  • Honeywell TZ-4 - page 1

    PRODUCT DATA 68-0259-1 ® U.S. Registered Trademark Copyright © 2002 Honeywell • All Rights Reserved TZ-4 TotalZone® Zone Control Panel APPLICATION The TZ-4 T otalZone Zone Control Panel co ntrols single-stage, multi-stage, conventional or heat pump heat/coo l equipment. It controls 2, 3 or 4 zones, and is expandable up to 32 zones with optiona ...

  • Honeywell TZ-4 - page 2

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 68-0259-1 2 SPECIFICATIONS Input Ratings: V oltage: 20-30 V ac, 50/60 Hz. Power: 13 V A, nomin al. Output Ratings: 1.5A run, 200,000 cycles (30 V ac). 3.5 inrush. 1.5A run, 100,000 cycles (30 V ac) 7.5A inrush. Humidity Ratings: 5 to 90 percent RH, non-condensing. T emper ature Ratings: Shipping: -20° to 120°F ...

  • Honeywell TZ-4 - page 3

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 3 68-0259-1 a Heat pump thermostat with single Y first-stage termi nals. See Heat Pump Thermostats section and Fig. 6. b Multi-stage and heat pump thermostats are not required to cont rol multi-stage and heat pump syst ems with T otalZone. They are used only when second stage or emergency heat control from the z ...

  • Honeywell TZ-4 - page 4

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 68-0259-1 4 INSTALLATION Mounting CAUTION Equipment Damage Hazard . Do not mount TZ-4 inside HV AC equipment Mount only on wall or on cold air return. Identifying DIP Switches This panel has two banks of DIP swi tches, DIP switch 4 (S4) and DIP switch 5 (S5), see Fig 15. Each b ank has eight individual switches ...

  • Honeywell TZ-4 - page 5

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 5 68-0259-1 Wiring Diagrams (Fig. 3 and 4) Conventional Thermostats Conventional (RWYG) thermostat s can be used to control conventional, multi-stage, and h eat pump equipment. If the thermostat has a common terminal, it is wired to C on the panel, see Fig. 3. A multi-st age thermost at is wired with the second ...

  • Honeywell TZ-4 - page 6

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 68-0259-1 6 Fig. 4. PC8900 with W890 0A,C Thermostat wiring. Heat Pump Thermostats Select a heat pump thermostat fr om T able 1. If the thermostat selected has a separate Y1 and W1 w ire, as shown in Fig. 5, leave the zone O/B thermostat type jumper on the TZ-4 disconnected, and wire as shown in Fi g. 5. If the ...

  • Honeywell TZ-4 - page 7

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 7 68-0259-1 . Fig. 5. He at pump the rmost at with sep arate Y1 and W1 terminals and multi-stage thermostat wiring. If the thermostat selected from T able 1 has a single Y terminal for first stage heat and cool, wire as shown in Fig. 6. Wire either O or B (not both) from the thermost at to the O/B terminal on th ...

  • Honeywell TZ-4 - page 8

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 68-0259-1 8 Fig. 7. Heat pump thermostat with 3-st age heat, 2-stage cool single Y thermostat wiring. Fig. 8. W iring ARD or ZD damp er to p anel. Fig. 9. Wiring AOBD damp er to p anel. Fig. 10. Wiri ng two AOBD dampers in p arallel. MARD Dampers or Damper s Using an ML6161 Motor Actuator Wire the MARD Damper or ...

  • Honeywell TZ-4 - page 9

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 9 68-0259-1 Fig. 12. MARD or ML6161 Damper Motor Actuator using R8222 Relay wiring. Transformer 1. Wire the transformers to the panel as shown in Fig. 13. One 40 V A, 24 V ac tra nsformer controls up to five ARD or ZD dampers. 2. Connect the transformer to termina ls R and C. 3. Add the auxiliary transformer if ...

  • Honeywell TZ-4 - page 10

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 68-0259-1 10 Fig. 15. T otalZone Add-A-Zone wir ing. Conventional Equipment Wire the heating and cooling eq uipment to the equipment terminals on the TZ-4 Pan el as shown in Fig. 16. Conventional Equipment: Set DIP switch 5-1 to on. Electric Furnaces: Set DIP switch 5 -6 to off to energize the fan with a call fo ...

  • Honeywell TZ-4 - page 11

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 1 1 68-025 9-1 Fig. 16. Wiring conventional h eating and cooling equipm ent to TZ-4 p anel. Heat Pump Equipment See Fig. 17-22 for heat pump wiring. Refer to manufacturer instructions for additional wiring de tails and substitute the TZ-4 equipment terminals for the thermostat terminals shown. — Connect the ch ...

