Инструкция обслуживания Carrier 38AKS028-044

24 страниц 0.55 mb
Скачать

Перейти на страницу of 24

Summary
  • Carrier 38AKS028-044 - page 1

    Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS ...................1 BEFORE INST ALLA TION .....................1 - 3 Rigging ......................................1 Placing Unit .................................3 Mounting Unit ...............................3 Compressor Mounting ........................3 INST A ...

  • Carrier 38AKS028-044 - page 2

    T able 1A — Physical Data — English UNIT 38AKS 028 034 044 COMPRESSOR Reciprocating Semi-Hermetic No. ...T ype 1...06E9265 1...06E9275 1...06E9299 No. Cyls (ea)...Speed, Rpm (60/50 Hz) 6...1750/1460 Capacity Steps 3 Oil Charge*, Pt 20.0 20.0 19.0 Oil Pressure Switch (psi) Set Points — Cutout 6 6 2 Differential — Cut-in 14 Max. Crankcase Hea ...

  • Carrier 38AKS028-044 - page 3

    Placing Unit — There must be 4 ft (1220 mm) for ser- vice on all sides of unit, and a minimum of 8 ft (2440 mm) clear air space above unit. For multiple units, allow 8 ft (2440 mm) separation between units for airflow and service. Mounting Unit — When unit is in proper location, use of mounting holes in base rails is recommended for securing u ...

  • Carrier 38AKS028-044 - page 4

    Receiver — No receiver is provided with the unit; it is recommended that one not be used. Piping Procedure — Do not remove run-around pipe from suction and liquid line stubs until piping connections are ready to be made. Pass nitrogen or other inert gas through piping while brazing, to prevent formation of copper oxide. Install field-supplied ...

  • Carrier 38AKS028-044 - page 5

    T able 2A — Refrigerant Piping Sizes — 60 Hz SINGLE SUCTION RISERS UNIT 38AKS LENGTH OF INTERCONNECTING PIPING, FT (M) 16-25 (4.9-7.6) 26-50 (7.9-15.2) 51-75 (15.5-22.8) 76-100 (23.2-30.5) 101-200 (30.8-60.9) LSL S L S L S L S 028 7 ⁄ 8 1 5 ⁄ 8 7 ⁄ 8 2 1 ⁄ 8 * 7 ⁄ 8 2 1 ⁄ 8 * 7 ⁄ 8 2 1 ⁄ 8 * 7 ⁄ 8 2 1 ⁄ 8 * 034 7 ⁄ 8 2 1 ? ...

  • Carrier 38AKS028-044 - page 6

    Power Supply — Electrical characteristics of available power supply must agree with unit nameplate rating. Supply voltage must be within limits shown in T able 3. IMPOR T ANT : Operating unit on improper supply volt- age, or with excessive phase imbalance, constitutes abuse and may af fect Carrier warranty . See Unbalanced 3-Phase Supply V oltage ...

  • Carrier 38AKS028-044 - page 7

    FIELD CONNECTIONS 1. Main Power — Bring wires from the fused disconnect switch through hole in bottom rail of unit to control box 11 12 (Fig. 6 and 7) and connect terminals , , and 13 line side of terminal block TB1 (see Fig. 8 and 9A or 9B). T o comply with NEC Article 440-14, the discon- nect must be located within sight from and readily ac- ce ...

  • Carrier 38AKS028-044 - page 8

    Fig. 6 — Dimensional Drawing, 38AKS028,034 LEGEND NEC — National Electrical Code VAV — V ariable Air V olume NOTES: 1. There must be minimum (2440 mm) 8 ft. clear air space above unit. 2. The approximate operating weight of the unit is: 50 AND 60 HZ UNIT WT (Lb) WT (Kg) 38AKS028 1650 748 38AKS028C 1804 818 38AKS034 1803 818 38AKS034C 2009 91 ...

  • Carrier 38AKS028-044 - page 9

    LEGEND NEC — National Electrical Code NOTES: 1. There must be minimum (2440 mm) 8 ft. clear air space above unit. 2. The approximate operating weight of the unit is: 50 HZ AND 60 HZ UNIT WT (Lb) WT (Kg) 38AKS044 2437 1 106 38AKS044C 2745 1246 Fig. 7 — Dimensional Drawing, 38AKS044 3. A ‘ ‘C’’ in the model number indicates unit has facto ...

  • Carrier 38AKS028-044 - page 10

    LEGEND AFS — Airflow Switch CB — Circuit Breaker EQUIP — Equipment FU — Fuse GND — Ground LLS1 — Liquid Line Solenoid for Solenoid Drop Control LLS2 — Liquid Line Solenoid for Capacity Control NEC — National Electrical Code, U.S.A. TB — T erminal Block TC — Thermostat Cooling Field Power Wiring Field Control Wiring Factory Inst ...

  • Carrier 38AKS028-044 - page 11

    BPR — Bypass Relay C— Contactor , Compressor DB — Circuit Breaker CR — Control Relay CM — Control Module EQUIP — Equipment FC — Fan Contactor Fig. 9A — Component Arrangement — 60 Hz FM — Fan Motor FU — Fuse GND — Ground LLSV — Liquid Line Solenoid V alve NEC — National Electrical Code (U.S.A.) TB — T erminal Block TRAN ...

