occurs, th e EEPROM will retain its data. *2. Use b0 to b7. *3. The o ffset and gain va lues should sati sfy th e followi ng conditi ons: Gain va lue - O ...

  • Mitsubishi Electronics MELSEC-F - page 105

    B-25 5 Buffer Memory (BFM) 5.3 Buffer Mem ory List (BFM) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog I ...

  • Mitsubishi Electronics MELSEC-F - page 106

    B-26 5 Buffer Memory (BFM) 5.3 Buffer Mem ory List (BFM) FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) BFM number Description Setting range Initial value Data ty pe Reference #126 *1 Upper/lower limit error status data (BFM #26) automatic transfer-to data register specification ...

  • Mitsubishi Electronics MELSEC-F - page 107

    B-27 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Inpu ...

  • Mitsubishi Electronics MELSEC-F - page 108

    B-28 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 5.4.2 BFM #2 to #5: Av eraging time Setting range: 1 to 4095 Initial value: K1 Numeric data type: Decimal (K) To change the channel data type from the immediate data (channels 1 ...

  • Mitsubishi Electronics MELSEC-F - page 109

    B-29 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Inpu ...

  • Mitsubishi Electronics MELSEC-F - page 110

    B-30 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 5.4.4 BFM #10 to #13: Channel data Numeric data type: Decimal (K) Use these buffer memories to store the A/D converted digital values. The channel data (BFM #10 to #13 for channe ...

  • Mitsubishi Electronics MELSEC-F - page 111

    B-31 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Inpu ...

  • Mitsubishi Electronics MELSEC-F - page 112

    B-32 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 5.4.8 BFM #22: Convenient function setting Initial value: H0000 Numeric data type: Hexadecimal (H) Turn on each bit (b0 to b8) of BFM #22 to enable the function assigned to each ...

  • Mitsubishi Electronics MELSEC-F - page 113

    B-33 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Inpu ...

  • Mitsubishi Electronics MELSEC-F - page 114

    B-34 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 5.4.9 BFM #26: Upper/ lower limit error status Initial value: H0000 Numeric data type: Hexadecimal (H) If channel data (BFM #10 to #13) is out of the range set by the lower limit ...

  • Mitsubishi Electronics MELSEC-F - page 115

    B-35 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Inpu ...

  • Mitsubishi Electronics MELSEC-F - page 116

    B-36 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 5.4.11 BFM #28: Over-scale status Initial value: H0000 Numeric data type: Hexadecimal (H) If the input analog value is out of the A/D conversion range, the following operation wi ...

  • Mitsubishi Electronics MELSEC-F - page 117

    B-37 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Inpu ...

  • Mitsubishi Electronics MELSEC-F - page 118

    B-38 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 5.4.13 BFM #30: Model code Initial value: K2080 Numeric data type: Decimal (K) "K2080" (fixed value) is stored as the model code. 5.4.14 BFM #41 to #44: Offset data / B ...

  • Mitsubishi Electronics MELSEC-F - page 119

    B-39 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Inpu ...

  • Mitsubishi Electronics MELSEC-F - page 120

    B-40 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 5.4.16 BFM #71 to #74: Lower limit error setting / BFM #81 to # 84: Upper limit error setting Setting range: See below. Initial value: See below. Numeric data type: Decimal (K) S ...

  • Mitsubishi Electronics MELSEC-F - page 121

    B-41 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Inpu ...

  • Mitsubishi Electronics MELSEC-F - page 122

    B-42 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 5.4.18 BFM #99: Cle arance of upper/lower limit error data and abrupt change detection data Initial value: H0000 Numeric data type: Hexadecimal (H) Three error data clearance com ...

  • Mitsubishi Electronics MELSEC-F - page 123

    B-43 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Inpu ...

  • Mitsubishi Electronics MELSEC-F - page 124

    B-44 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 3. Caution regarding EEPROM writing If data is written to BFM #0, #19, #21, #22, #125 to #129, or #198, the data will also be written to the 4AD EEPROM. → For a detailed descri ...

  • Mitsubishi Electronics MELSEC-F - page 125

    B-45 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Inpu ...

  • Mitsubishi Electronics MELSEC-F - page 126

    B-46 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 5.4.24 BFM #128: Over-scale status data automa tic transfer-to data register specification Setting range: 0 to 7999 Initial value (at delivery) : K210 Numeric data type: Decimal ...

  • Mitsubishi Electronics MELSEC-F - page 127

    B-47 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Inpu ...

  • Mitsubishi Electronics MELSEC-F - page 128

    B-48 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 5.4.28 BFM #199: Data history resetting/stoppage Initial value: H0000 Numeric data type: Hexadecimal (H) The data history resetting fu nction and the data history stoppage fun ct ...

  • Mitsubishi Electronics MELSEC-F - page 129

    B-49 5 Buffer Memory (BFM) 5.4 Buffer Memory D etails A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Inpu ...

  • Mitsubishi Electronics MELSEC-F - page 130

    B-50 6 Changing Input Ch aracteristics 6.1 Procedure for Changing Inpu t Characteristics FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 6. Changing Input Characteristics For the 4AD, the standard input characteristics are pr ovided for each in put mode (BFM #0) at the time of fa ...

  • Mitsubishi Electronics MELSEC-F - page 131

    B-51 6 Changing Input Ch aracteristics 6.1 Procedure for Changing Inpu t Characteristics A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD ...

  • Mitsubishi Electronics MELSEC-F - page 132

    B-52 6 Changing Input Ch aracteristics 6.1 Procedure for Changing Inpu t Characteristics FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 5 Create a sequence program. T o change the input characteristics, write the of fset data (BFM #41 to #44 ) and the gain data (BFM #51 to #54) ...

  • Mitsubishi Electronics MELSEC-F - page 133

    B-53 7 Examples of Practical Programs 7.1 Program That Uses Avera ging Time A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD ...

  • Mitsubishi Electronics MELSEC-F - page 134

    B-54 7 Examples of Practical Programs 7.1 Program That Uses Avera ging Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) •F o r F X 3G , FX 3U , FX 3UC Series PLCs *1. After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each settin ...

  • Mitsubishi Electronics MELSEC-F - page 135

    B-55 7 Examples of Practical Programs 7.2 Program That Use s Convenient F unctions A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3U ...

  • Mitsubishi Electronics MELSEC-F - page 136

    B-56 7 Examples of Practical Programs 7.2 Program That Use s Convenient F unctions FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 2. Example of sequence program •F o r F X 3U , FX 3UC Series PLCs *1. After setting the input mode, set the data writing time (waiting time) to 5 s ...

  • Mitsubishi Electronics MELSEC-F - page 137

    B-57 7 Examples of Practical Programs 7.2 Program That Use s Convenient F unctions A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3U ...

  • Mitsubishi Electronics MELSEC-F - page 138

    B-58 7 Examples of Practical Programs 7.3 Program That Uses Da ta History Function FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 7.3 Program That Uses Data History Function This section describes a program that uses the data history function of the 4AD. 1. Conditions The sequen ...

  • Mitsubishi Electronics MELSEC-F - page 139

    B-59 7 Examples of Practical Programs 7.3 Program That Uses Da ta History Function A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3U ...

  • Mitsubishi Electronics MELSEC-F - page 140

    B-60 7 Examples of Practical Programs 7.3 Program That Uses Da ta History Function FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) •F o r F X 3G , FX 3U , FX 3UC Series PLCs *1. After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each ...

  • Mitsubishi Electronics MELSEC-F - page 141

    B-61 7 Examples of Practical Programs 7.4 Initialization Program for 4AD (F actory Default) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U - ...

  • Mitsubishi Electronics MELSEC-F - page 142

    B-62 8 Troubleshooting 8.1 PL C Version Numb er Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 8. Troubleshooting This chapter describes troubleshooting methods and error codes. If the A/D conversion data is not input, or if the proper digital value is not input, check the ...

  • Mitsubishi Electronics MELSEC-F - page 143

    B-63 8 Troubleshooting 8.4 Er ror Stat us Check A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 8.4 ...

  • Mitsubishi Electronics MELSEC-F - page 144

    B-64 8 Troubleshooting 8.5 4AD Initialization and Test Program FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD/FX 3UC -4AD (4-channel Analog Input) 8. Digital filter setting error (b11) 1) Description of error The digital filter value (BFM #6 to #9) is not set correctly. 2) Remedy Set the digital filter value again ...

  • Mitsubishi Electronics MELSEC-F - page 145

    C-1 A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) FX 3G /FX 3U /FX 3UC Series Programmable Controllers Us ...

  • Mitsubishi Electronics MELSEC-F - page 146

    C-2 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) ...

  • Mitsubishi Electronics MELSEC-F - page 147

    C-3 1 Outline 1.1 Outline of Functions FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 1. Outline This chap ...

  • Mitsubishi Electronics MELSEC-F - page 148

    C-4 1 Outline 1.2 Setup Procedure Before Starting Operation FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) 1.2 Setup Procedure Befo re Starting Operation Before starting analog input using the 4AD-ADP, follow the procedure below to set up the system: Specifications: • Operation enviro ...

  • Mitsubishi Electronics MELSEC-F - page 149

    C-5 1 Outline 1.3 Connectable PLCs and Version Number FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 1.3 C ...

  • Mitsubishi Electronics MELSEC-F - page 150

    C-6 2 Specificat ions 2.1 Generic Specifications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) 2. Specifications This chapter describes the general, power supply, and performance specifications for the 4AD-ADP. 2.1 Generic Specifications *1. The criterion is shown in IEC61131-2. *2. If ...

  • Mitsubishi Electronics MELSEC-F - page 151

    C-7 2 Specificat ions 2.2 Power Supply Specifications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 2.2 P ...

  • Mitsubishi Electronics MELSEC-F - page 152

    C-8 2 Specificat ions 2.4 A/D Conversion Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) 2.4 A/D Conversion Time This section describes the A/D conversion time. 2.4.1 When connected to a FX 3U , FX 3UC PLC 1. A/D conversion and special data register update timing A/D conversion is p ...

  • Mitsubishi Electronics MELSEC-F - page 153

    C-9 2 Specificat ions 2.4 A/D Conversion Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 2.4.2 When co ...

  • Mitsubishi Electronics MELSEC-F - page 154

    C-10 3 Wiring FX 3U /FX 3UC Series PLC User's Manual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) 3. Wiring This chapter describes the 4AD-ADP wiring. Observe the following caution to wire the 4AD-ADP. WIRING PRECAUTIONS • Make sure to cut off all phases of the po wer su pply exter nally before attempting wiring work . Fa ...

  • Mitsubishi Electronics MELSEC-F - page 155

    C-11 3 Wiring 3.1 Terminal Layout FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 3.1 Terminal Layout The t ...

  • Mitsubishi Electronics MELSEC-F - page 156

    C-12 3 Wiring 3.2 Applicable Cables and Terminal Tightening Torque FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) 3.2 Applicable Cables and Te rminal Tightening Torque Use the foll owing cables to connect with the counterpart equipment. Terminat e the cable ends as shown below. 1. Cable ...

  • Mitsubishi Electronics MELSEC-F - page 157

    C-13 3 Wiring 3.3 Power Supply Line FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 3.3 Power Supply Line C ...

  • Mitsubishi Electronics MELSEC-F - page 158

    C-14 3 Wiring 3.4 Analog Input Line FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) 3.4 Analog Input Line For analog input, "voltage input" or "current input" can be selected for each channel. *1. Use the 2-core shielde d twisted pair cable for the analog input lines, ...

  • Mitsubishi Electronics MELSEC-F - page 159

    C-15 4 Programming 4.1 Loading of A/D Conversion Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 4. Pr ...

  • Mitsubishi Electronics MELSEC-F - page 160

    C-16 4 Programming 4.1 Loading of A/D Conversion Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) •F X 3G Series PLC The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the next adapter as the 2nd analog special adapter. However, in ...

  • Mitsubishi Electronics MELSEC-F - page 161

    C-17 4 Programming 4.2 List of Special Devices FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 4.2 List of ...

