Инструкция обслуживания Advantech ADAM-5560

194 страниц 38.82 mb
Скачать

Перейти на страницу of 194

Summary
  • Advantech ADAM-5560 - page 1

    User Manual ADAM-5560 Series Programmable Automation Controllers ...

  • Advantech ADAM-5560 - page 2

    ADAM-5560 Series User Manual ii Copyright The document ation and the sof tware included with th is product are cop yrighted 2012 by Advantech Co., Ltd. All r ights are reserv ed. Advantech Co., Ltd . reserves the right to make improvements in the product s descr ibed in this manual at any time without notice. No p art of this manual may be repr odu ...

  • Advantech ADAM-5560 - page 3

    iii ADAM-5560 Series User Manu al Declaration of Conformity CE This product has passed the CE test for env ironment al specifications when shielded cables are used for external wiring. W e recommend the use of shielded cables. This kind of cable is available from Advantec h. Please contact your local supplier for ordering information. FCC Class A N ...

  • Advantech ADAM-5560 - page 4

    ADAM-5560 Series User Manual iv Safety Instructions 1. Read these safety instructions carefully . 2. Keep this User Manual f or later reference. 3. Disconnect this equipment from any AC outlet before cleaning. Use a damp cloth. Do not use liquid or spray detergents fo r cleaning. 4. For plug-in equipment, the po wer outlet socket must be located n ...

  • Advantech ADAM-5560 - page 5

    v ADAM-5560 Series User Manu al Content s Chapter 1 Overview ...............................................1 1.1 Introduction .... ................... ................. ................ ................ ................ ....... 2 1.2 Features ................ ................ ................ ................ ................ ................ .... ...

  • Advantech ADAM-5560 - page 6

    ADAM-5560 Series User Manual vi Figure 2.4 COM1/COM4 RS-232/485 Settings ............. ... .... ... .. 22 Figure 2.5 COM1 RS-23 2/485 and Terminal Resistor Settings. 23 Figure 2.6 COM3 RS-23 2/485 and Terminal Resistor Settings. 23 Figure 2.7 COM4 RS-23 2/485 and Terminal Resistor Settings. 23 Figure 2.8 ADAM-5560 Series DIP Switch ....... ........ ...

  • Advantech ADAM-5560 - page 7

    vii ADAM-5560 Series User Manu al A.1 RS-485 Networks ........... ... .... ... ... ... .... ... ................ ... ... .... ... ................ ... 168 A.2 Basic Network Layout ....... ................. ................ ................ ................ ... 168 Figure A.1 Daisychaining ...... ................... ................ ................ ...

  • Advantech ADAM-5560 - page 8

    ADAM-5560 Series User Manual viii ...

  • Advantech ADAM-5560 - page 9

    Chapter 1 1 Overview ...

  • Advantech ADAM-5560 - page 10

    ADAM-5560 Series User Manual 2 1.1 Introduction ADAM-5560 Series Controlle r is Programm able Automation Controller designed for control tasks which require Industrial PC computing performance with the PLC’s robustness. ADAM-5560 Series Controller of fers Intel A TOM Z510P CPU along with control specific features such as watchdog time r , battery ...

  • Advantech ADAM-5560 - page 11

    3 ADAM-5560 Series User Manu al Chapter 1 Overview Designed for control t asks that meet robust and computing performance requirement s of PLC and Industrial PC’ s ADAM-5560 Series Controller is designed for control t asks which need Industrial PC’s computing performance and PLC’ s robustness. It s multiple functionalities include discrete, a ...

  • Advantech ADAM-5560 - page 12

    ADAM-5560 Series User Manual 4 Cross-Language Programming For some project integrate and scalable issue s, cross-language can help you to choose the different lang uage for you r projec t. Fo r example, you can use ladder (LD) on the simple I/O module control or simple log ical expression and u se Function Block (FB) on process control for more adv ...

  • Advantech ADAM-5560 - page 13

    5 ADAM-5560 Series User Manu al Chapter 1 Overview Real time multi-t ask engine ADAM-5560 Series Controller provides the multi-task and multi-program e nviron- ment. ADAM-5560 Series Controller ’s communication, dat a process and I/O access tasks are working independent, so the sy stem performance and ef ficiency are better than traditional PLC. ...

  • Advantech ADAM-5560 - page 14

    ADAM-5560 Series User Manual 6 Dual Ethernet Port s ADAM-5560 Series Controller provides tw o Ethernet port s for different application requirements such as redundant Ethernet conne ction for reliability concern or sep a - rated network connections for security conc ern. Bo th of the functions are possible to be implemented by customer’s applicat ...

  • Advantech ADAM-5560 - page 15

    7 ADAM-5560 Series User Manu al Chapter 1 Overview Remote maintenance via FTP Server and Diag Anywhere Sof tware For remote maintenance function, the built-in FTP server provides service for upload- ing application program or downloading dat a logging files. DiagAnywhere Sof twar e is also supported for remote cont rol, download and upload function ...

