Manual Pentair CP12

36 pages 0.57 mb
Download

Go to site of 36

Summary
  • Pentair CP12 - page 1

    Part #471949 Revision #A © 2001 HydroTemp Manufacturing Co., Inc. Note: Specifications may change without notice. Owners Operational Information Only Technicians See Separate Installation Manual OWNERS OPERA TION MANUAL Models: MiniMax Plus HP 400 (XLS400) MiniMax Plus HP 600 (XLS600) MiniMax Plus HP 800 (XLS800) MiniMax Plus HP 1000 (XLS1000) Min ...

  • Pentair CP12 - page 2

    OWNERS SECTION - TABLE OF CONTENTS 1. OPERATIONAL INSTRUCTIONS .............................................................................................. a. Introduction & Design Features b. Heater Control Panels & L.E.D. Status Lights 2. START UP PROCEDURES ............................................................................... ...

  • Pentair CP12 - page 3

    Owners/users should contact the factory service department for advice at: HYDROTEMP MANUFACTURING CO., INC. 12155 Metro Pkwy, Ste. 5 Ft Myers, FL 33912 (941) 768-1555 (941) 768-2856 (fax) www.warmpool.com RETURN ON INVESTMENT The costs of installing a heat pump are somewhat higher than a gas heater but you will save enough in opera- tional costs to ...

  • Pentair CP12 - page 4

    4 Super Quiet & Highly Ef ficient Compressor Desig n Sturdy Elevated Fiberglass Rust Proof Bottom Provides Proper Drainage Large Aluminum & Copper Lanced Fin Evaporator Air Coil and Coil Guard Easy Connect 2 Inch Plumbing With "Internal Automatic Bypass" Up To 90 GPM Sturdy Rust Proof Fiberglass Top Non Fading Quiet High Volume Fa ...

  • Pentair CP12 - page 5

    The electrical panel has an isolated compartment, located within the me- chanical compartment to prevent corrosion there. The heat from the com- pressor located just below the electrical compart- ment helps eliminate mois- ture as well. This exclu- sive design will substan- tially extend the life cycle of the heater. The fiber- glass cabinet is cor ...

  • Pentair CP12 - page 6

    DUAL THERMOSTAT CONTROL PANEL THERMOSTAT The thermostat dial is just like any other, when you set it at a certain setting the heater will heat up to that temperature and then shut off. When the pool/spa wa- ter temperature drops below this setting the heater will come on and start heating the water back up to the setting on the thermostat. You will ...

  • Pentair CP12 - page 7

    POOL MODE "Yellow": The yellow pool mode in- dicator light lets you know that you have selected the pool mode with the pool /spa select switch, (dual ther- mostat control only). This light will be off when the control is in spa mode. SPA MODE "Orange": The orange spa mode indicator light tells you that you have selected the spa ...

  • Pentair CP12 - page 8

    8 START UP PROCEDURES COMPRESSOR TIME DELAY BE AWARE THERE IS A 5 TO 7 MINUTE TIME DE- LAY BEFORE THE COMPRESSOR WILL START ONCE THE UNIT IS TURNED ON OR WHENEVER IT RESTARTS. All models. TURN T-STAT ALL THE WAY DOWN Make sure the thermostat dial is turned all the way to the “LEFT” so the unit will not start until you are ready. Then turn the c ...

  • Pentair CP12 - page 9

    9 HEAT EXCHANGER The compressed hot refrigerant releases it's heat to the pool water inside the heat exchanger. The exchanger is a tube within a tube construction, water passing through the inner tube, hot gas passing through the outer tube. The refriger- ant is transformed into a liquid state as it exits the heat exchanger. There- fore it is ...

  • Pentair CP12 - page 10

    NORMAL RUNNING TIME The heat pump system extracts the heat from the out- side air and delivers it to your pool. Therefore it pro- duces more BTU's (heat) the warmer it is outside. So take advantage of the higher air temperatures during the day by setting the timer for the warmest hours. Win- ter operation (during cold fronts) may require longe ...

  • Pentair CP12 - page 11

    THERMOSTAT SETTING There are no temperature reading numbers printed on the thermostat dial due to calibration changes from unit to unit. The demand for exact temperatures should be regulated by using a high quality thermometer right in the pool water. Normal temperatures for pools are 78 to 82 degrees F. Spa temperatures are 98 to a maximum of 104 ...