  • Mitsubishi Electronics MELSEC-F - page 162

    C-18 4 Programming 4.3 Switching of Input Mode FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) •F X 3G Series PLC R: Read / W: Write 4.3 Switching of Input Mode Turn the special auxiliary relay on/off to switch the input mode of 4AD-AD P between the current input mode and the voltage i ...

  • Mitsubishi Electronics MELSEC-F - page 163

    C-19 4 Programming 4.4 Input Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 4.4 Input Data Numeric da ...

  • Mitsubishi Electronics MELSEC-F - page 164

    C-20 4 Programming 4.5 Averaging Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) 4.5 Averaging Time Setting range: 1 to 4095 Initial value: K1 Numeric data type: Decimal (K) If the averaging time is set for the 4AD-ADP, the average data will be stored as the input data. The averagin ...

  • Mitsubishi Electronics MELSEC-F - page 165

    C-21 4 Programming 4.6 Error Status FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 4.6 Error Status If an ...

  • Mitsubishi Electronics MELSEC-F - page 166

    C-22 4 Programming 4.6 Error Status FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) 2. Program Example 1 (For FX 3G , FX 3U , FX 3UC Series PLC) *1. "1st" for the FX 3G PLC. 3. Program Example 2 (For FX 3U , FX 3UC Series PLC) Y000 M0 M8000 M1 M2 M3 M4 M5 M6 M7 Y001 Y002 Y003 Y ...

  • Mitsubishi Electronics MELSEC-F - page 167

    C-23 4 Programming 4.7 Model Code FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 4.7 Model Code Initial va ...

  • Mitsubishi Electronics MELSEC-F - page 168

    C-24 4 Programming 4.8 Basic Program Example FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) 4.8 Basic Program Example Create the following basic program example to read out analog conversion (A/D conversion) data. •F o r F X 3G , FX 3U , FX 3UC Series PLC The following program will se ...

  • Mitsubishi Electronics MELSEC-F - page 169

    C-25 4 Programming 4.8 Basic Program Example FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP •F o r F X 3 ...

  • Mitsubishi Electronics MELSEC-F - page 170

    C-26 5 Changing of Input Charac teristics 5.1 Example: Changing of Voltage Input Characteristics FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) 5. Changing of Input Characteristics Use the scaling instruction (SCL/FNC 259) for the FX 3U /FX 3UC Series PLC to change the input characteris ...

  • Mitsubishi Electronics MELSEC-F - page 171

    C-27 5 Changing of Input Charac teristics 5.1 Example: Changing of Voltage Input Characteristics FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U ...

  • Mitsubishi Electronics MELSEC-F - page 172

    C-28 5 Changing of Input Charac teristics 5.1 Example: Changing of Voltage Input Characteristics FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) 3. Example of program 2 (For FX 3G Series PLC) • For example, create the following program to change the digital input data (D110) of the 1st ...

  • Mitsubishi Electronics MELSEC-F - page 173

    C-29 6 Troubleshooting 6.1 PLC Version Number Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 6. Trou ...

  • Mitsubishi Electronics MELSEC-F - page 174

    C-30 6 Troubleshooting 6.3 Special Device Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) 6.3 Special Device Check Check whether the special devices for the 4AD-ADP are being used correctly: 1. Input mode switching Check that the special device for switching the input mode is set c ...

  • Mitsubishi Electronics MELSEC-F - page 175

    C-31 6 Troubleshooting 6.5 Error Status Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 6.5 Error Sta ...

  • Mitsubishi Electronics MELSEC-F - page 176

    C-32 6 Troubleshooting 6.5 Error Status Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-ADP (4-channel analog Input) MEMO ...

  • Mitsubishi Electronics MELSEC-F - page 177

    D-1 A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) FX 3G /FX 3U /FX 3UC Series Programmable Controllers Use ...

  • Mitsubishi Electronics MELSEC-F - page 178

    D-2 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) ...

  • Mitsubishi Electronics MELSEC-F - page 179

    D-3 1 Outline 1.1 Outline of Functions FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 1. Outline This chapt ...

  • Mitsubishi Electronics MELSEC-F - page 180

    D-4 1 Outline 1.2 Setup Procedure Before Starting Operation FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) 1.2 Setup Procedure Befo re Starting Operation Before starting analog input using the 2AD-BD, follow the procedure below to set up the system: Specif ications: • Operation environ ...

  • Mitsubishi Electronics MELSEC-F - page 181

    D-5 1 Outline 1.3 Connectable PLCs and Version Number FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 1.3 Co ...

  • Mitsubishi Electronics MELSEC-F - page 182

    D-6 2 Specificat ions 2.1 Generic Specifications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) 2. Specifications This chapter describes the general and performance specifications for the 2AD-BD. 2.1 Generic Specifications *1. The criterion is shown in IEC61131-2. *2. → For a detailed ...

  • Mitsubishi Electronics MELSEC-F - page 183

    D-7 2 Specificat ions 2.2 Performance Specifications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 2.2 Per ...

  • Mitsubishi Electronics MELSEC-F - page 184

    D-8 2 Specificat ions 2.3 A/D Conversion Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) 2.3 A/D Conversion Time This section describes the A/D conversion time. 1. A/D conversion and special data register update timing A/D conversion is performed at every scan time of the PLC. During ...

  • Mitsubishi Electronics MELSEC-F - page 185

    D-9 3 Wiring FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 3. Wiring This chapter describes the 2AD-BD wir ...

  • Mitsubishi Electronics MELSEC-F - page 186

    D-10 3 Wiring 3.1 Terminal Layout FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) 3.1 Terminal Layout The terminals of the 2AD-BD are arranged as follows: Signal V1+ I1+ V2+ I2+ VI- Applicatio n Channel 1 analog input Channel 2 analog inp ut COM terminal ...

  • Mitsubishi Electronics MELSEC-F - page 187

    D-11 3 Wiring 3.2 Applicable Cables and Terminal Tightening Torque FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW ...

  • Mitsubishi Electronics MELSEC-F - page 188

    D-12 3 Wiring 3.3 Analog Input Line FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) 3.3 Analog Input Line For analog input, "voltage input" or "current input" can be selected for each channel. *1. Use the 2-core shielde d twisted pair cable for the analog input lines, ...

  • Mitsubishi Electronics MELSEC-F - page 189

    D-13 4 Programming 4.1 Loading of A/D Conversion Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 4. Pro ...

  • Mitsubishi Electronics MELSEC-F - page 190

    D-14 4 Programming 4.2 List of Special Devices FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) 4.2 List of Special Devices If the 2AD-BD is connected, special devices will be assigned automatically as shown in the following table: R: Read / W: Write 4.3 Switching of Input Mode Turn the sp ...

  • Mitsubishi Electronics MELSEC-F - page 191

    D-15 4 Programming 4.4 Input Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 4.4 Input Data Numeric dat ...

  • Mitsubishi Electronics MELSEC-F - page 192

    D-16 4 Programming 4.5 Averaging Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) 4.5 Averaging Time Setting range: 1 to 4095 Initial value: K1 Numeric data type: Decimal (K) If the averaging time is set for the 2AD-BD, the average data will be stored as the input data. The averaging ...

  • Mitsubishi Electronics MELSEC-F - page 193

    D-17 4 Programming 4.6 Error Status FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 4.6 Error Status If an e ...

  • Mitsubishi Electronics MELSEC-F - page 194

    D-18 4 Programming 4.6 Error Status FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) 2. Program Example M8000 Normally ON M4 M5 M6 M7 Y004 Y005 Y006 Y007 EEPROM error in 1st board Averaging t ime setti ng error in 1st board Hardware error in 1st 2A D-BD Communicat ion data error i n 1st 2A ...

  • Mitsubishi Electronics MELSEC-F - page 195

    D-19 4 Programming 4.7 Model Code FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 4.7 Model Code Initial val ...

  • Mitsubishi Electronics MELSEC-F - page 196

    D-20 5 Changing of Input Charac teristics 5.1 Example: Changing of Voltage Input Characteristics FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) 5. Changing of Input Characteristics The input characteristics can be changed using sequence programs in FX 3G Series PLCs. 5.1 Example: Changin ...

  • Mitsubishi Electronics MELSEC-F - page 197

    D-21 6 Troubleshooting 6.1 PLC Version Number Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 6. Troub ...

  • Mitsubishi Electronics MELSEC-F - page 198

    D-22 6 Troubleshooting 6.5 Program Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) 4. Error status Check that no error is detected in the 2AD-BD. If an error is detected, check the details of the error, and then check the wiring and programs. → For a detailed description of speci ...

  • Mitsubishi Electronics MELSEC-F - page 199

    D-23 6 Troubleshooting 6.6 Error Status Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 5. 2AD-BD comm ...

  • Mitsubishi Electronics MELSEC-F - page 200

    D-24 6 Troubleshooting 6.6 Error Status Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -2AD-BD (2-channel analog Input) MEMO ...

  • Mitsubishi Electronics MELSEC-F - page 201

    E-1 A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) FX 3G /FX 3U /FX 3UC Series Programmable Controllers User ...

  • Mitsubishi Electronics MELSEC-F - page 202

    E-2 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) ...

  • Mitsubishi Electronics MELSEC-F - page 203

    E-3 1 Outline 1.1 Outlin e of Functions A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 1. Outline This chapt ...

  • Mitsubishi Electronics MELSEC-F - page 204

    E-4 1 Outline 1.2 Setup Proc edure Before Starti ng Operation FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 1.2 Setup Procedure Befo re Starting Operation Before starting to use the FX 3U -4DA, follow the procedure below to set up the system: Specificat ions: • Operation enviro nment ? ...

  • Mitsubishi Electronics MELSEC-F - page 205

    E-5 1 Outline 1.3 Connecta ble PLCs and Version Numbers A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 1.3 C ...

  • Mitsubishi Electronics MELSEC-F - page 206

    E-6 2 Specificat ions 2.1 Generic Specification s FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 2. Specifications This chapter describes the general, power supply, and performance specifications for the FX 3U -4DA. 2.1 Generic Specifications *1. The criterion is shown in IEC61131-2. *2. ...

  • Mitsubishi Electronics MELSEC-F - page 207

    E-7 2 Specificat ions 2.2 Power Suppl y Specifications A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 2.2 Po ...

  • Mitsubishi Electronics MELSEC-F - page 208

    E-8 2 Specificat ions 2.4 Output Mode (Cha racteristic s) BFM #0 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 2.4 Output Mode (Cha racteristics) BFM #0 For the FX 3U -4DA, there are two types of output characteristics: voltage (-10 to +10V) and current (0 to 20mA, 4 to 20mA) output char ...

  • Mitsubishi Electronics MELSEC-F - page 209

    E-9 3 Wiring FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 3. Wiring This chapter describes wiring of the F ...

  • Mitsubishi Electronics MELSEC-F - page 210

    E-10 3 Wiring 3.1 Terminal Layout FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 3.1 Terminal Layout The terminals of FX 3U -4DA are arranged as follows: 3.2 Cable and Terminal Tightening Torque The FX 3U -4DA terminal block is designed for M3 screws. The end disposal of the cable shown b ...

  • Mitsubishi Electronics MELSEC-F - page 211

    E-11 3 Wiring 3.3 Wiring to Power Supply Terminals A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 3.3 Wiring ...

  • Mitsubishi Electronics MELSEC-F - page 212

    E-12 3 Wiring 3.4 Anal og Outpu t Wiring FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 3.4 Analog Output Wiring The analog output mode, "voltage output "or "current output", can be selected for each channel. *1. For FX 3G /FX 3U Series PLC (AC power type), the 24V DC ...

  • Mitsubishi Electronics MELSEC-F - page 213

    E-13 4 Analog Output 4.1 Analog Outp ut Procedures A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 4. Analog ...

  • Mitsubishi Electronics MELSEC-F - page 214

    E-14 4 Analog Output 4.1 Analog Outp ut Procedures FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 3 Creation of sequence program Create the program as follows to output analog signals. • While referring to step 2, set the output mode "H****". • While referring to step 1, set ...