  • Advantech ADAM-5560 - page 16

    ADAM-5560 Series User Manual 8 Remote I/O Exp ansibility ADAM-5560 Series Controller supports not only Modb us/RTU Ma ster function via serial ports, but also the Modbus/TCP Client to retrieve data from remote I/O, and Modbus/TCP Server to exchange dat a with other Modbus devices via Etherne t port. This Modbus features are very useful when the con ...

  • Advantech ADAM-5560 - page 17

    9 ADAM-5560 Series User Manu al Chapter 1 Overview  Connector: DB-9 pin  T ransmission speed: Up to 1 15.2 Kbps  Max transmission dist ance: – RS-232: 50 feet (15.2 m) – RS-485: 4,000 feet (1220 m) 1.3.6 RS-485 interface (COM2)  Signals: DA T A +, DA T A -  Mode : Half duplex, multi-drop  Connector: Screw terminal  T ransmi ...

  • Advantech ADAM-5560 - page 18

    ADAM-5560 Series User Manual 10 1.3.1 1 Mechanical  Case: ABS+PC with captive mounting hardware  Plug-in screw terminal block: Accepts 0.5 mm 2 to 2.5 mm 2 , 1 - #12 or 2 - #14 to #22 A WG 1.3.12 Environment  Operating temperature: 0 ~ 55° C ( 32 ~ 122° F)  S torage temperature: -25° to 85° C (-13° to 185° F)  Humidity: 5 to 95 ...

  • Advantech ADAM-5560 - page 19

    11 ADAM-5560 Series User Manu al Chapter 1 Overview There are two LEDs besides each Ethern et p o rt. The LEDs indicate operating st atus, as explained below: TX (Green): This LED blinks whenever the ADAM-5560 Series Controller transmitting data to Ethernet. Link (Orange): This LED is on whenever the ADAM-5560 Series Controller connecting to Ethern ...

  • Advantech ADAM-5560 - page 20

    ADAM-5560 Series User Manual 12 ...

  • Advantech ADAM-5560 - page 21

    Chapter 2 2 Installation ...

  • Advantech ADAM-5560 - page 22

    ADAM-5560 Series User Manual 14 2.1 Overview This chapter describes how to in stall an ADAM-5560 Series Controller . A quick hookup scheme is provided that let you easily configu re your system before imple- menting it into your application. 2.2 System Requirement s Before you st art installing th e ADAM-5560 Series Controlle r , make sure the syst ...

  • Advantech ADAM-5560 - page 23

    15 ADAM-5560 Series User Manu al Chapter 2 Installation 2.3 Hardware Inst allation 2.3.1 Selecting I/O Module T o organize an ADAM-5560 Series control sy stem, you need to select I/O modules to interface the main unit with field de vices or processes that you ha ve previously deter- mined. There are several things sh ould be considered when yo u se ...

  • Advantech ADAM-5560 - page 24

    ADAM-5560 Series User Manual 16 Module ADAM- 5013 ADAM- 5017 ADAM- 5017UH ADAM- 5018 ADAM- 5024 Analog Input Resolution 16 bit 16 bit 12 bit 16 bit - Input Channel 3 8 8 7 - Sampling Rate 10 10 8K (T otal ) 10 - V oltage In put - ±150 mV ±500 mV ±1 V ±5 V ±10 V ±10 V 0~10V 0~20mV ±15 mV ±50 mV ±100 mV ±500 mV ±1 V ±2.5 V - Current Input ...

  • Advantech ADAM-5560 - page 25

    17 ADAM-5560 Series User Manu al Chapter 2 Installation Module ADAM- 5052 ADAM- 5055S ADA M- 5056 ADAM- 5056D ADAM- 5056S / 5056SO Analog Input Resolution - - - - - Input Channel -- -- - Sampling Rate -- -- - V oltage Input - - - - - Current Input -- -- - Direct Sensor Input -- -- - Analog Output Resolution - - - - - V oltage Output - - - - - Curre ...

  • Advantech ADAM-5560 - page 26

    ADAM-5560 Series User Manual 18 2.3.2 Selecting Power Supply Module ADAM-5560 Series Controller works under unregulated power so urce between +10 and +30 VDC. When you arrange d ifferent I/ O modules on ADAM-5560 Series Con- troller ’s backplane, it may require comp arab le power supply . Use the following step s as guidelines for selecting a pow ...

  • Advantech ADAM-5560 - page 27

    19 ADAM-5560 Series User Manu al Chapter 2 Installation Calculate the Summary of the whole system’s power consumption. For example, there are following items in your system. ADAM-5550KW * 3 & ADAM-5024 * 2 & ADAM-5017 * 4 & ADAM-5068 * 2 & ADAM-5056D * 2 The power consumption is: 17 W * 3 + 2.9 W * 2 + 1.25 * 4 + 1.8 W * 2 + 0.84 ...

