    TECHNICAL GUIDE SPLIT -SYSTEM HEA T PUMPS 13 SEER – R-22 MODELS: Y HJD18 THRU 60 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) Due to continuous produc t impr ovement, specifications are subject to change without notice. V isit us on th e web at www .york.com A dditional rating informa tion can be fo und at w ww .ahridirectory . org LISTED ISO 9001 Certifie ...

  • York YHJD18 THRU 60 - page 2

    398612-YTG-B-0608 2 Johnson Controls Unitary Products All dimensions are in inches. They are subject to cha nge without notice. Ce rtif ied dimensio ns will be provide d upon request. . Physical and Electrical Data MODEL YHJD18 S21S1 YHJD2 4 S21S1 YH JD30 S21S1 YH JD36 S21S1 YHJD42 S21S1 YHJD48 S21S1 YHJD60 S21S1 Unit Supply V oltage 208-230V , 1 ? ...

  • York YHJD18 THRU 60 - page 3

    398612-YTG-B-0608 Johnson Controls Unitary Produ cts 3 Additional R-22 Charge / Orifice Size for V arious Matched Systems Outdoor Unit YHJD18 S21S1 YHJD24 S21S1 YHJD30 S21S1 YHJD36 S21S1 YHJD42 S21S1 YHJD48 S21S1 YHJD60 S21S1 Required Orifice or TXV 1 1 TVM2A1 1 TVM2A1 1 TVM2A1 1 TVM2A1 1 TVM2C1 1 TVM2C1 1 TVM2C1 Factory Charge, lbs-oz 7 - 3 7 - 7 ...

  • York YHJD18 THRU 60 - page 4

    398612-YTG-B-0608 4 Johnson Controls Unitary Products PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refr igerant for th e condenser , the smallest evaporator and 15 feet of inter- connecting line tubing. 2. V erify the TXV or orifice and additional charge required for s pecific evaporator coil in t he system using the abo ...

  • York YHJD18 THRU 60 - page 5

    398612-YTG-B-0608 Johnson Controls Unitary Produ cts 5 COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT A L SENS. 13 SEER HP WITH MA YHJD18S21S1 MA08B 17 FC/MC18B 600 18.0 12.9 13.00 1 1.00 MA08B 17 FC/MC24B 600 18.0 12.9 13.00 1 1.00 MA08B 17 FC/MC30B 600 18.0 12.9 13.0 ...

  • York YHJD18 THRU 60 - page 6

    398612-YTG-B-0608 6 Johnson Controls Unitary Products — = Not applicable. 13 SEER HP WITH A V / SV / F*FV - V ARIABLE SPEED YHJD18S21S1 A V24 17 – 565 18.0 13.4 14.00 12.00 YHJD24S21S1 A V24 17 – 770 23.0 17.5 14.00 12.00 YHJD30S21S1 A V36 21 – 1015 29.0 22.0 14.00 12.00 YHJD36S21S1 A V36 21 – 1270 35.0 26.2 14.00 12.00 A V/SV48 24 – 12 ...

  • York YHJD18 THRU 60 - page 7

    398612-YTG-B-0608 Johnson Controls Unitary Produ cts 7 COOLING CAP ACITY - Up flow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RA TED CFM NET MBH SEER 1 EER TOT A L SENS. YHJD18S21S1 450 - 750 14,17 FC/MC/PC/UC18 600 18.0 12.9 13.00 1 1.00 450 - 750 14,17 FC/MC/PC/UC24 600 18.0 12. ...

  • York YHJD18 THRU 60 - page 8

    398612-YTG-B-0608 8 Johnson Controls Unitary Products COOLING CAP ACITY - With V ariable Spe ed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT A L SENS. 13 SEER HP WITH V ARIABLE SPEED FURNACES 2 YHJD18S21S1 PV8*A12 FC/MC/PC/UC18A 14 600 18.0 13.4 14.00 12.00 PV9*A12 FC/MC/PC/UC18A 14 600 18 ...

  • York YHJD18 THRU 60 - page 9

    398612-YTG-B-0608 Johnson Controls Unitary Produ cts 9 YHJD36S21S1 PV8*A12 FC/MC/PC/UC37A 14 1200 35.0 26.0 13 .55 1 1.00 PV9*A12 FC/MC/PC/UC37A 14 1200 35.0 25.8 13 .25 1 1.00 PV8*B16 FC/MC/PC/UC43B 17 1200 35.0 26.2 14 .00 12.00 PV8*C16 FC/MC/PC/UC43C 21 1200 35.0 26.2 14.00 12.00 PV8*C20 FC/MC/PC/UC43C 21 1200 35.0 26.0 13.85 12.00 P(C,V)9*B12 F ...

  • York YHJD18 THRU 60 - page 10

    398612-YTG-B-0608 10 Johnson Controls Unitary Products HEA TING PERFORMANCE - With Air Handler UNIT MODEL* AIR HANDLER COIL 1 MODEL ARI HEA TING 2 47 ° F1 7 ° FH S P F MBH COP KW MBH COP KW STD 13 SEER HP WITH MA YHJD18S21S1 MA08B FC/MC18B 17.0 3.26 1.54 9.0 2.18 1 .23 7.70 MA08B FC/MC24B 17.0 3.26 1.54 9 .0 2.18 1.23 7 .70 MA08B FC/MC30B 17.0 3. ...

  • York YHJD18 THRU 60 - page 11

    398612-YTG-B-0608 Johnson Controls Unitary Produ cts 11 CP equals MBH output divided by (t otal KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating ou tput during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. 13 SEER HP WITH A V / SV / ...

  • York YHJD18 THRU 60 - page 12

    398612-YTG-B-0608 12 Johnson Controls Unitary Products CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. HEA TING PERFORMANCE - Up flo ...

