    Use, Care, and Installation Guide www .zephyronline.com Model number: Serial Number: FEB09.0201 © Zephyr Corporation Milano W all ZMI-M90AS ZMI-M90AG ...

  • Zephyr ZMIM90AG - page 2

    www .zephyronline.com ...

  • Zephyr ZMIM90AG - page 3

    1 SAFETY NOTICE ................................................................. 2-3 LIST OF MA TERIALS ....................................................... 4 INST ALLA TION Ducting Calculation Sheet ....................................... 5 Mounting Height & Clearance ................................ 6 Ducting Options ..................... ...

  • Zephyr ZMIM90AG - page 4

    Important Safety Notice READ AND SA VE THESE INSTRUCTIONS 2 www .zephyronline.com W ARNING TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT USE THIS F AN WITH ANY SOLID-ST A TE CONTROL DEVICE. W ARNING TO REDUCE THE RISK OF FIRE ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSER VE THE FOLLOWING: a. Use this unit only in the manner intended by the man ...

  • Zephyr ZMIM90AG - page 5

    Important Safety Notice 3 W ARNING TO REDUCE THE RISK OF FIRE, USE ONL Y MET AL DUCTWORK. CAUTION T o reduce risk of fi re and to properly exhaust air outside - Do not vent exhaust air into spaces within walls, ceilings, attics, crawl spaces or garages. OPERA TION Always leave safety grilles and fi lters in place. Without these components, operat ...

  • Zephyr ZMIM90AG - page 6

    List of Materials 4 www .zephyronline.com (3) Wire Nuts (3) M4 x 1-1/2” (2) M4 x 1” (4) 3/16” x 8 (4) M3.5 x 8 P ARTS NOT SUPPLIED - Ducting, conduit and all installation tools - Cable connector (if required by local codes) - Duct cover extension accessory - Z1C-00MI - Recirculating kit accessory - ZRC-0040 HARDW ARE P ACKAGE CONTENTS MODELS: ...

  • Zephyr ZMIM90AG - page 7

    5 Duct pieces To t a l Equivalent number length x used = 3- 1/ 4” x 10” Rect., straight 1 Ft. x ( ) = Ft. 8” Round, straight 1 Ft. x ( ) = Ft. 3- 1/ 4” x 10” Rect. 90 0 elb ow 15 Ft. x ( ) = Ft. 3- 1/ 4” x 10” Rect. 45 0 elb ow 9 Ft. x ( ) = Ft. 3- 1/ 4” x 10” Rect. 90 0 flat elb ow 24 Ft. x ( ) = Ft. 3- 1/ 4” x 10” Rect. wall ...

  • Zephyr ZMIM90AG - page 8

    Installation – Mounting Height & Clearance 6 www .zephyronline.com DUCTING A minimum of 6” round duct must be used to maintain maximum air fl ow ef fi ciency . Always use rigid type metal ducts only . Flexible ducts could restrict air fl ow by up to 50%. Use calculation worksheet to compute total duct work (Page 5). AL WA YS, when possib ...

  • Zephyr ZMIM90AG - page 9

    7 W ARNING FIRE HAZARD NEVER exhaust air or terminate duct work into spaces between walls, crawl spaces, ceiling, attics or garages. All exhaust must be ducted to the outside, unless using the recirculating option. Use single wall rigid Metal ductwork only . Fasten all connections with sheet metal screws and tape all joints w/ certi fi ed Silver T ...

  • Zephyr ZMIM90AG - page 10

    8 www .zephyronline.com Installation – Hood Speci fi cations 23 15/16” min. ducted - 26 1/2” min. recirc. - 30” max. - 49” 10 1/2” elec. k/o 4” 8 1/2” 35 7/16” 14” 20 1/2” 6” Ø top of hood front of hood side of hood ...

  • Zephyr ZMIM90AG - page 11

    9 1. Measure from range top to hood bottom and mark line A. (28” minimum from range top) . 2. Plum and mark center line. 3. Mark mounting height line B. (15-3/8” from line A) 4. Mark mounting spread from C/L. (8-7/8”) 5. Fasten (2) M4 x 1-1/2” screws into studs on line B but do not tighten all the way . Note: Wood blocking may need to be ad ...

  • Zephyr ZMIM90AG - page 12

    10 www .zephyronline.com (blower housing) Ductless recirculation is intended for applications where an exhaust duct work is not possible to be installed. When converted, the hood functions as a recirculating hood rather than an exhaust hood. Fumes and exhaust from cooking are drawn and fi ltered by a set of optional charcoal fi lters. The air is ...