  • Advantech ADAM-5560 - page 28

    ADAM-5560 Series User Manual 20 Select a suitable power supply from T able 2.4 or other comp arable power resource for system operation. 2.3.3 Inst all Main Unit and Modules While inserting modules into the system, align the PC board of the module with the grooves on the top and bottom of the system. Push th e module straight into the sys- tem unti ...

  • Advantech ADAM-5560 - page 29

    21 ADAM-5560 Series User Manu al Chapter 2 Installation 2.3.5 Mounting The ADAM-5560 Series Controller can be in stalled on a p anel or on a DIN rail. 2.3.5.1 Panel Mount Mount the system on th e panel horizontally to provide proper ventilation. Y ou cannot mount the system vertically , upside down or on a flat horizont al surface. A standard #7 ta ...

  • Advantech ADAM-5560 - page 30

    ADAM-5560 Series User Manual 22 The system can also be secured to the cabi net by using mounting rails. If you mount the system on a rail, you s hould also consider using end brackets at each end of the rail. The ended bracket s help keep th e system from sliding horizonta lly along the rail. This minimizes the possibility of accident ally pulling ...

  • Advantech ADAM-5560 - page 31

    23 ADAM-5560 Series User Manu al Chapter 2 Installation COM1 Jumper Setting The Communication port of COM1 is set by CN4, CN5, CN6 (Mode) and CN7 (T ermi- nal Resistor). Figure 2.5 COM1 RS-232/485 and T erminal Resistor Settings COM3 Jumper Setting The Communication port of COM3 is set by CN9, CN10, CN1 1 (Mode) and CN12 (T erminal Resistor). Figur ...

  • Advantech ADAM-5560 - page 32

    ADAM-5560 Series User Manual 24 2.3.6.2 DIP Switch Setting Figure 2.8 ADAM-5560 Series DIP Switch Device ID Setting: Y ou can set up your device ID by changing DIP Switch 1-8. The available ID for ADAM-5560 Series Controller is from 0 to 255. Please refer to the T able 2.6 Device ID DIP Switch T able to set up your Device ID. T able 2.5: Device ID ...

  • Advantech ADAM-5560 - page 33

    25 ADAM-5560 Series User Manu al Chapter 2 Installation 2.3.7 COM Port Pin Assignment s Figure 2.9 RS-232 Port Pin Assignment Figure 2.10 RS-485 Port Pin Assignment ...

  • Advantech ADAM-5560 - page 34

    ADAM-5560 Series User Manual 26 2.4 System Wi ring and Connections This section provides basic information on wiring the power su pply , I/O modules and communication port connection. 2.4.1 Power Supply Wiring Although the ADAM-5560 Series Co ntroller is designed for a stan dard industrial unregulated 24 V DC power supply , they accept any power un ...

  • Advantech ADAM-5560 - page 35

    27 ADAM-5560 Series User Manu al Chapter 2 Installation 2.4.3.1 Remote I/O Wiring Modbus/RT U Master Function via COM1/COM2/COM4 RS-485: Figure 2.12 Remote I/O Wirin g Y ou can connect typical 128 ADAM-4000 Modbus Remote I/O modules via COM1/ COM2/COM4. Please set the COM1 and COM4 as RS-485 mode. 2.4.4 Ethernet Network Connection The ADAM-5560 Ser ...

  • Advantech ADAM-5560 - page 36

    ADAM-5560 Series User Manual 28 ...

  • Advantech ADAM-5560 - page 37

    3 Quick Start Chapter 3 ...

  • Advantech ADAM-5560 - page 38

    ADAM-5560 Series User Manual 30 This chapter will help you get familiar with ADAM-5560KW Controller and Multiprog Programming Software by following step by step examples. In this chapter , you need to prepare the system configur ation as below . Main Module: ADAM-5560KW X1, IP Address: 192.168.1.5 Local I/O Modules: ADAM-5051D in Slot 0 ADAM-5056D ...

  • Advantech ADAM-5560 - page 39

    31 ADAM-5560 Series User Manu al Chapter 3 Quick Start 3.1 Set IP Address to ADAM-5560KW 1. [P AC Device] Power up ADAM-5560KW and click “S tart”. 2. [P AC Device] Click “Settings” and “Network and Dial-up Connections”. ...

  • Advantech ADAM-5560 - page 40

    ADAM-5560 Series User Manual 32 3. [PAC Device] Right click “PCI-RTL8139 1” icon and then click “Properties”. 4. [PAC Device] T ype IP Address like “192.168.1.5” and Subnet Mask “255.255.255.0”. ...

  • Advantech ADAM-5560 - page 41

    33 ADAM-5560 Series User Manu al Chapter 3 Quick Start 5. [PAC Device] Right click “PCI-R TL81392” icon and then click “Properties”. 6. [PAC Device] T ype IP Address like “192.168.1.6” an d Subnet Mask “255.255.255.0”. Now the IP address conf iguration has been finished. ...