  • York YHJD18 THRU 60 - page 13

    398612-YTG-B-0608 Johnson Controls Unitary Produ cts 13 HEA TING CAP ACITY - Wit h V ariable S peed Furnac es UNIT MODEL V ARIABLE SPEED FURNACE COIL 1 MODEL ARI HEA TING 2 47 ° F1 7 ° FH S P F MBH COP KW MBH COP KW STD 13 SEER HP WITH V ARIABLE SPEED FURNACES 3 YHJD18S21S1 PV8*A12 FC/MC/PC/UC18A 17.0 3.46 1.41 9 .0 2.32 1.09 8 .00 PV9*A12 FC/MC/ ...

  • York YHJD18 THRU 60 - page 14

    398612-YTG-B-0608 14 Johnson Controls Unitary Products CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. YHJD36S21S1 PV8*A12 FC/MC/PC/ ...

  • York YHJD18 THRU 60 - page 15

    398612-YTG-B-0608 Johnson Controls Unitary Produ cts 15 ACCESSORIES Refer to Price Manual for specific model numbers. St art Assist Kit (2SA067*) Blower Time Delay - A vailable to increase efficiency when installed. Installs on indoor section and maintains blower for approximately one minute a fter cooling thermostat has been satisfied. Hard St art ...

  • York YHJD18 THRU 60 - page 16

    398612-YTG-B-0608 16 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree abo ve the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York YHJD18 THRU 60 - page 17

    398612-YTG-B-0608 Johnson Controls Unitary Produ cts 17 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...

  • York YHJD18 THRU 60 - page 18

    398612-YTG-B-0608 18 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree abo ve the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York YHJD18 THRU 60 - page 19

    398612-YTG-B-0608 Johnson Controls Unitary Produ cts 19 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...

  • York YHJD18 THRU 60 - page 20

    398612-YTG-B-0608 20 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree abo ve the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York YHJD18 THRU 60 - page 21

    398612-YTG-B-0608 Johnson Controls Unitary Produ cts 21 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...

  • York YHJD18 THRU 60 - page 22

    398612-YTG-B-0608 22 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree abo ve the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York YHJD18 THRU 60 - page 23

    398612-YTG-B-0608 Johnson Controls Unitary Produ cts 23 Multipliers for determining the performance with other indoor sections . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD18S21S1 EV APORA TOR COIL MODEL NO AHP18 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 450 600 750 MBTUH KW C.O.P . MBTUH KW C.O.P . MBTUH ...

  • York YHJD18 THRU 60 - page 24

    398612-YTG-B-0608 24 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD24S21S1 EV APORA TOR COIL MODEL NO AHP24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 600 800 1000 MBTUH KW C.O.P . MBTUH KW C.O.P . MBTU ...

  • York YHJD18 THRU 60 - page 25

    398612-YTG-B-0608 Johnson Controls Unitary Produ cts 25 Multipliers for determining the performance with other indoor sections . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD30S21S1 EV APORA TOR COIL MODEL NO AHP30 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 800 1000 1200 MBTUH KW C.O.P . MBTUH KW C.O.P . MBT ...

  • York YHJD18 THRU 60 - page 26

    398612-YTG-B-0608 26 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD36S21S1 EV APORA TOR COIL MODEL NO AHP36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1000 1200 1400 MBTUH KW C.O.P . MBTUH KW C.O.P . MB ...

  • York YHJD18 THRU 60 - page 27

    398612-YTG-B-0608 Johnson Controls Unitary Produ cts 27 Multipliers for determining the performance with other indoor sections . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD42S21S1 EV APORA TOR COIL MODEL NO FC/MC/PC/UC48 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1200 1400 1600 MBTUH KW C.O.P . MBTUH KW C. ...

  • York YHJD18 THRU 60 - page 28

    398612-YTG-B-0608 28 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD48S21S1 EV APORA TOR COIL MODEL NO AHP/SHP48 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1400 1600 1800 MBTUH KW C.O.P . MBTUH KW C.O.P ...

  • York YHJD18 THRU 60 - page 29

    398612-YTG-B-0608 Johnson Controls Unitary Produ cts 29 Multipliers for determining the performance with other indoor sections . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD60S21S1 EV APORA TOR COIL MODEL NO FC/MC62 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1600 1800 2000 MBTUH KW C.O.P . MBTUH KW C.O.P . ...

  • York YHJD18 THRU 60 - page 30

    Subject to change without notice. Printe d in U.S.A. 398612-YTG-B-0608 Copyright © 2008 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 398612-YTG-A-0408 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 NOTES ...

Производитель York Категория Heat Pump

Документы, которые мы получаем от производителя устройства York YHJD18 THRU 60 мы можем разделить на несколько групп. Это в частности:
- технические чертежи York
- инструкции обслуживания YHJD18 THRU 60
- паспорта изделия York
- информационные брошюры
- энергетические этикетки York YHJD18 THRU 60
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания York YHJD18 THRU 60.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа York YHJD18 THRU 60, инструкции обслуживания, короткие инструкции или инструкции пользователя York YHJD18 THRU 60. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия York YHJD18 THRU 60.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства York YHJD18 THRU 60, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании York YHJD18 THRU 60 пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей York YHJD18 THRU 60.

Полная инструкция обслуживания York, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией York YHJD18 THRU 60 - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания York YHJD18 THRU 60, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся York YHJD18 THRU 60, которое найдем в данном документе
3. Советы по использованию основных функций устройства York YHJD18 THRU 60 - которые должны облегчить нам первые шаги во время использования York YHJD18 THRU 60
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем York YHJD18 THRU 60
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра York YHJD18 THRU 60 в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся York YHJD18 THRU 60?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с York YHJD18 THRU 60, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с York YHJD18 THRU 60 со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)