  • Mitsubishi Electronics MELSEC-F - page 215

    E-15 5 Buffer Memory (BFM) 5.1 Assi gnment of Unit Numbers and Outli ne of Buffer Memory A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA ...

  • Mitsubishi Electronics MELSEC-F - page 216

    E-16 5 Buffer Memory (BFM) 5.2 Buffer M emory Reading/Wr iting Method FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 2. Outline of buffer memory The digital values set in FX 3U -4DA will be converted to analog signals. To switch the output mode between voltage output and current output, o ...

  • Mitsubishi Electronics MELSEC-F - page 217

    E-17 5 Buffer Memory (BFM) 5.2 Buffer M emory Reading/Wr iting Method A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog ...

  • Mitsubishi Electronics MELSEC-F - page 218

    E-18 5 Buffer Memory (BFM) 5.3 Buffer Memory List (BFM) FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 5.3 Buffer Memory List (BFM) FX 3U -4DA incorporates the following buffer memories. → For a detailed description of the buffer memory, refer to Section 5.4 and subsequent sections. *1. ...

  • Mitsubishi Electronics MELSEC-F - page 219

    E-19 5 Buffer Memory (BFM) 5.3 Buffer Memory List (BFM) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) *1. I ...

  • Mitsubishi Electronics MELSEC-F - page 220

    E-20 5 Buffer Memory (BFM) 5.3 Buffer Memory List (BFM) FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) BFM number Description Set ting range Initial value Data type Referenc e #80 Start/stop of table output function *1 H0000 He xadeci- mal Chapter 6 #81 Channel-1 output pattern K1 to K10 ...

  • Mitsubishi Electronics MELSEC-F - page 221

    E-21 5 Buffer Memory (BFM) 5.4 Buff er Memory Details A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 5.4 Buf ...

  • Mitsubishi Electronics MELSEC-F - page 222

    E-22 5 Buffer Memory (BFM) 5.4 Buff er Memory Details FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 2. Caution regarding EEPROM writing If data is written to BFM #0, #5, #10 to #17, #19, #32 to #35, #50 to #54 or #60 to #63, the data will also be written to the FX 3U -4DA EEPROM. Do not ...

  • Mitsubishi Electronics MELSEC-F - page 223

    E-23 5 Buffer Memory (BFM) 5.4 Buff er Memory Details A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 5.4.4 B ...

  • Mitsubishi Electronics MELSEC-F - page 224

    E-24 5 Buffer Memory (BFM) 5.4 Buff er Memory Details FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 5.4.5 BFM #9: Offs et/gain setting value write command Initial value: H0000 Numeric data type: Hexadecimal (H) Channel numbers are assigned to 4 lower bits of BFM #9. If one of those bits ...

  • Mitsubishi Electronics MELSEC-F - page 225

    E-25 5 Buffer Memory (BFM) 5.4 Buff er Memory Details A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 5.4.6 B ...

  • Mitsubishi Electronics MELSEC-F - page 226

    E-26 5 Buffer Memory (BFM) 5.4 Buff er Memory Details FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 3. Cautions regarding offset/gain data change • If the analog value specification mode (mode 1 or 4) is used, the offset/gain cannot be changed. However, the characteristics can be chang ...

  • Mitsubishi Electronics MELSEC-F - page 227

    E-27 5 Buffer Memory (BFM) 5.4 Buff er Memory Details A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 5.4.8 B ...

  • Mitsubishi Electronics MELSEC-F - page 228

    E-28 5 Buffer Memory (BFM) 5.4 Buff er Memory Details FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 5.4.10 BFM #2 9: Error status Initial value: H0000 Numeric data type: Hexadecimal (H) Error data is assigned each bit of BFM #29. 2. Caution regarding error status If the error cause is el ...

  • Mitsubishi Electronics MELSEC-F - page 229

    E-29 5 Buffer Memory (BFM) 5.4 Buff er Memory Details A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 5.4.11 ...

  • Mitsubishi Electronics MELSEC-F - page 230

    E-30 5 Buffer Memory (BFM) 5.4 Buff er Memory Details FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 5.4.13 BFM #38: Upper/lower limit function setting Initial value: H0000 Numeric data type: Hexadecimal (H) When any of the output data (BFM #1 to #4) becomes less than the lower limit (BMF ...

  • Mitsubishi Electronics MELSEC-F - page 231

    E-31 5 Buffer Memory (BFM) 5.4 Buff er Memory Details A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 5.4.14 ...

  • Mitsubishi Electronics MELSEC-F - page 232

    E-32 5 Buffer Memory (BFM) 5.4 Buff er Memory Details FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 5.4.16 BFM #41 to #44: Lower limit values of upper/lower limit function BFM #45 to #48: Upper limit valu es of upper/lower limit function Initial value: See below Numeric data type: Decima ...

  • Mitsubishi Electronics MELSEC-F - page 233

    E-33 5 Buffer Memory (BFM) 5.4 Buff er Memory Details A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 5.4.17 ...

  • Mitsubishi Electronics MELSEC-F - page 234

    E-34 5 Buffer Memory (BFM) 5.4 Buff er Memory Details FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 3. Cautions regarding use of the output corrective function by load resistance • While changing the settings, the output is stopped, and H0000 is automatically written in the output stat ...

  • Mitsubishi Electronics MELSEC-F - page 235

    E-35 5 Buffer Memory (BFM) 5.4 Buff er Memory Details A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 5.4.19 ...

  • Mitsubishi Electronics MELSEC-F - page 236

    E-36 5 Buffer Memory (BFM) 5.4 Buff er Memory Details FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 5.4.20 BFM #62: Upper/lower limit function status data automatic transfer-to data regis ter specification Setting range: 0 to 7999 Initial value: K201 Numeric data type: Decimal (K) Use th ...

  • Mitsubishi Electronics MELSEC-F - page 237

    E-37 5 Buffer Memory (BFM) 5.4 Buff er Memory Details A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 5.4.21 ...

  • Mitsubishi Electronics MELSEC-F - page 238

    E-38 6 Table Output Fun ction 6.1 Outli ne of Table Output Function FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 6. Table Output Function This chapter describes the table output function of FX 3U -4DA 6.1 Outline of Table Output Function 1. Explanation of the function This function sets ...

  • Mitsubishi Electronics MELSEC-F - page 239

    E-39 6 Table Output Fun ction 6.2 Preparat ion of data table A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) ...

  • Mitsubishi Electronics MELSEC-F - page 240

    E-40 6 Table Output Fun ction 6.2 Preparat ion of data table FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 3. Details of data table (1) Number of patterns (number of data items: 1) Store the number of patterns at the top of the data table (device specified in BFM #98). Up to 10 patterns ...

  • Mitsubishi Electronics MELSEC-F - page 241

    E-41 6 Table Output Fun ction 6.2 Preparat ion of data table A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) ...

  • Mitsubishi Electronics MELSEC-F - page 242

    E-42 6 Table Output Fun ction 6.2 Preparat ion of data table FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 4. Example of data table The following table shows an example of data table containing two patterns prepared in and after D5000. Patterns 1 and 2 are in the output mode 1. Data regi ...

  • Mitsubishi Electronics MELSEC-F - page 243

    E-43 6 Table Output Fun ction 6.2 Preparat ion of data table A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) ...

  • Mitsubishi Electronics MELSEC-F - page 244

    E-44 6 Table Output Fun ction 6.3 Proced ures for transf erring data table to bu ffer memory FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 6.3 Procedures for transferring data table to buffer memory The data table prepared in the data registers (D1000 to D7999) in the PLC or the expansio ...

  • Mitsubishi Electronics MELSEC-F - page 245

    E-45 6 Table Output Fun ction 6.3 Proced ures for transf erring data table to bu ffer memory A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U ...

  • Mitsubishi Electronics MELSEC-F - page 246

    E-46 6 Table Output Fun ction 6.3 Proced ures for transf erring data table to bu ffer memory FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 4. Example of transfer of data table The data table below shows the writing of K5000 to BFM#98 and H0001 to BFM#99. Data starting from D5000 is trans ...

  • Mitsubishi Electronics MELSEC-F - page 247

    E-47 6 Table Output Fun ction 6.3 Proced ures for transf erring data table to bu ffer memory A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U ...

  • Mitsubishi Electronics MELSEC-F - page 248

    E-48 6 Table Output Fun ction 6.4 Procedure s for executing tabl e output function FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 6.4 Procedures for executing table output function After setting the output patterns for the channels (BFM #81 to #84) and the number outputs for the channels ...

  • Mitsubishi Electronics MELSEC-F - page 249

    E-49 6 Table Output Fun ction 6.4 Procedure s for executing tabl e output function A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-ch ...

  • Mitsubishi Electronics MELSEC-F - page 250

    E-50 6 Table Output Fun ction 6.5 Detail s of table output error FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 6.5 Details of table output error When an error related to the table output function occurs, the error code is stored in BFM #90, and the device number or the buffer memory that ...

  • Mitsubishi Electronics MELSEC-F - page 251

    E-51 6 Table Output Fun ction 6.5 Detail s of table output error A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ...

  • Mitsubishi Electronics MELSEC-F - page 252

    E-52 6 Table Output Fun ction 6.6 Examples us es of table output funct ion FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 6.6 Examples uses of table output function [Uses of table output function] • Inverter frequency setting, servo speed control, etc. 1. Inverter frequency setting The ...

  • Mitsubishi Electronics MELSEC-F - page 253

    E-53 7 Changing Output Characteristic 7.1 Procedure for Changing Output Characteri stics A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA ...

  • Mitsubishi Electronics MELSEC-F - page 254

    E-54 7 Changing Output Characteristic 7.1 Procedure for Changing Output Characteri stics FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 3 Determine the output characteristics to be changed. Example: Change to output voltage of 1 to 5 V with digital values 0 to 32000 4 Determine the offset ...

  • Mitsubishi Electronics MELSEC-F - page 255

    E-55 7 Changing Output Characteristic 7.1 Procedure for Changing Output Characteri stics A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA ...

  • Mitsubishi Electronics MELSEC-F - page 256

    E-56 8 Examples of Practical Programs 8.1 Example of Program for Analog Output Oper ation (Regular Operation) FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 8. Examples of Practical Programs 8.1 Example of Program for Analog Ou tput Operation (R egular Operation) When you want to use the ...

  • Mitsubishi Electronics MELSEC-F - page 257

    E-57 8 Examples of Practical Programs 8.2 Example of Program using Useful Funct ions A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4- ...

  • Mitsubishi Electronics MELSEC-F - page 258

    E-58 8 Examples of Practical Programs 8.2 Example of Program using Useful Funct ions FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 2. Example of sequence program •F o r F X 3U , FX 3UC Series PLCs *1. The output mode setting, setting of corrective function by load characteristics and s ...

  • Mitsubishi Electronics MELSEC-F - page 259

    E-59 8 Examples of Practical Programs 8.2 Example of Program using Useful Funct ions A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4- ...

  • Mitsubishi Electronics MELSEC-F - page 260

    E-60 8 Examples of Practical Programs 8.3 Exampl e of Program for Table Outpu t Operation (Pattern Out put Operation) FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 8.3 Example of Program for Table Ou tput Operation (Pattern Output Operation) This section describes a practical program tha ...

  • Mitsubishi Electronics MELSEC-F - page 261

    E-61 8 Examples of Practical Programs 8.3 Exampl e of Program for Table Outpu t Operation (Pattern Out put Operation) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Anal ...

  • Mitsubishi Electronics MELSEC-F - page 262

    E-62 8 Examples of Practical Programs 8.3 Exampl e of Program for Table Outpu t Operation (Pattern Out put Operation) FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) •F o r F X 3G , FX 3U , FX 3UC Series PLCs *1. The output mode setting is retained in the EEPROM of the FX 3U -4DA. For th ...

  • Mitsubishi Electronics MELSEC-F - page 263

    E-63 8 Examples of Practical Programs 8.4 Program to Ini tialize FX3U- 4DA (Factory Default) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U ...