  • Carrier 38AKS028-044 - page 12

    LEGEND BPR — Bypass Relay C— Contactor , Compressor CB — Circuit Breaker CR — Control Relay CM — Control Module EQUIP — Equipment FC — Fan Contactor FM — Fan Motor FU — Fuse GND — Ground LLSV — Liquid Line Solenoid V alve NEC — National Electrical Code (U.S.A.) TB — T erminal Block TDR — T ime Delay Relay TRAN — T rans ...

  • Carrier 38AKS028-044 - page 13

    ST ART -UP Initial Check Do not attempt to start the condensing unit, even mo- mentarily, until the following steps have been com- pleted. Compressor damage may result. 1. Check all auxiliary components, such as air -handling equip- ment, and other equipment. Consult the manufacturer ’ s instructions regarding any other equipment connected to the ...

  • Carrier 38AKS028-044 - page 14

    Fig. 10 — 38AKS028 Charging Chart, 50/60 Hz 14 ...

  • Carrier 38AKS028-044 - page 15

    Fig. 1 1 — 38AKS034 Charging Chart, 50/60 Hz 15 ...

  • Carrier 38AKS028-044 - page 16

    Fig. 12 — 38AKS044 Charging Chart, 50/60 Hz 16 ...

  • Carrier 38AKS028-044 - page 17

    FOR SER VICING ONL Y — T o speed up the 5-minute anti- short cycle, a temporary jumper may be placed between ter- minals T1 and T6 of the control module. This jumper must be removed after servicing is com- plete. Failure to remove this jumper is considered abu- sive treatment and will void the Carrier warranty. Bypass Relay (BPR) — All units ar ...

  • Carrier 38AKS028-044 - page 18

    COMPRESSOR END AND RIGHT -SIDE VIEW TRAN2 CB1 CB2 TB3 FC3 FC2 FC CM CR1 TRAN1 TB2 C1 COMPRESSOR END, CONTROL P ANEL REMOVED OIL PRESSURE SAFETY SWITCH COMPRESSOR END, LEFT -SIDE ACCESS DOOR (JUNCTION BOX COVER REMOVED) LIQUID LINE SERVICE VA LV E COMPRESSOR END, RIGHT -SIDE ACCESS DOOR Fig. 13 — 38AKS Unit with Access Panels Removed 18 ...

  • Carrier 38AKS028-044 - page 19

    Fan Adjustment — Adjust fan as shown in Fig. 14. Oil Charge — Compressors are factory charged with oil as follows: COMPRESSOR AMOUNT pints (liters) 06E9265 20.0 (9.4) 06E9275 20.0 (9.4) 06E9299 19.0 (9.0) When additional oil or a complete charge is required, use only Carrier-approved compressor oil: Petroleum Specialities Inc. ................. ...

  • Carrier 38AKS028-044 - page 20

    Oil Pressure Safety Switch (OPS) — The OPS in the control circuit stops the compressor and unit, if proper oil pressure dif ferential is not established at start-up or main- tained during operation. If OPS stops the unit, determine the cause and correct before restarting unit. Failure to do so will constitute abuse. Equipment failur e due to abus ...

  • Carrier 38AKS028-044 - page 21

    TROUBLESHOOTING SYMPTOM AND PROBABLE CAUSE PROBABLE REMEDY COMPRESSOR DOES NOT RUN 1. Control circuit breaker tripped 1. Reset control circuit breaker 2. Power line open 2. Reset circuit breaker 3. Oil pressure switch tripped 3. Reset oil pressure switch at unit 4. Safety device tripped 4. Reset control circuit with thermostat 5. Contactor stuck op ...

  • Carrier 38AKS028-044 - page 22

    P ACKAGED SERVICE TRAINING Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover: • Unit Familiarization • Installation Overview • Maintenance • Operating Sequence A large selection of product, theory , and skills programs is available. Al ...

  • Carrier 38AKS028-044 - page 23

    ST ART -UP CHECKLIST (Remove and store in job file) A. Preliminary Information OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUF ACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES B. Pre-Start-Up OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y . DOES IT AGREE ...

  • Carrier 38AKS028-044 - page 24

    C. Start-Up CHECK EV APORA TOR F AN SPEED AND RECORD. CHECK CONDENSER F AN SPEED AND RECORD. AFTER A T LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS: OIL PRESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP ENTERING CONDENSER AIR TEMP LEA VING CONDENSER AIR TEMP EV AP ENTERING AIR DB TEMP EV AP ENTER ...

Производитель Carrier Категория Air Conditioner

Документы, которые мы получаем от производителя устройства Carrier 38AKS028-044 мы можем разделить на несколько групп. Это в частности:
- технические чертежи Carrier
- инструкции обслуживания 38AKS028-044
- паспорта изделия Carrier
- информационные брошюры
- энергетические этикетки Carrier 38AKS028-044
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Carrier 38AKS028-044.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Carrier 38AKS028-044, инструкции обслуживания, короткие инструкции или инструкции пользователя Carrier 38AKS028-044. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Carrier 38AKS028-044.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Carrier 38AKS028-044, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Carrier 38AKS028-044 пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Carrier 38AKS028-044.

Полная инструкция обслуживания Carrier, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Carrier 38AKS028-044 - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Carrier 38AKS028-044, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Carrier 38AKS028-044, которое найдем в данном документе
3. Советы по использованию основных функций устройства Carrier 38AKS028-044 - которые должны облегчить нам первые шаги во время использования Carrier 38AKS028-044
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Carrier 38AKS028-044
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Carrier 38AKS028-044 в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Carrier 38AKS028-044?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Carrier 38AKS028-044, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Carrier 38AKS028-044 со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)