Summary
  • American Power Conversion 120VAC - page 1

    990-1079, Rev ision 01 10/01 User’s Manual English APC Smart-UPS ® 1400VA XL 230VA C/120VAC /100VAC 3U Rack and Stack Uninterr uptible Pow er Supply ...

  • American Power Conversion 120VAC - page 2

    TABLE OF CONT ENTS 1: Safet y Inform ation ............................................................................................................................................................ 1 Handling Saf ety ................................................................................................................ .................. ...

  • American Power Conversion 120VAC - page 3

    ...

  • American Power Conversion 120VAC - page 4

    ...

  • American Power Conversion 120VAC - page 5

    1 1: S AF E T Y I NFORMA TION American Po w er Conversion Corpo ration (APC) is the leading national and international manufac- turer of state-of- the-art uninterru ptible power s upplies , redundant swit ches, power m anageme nt soft- ware, an d related equi pment. APC produ cts protect h ardwa re, software, an d data from th e threat of po wer di ...

  • American Power Conversion 120VAC - page 6

    2  In order to maintain compliance with the EMC directive, output cords attached to the UPS should n ot exceed 10 meters in leng th.  Pluggable equipment includes a protective earth condu ctor that carries the leakage curren t from the load devices (computer equipment). Total leakage current must not exceed 3.5 mA. D EENERGIZING S AFE TY  ...

  • American Power Conversion 120VAC - page 7

    3 2: I NST ALLA TION The UPS has a “rack and s tack” design that prov ides two moun ting options. The UPS can be mounte d in a 46.5 cm (19-in ch) equipmen t rack or st acked on a batte ry pack(s ) model SU24RMXLBP2U. Hard w are is provided for either option. U NPACKING Inspect the UPS upon receipt. A PC designed robus t packag ing for your prod ...

  • American Power Conversion 120VAC - page 8

    4 S TACKI NG TH E UPS ON A B ATTERY P ACK Note: For rack m ounting, proceed to Mountin g the UP S in a Rack , below . Do not step o n the UPS. The UPS chassi s is not desig ned to sup- port additiona l weight. When stacking the UPS with an external battery pack, position the UPS on top of the 2U battery pack. The top of the battery pa ck has indent ...

  • American Power Conversion 120VAC - page 9

    5 3. Attach the mounting brackets to the UPS before mounting the UPS in your rack, (below ). Each mounting bracket attaches to the UPS with four s crews (included). Two sets of bracket holes are located on the si des of the UPS. If you are us ing a four-post rack , attach the mounting brackets in the forward position. For two po st rack m ounting a ...

  • American Power Conversion 120VAC - page 10

    6 2. Locate the battery cables tucked on top of the battery  . 3. Locate the UPS battery connector jack  to the right of the battery tray. 4. To connect the battery cable plug to the battery jack, push the plug into the jack firmly to ensure a tight connection. You will hear a “snap” when the connector is seated pro p- erly. 5. Tuck the w ...

  • American Power Conversion 120VAC - page 11

    7 connection, loosen the screw and conn ect the surge su ppression devi ce ground lead. Tigh ten the screw to secure the lead. • 100V models : In order t o operat e at the fu ll VA rat ing of the 1400VA product , the su pplied 15A plug mu st be replaced w ith a 20A plug . This change mus t be done by qu alified service personnel. Refer to the web ...

  • American Power Conversion 120VAC - page 12

    8 3: O PERA TION S MAR T -UP S F RONT P ANEL O PERATIO N The ON and OFF buttons are u sed to power th e UPS and act as master controls f or the connected equipment. Make sure connected equipment is switched to the ON p osition. The UPS remains on as long as it is attached to utility power. Power On Press and release the button to supply power t o t ...

  • American Power Conversion 120VAC - page 13

    9 S ELF -T EST Automatic Self-Te st The UPS performs a self-test automatically when turn ed on, and every two we eks thereafter (by def ault). Refer to Us er Conf igur- able Items for details on changing the default interval. Automatic self-test eases maintenance requirements by eliminating the need for periodic m anual self-tes ts. During the self ...

  • American Power Conversion 120VAC - page 14

    10 AVR Tr im This LED illuminates to indicate the UPS is compensating for a high utility voltage. AVR Boost This LED illuminates to indicate the UPS is compensating for a low utility voltage. B ATTERY P OWER If the utility power fails, the UPS can pro vide power to the connected equipment from its internal battery for a finite period. The UPS sound ...

  • American Power Conversion 120VAC - page 15

    11 S MAR T -UPS R EA R P ANE L 230V m odels 120V/100V m odel s B ASIC C ONNE CTORS Serial Port Power management s oftware and interface k its can be used w ith the UPS. Use only int erface kits supplied or approved by AP C. If us ed, connect the interf ace cable to the 9-pin computer interface port. Secure the connector screw s to complete the conn ...

  • American Power Conversion 120VAC - page 16

    12 D EFAULT S ETTI NGS Voltage Sensitivity The UPS d etec ts line vo ltage disto rtio ns (s uch a s spike s, not che s, dip s, and swells) as well as distortions caused by operation with inexpensive fuel-powered gen erators. By default, the UPS reacts to distortion s by transferring to on -battery operation to protect the con nected equipment. Wher ...

  • American Power Conversion 120VAC - page 17

    13 O N B ATTERY O PERA TION The Smart-UPS switches to b attery operation automaticall y if the utility power fails. While running on-battery, an intern al alarm sounds (periodic beeps). Pre ss the button (front pane l) to silence the UPS alarm (for the curren t alarm only). You can change the au dible indicator if you are using the Powe rChute soft ...