  • Mitsubishi Electronics MELSEC-F - page 264

    E-64 9 Troubleshooting 9.1 PLC Version Number Chec k FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 9. Troubleshooting This chapter describes the troubleshooting methods and error codes. If the D/A conversion data is not output, or if the proper digital value is not output, check the foll ...

  • Mitsubishi Electronics MELSEC-F - page 265

    E-65 9 Troubleshooting 9.4 Error Status Check A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 9.4 Error Statu ...

  • Mitsubishi Electronics MELSEC-F - page 266

    E-66 9 Troubleshooting 9.5 FX3U-4DA Init ialization and Test Program FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA (4-channel Analog Outp ut) 6. Upper/lower limit functi on value setting error (b6) 1) Description of error The bit will turn on when the setting value of the upper/lower limit function is not correctl ...

  • Mitsubishi Electronics MELSEC-F - page 267

    F-1 A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) FX 3G /FX 3U /FX 3UC Series Programmable Controllers U ...

  • Mitsubishi Electronics MELSEC-F - page 268

    F-2 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) ...

  • Mitsubishi Electronics MELSEC-F - page 269

    F-3 1 Outline 1.1 Outline of Functions FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 1. Outline This cha ...

  • Mitsubishi Electronics MELSEC-F - page 270

    F-4 1 Outline 1.2 Setup Procedure Before Starting Operation FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) 1.2 Setup Procedure Befo re Starting Operation Before starting analog output using the 4DA-ADP, follow the procedure below to set up the system: Specifications: • Operation envi ...

  • Mitsubishi Electronics MELSEC-F - page 271

    F-5 1 Outline 1.3 Connectable PLCs and Version Numbers FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 1.3 ...

  • Mitsubishi Electronics MELSEC-F - page 272

    F-6 2 Specificati ons 2.1 Generic Specifications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) 2. Specifications This chapter describes the general, power supply, and performance specifications for 4DA-ADP. 2.1 Generic Specifications *1. The criterion is shown in IEC61131-2. *2. If 4D ...

  • Mitsubishi Electronics MELSEC-F - page 273

    F-7 2 Specificati ons 2.2 Power Supply Specifications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 2.2 ...

  • Mitsubishi Electronics MELSEC-F - page 274

    F-8 2 Specificati ons 2.4 D/A Conversion Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) 2.4 D/A Conversion Time This section describes the D/A conversion time. 2.4.1 When connected to a FX 3U , FX 3UC PLC 1. D/A conversion and special data register update timing D/A conversion is ...

  • Mitsubishi Electronics MELSEC-F - page 275

    F-9 2 Specificati ons 2.4 D/A Conversion Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 2.4.2 When c ...

  • Mitsubishi Electronics MELSEC-F - page 276

    F-10 3 Wiring FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) 3. Wiring This chapter describes the 4DA-ADP wiring. Observe the following caution to wire the 4DA-ADP. WIRING PRECAUTIONS • Make sure to cut off all phases of the po wer su pply exter nally before attempting wiring work . ...

  • Mitsubishi Electronics MELSEC-F - page 277

    F-11 3 Wiring 3.1 Terminal Layout FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 3.1 Terminal Layout The ...

  • Mitsubishi Electronics MELSEC-F - page 278

    F-12 3 Wiring 3.2 Applicable Cables and Terminal Tightening Torque FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) 3.2 Applicable Cables and Te rminal Tightening Torque Use the foll owing cables to connect with the counterpart equipment. Terminate the cable end as shown below. 1. Cable ...

  • Mitsubishi Electronics MELSEC-F - page 279

    F-13 3 Wiring 3.3 Power Supply Line FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 3.3 Power Supply Line ...

  • Mitsubishi Electronics MELSEC-F - page 280

    F-14 3 Wiring 3.4 Analog Output Line FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) 3.4 Analog Output Line The analog output type, "voltage output" or "current output", can be selected for each channel. *1. Use 2-core shielded twisted pair cable for the analog outpu ...

  • Mitsubishi Electronics MELSEC-F - page 281

    F-15 4 Programmin g 4.1 Writing of D/A Conversion Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 4. ...

  • Mitsubishi Electronics MELSEC-F - page 282

    F-16 4 Programmin g 4.1 Writing of D/A Conversion Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) •F X 3G Series PLC The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the next adapter as the 2nd analog special adapter. In this c ...

  • Mitsubishi Electronics MELSEC-F - page 283

    F-17 4 Programmin g 4.2 List of Special Devices FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 4.2 List o ...

  • Mitsubishi Electronics MELSEC-F - page 284

    F-18 4 Programmin g 4.3 Switching of Output Mode FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) •F X 3G Series PLC R: Read / W: Wr ite 4.3 Switching of Output Mode Turn the special auxiliary relay on/off to switch the output mode of 4DA-ADP between the current output mode and the vol ...

  • Mitsubishi Electronics MELSEC-F - page 285

    F-19 4 Programmin g 4.4 Output Holding Function Cancellation Setting FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD ...

  • Mitsubishi Electronics MELSEC-F - page 286

    F-20 4 Programmin g 4.5 Output Setting Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) 4.5 Output Setting Data Numeric data type: Decimal (K) The 4DA-ADP performs D/A conversion on the o utput setting data (digital data) into analog data, and outputs the analog data. Use the specia ...

  • Mitsubishi Electronics MELSEC-F - page 287

    F-21 4 Programmin g 4.6 Error Status FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 4.6 Error Status 1. D ...

  • Mitsubishi Electronics MELSEC-F - page 288

    F-22 4 Programmin g 4.6 Error Status FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) 3. Program Example 2 (For FX 3U , FX 3UC Series PLC) Y000 D8268.0 Y001 D8268.1 Y002 D8268.2 Y003 D8268.3 Y004 D8268.4 Channel-1 output data setting error in 1st adapter Channel-2 output data setting err ...

  • Mitsubishi Electronics MELSEC-F - page 289

    F-23 4 Programmin g 4.7 Model Code FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 4.7 Model Code Initial ...

  • Mitsubishi Electronics MELSEC-F - page 290

    F-24 5 Changing of Output Characteristi cs 5.1 Example: Changing of Voltage Out put Characteristics FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) 5. Changing of Output Characteristics Use the scaling instruction (SCL/FNC 259) for the FX 3U /FX 3UC Series PLC to change the output chara ...

  • Mitsubishi Electronics MELSEC-F - page 291

    F-25 5 Changing of Output Characteristi cs 5.1 Example: Changing of Voltage Out put Characteristics FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX ...

  • Mitsubishi Electronics MELSEC-F - page 292

    F-26 6 Troubleshootin g 6.1 PLC Version Number Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) 6. Troubleshooting This chapter describes the troubleshooting methods and error status. If analog data is not output, or if the proper analog value is not output, check the follo wing it ...

  • Mitsubishi Electronics MELSEC-F - page 293

    F-27 6 Troubleshootin g 6.4 Program Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 6.4 Program Chec ...

  • Mitsubishi Electronics MELSEC-F - page 294

    F-28 6 Troubleshootin g 6.5 Error Status Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4DA-ADP (4-channel analog Output) 3. 4DA-ADP hardware error (b6) 1) Description of error The 4DA-ADP is not operating properly. 2) Remedy Check that the 24V DC power is properly supplied to the 4DA-ADP. Also check that the 4DA ...

  • Mitsubishi Electronics MELSEC-F - page 295

    G-1 A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) FX 3G /FX 3U /FX 3UC Series Programmable Controllers Us ...

  • Mitsubishi Electronics MELSEC-F - page 296

    G-2 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) ...

  • Mitsubishi Electronics MELSEC-F - page 297

    G-3 1 Outline 1.1 Outline of Functions FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 1. Outline This chap ...

  • Mitsubishi Electronics MELSEC-F - page 298

    G-4 1 Outline 1.2 Setup Procedure Before Starting Operation FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) 1.2 Setup Procedure Befo re Starting Operation Before starting analog output using the 1DA-BD, follow the procedure below to set up the system: Specif ications : • Operation envi ...

  • Mitsubishi Electronics MELSEC-F - page 299

    G-5 1 Outline 1.3 Connectable PLCs and Version Numbers FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 1.3 ...

  • Mitsubishi Electronics MELSEC-F - page 300

    G-6 2 Specificati ons 2.1 Generic Specifications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) 2. Specifications This chapter describes the general and performance specifications for 1DA-BD. 2.1 Generic Specifications *1. The criterion is shown in IEC61131-2. *2. → For a detailed des ...

  • Mitsubishi Electronics MELSEC-F - page 301

    G-7 2 Specificati ons 2.2 Performance Specifications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 2.2 Pe ...

  • Mitsubishi Electronics MELSEC-F - page 302

    G-8 2 Specificati ons 2.3 D/A Conversion Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) 2.3 D/A Conversion Time This section describes the D/A conversion time. 1. D/A conversion and special data register update timing D/A conversion is performed at every scan time of the PLC. Durin ...

  • Mitsubishi Electronics MELSEC-F - page 303

    G-9 3 Wiring FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 3. Wiring This chapter describes the 1DA-BD wi ...

  • Mitsubishi Electronics MELSEC-F - page 304

    G-10 3 Wiring 3.1 Terminal Layout FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) 3.1 Terminal Layout The terminals of the 1DA-BD are arranged as follows: Signal •• V+ I+ VI- Applicatio n Unused terminal Output terminal COM terminal ...

  • Mitsubishi Electronics MELSEC-F - page 305

    G-11 3 Wiring 3.2 Applicable Cables and Terminal Tightening Torque FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PT ...

  • Mitsubishi Electronics MELSEC-F - page 306

    G-12 3 Wiring 3.3 Analog Output Line FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) 3.3 Analog Output Line *1. Use 2-core shielded twisted pair cable for the analog output lines, and separate the analog output lines from other power lines or inductive lines. *2. Ground the shielded wire ...

  • Mitsubishi Electronics MELSEC-F - page 307

    G-13 4 Programmin g 4.1 Writing of D/A Conversion Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 4. P ...

  • Mitsubishi Electronics MELSEC-F - page 308

    G-14 4 Programmin g 4.2 List of Special Devices FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) 4.2 List of Special Devices If 1DA-BD is connected, special devices will be assigned automatically as shown in the following table: R: Read / W: Write 4.3 Switching of Output Mode Turn the spe ...

  • Mitsubishi Electronics MELSEC-F - page 309

    G-15 4 Programmin g 4.4 Output Holding Function Cancellation Setting FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD- ...

  • Mitsubishi Electronics MELSEC-F - page 310

    G-16 4 Programmin g 4.6 Error Status FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) 4.6 Error Status 1. Description of setting If an error is detected on 1DA-BD, the error status data will be stored in the corresponding special data register. The following table shows the special data r ...

  • Mitsubishi Electronics MELSEC-F - page 311

    G-17 4 Programmin g 4.8 Basic Program Example FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 4.8 Basic Pro ...

  • Mitsubishi Electronics MELSEC-F - page 312

    G-18 5 Changing of Output Characteristi cs 5.1 Example: Changing of Voltage Out put Characteristics FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) 5. Changing of Output Characteristics The output characteristics can be changed using sequence programs in FX 3G Series PLCs. 5.1 Example: C ...

  • Mitsubishi Electronics MELSEC-F - page 313

    G-19 6 Troubleshootin g 6.1 PLC Version Number Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 6. Tro ...

  • Mitsubishi Electronics MELSEC-F - page 314

    G-20 6 Troubleshootin g 6.5 Program Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3G -1DA-BD (1-channel analog Output) 6.5 Program Check Check the following items for the program: 1. Device for setting specified digital value Check that different values are not written to this device using other programs. 6.6 Error ...

  • Mitsubishi Electronics MELSEC-F - page 315

    H-1 A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) FX 3G /FX 3U /FX 3UC Series Pr ...

  • Mitsubishi Electronics MELSEC-F - page 316

    H-2 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) ...

  • Mitsubishi Electronics MELSEC-F - page 317

    H-3 1 Outline 1.1 Outline of Functions FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ...