  • Advantech ADAM-5560 - page 42

    ADAM-5560 Series User Manual 34 7. If your PC has inst alled DiagAnywhere Sof tware, you can search the ADAM- 5560KW and check the Ethernet connectio n. Please click the “Remote device” and click “Search” button. 8. Click “ADAM-5560” and then click OK button without ente ring any password. ...

  • Advantech ADAM-5560 - page 43

    35 ADAM-5560 Series User Manu al Chapter 3 Quick Start 9. The screen of ADAM-5560KW will be shown in the window . Now it is possible to remotely control the ADAM-5560KW by PC’ s mouse. 3.2 Configure ADAM-5000 Local I/O 1. [P AC Device] Click “S tart” -> “Programs” -> “Advantech” -> “Adam.NET Utility”. ...

  • Advantech ADAM-5560 - page 44

    ADAM-5560 Series User Manual 36 2. [P AC Device] Click “Local system” to view the local I/O modules. 3. [P AC Device] ADAM-5051 and ADAM-5056 are listed. Sele ct “ADAM-5051”. ...

  • Advantech ADAM-5560 - page 45

    37 ADAM-5560 Series User Manu al Chapter 3 Quick Start 4. [PAC Device] Check the st ate of DI 0 is “ON”. 5. [PAC Device] Change the st ate of DI 0 to “OFF” and check the d isplay . ...

  • Advantech ADAM-5560 - page 46

    ADAM-5560 Series User Manual 38 6. [PAC Device] Select “ADAM-5056”. 7. [PAC Device] Change the state of DO 0, DO 2, DO 4 , DO 6, DO 8, DO 10,DO 12, DO 14 to “ON” and check the display . ...

  • Advantech ADAM-5560 - page 47

    39 ADAM-5560 Series User Manu al Chapter 3 Quick Start 3.3 Multiprog Inst allation Following will guide you how to setup Mult iprog IEC-61 131-3 development environ- ment on your PC. 1. Please use your web browser to visit Ad vantech web site. (www .advan- tech.com) 2. T y pe "ADAM-5560" on the search box which is on the right-up corner o ...

  • Advantech ADAM-5560 - page 48

    ADAM-5560 Series User Manual 40 2. Click “OK” to enter the DEMO Mode. 3. Click “Register” to enter the Registration Code. ...

  • Advantech ADAM-5560 - page 49

    41 ADAM-5560 Series User Manu al Chapter 3 Quick Start 4. Enter the Registration Code which come s with Advantech Multiprog Sof tware License Sheet. 5. Click “OK” to finish the registration. ...

  • Advantech ADAM-5560 - page 50

    ADAM-5560 Series User Manual 42 6. Open a new project and st art to create the test project. 7. Select “ADAM-5560KW” item and then click “OK”. ...

  • Advantech ADAM-5560 - page 51

    43 ADAM-5560 Series User Manu al Chapter 3 Quick Start 8. Double click “Advant ech DAQ” item. 9. Check the folder is at “Input”. ...

  • Advantech ADAM-5560 - page 52

    ADAM-5560 Series User Manual 44 10. Select “ADAM5051” and then click “Add”. 11 . Select “0” for “Board ID”. Set “0” to “S tart Address” and then click “OK”. ...

  • Advantech ADAM-5560 - page 53

    45 ADAM-5560 Series User Manu al Chapter 3 Quick Start 12. Click “Create All Input V ariables” and then click “OK”. 13. Click “Output” folder . Select “ADAM5056” and then click “Add”. ...

  • Advantech ADAM-5560 - page 54

    ADAM-5560 Series User Manual 46 14. Select “1” for “Board ID”. Set “0” to “S tart Address” an d then click “OK”. 15. Click “Create All Input V ari ables” and then click “OK”. ...

  • Advantech ADAM-5560 - page 55

    47 ADAM-5560 Series User Manu al Chapter 3 Quick Start 16. Double click “main” and graphi cal worksheet will be shown. 17. Click on the graphical editor and ladder obje cts will be activated. ...

  • Advantech ADAM-5560 - page 56

    ADAM-5560 Series User Manual 48 18. Add a cont act network. 19. Double click “C000”. ...

  • Advantech ADAM-5560 - page 57

    49 ADAM-5560 Series User Manu al Chapter 3 Quick Start 20. Dialog box of “Contact/Coi l Property” will be shown. 21. Click “Global scope”. Select “In_ ADAM5051_ 0_0” and then click “Apply”. ...

  • Advantech ADAM-5560 - page 58

    ADAM-5560 Series User Manual 50 22. “Common” folder will be shown. Click “Cont act” folder . 23. Click “Global”. Select “ADAM5051_B00C000_I” an d then click “Apply”. ...