  • Pentair CP12 - page 12

    RERADIATION CONVECTION EVAPORATION WIND CONDUCTION Pool Shell Pool Surface Warm Pool Water UNDERSTANDING HEA T LOSS It is important to understand how your pool loses heat. The greatest heat loss occurs at the water surface. You will need to adjust the operational time to compensate for added heat loss during the colder months. See the diagram on th ...

  • Pentair CP12 - page 13

    CONTROLLING HEAT LOSS A good way to control heat loss is to slow the wind speed through your pool area by placing plants such as shrubs or bushes around the pool's perimeter. Plants will break up the air flow and diffuse the wind speed. If the pool area is to be fenced in, choose a wood shadow box type design. A solid type fence or wall does n ...

  • Pentair CP12 - page 14

    OWNERS MAINTENANCE & CARE There are some considerations that should be taken concerning the environment where your heater is installed. The heater is usually placed near the pool filtering system. There are certain things in this area you will need to be aware of to insure long life and prevent unnecessary damage. SPRINKLERS Make sure there are ...

  • Pentair CP12 - page 15

    15 WATER PIPING LEAK ? When the unit operates, it will produce condensation that will drain from the bottom of the unit. Do not mistake condensation with a water piping leak. There is a certain procedure to follow to check the unit for leaks: Shut the heat pump and filtering system off. Allow all the condensation to drain from the unit for at least ...

  • Pentair CP12 - page 16

    FILTER CLEANING & CARE Your filter system should be cleaned at least twice a month. See manufacturer's directions for proper filter cleaning methods. Size and conditions may require you to clean the filter more often. A filter is considered "dirty", whenever it restricts the flow rate by 10% or more. You can use the pressure gaug ...

  • Pentair CP12 - page 17

    Often times, when these auto vacuums begin to wear, they require more suction from the pump to operate. Diverting all vacuum through the auto vac may help it run better but will restrict the overall water flow through the entire system and the heater. If you have a low water flow situation where the heater is not getting enough water through the co ...

  • Pentair CP12 - page 18

    The heat pump in equipped with a internal "Automatic Bypass" valve. A variable rate spring valve is used to regulate the wa- ter flow through the heat ex- changer. Steady flow will be de- livered over a wide range of flow rates. This automatic valve can handle a maximum flow rate of 90 gallons per minute. The automatic valve will com- pen ...

  • Pentair CP12 - page 19

    8" 2 LB CHEMICAL RESISTANT CHECK VALVE Part# 888-018 LOOP ABOVE TO POOL CHLORI- NATOR FROM HEATER The chemical resistant check valve and loop must be in- stalled with all types of chlorinators to prevent chlorine migration to the heater. The loop should extend at least 8 inches above the chlorinator top. The chemical resistant check valve shou ...

  • Pentair CP12 - page 20

    W A TER BALANCE MAINTENANCE The chemical balance of your pool/spa water and the methods used in adding pool chemicals will directly effect the life of your heater. Like no other precaution you could take, it is very important that these guidelines are followed in order to prevent damage to the heat exchanger/water coil and possibly the entire syste ...

  • Pentair CP12 - page 21

    21 These chemical outlines should not be considered as a “how to” balance your pool/spa water, but just a refer- ence on how chemical balance effects the heater and gives suggested test values. You should always consult a pool professional and follow all chemical manufacturers di- rections, unless they conflict with this manual. CHLORINE Chlori ...

  • Pentair CP12 - page 22

    22 TOTAL ALKALINITY Total Alkalinity is a test given to determine the over- all mineral content of the water. Total alkalinity lev- els should be within the range from 90 p.p.m. to 120 p.p.m. The total alkalinity is described as a buffer against acetic conditions and acts as a stabilizer for the pH. It keeps the pH from fluctuating up and down. A l ...

  • Pentair CP12 - page 23

    CHLORINATOR PLACEMENT 1. All chlorinators should have a chemical resistant check valve and a loop plumbed at least 8 inches above the chlorinator, between it and the heater, as far down line from the heater as possible. 2. Never plumb a chlorinator into the suction side of the circulation pump. All automatic chemical feeders should be as far down l ...

  • Pentair CP12 - page 24

    24 COMMERCIAL FEEDERS We strongly suggest that all chemical feeders be placed "down line" of the heater. In a "closely monitored" commercial pool situation where a vacuum type filter system is used in conjunction with a surge tank, there are some exceptions to chemical injection. Some liquid chlorine (sodium hypochlorite) feeder ...