  • Mitsubishi Electronics MELSEC-F - page 318

    H-4 1 Outline 1.2 Setup Procedure Before Starting Operation FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) 1.2 Setup Procedure Befo re Starting Operation Before starting analog input / output using the 3A-ADP, follow the procedure below to set up the system: Spe ...

  • Mitsubishi Electronics MELSEC-F - page 319

    H-5 1 Outline 1.3 Connectable PLCs and Version Number FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J F ...

  • Mitsubishi Electronics MELSEC-F - page 320

    H-6 2 Specificat ions 2.1 Generic Specifications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) 2. Specifications This chapter describes the general, power supply, and performance specifications for the 3A-ADP. 2.1 Generic Specifications *1. The criterion is sho ...

  • Mitsubishi Electronics MELSEC-F - page 321

    H-7 2 Specificat ions 2.3 Performance Specifications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX ...

  • Mitsubishi Electronics MELSEC-F - page 322

    H-8 2 Specificat ions 2.4 Conversion Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) 2.4 Conversion Time This section describes the conversion time. 2.4.1 When connected to a FX 3U , FX 3UC PLC 1. Conversion and special da ta register update timing A/D and D ...

  • Mitsubishi Electronics MELSEC-F - page 323

    H-9 2 Specificat ions 2.4 Conversion Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PT ...

  • Mitsubishi Electronics MELSEC-F - page 324

    H-10 3 Wiring FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) 3. Wiring This chapter describes the 3A-ADP wiring. Observe the following caution to wire the 3A-ADP. WIRING PRECAUTIONS • Make sure to cut off all phases of the po wer su pply exter nally before att ...

  • Mitsubishi Electronics MELSEC-F - page 325

    H-11 3 Wiring 3.1 Terminal Layout FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP ...

  • Mitsubishi Electronics MELSEC-F - page 326

    H-12 3 Wiring 3.2 Applicable Cables and Terminal Tightening Torque FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) 3.2 Applicable Cables and Te rminal Tightening Torque Use the foll owing cables to connect with the counterpart equipment. Terminat e the cable ends ...

  • Mitsubishi Electronics MELSEC-F - page 327

    H-13 3 Wiring 3.3 Power Supply Line FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - AD ...

  • Mitsubishi Electronics MELSEC-F - page 328

    H-14 3 Wiring 3.4 Analog Input / output Line FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) 3.4 Analog Input / output Line 3.4.1 Analog Input Line For analog input, "voltage input" or "current input" can be selected for each channel. *1. Use ...

  • Mitsubishi Electronics MELSEC-F - page 329

    H-15 3 Wiring 3.5 Grounding FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP 3.5 Gr ...

  • Mitsubishi Electronics MELSEC-F - page 330

    H-16 4 Programming 4.1 Loading/Writing of Conversion Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) 4. Programming This chapter explains how to create programs for inputting and outputting analog data using the 3A-ADP. 4.1 Loading/Writing of Conversion Data ...

  • Mitsubishi Electronics MELSEC-F - page 331

    H-17 4 Programming 4.2 List of Special Devices FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4 ...

  • Mitsubishi Electronics MELSEC-F - page 332

    H-18 4 Programming 4.3 Switching of Input Mode FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) •F X 3G Series PLC R: Read / W: Write 4.3 Switching of Input Mode Turn the special auxiliary relay on/off to switch t he input mode of 3A-ADP between the current inpu ...

  • Mitsubishi Electronics MELSEC-F - page 333

    H-19 4 Programming 4.4 Switching of Output Mode FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U - ...

  • Mitsubishi Electronics MELSEC-F - page 334

    H-20 4 Programming 4.6 Setting whether or not a channel is used FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) 4.6 Setting whether or not a channel is used The 3A-ADP sets to ON or OFF special auxiliary relays to set whether or not each channel is used. This set ...

  • Mitsubishi Electronics MELSEC-F - page 335

    H-21 4 Programming 4.7 Input Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP ...

  • Mitsubishi Electronics MELSEC-F - page 336

    H-22 4 Programming 4.8 Output Setting Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) 4.8 Output Setting Data Numeric data type: Decimal (K) The 3A-ADP performs D/A conversion on the output se tting data (digital data) into analog data, and outputs the analo ...

  • Mitsubishi Electronics MELSEC-F - page 337

    H-23 4 Programming 4.9 Averaging Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ...

  • Mitsubishi Electronics MELSEC-F - page 338

    H-24 4 Programming 4.10 Error Status FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) 4.10 Error Status If an error is detected in the 3A-ADP, the error status data will be stored in the corresponding special data register. The following table shows the special da ...

  • Mitsubishi Electronics MELSEC-F - page 339

    H-25 4 Programming 4.10 Error Status FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - A ...

  • Mitsubishi Electronics MELSEC-F - page 340

    H-26 4 Programming 4.11 Model Code FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) 4.11 Model Code Initial value: K50 Numeric data type: Decimal (K) When the 3A-ADP is connected, model code "50" is stored in the corresponding special data register. The ...

  • Mitsubishi Electronics MELSEC-F - page 341

    H-27 4 Programming 4.12 Basic Program Example FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4A ...

  • Mitsubishi Electronics MELSEC-F - page 342

    H-28 4 Programming 4.12 Basic Program Example FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) •F X 3U , FX 3U C Seri es PLC The following program will set channel 1 of the 1s t adapter to voltage input mode and channel 2 to current input mode, and will store th ...

  • Mitsubishi Electronics MELSEC-F - page 343

    H-29 5 Changing of Inp ut/output Characteristics 5.1 Example: Changing of Voltage Input Characteristics FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G ...

  • Mitsubishi Electronics MELSEC-F - page 344

    H-30 5 Changing of Inp ut/output Characteristics 5.1 Example: Changing of Voltage Input Characteristics FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) 2. Example of program 1 (FX 3U , FX 3UC Series PLC) • For example, create the following program to change the ...

  • Mitsubishi Electronics MELSEC-F - page 345

    H-31 5 Changing of Inp ut/output Characteristics 5.1 Example: Changing of Voltage Input Characteristics FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G ...

  • Mitsubishi Electronics MELSEC-F - page 346

    H-32 5 Changing of Inp ut/output Characteristics 5.2 Example: Changing of Voltage Out put Characteristics FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) 5.2 Example: Changing of Vo ltage Output Characteristics This section describes an example of a program that ...

  • Mitsubishi Electronics MELSEC-F - page 347

    H-33 5 Changing of Inp ut/output Characteristics 5.2 Example: Changing of Voltage Out put Characteristics FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3 ...

  • Mitsubishi Electronics MELSEC-F - page 348

    H-34 6 Troubleshooting 6.1 PLC Version Number Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) 6. Troubleshooting This chapter describes troubleshooting methods and error statuses. Refer to the following items when conversion data is not input or output, or ...

  • Mitsubishi Electronics MELSEC-F - page 349

    H-35 6 Troubleshooting 6.4 Program Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW ...

  • Mitsubishi Electronics MELSEC-F - page 350

    H-36 6 Troubleshooting 6.5 Error Status Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -3A-ADP (2-channel analog Input, 1-cha nnel analog output) 2. Output data setting error (b2) 1) Description of error The specified digital value is outside the specified range. Analog data will not be correctly output. 2) Remedy ...

  • Mitsubishi Electronics MELSEC-F - page 351

    I-1 A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) FX 3G /FX 3U /FX 3UC ...

  • Mitsubishi Electronics MELSEC-F - page 352

    I-2 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) ...

  • Mitsubishi Electronics MELSEC-F - page 353

    I-3 1 Outline 1.1 Outline of F unctions FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U ...

  • Mitsubishi Electronics MELSEC-F - page 354

    I-4 1 Outline 1.2 Setup Procedure Before Starting Operation FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) 1.2 Setup Procedure Befo re Starting Operation Before starting analog input using the PT-ADP, follow the procedure below to set up the system: Spe ...

  • Mitsubishi Electronics MELSEC-F - page 355

    I-5 1 Outline 1.3 Connec table PLC and Its Ve rsion Numb er FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4A ...

  • Mitsubishi Electronics MELSEC-F - page 356

    I-6 2 Specificat ions 2.1 Generic Specifications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) 2. Specifications This chapter describes the general, power supply, and performance specifications for the PT-ADP. 2.1 Generic Specifications *1. The criteri ...

  • Mitsubishi Electronics MELSEC-F - page 357

    I-7 2 Specificat ions 2.2 Power S upply Specifications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT ...

  • Mitsubishi Electronics MELSEC-F - page 358

    I-8 2 Specificat ions 2.4 A/D Conversion Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) 2.4 A/D Conversion Time This section describes the A/D conversion time. 2.4.1 When connected to a FX 3U , FX 3UC PLC 1. A/D conversion and special data register ...

  • Mitsubishi Electronics MELSEC-F - page 359

    I-9 2 Specificat ions 2.5 Temper ature Measu rement FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ...

  • Mitsubishi Electronics MELSEC-F - page 360

    I-10 3 Wiring FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) 3. Wiring This chapter describes the PT-ADP wiring. Observe the following caution to wire the PT-ADP. WIRING PRECAUTIONS • Make sure to cut off all phases of the po wer su pply exter nally b ...

  • Mitsubishi Electronics MELSEC-F - page 361

    I-11 3 Wiring 3.1 Terminal Layout FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-P ...

  • Mitsubishi Electronics MELSEC-F - page 362

    I-12 3 Wiring 3.2 Applicable Cable and Te rminal Tightening Torque FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) 3.2 Applicable Cable and Te rminal Tightening Torque Use the foll owing cables to connect with the counterpart equipment. Terminate the cab ...

  • Mitsubishi Electronics MELSEC-F - page 363

    I-13 3 Wiring 3.3 Power Supply Line FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD ...

  • Mitsubishi Electronics MELSEC-F - page 364

    I-14 3 Wiring 3.4 Selection of the Platinum Resistance Thermometer Sensor FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) 3.4 Selection of the Platinum Resistance Thermometer Sensor Select the Pt100 3-wire platinum resistance thermometer sensor. This the ...

  • Mitsubishi Electronics MELSEC-F - page 365

    I-15 4 Programming 4.1 Loading of A/D Conversion Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT ...

  • Mitsubishi Electronics MELSEC-F - page 366

    I-16 4 Programming 4.1 Loading of A/D Conversion Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) •F X 3G Series PLC The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the next adapter as the 2nd a ...

  • Mitsubishi Electronics MELSEC-F - page 367

    I-17 4 Programming 4.2 List of Special Devices FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J ...

  • Mitsubishi Electronics MELSEC-F - page 368

    I-18 4 Programming 4.3 Selection of Temperature Unit FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) •F X 3G Series PLC R: Read / W: Write 4.3 Selection of Temperature Unit To switch the temperature unit of the PT-ADP turn the special auxiliary relay O ...

  • Mitsubishi Electronics MELSEC-F - page 369

    I-19 4 Programming 4.4 Temper ature Measu rement FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP ...

  • Mitsubishi Electronics MELSEC-F - page 370

    I-20 4 Programming 4.5 Averaging Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) 4.5 Averaging Time Setting range: 1 to 4095 Initial value: K1 Numeric data type: Decimal (K) If the averaging time is set for the PT-ADP, the averaged temperature measu ...

  • Mitsubishi Electronics MELSEC-F - page 371

    I-21 4 Programming 4.6 Error Status FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD ...

  • Mitsubishi Electronics MELSEC-F - page 372

    I-22 4 Programming 4.6 Error Status FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) •F o r F X 3U , FX 3UC Series PLC 2. Program Example 1 (For FX 3G , FX 3U , FX 3UC Series PLC) *1. "1st" for the FX 3G PLC. Error st atus of 1s t analog sp ec ...

  • Mitsubishi Electronics MELSEC-F - page 373

    I-23 4 Programming 4.6 Error Status FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD ...

  • Mitsubishi Electronics MELSEC-F - page 374

    I-24 4 Programming 4.7 Model Code FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) 4.7 Model Code Initial value: K20 Numeric data type: Decimal (K) When the PT-ADP is connected, model code "20" will be stored in the corresponding special data re ...