  • Advantech ADAM-5560 - page 59

    51 ADAM-5560 Series User Manu al Chapter 3 Quick Start 24. Click “OK”. 25. Double click “C001”. ...

  • Advantech ADAM-5560 - page 60

    ADAM-5560 Series User Manual 52 26. Click “Global”. Select “ADAM50 56_B01C000_O” and then click “Apply”. 27. Click “OK”. ...

  • Advantech ADAM-5560 - page 61

    53 ADAM-5560 Series User Manu al Chapter 3 Quick Start 28. Back to graphical editor . 29. Right click “Resource: ADV_CE” and then click “Settings”. ...

  • Advantech ADAM-5560 - page 62

    ADAM-5560 Series User Manual 54 30. T ype IP Address of ADAM-5560KW as “192.168.1 .5”. 31. Click “Make” to build the exe cution fi le. Check the project has been compiled successfully . ...

  • Advantech ADAM-5560 - page 63

    55 ADAM-5560 Series User Manu al Chapter 3 Quick Start 32. Click “Project Control Dialog” and then click “Download”. 33. Check “Include boot project” and then click “Download ”. ...

  • Advantech ADAM-5560 - page 64

    ADAM-5560 Series User Manual 56 34. Downloading execution file to ADAM-556 0KW . 35. Click “Cold” to execute a cold st art. During a cold sta rt all data are initialized. ...

  • Advantech ADAM-5560 - page 65

    57 ADAM-5560 Series User Manu al Chapter 3 Quick Start 36. Click “Debug On/Of f” to turn on the debug functio n. The ADAM-5560KW is run- ning correctly when you see the st atus bar turns green color . Y ou can see the DI0 and DO0 are turned blue co lor . It means the st ate is F ALSE. 37. When you change the st ate of ADAM-5051D CH0 as ON, ADAM ...

  • Advantech ADAM-5560 - page 66

    ADAM-5560 Series User Manual 58 38. Finish the test project and do n ot forget to save it properly . ...

  • Advantech ADAM-5560 - page 67

    59 ADAM-5560 Series User Manu al Chapter 3 Quick Start 3.5 S pecial Module Support in KW ADAM-5050 is one of mix digi tal input /output module and ea ch channel can be inde- pendently configured to be an input or an output channel by the setting of it s DIP switch (Please refer the user manu al of ADAM-5000 IO Module to get more det ail). For the A ...

  • Advantech ADAM-5560 - page 68

    ADAM-5560 Series User Manual 60 ...

  • Advantech ADAM-5560 - page 69

    Chapter 4 4 Modbus Functions ...

  • Advantech ADAM-5560 - page 70

    ADAM-5560 Series User Manual 62 4.1 Introduction The Modbus functions of ADAM-5560KW Cont rolle r are powerfu l featu res which pro- vide high expansib ility and flexibility for user ’s applications. The supported mod bus functions include following items.  Modbus/R TU Master Function: Connect to Modbus/R TU remote I/O modules such as Modbus m ...

  • Advantech ADAM-5560 - page 71

    63 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 4.2.1 An example to demonstrate how to connect to ADAM-6050 for Modbus/TCP client function 1. [PAC Device] Run ADAM.NET utility by clicki ng “S tart” -> “Programs” -> “Advantech” -> AdamNET Utility . 2. [PAC Device] Select “ADAM5000TCP_6000” item. ...

  • Advantech ADAM-5560 - page 72

    ADAM-5560 Series User Manual 64 3. [PAC Device] Click “Search” button. 4. [PAC Device] Click “192.168.1.12” item and then “6050” item will show . ...

  • Advantech ADAM-5560 - page 73

    65 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 5. [PAC Device] Click “6050” item to see the channel setting. 6. [PAC Device] Enter “00000000” and then click “OK” b utton. ...

  • Advantech ADAM-5560 - page 74

    ADAM-5560 Series User Manual 66 7. [PAC Device] Check ADAM-6050 DI bit 0 is OFF . 8. [PAC Device] T urn on ADAM-6050 DI bit 0 and make sure the st atus is ON in the utility . ...

  • Advantech ADAM-5560 - page 75

    67 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 9. [PAC Device] ADAM-6050 setting is correct. Ex it from the ADAM.NET utility . 10. Open “T est.mwt” and follow the example in section 3.4. ...

  • Advantech ADAM-5560 - page 76

    ADAM-5560 Series User Manual 68 11 . Double-click “main” to show the program in graphical editor . 12. Double-click “Advant ech_DAQ” to show the “I/O Configuration” dialog box. ...

  • Advantech ADAM-5560 - page 77

    69 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 13. Click “MODBUSTCP” item and then click “Add” button. 14. Set Modbus Command: “1X”, Slave ID: 1, Slave IF: “192 .168.1.12”, Data T ype: “BOOL”, S tart Address: “1”, No. of point s: 12. ...

  • Advantech ADAM-5560 - page 78

    ADAM-5560 Series User Manual 70 15. Click “Create All Input V ari ables” then click “OK” button. 16. Click “Cont act Network” button. ...