  • Honeywell TZ-4 - page 12

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 68-0259-1 12 Fig. 17. Wiring si ngle-st age heat pump with auxiliary he at. Fig. 18. Wiring si ngle-stage heat pump with separate auxiliary and emergency hea t. T wo-speed Comp ressor: Wire the first stage compre ssor to Y1 and the second stage compressor to Y2. If the same heat source is used for auxiliary heat ...

  • Honeywell TZ-4 - page 13

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 13 68-0259-1 Fig. 21. Du al Fuel with sing le-st age heat pump and single- stage fossil fuel. Fig. 22. Dual fuel wi th two-st age heat pump and one- or two-stage fossil fuel. Water Source Heat Pumps Wire the equipment, as applicable, to the TZ-4 as shown in Fig. 17-19. Refer to manu factur er instructions for ad ...

  • Honeywell TZ-4 - page 14

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 68-0259-1 14 Purge Mode At the end of every call for heat or cool, the panel enters a Purge mode that hol ds open the calling zo ne damper for two (default) or three and one-ha lf minutes. During this time, the panel or the HV AC equipment can be configured to operate the fa n. The Purge LED l ights to signal th ...

  • Honeywell TZ-4 - page 15

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 15 68-0259-1 HEAT PUMP OPERATION The panel can control singl e- or two- stage heat pumps with or without auxiliary heat. Set DIP switch 5 -1 to Off for heat pump control. This energizes equipment terminal Y1 on a call for first stage heat or cool. If second stage is configured to operate with DIP switch 4-1 and ...

  • Honeywell TZ-4 - page 16

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 68-0259-1 16 Thermostat Operation Conventional Thermostats Conventional (R,W ,Y ,G) heat/cool thermostat s can be used with the TZ-4 to control single or multi-stage gas, electric or oil systems and heat pumps with auxiliary heat. The panel can be configured to control second stage heat and cool and third stage ...

  • Honeywell TZ-4 - page 17

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 17 68-0259-1 Use DIP switch 5-2 to chang e cooli ng limit settings: Zone-A-Lone Switch When the Zone-A-Lone switch is in the occupied (up) position and the OC/OC terminals are no t used, the system functions as a zone control system. When switched to the unoccupied (down) position, al l dampers are opened and al ...

  • Honeywell TZ-4 - page 18

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 68-0259-1 18 TROUBLESHOOTING T abl e 8. T rouble shooting. Symptom Possible Cau se Action No LEDs are Illuminated No power to the board. Check for 24 V ac (±10%) across R and C. T r ansformers out of phase If 48 V ac across R and T1, reverse T 1 and T2 wires. Shorted wire. Check thermal circuit breaker . If hot ...

  • Honeywell TZ-4 - page 19

    TZ-4 T OTALZONE® ZONE CONTROL PANEL 19 68-0259-1 T able 9. LED In dicators. LED Color Illuminated Not Illuminated Flashing Heat Red Heat call . No heat calls. High limit reached. Cool Green Cool call. No cool calls. Low limit reached. Purge Amber Purge mode. Not in Purge mode. • DA T S failure: slow flash. • OT failure: fast flash. • DA TS a ...

  • Honeywell TZ-4 - page 20

    68-0259-1 G .H. Rev . 12-02 www .honeywell.com/yourhome Automation and Control Solutions Honeywell Honeywell Li mited-Honeywel l Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 5542 2 Scarborough, Ontario M1V 4Z9 TZ-4 T OTALZONE® ZONE CONTROL PANEL ...

Manufacturer Honeywell Category Thermostat

Documents that we receive from a manufacturer of a Honeywell TZ-4 can be divided into several groups. They are, among others:
- Honeywell technical drawings
- TZ-4 manuals
- Honeywell product data sheets
- information booklets
- or energy labels Honeywell TZ-4
All of them are important, but the most important information from the point of view of use of the device are in the user manual Honeywell TZ-4.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Honeywell TZ-4, service manual, brief instructions and user manuals Honeywell TZ-4. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Honeywell TZ-4.

A complete manual for the device Honeywell TZ-4, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Honeywell TZ-4 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Honeywell TZ-4.

A complete Honeywell manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Honeywell TZ-4 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Honeywell TZ-4, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Honeywell TZ-4, that we can find in the current document
3. Tips how to use the basic functions of the device Honeywell TZ-4 - which should help us in our first steps of using Honeywell TZ-4
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Honeywell TZ-4
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Honeywell TZ-4 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Honeywell TZ-4?

Use the form below

If you did not solve your problem by using a manual Honeywell TZ-4, ask a question using the form below. If a user had a similar problem with Honeywell TZ-4 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)