  • Mitsubishi Electronics MELSEC-F - page 375

    I-25 4 Programming 4.8 Basic Program Example FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J F ...

  • Mitsubishi Electronics MELSEC-F - page 376

    I-26 5 Troubleshooting 5.1 PLC Version Number Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) 5. Troubleshooting This chapter describes the troubleshooting methods and error status. If the temperature measurement data is not input, or if the proper ...

  • Mitsubishi Electronics MELSEC-F - page 377

    I-27 5 Troubleshooting 5.4 Program Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U ...

  • Mitsubishi Electronics MELSEC-F - page 378

    I-28 5 Troubleshooting 5.5 Error Status Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PT-ADP (4-channel Platinum Resistance Thermomet er Data Input) 4. PT-ADP hardware error (b6) 1) Description of error The PT-ADP does not operate properly. 2) Remedy Check that the 24V DC power is properly supplied to the PT ...

  • Mitsubishi Electronics MELSEC-F - page 379

    J-1 A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD-PTW - ADP FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) FX 3G /FX 3U /FX 3UC ...

  • Mitsubishi Electronics MELSEC-F - page 380

    J-2 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) ...

  • Mitsubishi Electronics MELSEC-F - page 381

    J-3 1 Outline 1.1 Outline of F unctions FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U ...

  • Mitsubishi Electronics MELSEC-F - page 382

    J-4 1 Outline 1.2 Setup Procedure Before Starting Operation FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) 1.2 Setup Procedure Befo re Starting Operation Before starting analog input using the PTW-ADP, fo llow the procedure below to set up the system: ...

  • Mitsubishi Electronics MELSEC-F - page 383

    J-5 1 Outline 1.3 Connec table PLC and Its Ve rsion Numb er FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4 ...

  • Mitsubishi Electronics MELSEC-F - page 384

    J-6 2 Specificat ions 2.1 Generic Specifications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) 2. Specifications This chapter describes the general, power supply, and performance specifications for the PTW-ADP. 2.1 Generic Specifications *1. The crite ...

  • Mitsubishi Electronics MELSEC-F - page 385

    J-7 2 Specificat ions 2.2 Power S upply Specifications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -P ...

  • Mitsubishi Electronics MELSEC-F - page 386

    J-8 2 Specificat ions 2.4 A/D Conversion Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) 2.4 A/D Conversion Time This section describes the A/D conversion time. 2.4.1 When connected to a FX 3U , FX 3UC PLC 1. A/D conversion and special data registe ...

  • Mitsubishi Electronics MELSEC-F - page 387

    J-9 2 Specificat ions 2.5 Temper ature Measu rement FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ...

  • Mitsubishi Electronics MELSEC-F - page 388

    J-10 3 Wiring FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) 3. Wiring This chapter describes the PTW-ADP wiring. Observe the following caution to wire the PTW-ADP. WIRING PRECAUTIONS • Make sure to cut off all phases of the po wer su pply exter nall ...

  • Mitsubishi Electronics MELSEC-F - page 389

    J-11 3 Wiring 3.1 Terminal Layout FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4AD- ...

  • Mitsubishi Electronics MELSEC-F - page 390

    J-12 3 Wiring 3.2 Applicable Cable and Te rminal Tightening Torque FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) 3.2 Applicable Cable and Te rminal Tightening Torque Use the foll owing cables to connect with the counterpart equipment. Terminate the ca ...

  • Mitsubishi Electronics MELSEC-F - page 391

    J-13 3 Wiring 3.3 Power Supply Line FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4A ...

  • Mitsubishi Electronics MELSEC-F - page 392

    J-14 3 Wiring 3.4 Selection of the Platinum Resistance Thermometer Sensor FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) 3.4 Selection of the Platinum Resistance Thermometer Sensor Select the Pt100 3-wire platinum resistance thermometer sensor. This th ...

  • Mitsubishi Electronics MELSEC-F - page 393

    J-15 4 Programming 4.1 Loading of A/D Conversion Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT ...

  • Mitsubishi Electronics MELSEC-F - page 394

    J-16 4 Programming 4.1 Loading of A/D Conversion Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) •F X 3G Series PLC The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the next adapter as the 2nd ...

  • Mitsubishi Electronics MELSEC-F - page 395

    J-17 4 Programming 4.2 List of Special Devices FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP ...

  • Mitsubishi Electronics MELSEC-F - page 396

    J-18 4 Programming 4.3 Selection of Temperature Unit FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) •F X 3G Series PLC R: Read / W: Write 4.3 Selection of Temperature Unit To switch the temperature unit of the PTW-ADP turn the special auxiliary relay ...

  • Mitsubishi Electronics MELSEC-F - page 397

    J-19 4 Programming 4.4 Temper ature Measu rement FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - AD ...

  • Mitsubishi Electronics MELSEC-F - page 398

    J-20 4 Programming 4.5 Averaging Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) 4.5 Averaging Time Setting range: 1 to 4095 Initial value: K1 Numeric data type: Decimal (K) If the averaging time is set for the PTW-ADP, the averaged temperature mea ...

  • Mitsubishi Electronics MELSEC-F - page 399

    J-21 4 Programming 4.6 Error Status FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4A ...

  • Mitsubishi Electronics MELSEC-F - page 400

    J-22 4 Programming 4.6 Error Status FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) •F o r F X 3U , FX 3UC Series PLC 2. Program Example 1 (For FX 3G , FX 3U , FX 3UC Series PLC) *1. "1st " for the FX 3G PLC. Error st atus of 1st analog s pe ...

  • Mitsubishi Electronics MELSEC-F - page 401

    J-23 4 Programming 4.6 Error Status FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3U -4A ...

  • Mitsubishi Electronics MELSEC-F - page 402

    J-24 4 Programming 4.7 Model Code FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) 4.7 Model Code Initial value: K21 Numeric data type: Decimal (K) When the PTW-ADP is connected, model code "21" will be stored in the corresponding special data ...

  • Mitsubishi Electronics MELSEC-F - page 403

    J-25 4 Programming 4.8 Basic Program Example FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J ...

  • Mitsubishi Electronics MELSEC-F - page 404

    J-26 5 Troubleshooting 5.1 PLC Version Number Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) 5. Troubleshooting This chapter describes the troubleshooting methods and error status. If the temperature measurement data is not input, or if the prope ...

  • Mitsubishi Electronics MELSEC-F - page 405

    J-27 5 Troubleshooting 5.4 Program Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) A Common Items B FX 3U -4AD FX 3UC -4AD C FX 3U -4AD-ADP D FX 3G -2AD-BD E FX 3U -4DA F FX 3U -4DA-ADP G FX 3G -1DA-BD H FX 3U -3A-ADP I FX 3U -4AD -PT - ADP J FX 3 ...

  • Mitsubishi Electronics MELSEC-F - page 406

    J-28 5 Troubleshooting 5.5 Error Status Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PTW-ADP (4-channel Plat inum Resistance Thermometer Data Input) 4. PTW-ADP hardware error (b6) 1) Description of error The PTW-ADP does not operate properly. 2) Remedy Check that the 24V DC power is properly supplied to the ...

  • Mitsubishi Electronics MELSEC-F - page 407

    K-1 K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) FX 3G /FX 3U /FX 3UC Series Programmable Controllers User's Manual [Analog Control Edition] FX 3U -4AD-PNK-ADP (4-channel Resistance ...

  • Mitsubishi Electronics MELSEC-F - page 408

    K-2 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channe l Resistance Thermo couple Data Input) ...

  • Mitsubishi Electronics MELSEC-F - page 409

    K-3 1 Outline 1.1 Out line of Functi ons FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 1. Outline This chapter describes the outline of FX 3U -4AD-PNK-ADP (referred to as PNK-ADP). 1.1 Ou ...

  • Mitsubishi Electronics MELSEC-F - page 410

    K-4 1 Outline 1.2 Set up Procedure Befo re Startin g Operation FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) 1.2 Setup Procedure Befo re Starting Operation Before starting analog input using PNK-ADP, follow the procedure below to set up the system: Specificati ...

  • Mitsubishi Electronics MELSEC-F - page 411

    K-5 1 Outline 1.3 Connecta ble PLC and Its Ver sion Number FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 1.3 Connectable PLC an d Its Version Number PNK-ADP is compatible with the followi ...

  • Mitsubishi Electronics MELSEC-F - page 412

    K-6 2 Specificat ions 2.1 Generic Speci fications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) 2. Specifications This chapter describes the general, power supply, and performance specifications for the PNK-ADP. 2.1 Generic Specifications *1. The criterion is ...

  • Mitsubishi Electronics MELSEC-F - page 413

    K-7 2 Specificat ions 2.3 Perfor mance Specification s FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 2.3 Performance Specifications Item Specifica tions Centigrade ( ° C) Fahrenheit ( ° ...

  • Mitsubishi Electronics MELSEC-F - page 414

    K-8 2 Specificat ions 2.4 A/D Conversi on Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) 2.4 A/D Conversion Time This section describes the A/D conversion time. 2.4.1 When connected to a FX 3U , FX 3UC PLC 1. A/D conversion and special data register update ...

  • Mitsubishi Electronics MELSEC-F - page 415

    K-9 2 Specificat ions 2.5 Temperat ure Measurement FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 2.4.2 When connected to a FX 3G PLC 1. A/D conversion and special data register update tim ...

  • Mitsubishi Electronics MELSEC-F - page 416

    K-10 3 Wiring FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK -ADP (4-channel Ther mometer Data Input) 3. Wiring This chapter describes the PNK-ADP wiring. Observe the following caution to wire the PNK-ADP. WIRING PRECAUTIONS • Make sure to cut off all phases of the po wer su pply exter nally before attempting ...

  • Mitsubishi Electronics MELSEC-F - page 417

    K-11 3 Wiring 3.1 Terminal Layout FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 3.1 Terminal Layout The terminals of the PNK-AD P are arranged as follows: Signal Applic ation External pow ...

  • Mitsubishi Electronics MELSEC-F - page 418

    K-12 3 Wiring 3.2 Appl icable Cables and Terminal Tight ening Torque FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) 3.2 Applicable Cables and Te rminal Tightening Torque Use the foll owing cables to connect with the counterpart equipment. Terminate the cable en ...

  • Mitsubishi Electronics MELSEC-F - page 419

    K-13 3 Wiring 3.3 Power Supply Line FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 3.3 Power Supply Line Connect the 24V DC power supply line of the PNK-ADP to the 24+ and 24- terminals of ...

  • Mitsubishi Electronics MELSEC-F - page 420

    K-14 3 Wiring 3.4 Sel ection of the Resi stance Thermometer Sensor FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) 3.4 Selection of the Resistance Thermometer Sensor Select the Pt1000/Ni1000 (2-wire or 3-wire sensors) resistance thermometer sensor. 3.5 Wiring of ...

  • Mitsubishi Electronics MELSEC-F - page 421

    K-15 3 Wiring 3.6 Ca ution Reg arding Wiring FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 3.6 Caution Regarding Wiring • It is not possible to connect different types of resi stance th ...

  • Mitsubishi Electronics MELSEC-F - page 422

    K-16 4 Programming 4.1 Loadi ng of A/D Conversio n Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) 4. Programming This chapter describes how to create programs that can read out the analog data using the PNK-ADP. 4.1 Loading of A/D Conversion Data 1) The in ...

  • Mitsubishi Electronics MELSEC-F - page 423

    K-17 4 Programming 4.1 Loadi ng of A/D Conversio n Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) •F X 3G Series PLC The analog special adapter nearest to the main unit is counted a ...

  • Mitsubishi Electronics MELSEC-F - page 424

    K-18 4 Programming 4.2 List o f Special Devices FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) 4.2 List of Special Devices If PNK-ADP is connected, special devices will be a ssigned automatically as shown in the following table: •F X 3U , FX 3UC Series PLC R: ...

  • Mitsubishi Electronics MELSEC-F - page 425

    K-19 4 Programming 4.3 Select ion of Temperatu re Unit FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) •F X 3G Series PLC R: Read / W: Write 4.3 Selection of Temperature Unit The state of ...