  • Advantech ADAM-5560 - page 79

    71 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 17. Double-click “C002”. 18. Click “Gloabal scope” folder . ...

  • Advantech ADAM-5560 - page 80

    ADAM-5560 Series User Manual 72 19. Select “In_MBTCPDR V_0_1” and then click “Apply”. 20. Click “Contact” folder . ...

  • Advantech ADAM-5560 - page 81

    73 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 21. Select “MBTR_1X0001_BOOL_00” and the n click “Apply”. 22. Check the setting is correct and then click “OK”. ...

  • Advantech ADAM-5560 - page 82

    ADAM-5560 Series User Manual 74 23. Double-clic k “C003”. 24. Select “ADAM5056_B01C001_0” and t hen click “Apply”. ...

  • Advantech ADAM-5560 - page 83

    75 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 25. Check the setting is correct and then click “OK”. 26. Click “Make” button to make the execution file. ...

  • Advantech ADAM-5560 - page 84

    ADAM-5560 Series User Manual 76 27. Check compile result is correct. 28. Click “Project Control Dia log” and then click “S top” and “Reset”. ...

  • Advantech ADAM-5560 - page 85

    77 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 29. Click “Download” button. Check the “Inclu de Bootproject” item and then click “Download” button to proceed with the download p rocess. 30. Execution file is downloading. ...

  • Advantech ADAM-5560 - page 86

    ADAM-5560 Series User Manual 78 31. Click “Cold” to run the project. 32. Check the sta tus of ADAM-6050 DI bit 0 and ADAM-50 56D DO bit 1 are OFF . ...

  • Advantech ADAM-5560 - page 87

    79 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 33. T urn on ADAM-6050 DI bit 0 and check th e st atus of ADAM-5056D DO bit 1 is turned ON correctly . 34. Save the project properly . ...

  • Advantech ADAM-5560 - page 88

    ADAM-5560 Series User Manual 80 4.3 Modbus/RTU Master Function The Modbus/R TU master function is supported by COM1/COM2/COM4 RS-485 Ports of ADAM-5560 Series Controller . There ar e typical 128 I/O modules can be connect ed to each COM port. So far , there are 12 modules of ADA M- 4000 Series s upport mod- bus protocol as following list. (Please r ...

  • Advantech ADAM-5560 - page 89

    81 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions System Wiring: COM4 Jumper Settings: Note! After changing the ju mper settings, please reset th e ADAM-5560 Series Controller. ...

  • Advantech ADAM-5560 - page 90

    ADAM-5560 Series User Manual 82 RS-485 Port Pin Assignment: 1. [P AC Device] Run ADAM.NET utility by clicki ng “S tart” -> “Programs” -> “Advantech” -> Ad amNET Utility . ...

  • Advantech ADAM-5560 - page 91

    83 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 2. [P AC Device] Select “ADAM4000_5000” item. 3. [P AC Device] Select “COM4” and then click “Search” button. ...

  • Advantech ADAM-5560 - page 92

    ADAM-5560 Series User Manual 84 4. [P AC Device] Click “S tart” button and “4018P” will be shown. 5. [P AC Device] Click “4018P” to see the module setting. ...

  • Advantech ADAM-5560 - page 93

    85 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 6. [P AC Device] Click “Data area” to check the reading of Channel 0 is cor rect. This channel will be used by following demonstratio n. 7. [P AC Device] Select “COM4” and then click “Adam Commander” button. ...

  • Advantech ADAM-5560 - page 94

    ADAM-5560 Series User Manual 86 8. [P AC Device] Input “#010” and click “Send”. Check the response of the CH0 reading is correct. 9. [P AC Device] Set the ADAM-4018+ to initial mode by changing th e switch position to “Init” side and then resetting the module. The switch is at the left side of the module. After that, se lect “COM 4” ...

  • Advantech ADAM-5560 - page 95

    87 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 10. [P AC Device] Click “S tart” and “4018(*)” will be shown. “*” represent s the module is at initial mode. 11 . [P AC Device] Select “4018P(*)” and then change the Protocol setting to “Modbus”. ...

  • Advantech ADAM-5560 - page 96

    ADAM-5560 Series User Manual 88 12. [P AC Device] Click “OK” to change the set ting. 13. [P AC Device] Select “Data area” and check the CH0 reading. Click “W aveScan” to see the wavescan window . ...

  • Advantech ADAM-5560 - page 97

    89 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 14. [P AC Device] Check CH0 reading and then close the window . 15. [P AC Device] Set the ADAM-4018+ to normal mode by changing the switch position to “Normal” side and then resetting the mod ule. After that, select “COM4” and then click “Search” and “S tart” buttons. ...

  • Advantech ADAM-5560 - page 98

    ADAM-5560 Series User Manual 90 16. [P AC Device] Click “4018P(01)” to see the module setting. 17. [P AC Device] Select “Data area” folder and check CH0 reading. ...