  • Zephyr ZMIM90AG - page 13

    11 Lights On/Dim/Off 15 Min Delay Off Display (speed level, delay off, filter clean/change) Adjust 6 Speed Levels Blower On/Off 1. Blower On/Off By pressing the blower is switched on and off. When switched on, the blower starts up on speed level 3. 2. Speed Selection The 6 speed levels are selected by pressing to decrease and to increase speed leve ...

  • Zephyr ZMIM90AG - page 14

    Features & Controls – Charcoal Filter Change Reminder 12 www .zephyronline.com Charcoal Filter Change Reminder (charcoal filter , if installed) When your hood is installed as a recirculating unit, it is fitted with a set of charcoal filters to purify exhaust and fumes from cooking, then re-circulates the air within the home. These charcoal fi ...

  • Zephyr ZMIM90AG - page 15

    Features & Controls – Metal Mesh Filter Clean Reminder 13 Metal Filter Clean Reminder (metal mesh filter) Whether your hood is installed as an exhaust or purifying unit, a set if metal mesh filters are fitted by the factory , These metal mesh filters are intended to filter out residue from cooking. They need not be replaced on a regular basis ...

  • Zephyr ZMIM90AG - page 16

    14 www .zephyronline.com SURF ACE MAINTENANCE: Clean periodically with hot soapy water and clean cotton cloth. Do not use corrosive or abrasive detergent , or steel wool/scouring pads which will scratch and damage surface. For heavier soil use liquid degreaser . After cleaning it is recommended that you use non-abrasive stainless steel polish/clean ...

  • Zephyr ZMIM90AG - page 17

    Maintenance - Lights 15 of the REPLACING LIGHT BULBS CAUTION: Light bulb becomes extremely hot when turned on. DO NOT touch bulb until switched off and cooled. T ouching hot bulbs could cause serious burns. Make sure all power is turned off and bulbs are not hot. Remove by turning bulb counter clockwise. Note: Bulb does not unscrew; it turns 60 deg ...

  • Zephyr ZMIM90AG - page 18

    16 www .zephyronline.com T roubleshooting TROUBLESHOOTING PROCEDURES FOR MILANO W ALL Issue Cause What to do After installation, the unit doesn’t work. 1. The power source is not turned ON. 1. Make sure the circuit breaker and the unit’s power is ON. 2. The power line and the cable locking connector is not connecting properly . 2. Check the pow ...

  • Zephyr ZMIM90AG - page 19

    List of Parts & Accessories 17 DESCRIPTION P ART# Replacement Parts Light Bulb GU-10 50W (each) Z0B-0020 Metal Mesh Filter (each) 5020001 1 Optional Accessories Recirculating Kit ZRC-0040 Replacement Charcoal Filter Z0F-C002 Duct Cover Extension Z1C-00MI T o order parts, visit us online at http://store.zephyronline.com or call us at 1.888.880.8 ...

  • Zephyr ZMIM90AG - page 20

    1-888-880-8368 STAPLE YOUR RECEIPT HERE TO OBTAIN SERVICE UNDER WARRANTY OR FOR ANY SERVICE RELATED QUESTIONS, please call: Zephyr Corporation (referred to herein as “we” or “us”) warrants to the original consumer purchaser (referred to herein as “you” or “your”) of Zephyr products (the “Products”) that such Products will be fre ...

Производитель Zephyr Категория Ventilation Hood

Документы, которые мы получаем от производителя устройства Zephyr ZMIM90AG мы можем разделить на несколько групп. Это в частности:
- технические чертежи Zephyr
- инструкции обслуживания ZMIM90AG
- паспорта изделия Zephyr
- информационные брошюры
- энергетические этикетки Zephyr ZMIM90AG
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Zephyr ZMIM90AG.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Zephyr ZMIM90AG, инструкции обслуживания, короткие инструкции или инструкции пользователя Zephyr ZMIM90AG. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Zephyr ZMIM90AG.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Zephyr ZMIM90AG, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Zephyr ZMIM90AG пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Zephyr ZMIM90AG.

Полная инструкция обслуживания Zephyr, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Zephyr ZMIM90AG - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Zephyr ZMIM90AG, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Zephyr ZMIM90AG, которое найдем в данном документе
3. Советы по использованию основных функций устройства Zephyr ZMIM90AG - которые должны облегчить нам первые шаги во время использования Zephyr ZMIM90AG
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Zephyr ZMIM90AG
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Zephyr ZMIM90AG в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Zephyr ZMIM90AG?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Zephyr ZMIM90AG, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Zephyr ZMIM90AG со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)