  • Mitsubishi Electronics MELSEC-F - page 426

    K-20 4 Programming 4.4 Input sensor selecti on FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) 4.4 Input sensor selection Turn on the Pt1000 type or off the Ni1000 type selection special auxiliary relay to select the Pt1000 or Ni1000 for PNK-ADP. The input senso ...

  • Mitsubishi Electronics MELSEC-F - page 427

    K-21 4 Programming 4.5 Temperat ure Measurement FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 4.5 Temperature Measurement The temperature data input in the PNK-ADP will be stored in the s ...

  • Mitsubishi Electronics MELSEC-F - page 428

    K-22 4 Programming 4.6 Averagi ng Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) 4.6 Averaging Time Setting range: 1 to 4095 Initial value: K64 Numeric data type: Decimal (K) If the averaging time is set for the PNK-ADP, the av eraged temperature measureme ...

  • Mitsubishi Electronics MELSEC-F - page 429

    K-23 4 Programming 4.7 Error St atus FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 4.7 Error Status If an error is detected on PNK-ADP, the error status data will be stored in the corresp ...

  • Mitsubishi Electronics MELSEC-F - page 430

    K-24 4 Programming 4.7 Error St atus FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) •F o r F X 3U , FX 3UC Series PLC 2. Program Example 1 (For FX 3G , FX 3U , FX 3UC Series PLC) *1. "1st" for the FX 3G PLC. Error status in the 1st analog special ad ...

  • Mitsubishi Electronics MELSEC-F - page 431

    K-25 4 Programming 4.7 Error St atus FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 3. Program Example 2 (For FX 3U , FX 3UC Series PLC) Y000 D8268.0 Y001 D8268.1 Y002 D8268.2 Y003 D8268.3 ...

  • Mitsubishi Electronics MELSEC-F - page 432

    K-26 4 Programming 4.8 Model Code FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) 4.8 Model Code Initial value: K11 Numeric data type: Decimal (K) When the PNK-ADP is connected, model code "11" will be stored in the special data register. The following ...

  • Mitsubishi Electronics MELSEC-F - page 433

    K-27 4 Programming 4.9 Basic Progr am Example FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 4.9 Basic Program Example Create the following basic program to r ead out the temperature measu ...

  • Mitsubishi Electronics MELSEC-F - page 434

    K-28 4 Programming 4.9 Basic Progr am Example FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) •F o r F X 3U , FX 3UC Series PLC The following program will select Pt1000 and will store the temperature measurement data ( ° C ) of channels 1 and 2 of the 1st ada ...

  • Mitsubishi Electronics MELSEC-F - page 435

    K-29 5 Troubleshooting 5.1 PLC Versio n Number Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 5. Troubleshooting This chapter describes the troubleshooting methods and error status. ...

  • Mitsubishi Electronics MELSEC-F - page 436

    K-30 5 Troubleshooting 5.4 Progr am Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) 5.4 Program Check Check the following items for the program: 1. Cancellation of erro r status at power-on When the power is turned off and then on again, the error status s ...

  • Mitsubishi Electronics MELSEC-F - page 437

    K-31 5 Troubleshooting 5.5 Err or Status Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 4. PNK-ADP hardware error (b6) 1) Description of error The PNK-ADP does not operate properly. ...

  • Mitsubishi Electronics MELSEC-F - page 438

    K-32 5 Troubleshooting 5.5 Err or Status Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-PNK-ADP (4- channel Resistance Thermometer Data Input) MEMO ...

  • Mitsubishi Electronics MELSEC-F - page 439

    L-1 K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) FX 3G /FX 3U /FX 3UC Series Programmable Controllers User's Manual [Analog Control Edition] FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Inp ...

  • Mitsubishi Electronics MELSEC-F - page 440

    L-2 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) ...

  • Mitsubishi Electronics MELSEC-F - page 441

    L-3 1 Outline 1.1 Out line of Functi ons FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 1. Outline This chapter describes the outline of FX 3U -4AD-TC -ADP (referred to as TC-ADP). 1.1 Outline of Fun ...

  • Mitsubishi Electronics MELSEC-F - page 442

    L-4 1 Outline 1.2 Set up Procedure Befo re Startin g Operation FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) 1.2 Setup Procedure Befo re Starting Operation Before starting analog input using TC-ADP, foll ow the procedure below to set up the system: Specifica tions: • O ...

  • Mitsubishi Electronics MELSEC-F - page 443

    L-5 1 Outline 1.3 Connecta ble PLC and Its Ver sion Number FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 1.3 Connectable PLC an d Its Version Number TC-ADP is compatible with the following PLC. 1. V ...

  • Mitsubishi Electronics MELSEC-F - page 444

    L-6 2 Specificat ions 2.1 Generic Speci fications FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) 2. Specifications This chapter describes the general, power supply, and performance specifications for the TC-ADP. 2.1 Generic Specifications *1. The criterion is shown in IEC ...

  • Mitsubishi Electronics MELSEC-F - page 445

    L-7 2 Specificat ions 2.3 Perfor mance Specification s FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 2.3 Performance Specifications Item Specifica tions Centigrade ( ° C) Fahrenheit ( ° F) Input s ...

  • Mitsubishi Electronics MELSEC-F - page 446

    L-8 2 Specificat ions 2.4 A/D Conversi on Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) 2.4 A/D Conversion Time This section describes the A/D conversion time. 2.4.1 When connected to a FX 3U , FX 3UC PLC 1. A/D conversion and special data register update timing A/D ...

  • Mitsubishi Electronics MELSEC-F - page 447

    L-9 2 Specificat ions 2.5 Temperat ure Measurement FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 2.4.2 When connected to a FX 3G PLC 1. A/D conversion and special data register update timing A/D con ...

  • Mitsubishi Electronics MELSEC-F - page 448

    L-10 3 Wiring FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) 3. Wiring This chapter describes the TC-ADP wiring. Observe the following caution to wire the TC-ADP. WIRING PRECAUTIONS • Make sure to cut off all phases of the po wer su pply exter nally before attempting wi ...

  • Mitsubishi Electronics MELSEC-F - page 449

    L-11 3 Wiring 3.1 Terminal Layout FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 3.1 Terminal Layout The terminals of the TC-ADP are arranged as follows: Signal Application Exter nal pow er Unused (D ...

  • Mitsubishi Electronics MELSEC-F - page 450

    L-12 3 Wiring 3.2 Appl icable Cables and Terminal Tight ening Torque FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) 3.2 Applicable Cables and Te rminal Tightening Torque Use the foll owing cables to connect with the counterpart equipment. Terminate the cable end as shown ...

  • Mitsubishi Electronics MELSEC-F - page 451

    L-13 3 Wiring 3.3 Power Supply Line FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 3.3 Power Supply Line Connect the 24V DC power supply line of the TC-ADP to the 24+ and 24- terminals of the termina ...

  • Mitsubishi Electronics MELSEC-F - page 452

    L-14 3 Wiring 3.4 Select ion of the Ther mocouple FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) 3.4 Selection of the Thermocouple 3.4.1 Thermocouple type • There are 2 types of thermocouples: K type and J type. When sele cting the thermocouple type, make sure that the ...

  • Mitsubishi Electronics MELSEC-F - page 453

    L-15 3 Wiring 3.6 Ca ution Reg arding Wiring FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 3.5.2 Wiring of the thermocouple type J *1. To use a J thermocouple type, be sure to connect the thermocoup ...

  • Mitsubishi Electronics MELSEC-F - page 454

    L-16 4 Programming 4.1 Loadi ng of A/D Conversio n Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) 4. Programming This chapter describes how to create programs that can read out the analog data using the TC-ADP. 4.1 Loading of A/D Conversion Data 1) The input analog d ...

  • Mitsubishi Electronics MELSEC-F - page 455

    L-17 4 Programming 4.1 Loadi ng of A/D Conversio n Data FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) •F X 3G Series PLC The analog special adapter nearest to the main unit is counted as the 1st a ...

  • Mitsubishi Electronics MELSEC-F - page 456

    L-18 4 Programming 4.2 List o f Special Devices FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) 4.2 List of Special Devices If TC-ADP is connected, special devices will be assi gned automatically as shown in the following table: •F X 3U , FX 3UC Series PLC R: Read / W: W ...

  • Mitsubishi Electronics MELSEC-F - page 457

    L-19 4 Programming 4.3 Select ion of Temperatu re Unit FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) •F X 3G Series PLC R: Read / W: Write 4.3 Selection of Temperature Unit The state of special au ...

  • Mitsubishi Electronics MELSEC-F - page 458

    L-20 4 Programming 4.4 Sel ection of Type K o r J FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) 4.4 Selection of Type K or J Turn on the J type or off the K type selection special auxiliary relay to select the thermocouple type J or K for TC-ADP. The thermocouple type wi ...

  • Mitsubishi Electronics MELSEC-F - page 459

    L-21 4 Programming 4.5 Temperat ure Measurement FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 4.5 Temperature Measurement The temperature data input in the TC-ADP will be stored in the special data ...

  • Mitsubishi Electronics MELSEC-F - page 460

    L-22 4 Programming 4.6 Averagi ng Time FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) 4.6 Averaging Time Setting range: 1 to 4095 Initial value: K64 Numeric data type: Decimal (K) If the averaging time is set for the TC-ADP, the aver aged temperature measurement data will ...

  • Mitsubishi Electronics MELSEC-F - page 461

    L-23 4 Programming 4.7 Error St atus FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 4.7 Error Status If an error is detected on TC-ADP, the error status data will be stored in the corresponding speci ...

  • Mitsubishi Electronics MELSEC-F - page 462

    L-24 4 Programming 4.7 Error St atus FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) •F o r F X 3U , FX 3UC Series PLC 2. Program Example 1 (For FX 3G , FX 3U , FX 3UC Series PLC) *1. "1st" for the FX 3G PLC. Error stat us in the 1st analog s pecial adapter b6 ...

  • Mitsubishi Electronics MELSEC-F - page 463

    L-25 4 Programming 4.7 Error St atus FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 3. Program Example 2 (For FX 3U , FX 3UC Series PLC) Y000 D8268.0 Y001 D8268.1 Y002 D8268.2 Y003 D8268.3 Y004 D8268 ...

  • Mitsubishi Electronics MELSEC-F - page 464

    L-26 4 Programming 4.8 Model Code FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) 4.8 Model Code Initial value: K10 Numeric data type: Decimal (K) When the TC-ADP is connected, model code "10" will be stored in the special data register. The following table shows ...

  • Mitsubishi Electronics MELSEC-F - page 465

    L-27 4 Programming 4.9 Basic Progr am Example FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 4.9 Basic Program Example Create the following basic program to r ead out the temperature measurement data ...

  • Mitsubishi Electronics MELSEC-F - page 466

    L-28 4 Programming 4.9 Basic Progr am Example FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) •F o r F X 3U , FX 3UC Series PLC The following program will select thermocouple type K and will store the temperature measurement data ( ° C ) of channels 1 and 2 of the 1st a ...

  • Mitsubishi Electronics MELSEC-F - page 467

    L-29 5 Troubleshooting 5.1 PLC Versio n Number Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 5. Troubleshooting This chapter describes the troubleshooting methods and error status. If the temp ...

  • Mitsubishi Electronics MELSEC-F - page 468

    L-30 5 Troubleshooting 5.4 Progr am Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) 5.4 Program Check Check the following items for the program: 1. Cancellation of erro r status at power-on When the power is turned off and then on again, the error status should be cl ...

  • Mitsubishi Electronics MELSEC-F - page 469

    L-31 5 Troubleshooting 5.5 Err or Status Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 4. TC-ADP hardware error (b6) 1) Description of error The TC-ADP does not operate properly. 2) Remedy Che ...

  • Mitsubishi Electronics MELSEC-F - page 470

    L-32 5 Troubleshooting 5.5 Err or Status Check FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition FX 3U -4AD-TC-ADP (4-channel Th ermocouple Data Input) MEMO ...