  • Pentair CP12 - page 25

    SHUT DOWN & FREEZE PROTECTION PROCEDURES When shutting the unit down for the end of the swimming season you must consider some items to protect the unit from inclement weather. It is best in most situations to shut the unit off by turning the thermostat all the way down, to the "left". Leave power ,(circuit breaker), to the unit “on ...

  • Pentair CP12 - page 26

    POSSIBLE CAUSE CONDITION POSSIBLE REMEDY All control lights off. Unit will not start. Control Ready light ON. Water Press. OK light OFF. T-Stat On light OFF. Low & High Press. lights OFF. Unit will not start. Low water flow through heater. Dirty or worn filters or clogged lint traps. Clogged filter pump impeller. Improper plumbing valve setting ...

  • Pentair CP12 - page 27

    Control Ready light ON. Water Press. OK light ON T-Stat On light ON Fan is not turning. Unit will not start. Low water flow through heater. Dirty or worn filters or clogged lint traps. Clogged filter pump impeller. Improper plumbing valve settings. Wait for the 90 second compressor time delay. Clean entire filtering system and or replace fil- ter e ...

  • Pentair CP12 - page 28

    MANDATORY BONDING TO POOL STEEL (This is in addition to electrical ground) Make sure that the unit cabinet is bonded to the pool steel. Most codes require that the circulation pump be bonded as well. You can connect at that point using at least a #6 gauge or larger solid copper wire. Use the external bond lug on the cabinet to insure a good bond. B ...

  • Pentair CP12 - page 29

    HOW TO GET SERVICE When you experience trouble with your unit, you should follow these simple procedures before requesting service on your pool/spa heat pump. 1. You should follow all start up procedures as described in this booklet. Without exception you should clean the filtering system thoroughly, consult the manufacturers directions for proper ...

  • Pentair CP12 - page 30

    30 GLOSSARY OF TERMS A/C Contractor: A company licensed by the state and local au- thorities to perform heating ventilation and air-conditioning in- stallation or repair including pool heat pumps. Allow no others to repair this unit. Acetic: Describing pool/spa water that is aggressive in nature with a Ph value below 7.6. Like acid, orange juice, v ...

  • Pentair CP12 - page 31

    Circuit Breaker: An automatic switch that will shut the power off to an electrical device (heater, circulation pump) when an over- load or short occurs. Located in the electrical supply panel in your home or near the associated equipment. Circulation Pump: An electric water pump that circulates water through the filter and other pool related equipm ...

  • Pentair CP12 - page 32

    32 Floating Thermometer: A thermometer that floats on the water surface with the main sensing bulb in the water. Indicates the ac- tual pool or spa temperature it’s floating in. A tie on type will work the same. Flow Control Valve: A valve or check valve that controls water flow either automatically or manually. Freon™: Trade name for a type of ...

  • Pentair CP12 - page 33

    Serial Number: A twelve digit number on the identification sticker on the outside of the heater cabinet. Needed for all records, war- ranty request etc. Shadow-Box Fence: A fence that is made to allow air to pass through it freely without restriction. Shock Treatment: Adding a larger than normal dose of chlorine to the pool water to kill contaminat ...

  • Pentair CP12 - page 34

    34 This page is blank. ...

  • Pentair CP12 - page 35

    35 This page is blank. ...

  • Pentair CP12 - page 36

    Manufactured by: © 2001 HydroT emp Manufacturing Co., Inc. 941-768-1555 www.warmpool.com Heat Pumps ...

Manufacturer Pentair Category Air Compressor

Documents that we receive from a manufacturer of a Pentair CP12 can be divided into several groups. They are, among others:
- Pentair technical drawings
- CP12 manuals
- Pentair product data sheets
- information booklets
- or energy labels Pentair CP12
All of them are important, but the most important information from the point of view of use of the device are in the user manual Pentair CP12.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Pentair CP12, service manual, brief instructions and user manuals Pentair CP12. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Pentair CP12.

Similar manuals

A complete manual for the device Pentair CP12, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Pentair CP12 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Pentair CP12.

A complete Pentair manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Pentair CP12 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Pentair CP12, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Pentair CP12, that we can find in the current document
3. Tips how to use the basic functions of the device Pentair CP12 - which should help us in our first steps of using Pentair CP12
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Pentair CP12
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Pentair CP12 in a specific country, if it was not possible to solve the problem on our own.