  • American Power Conversion 120VAC - page 18

    14 4: U SER C ONFIGU RA B LE I TEMS N OTE : S ETT ING T HESE IT E MS REQ UIR ES SO FT WAR E OR OP TIO NA L HA RDWA RE . F UNCTION F ACTORY D EFAULT U SER S ELECTABLE C HOICES D ESCRIPTION Automatic Self- Tes t Every 14 day s (336 hours ) Every 7 day s (168 hours ), On Startup Only, No Self-Test This function sets the interval at which the UPS will ...

  • American Power Conversion 120VAC - page 19

    15 N OTE : S ETT ING T HESE IT E MS REQ UIR ES SO FT WAR E OR OP T IONA L HA RDWA RE . F UNCTION F ACTORY D EFAULT U SER S ELECTABLE C HOICES D ESCRIPTION High Transfer Point 230V models : 253VAC 120V models : 132VAC 100V models : 110VAC 230V models : 264, 271, 280VAC 120V models : 129, 135, 138VAC 100V models : 108, 112, 114VAC To avoid unn ecessa ...

  • American Power Conversion 120VAC - page 20

    16 5: T RA NSP ORT ING Y OU R S MA RT -UPS Always DISCONNEC T THE B ATTERY before shipp ing in co mpliance with U.S. Departm ent of Transp ortation (DOT ) regulations . The battery m ay remain in the UPS; it does not have to be rem oved. D ISCONNECTING THE B ATTERY FOR T RANSPORT The battery is accessible f rom the fron t of the UPS. This proce- du ...

  • American Power Conversion 120VAC - page 21

    17 6: S T OR A GE AND M AI N T E N AN C E S TORAG E S TORAGE C ONDITIONS Store the UPS covered and positioned as for proper functioning, in a cool, dr y location, with its bat- teries fully charged. Disconn ect any cables connected to th e computer interface port to av oid unnec- es s ary bat tery dr aina ge. E XTENDED S TORAG E At -15 t o +30 ° C ...

  • American Power Conversion 120VAC - page 22

    18 R EPL ACING THE B ATTERY M ODULE 1. The plug on the new battery module i s taped to the side of the battery. Remove this tape allo wing the plug and the attached white cord and battery cables to come to the front of the battery. 2. Supporti ng the new battery modul e on th e bottom, alig n it with the bat- tery door open ing and slide it int o t ...

  • American Power Conversion 120VAC - page 23

    19 7: T ROUBLESHOOTING Use the chart belo w to solve minor Smart-UPS installation and operation problems. Re fer to the APC web site, www.apc.com , for assistance with com p lex UPS problems. P ROBLEM AND P OSSI BLE C AUSE S OLUTION UPS WILL NOT TURN ON butto n not pus hed. Press t he butto n once to po wer the UPS an d the con nected equipm ent. U ...

  • American Power Conversion 120VAC - page 24

    20 P ROBLEM AND P OSSIB LE C AU S E S OLUTION A LL LED S ARE OF F AND THE UPS IS PLUGGED IN TO A WA LL OUTLET The U P S is shut down and t he battery is discha rged from an extended o utage. None. The U PS will return t o norm al operatio n when the pow er is restored and the battery has a su fficient ch arge. T HE REPLACE BATT ERY LED IS LIT Weak ...

  • American Power Conversion 120VAC - page 25

    21 S ERVICE If the UPS requires s er vice do not return it to the dealer. In st ead, follow these s teps : 1. Revi e w the problem s discussed in th e Troubleshooting secti on of this manual to eliminate com- mon probl e ms . 2. Verify that no circuit break ers are tripped. 3. If the problem persists, contact APC Customer Service through the APC we ...

  • American Power Conversion 120VAC - page 26

    22 8: R EGULA TOR Y A ND W AR R AN TY I NFOR M A TION R EGULATORY A GE NCY A PPROVALS AND R ADIO F RE QUENCY W ARNINGS 230V MOD EL S This is a Class A pr oduc t. In a dom estic enviro n- ment this prod uct ma y cause ra dio interf erenc e, in which case the user may be re quired to take correc- tive ac tions. 120V MOD EL S 120V S TAN DARD C LASS A ...

  • American Power Conversion 120VAC - page 27

    23 D ECLARATION OF C ONF ORM ITY L IMITED W ARRA NTY American Power Conversion (APC) warrants its products t o be free from defects in materia ls and workmanship for a period of two years from th e date of pu rcha se. Its ob ligat ion under t his warra nty is limi ted to repairin g or repla cing, at its own sole o p- tion, any such defect ive p rod ...

Производитель American Power Conversion Категория Power Supply

Документы, которые мы получаем от производителя устройства American Power Conversion 120VAC мы можем разделить на несколько групп. Это в частности:
- технические чертежи American Power Conversion
- инструкции обслуживания 120VAC
- паспорта изделия American Power Conversion
- информационные брошюры
- энергетические этикетки American Power Conversion 120VAC
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания American Power Conversion 120VAC.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа American Power Conversion 120VAC, инструкции обслуживания, короткие инструкции или инструкции пользователя American Power Conversion 120VAC. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия American Power Conversion 120VAC.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства American Power Conversion 120VAC, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании American Power Conversion 120VAC пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей American Power Conversion 120VAC.

Полная инструкция обслуживания American Power Conversion, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией American Power Conversion 120VAC - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания American Power Conversion 120VAC, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся American Power Conversion 120VAC, которое найдем в данном документе
3. Советы по использованию основных функций устройства American Power Conversion 120VAC - которые должны облегчить нам первые шаги во время использования American Power Conversion 120VAC
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем American Power Conversion 120VAC
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра American Power Conversion 120VAC в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся American Power Conversion 120VAC?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с American Power Conversion 120VAC, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с American Power Conversion 120VAC со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)