  • Advantech ADAM-5560 - page 99

    91 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 18. [P AC Device] Select “COM4” and then click “Adam Commander”. 19. [P AC Device] Change to “MODBUS” folder . ...

  • Advantech ADAM-5560 - page 100

    ADAM-5560 Series User Manual 92 20. [P AC Device] Check the reading of CH0. The formula is (1215*1370) / 65 536 = 25.4 ºC. 21. Open the “T est.mwt” project and then double-click “main”. ...

  • Advantech ADAM-5560 - page 101

    93 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 22. Double-click “Advantech_DAQ”. 23. Select “MODBUSRTU” and then click “Add” button. ...

  • Advantech ADAM-5560 - page 102

    ADAM-5560 Series User Manual 94 24. Set COM: “COM4”, Modbus Command: “3 X”, Slave ID: 1, S tart Address: “1”, No. of points: 8, Data T ype: “INT”. 25. Click “Create All Input V a riables” and then click “OK”. ...

  • Advantech ADAM-5560 - page 103

    95 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 26. Click “Edit Wizard” to see the function blocks. 27. Find the “GT” Greater Than Function Block. ...

  • Advantech ADAM-5560 - page 104

    ADAM-5560 Series User Manual 96 28. Add one “GT” function block. 29. Add one coil by clicking “Ad d Coil Right” button. ...

  • Advantech ADAM-5560 - page 105

    97 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 30. Connect “C004” coil to “GT” output. 31. Double-click the first input of “GT” function block. ...

  • Advantech ADAM-5560 - page 106

    ADAM-5560 Series User Manual 98 32. Select “Global scope” folder . 33. Select “In_MBR TUDR V_769_772” and then click “Apply”. ...

  • Advantech ADAM-5560 - page 107

    99 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 34. Select “MBR_3X0001_INT_769_I” to read CH0 of ADAM-4018+ module and then click “Apply”. 35. Double-click on the se co nd i npu t o f “ GT” fun ct ion blo ck . ...

  • Advantech ADAM-5560 - page 108

    ADAM-5560 Series User Man ual 100 36. T ype “1 196” and then Click “Apply” and “OK”. 37. Check the setting “1 196” is correct. (1 196*1370)/65536 = 25ºC ...

  • Advantech ADAM-5560 - page 109

    101 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 38. Double-click “C004”. 39. Select “ADAM5056_B01C002_O” to connec t the “GT” function block output to ADAM-5056D DO bit 2. Click “Apply” and “OK”. ...

  • Advantech ADAM-5560 - page 110

    ADAM-5560 Series User Man ual 102 40. Click “Make” button t o make the execution file. 41. Check compile result is correct. ...

  • Advantech ADAM-5560 - page 111

    103 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 42. Click “Project Control Dialog” button and then click “S top” and “Reset”. 43. Click “Download” button. Check the “Include bootproject” item and then click “Download” to proceed with download process. ...

  • Advantech ADAM-5560 - page 112

    ADAM-5560 Series User Man ual 104 44. Project is downloading. 45. Click “Cold” button to run the project. ...

  • Advantech ADAM-5560 - page 113

    105 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 46. Click “Debug on/of f” button. 47. Check the reading of ADAM-4018+ CH0 is “1088” which is less than “1 196”. The ADAM-5056D DO CH2 is OFF . ...

  • Advantech ADAM-5560 - page 114

    ADAM-5560 Series User Man ual 106 48. Heating the thermocouple of ADAM-4018+ CH0. When the readi ng is gr eat er than “1 196”, the ADAM-5056D DO CH2 will turn ON. 49. Save the project for following demonstration. ...

  • Advantech ADAM-5560 - page 115

    107 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 4.4 Modbus/TCP Server Functions ADAM-5560 Series Controller support s M odbus/TCP server function for connecting to HMI/SCADA software. The Modbus/TCP ser ver function is supported by using Ethernet port of ADAM-5560 Series Controller . 4.4.1 Modbus Address Mapping ADAM-5560 Series Contro ...

  • Advantech ADAM-5560 - page 116

    ADAM-5560 Series User Man ual 108 4.4.2 Example 1. Open the “T est.mwt” and add one “Move” f unction block. 2. “Move” function block will be shown on gra phical editor . ...

  • Advantech ADAM-5560 - page 117

    109 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 3. Double-click the input of “Move” function b lock. Select “MBTR_1X0001_BOOL_00” (ADAM-6050 DI bit 0) and then click “Apply” and “OK”. 4. Double-click output of “M ove” function block. ...

  • Advantech ADAM-5560 - page 118

    ADAM-5560 Series User Man ual 110 5. T ype “MB0X0001” and click “Apply” button. 6. Select “BOOL” for Dat a T ype. T ype “%mw3.0.0” for “I/O address” and th en click “Apply” and “OK”. ...