  • Mitsubishi Electronics MELSEC-F - page 471

    M-1 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition PID Instruction (FNC 88) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) FX 3G /FX 3U /FX 3UC Series Programmable Controllers User's Manual [Analog Control Edition] PID Instruction (FNC 88) Foreword This manual describes the control methods for u ...

  • Mitsubishi Electronics MELSEC-F - page 472

    M-2 FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition PID Instruction (FNC 88) ...

  • Mitsubishi Electronics MELSEC-F - page 473

    FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) M-3 1 Outline 1.1 Outlin e of function K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 1. Outline This chapter describes the outline of PID instruction (FNC88) for the FX 3U /FX 3UC /FX 3G Series PLC. 1.1 Outline of function The P ...

  • Mitsubishi Electronics MELSEC-F - page 474

    M-4 1 Outline FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) 1.2 Basi c Operation Exp ressions in P ID Instructio n (Reference) 1.2 Basic Operation Expressions in PID Instruction (Reference) The PID instruction executes using the speed type or measured value differential type operation expression. Acc ...

  • Mitsubishi Electronics MELSEC-F - page 475

    FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) M-5 2 How to Use PID Instruction 2.1 Explan ation of funct ion and operat ion K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 2. How to Use PID Instruction 1. Instruction format 2. Set data 3. Target devic es S : Only available fo ...

  • Mitsubishi Electronics MELSEC-F - page 476

    M-6 2 How to Use PID Instruction FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) 2.2 Relati onship Between Paramet er Setting and Auto -Tuning Explanation of set items *1. When auto-tuning is not executed for the limit cycle method, the same number of devices as those occupied in the step response meth ...

  • Mitsubishi Electronics MELSEC-F - page 477

    FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) M-7 3 Parameter 3.1 Param eter List: (S3) to (S3) + 28 K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 3. Parameter This chapter describes various parameters of PID instruction. 3.1 Parameter List: (S3) to (S3) + 28 Set item Setti ...

  • Mitsubishi Electronics MELSEC-F - page 478

    M-8 3 Parameter FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) 3.1 Paramet er List: (S3) t o (S3) + 28 *1. +20 to +24 become occupied only if bits 1, 2, or 5 are set to "1" to determine the action (ACT) of +1. +20 *1 Input variation (incremental) alarm set value 0 to 32767 It is valid when o ...

  • Mitsubishi Electronics MELSEC-F - page 479

    FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) M-9 3 Parameter 3.2 Deta ils of Param eters K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 3.2 Details of Parameters 3.2.1 Sampling time (T S ): (S3) Setting range: 1 to 32767 [ms] Set the cycle time (ms) for the PID operation. ? ...

  • Mitsubishi Electronics MELSEC-F - page 480

    M-10 3 Parameter FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) 3.2 Deta ils of Para meters 3.2.2 Operation setting (ACT):(S3)+1 Setting range: OFF = forward opera tion, ON = backward operation 1. Forward operation or back ward operation: +1, bit 0 Select the PID control direction (forward or backward ...

  • Mitsubishi Electronics MELSEC-F - page 481

    FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) M-11 3 Parameter 3.2 Deta ils of Param eters K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 2. Alarm setting (for input variation and outp ut variation): +1, bit 1 and bit 2 Setting range: OFF, ON The input variation and output v ...

  • Mitsubishi Electronics MELSEC-F - page 482

    M-12 3 Parameter FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) 3.2 Deta ils of Para meters 3.2.3 Input filter ( α ): (S3)+2 Setting range: 0 to 99[%] PID control: Proportional operation, integr al operation and diff erential operation The input filter ( α ) is a software filter to reduce the fluctu ...

  • Mitsubishi Electronics MELSEC-F - page 483

    FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) M-13 3 Parameter 3.2 Deta ils of Param eters K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 3.2.4 Proportional gain (K P ): (S3)+3 Setting range: 1 to 32767[%] PID control: Proportional operation During the proportional operation ...

  • Mitsubishi Electronics MELSEC-F - page 484

    M-14 3 Parameter FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) 3.2 Deta ils of Para meters Example 1: PI operation in heating (backward operation) Example 2: Proportion al operation (P operation) in cooling (forward oper ation) Important point The integral operation changes the output so that the con ...

  • Mitsubishi Electronics MELSEC-F - page 485

    FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) M-15 3 Parameter 3.2 Deta ils of Param eters K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 3.2.6 Differential gain (K D ): (S 3)+5 Setting range: 0 t o 100[%] PID control: Diff erential operation The filter is applied to the out ...

  • Mitsubishi Electronics MELSEC-F - page 486

    M-16 3 Parameter FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) 3.2 Deta ils of Para meters Example 1: PID operation in heating (backward operation) Example 2: PID operation in cooling (forward operat ion) T ime T emperature Changes caused by disturbance T D3 > T D2 > T D1 PI operation (without ...

  • Mitsubishi Electronics MELSEC-F - page 487

    FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) M-17 3 Parameter 3.2 Deta ils of Param eters K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 3.2.8 Alarm output flag: (S3)+24 When the input variation [ + 1, bit 1] is set to 1 When the output variation [ +1, bit 2] is set to 1 - ...

  • Mitsubishi Electronics MELSEC-F - page 488

    M-18 4 Auto-Tuning FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) 4.1 Limit Cy cle Meth od 4. Auto-Tuning This chapter describes the auto-tuning function of PID instruction. The auto-tuning function will automatically set the impor tant constants, such as the proportional gain and the integral time, t ...

  • Mitsubishi Electronics MELSEC-F - page 489

    FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) M-19 4 Auto-Tuning 4.1 Limit Cycl e Method K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 4.1.2 Auto-tuning procedure 1 Set the forward or backward operation Set the operation direction flag (bit 0) in the operation setting p ara ...

  • Mitsubishi Electronics MELSEC-F - page 490

    M-20 4 Auto-Tuning FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) 4.1 Limit Cy cle Meth od - τ τ τ on on 1 50 × 4.1.3 Reference: How to obtai n three constants in PID c ontrol (limit cycle method) For acquiring satisfactory control results in PID control, it is necessary to obtain the optimal valu ...

  • Mitsubishi Electronics MELSEC-F - page 491

    FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) M-21 4 Auto-Tuning 4.2 Step Resp onse Method K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 4.2 Step Response Method 4.2.1 Parameters to be set by auto-tuning (step response method) 4.2.2 Auto-tuning procedure 1 T ran sferring th ...

  • Mitsubishi Electronics MELSEC-F - page 492

    M-22 4 Auto-Tuning FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) 4.3 Cautio ns on Auto-Tuning Execu tion 4.2.3 Reference: How to obtai n three constants in PID control (step response method) For acquiring satisfactory control results during PID control, it is necessary to obtain the optimal value of ...

  • Mitsubishi Electronics MELSEC-F - page 493

    FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) M-23 5 Example of Practical Programs (for Step Response Method) 5.1 Example: System and operati on K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) 5. Example of Practical Programs (for Step Response Method) The following is an exa ...

  • Mitsubishi Electronics MELSEC-F - page 494

    M-24 5 Example of Practical Programs (for Step Response Method) FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) 5.2 Progra m example of auto-tun ing (step respons e method) and PID con trol 5.2 Program example of auto-tuning (ste p response method) and PID control M8002 The mode of FX 2N -4AD-TC is se ...

  • Mitsubishi Electronics MELSEC-F - page 495

    FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) M-25 5 Example of Practical Programs (for Step Response Method) 5.2 Progr am example of auto-t uning (step respon se method) and PID contr ol K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) Auto-tuning operation i s confir med. Au ...

  • Mitsubishi Electronics MELSEC-F - page 496

    M-26 5 Example of Practical Programs (for Step Response Method) FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) 5.3 Prog ram example of auto- tuning (step resp onse method) 5.3 Program example of auto-tuning (step response method) X010 K500 D500 Auto-tuning i s started. The targ et va lue is set (to 5 ...

  • Mitsubishi Electronics MELSEC-F - page 497

    FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) M-27 5 Example of Practical Programs (for Step Response Method) 5.3 Progr am example of auto-t uning (step respo nse method) K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) M1 PID operation K2000 T246 T246 T246 D502 Y021 M8067 Err ...

  • Mitsubishi Electronics MELSEC-F - page 498

    M-28 6 Troubleshooting FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) 6.1 Error Codes 6. Troubleshooting 6.1 Error Codes When an error occurs in the set value of a control parameter or the data acqui red during the PID operation, the operation error flag M8067 turns ON, and a corresponding error code ...

  • Mitsubishi Electronics MELSEC-F - page 499

    FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) M-29 6 Troubleshooting 6.1 Erro r Codes K FX 3U -4AD-PNK - ADP L FX 3U -4AD-TC - ADP M PID Inst ruction (FNC 88) Caution With regard to the measured value (PV) in PID, normal measurement data should be read before PID operation begins. Especially when the ...

  • Mitsubishi Electronics MELSEC-F - page 500

    M-30 6 Troubleshooting FX 3G /FX 3U /FX 3UC PLC User's Manual - Analog Contro l Edition PID Instruction (FNC 88) 6.1 Error Codes MEMO ...

  • Mitsubishi Electronics MELSEC-F - page 501

    i Warranty FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Warranty Please confirm the following product warra nty details before using this product. 1. Gratis Warranty Term and Gratis Warranty Range If any faults or defects (he reinafter "Failure") found to be the responsibility of M itsubis hi occurs during use of ...

  • Mitsubishi Electronics MELSEC-F - page 502

    ii Revised History FX 3G /FX 3U /FX 3UC PLC User's Man ual - Analog Control Edition Revised History Date Revision Desc ription 7/2005 A First E dition 2/2006 B • FX 3U -4A D is added to B. •F X 3U -4DA is inserted to D. • Adding and rev ising the other descriptions. 3/2006 C • B-8 page, 2. 2 The Power Supply Specifica tion for the FX 3 ...

  • Mitsubishi Electronics MELSEC-F - page 503

    ...

  • Mitsubishi Electronics MELSEC-F - page 504

    HEAD OFFICE: TOKYO BUILDING, 2-7-3 MARUN OUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN HIMEJI WORKS: 840, CHIYO DA CHO, HIMEJI, JAPAN JY997D16701G (MEE) Effective June. 2009 Specifications are subject to chang e without notice. USER'S MANUAL - Analog Control Edition FX 3G /FX 3U /FX 3UC SERIES PROGRAMMABLE CONTR OLLERS MODEL FX3U-U-ANALOG-E MODEL C ...

Manufacturer Mitsubishi Electronics Category Home Theater Server

Documents that we receive from a manufacturer of a Mitsubishi Electronics MELSEC-F can be divided into several groups. They are, among others:
- Mitsubishi Electronics technical drawings
- MELSEC-F manuals
- Mitsubishi Electronics product data sheets
- information booklets
- or energy labels Mitsubishi Electronics MELSEC-F
All of them are important, but the most important information from the point of view of use of the device are in the user manual Mitsubishi Electronics MELSEC-F.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Mitsubishi Electronics MELSEC-F, service manual, brief instructions and user manuals Mitsubishi Electronics MELSEC-F. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Mitsubishi Electronics MELSEC-F.

A complete manual for the device Mitsubishi Electronics MELSEC-F, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Mitsubishi Electronics MELSEC-F by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Mitsubishi Electronics MELSEC-F.

A complete Mitsubishi Electronics manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Mitsubishi Electronics MELSEC-F - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Mitsubishi Electronics MELSEC-F, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Mitsubishi Electronics MELSEC-F, that we can find in the current document
3. Tips how to use the basic functions of the device Mitsubishi Electronics MELSEC-F - which should help us in our first steps of using Mitsubishi Electronics MELSEC-F
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Mitsubishi Electronics MELSEC-F
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Mitsubishi Electronics MELSEC-F in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Mitsubishi Electronics MELSEC-F?

Use the form below

If you did not solve your problem by using a manual Mitsubishi Electronics MELSEC-F, ask a question using the form below. If a user had a similar problem with Mitsubishi Electronics MELSEC-F it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)