  • Advantech ADAM-5560 - page 119

    111 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 7. Click “Make” button to make the execution file. 8. Check compile resul t is correct. ...

  • Advantech ADAM-5560 - page 120

    ADAM-5560 Series User Man ual 112 9. Click “Project Control Dialog” button and then click “S top”. 10. C l i c k “Reset” button. ...

  • Advantech ADAM-5560 - page 121

    113 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 11 . Click “Download ” button. Check the “Include bootproject” item and then click “Download” to proceed with download process. 12. Project is downloading. ...

  • Advantech ADAM-5560 - page 122

    ADAM-5560 Series User Man ual 114 13. Click “Cold” to run the project. Click “Debug on/of f” button to see the result. 14. Run Modbus/TCP Client u tility Modscan and check the value of I/O address mw3.0.0 and Modscan I/O address 00001 are the same. ...

  • Advantech ADAM-5560 - page 123

    115 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 15. Change the status o f ADAM-6050 DI bit 0 to “1”. Check the values of I/O address mw3.0.0 and Modscan I/O address 00 001 are all changed to “1”. 16. Add one more “Move” fu nction block for analog measurement. ...

  • Advantech ADAM-5560 - page 124

    ADAM-5560 Series User Man ual 116 17. Double-click the input of the 2 nd “Move” function block. Select “MBR_3X0001_INT_769_I” (ADAM-4018+ CH0) and then click “App ly” and “OK”. 18. Double-click the output. ...

  • Advantech ADAM-5560 - page 125

    117 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 19. T ype “MB4X0001” and then click “Apply”. 20. Select “INT” for Data T ype. T ype “%mw3.2” for “I/O address” and then click “Apply” and “OK”. ...

  • Advantech ADAM-5560 - page 126

    ADAM-5560 Series User Man ual 118 21. Click “Make” button to make the execution file and check the compile result is correct. 22. Click “Project Control Dialog” b utton. ...

  • Advantech ADAM-5560 - page 127

    119 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 23. Click “S top” and “Reset” button. 24. Click “Download” button. Check the “Include bootproject” item and then click “Download” to proceed with download process. ...

  • Advantech ADAM-5560 - page 128

    ADAM-5560 Series User Man ual 120 25. Project is downloading. 26. Click “Cold” to run the project . Click “Debug on/of f” button to see the result. ...

  • Advantech ADAM-5560 - page 129

    121 ADAM-5560 Series User Manu al Chapter 4 Modbus Functions 27. Run Modbus/TCP Client utility Modscan and check the values of I/O address mw3.2 and Modscan I/O address 40002 are the same. 28. Save the project and the test is finish ed. ...

  • Advantech ADAM-5560 - page 130

    ADAM-5560 Series User Man ual 122 ...

  • Advantech ADAM-5560 - page 131

    Chapter 5 5 Network Functions ...

  • Advantech ADAM-5560 - page 132

    ADAM-5560 Series User Man ual 124 5.1 W e b Server Functions ADAM-5560 Series Controller features bui lt-in web server function of Windows CE 5.0. Before you using the web server function, please do follow the step s in section 7.1.1 to configure the basic settings properly . For monitoring and co ntrolling the local I/O modules on ADAM-5560 Series ...

  • Advantech ADAM-5560 - page 133

    125 ADAM-5560 Series User Manu al Chapter 5 Network Functions 2. The NAS Admin page will be shown. T ype in the password, for examp le, “admin” and then click “Apply”. 3. Gateway is resetting. ...

  • Advantech ADAM-5560 - page 134

    ADAM-5560 Series User Man ual 126 4. Internet Explorer will connect to server automatically an d ask to type the user name and password a gain. 5. Change the Device Name like “A DAM-5510-1” and then click “Apply”. ...

  • Advantech ADAM-5560 - page 135

    127 ADAM-5560 Series User Manu al Chapter 5 Network Functions 6. Click “Add/Del Users” to change the password of user name “ad min”, if necessary . 7. T ype “admin” in “User” field. In foll owing example, please type “admin” in “Password” field and then click “Apply New”. ...

  • Advantech ADAM-5560 - page 136

    ADAM-5560 Series User Man ual 128 8. The message “Add/Modify User Success” will be shown. 9. Run “Configuration Utility”. ...

  • Advantech ADAM-5560 - page 137

    129 ADAM-5560 Series User Manu al Chapter 5 Network Functions 10. Click “Misc” folder . 11 . Change to “Misc” folder and “Web Server Root” will be modified. 12. User can put the developed web page in the specific fo lder in ADAM-5560 and link the webpage by change the W eb Server Root. ...

  • Advantech ADAM-5560 - page 138

    ADAM-5560 Series User Man ual 130 13. Click “OK” to reboot the ADAM-5 560. ...

  • Advantech ADAM-5560 - page 139

    131 ADAM-5560 Series User Manu al Chapter 5 Network Functions 5.2 FTP Server Function ADAM-5560 Series Controller features built-in FTP Server function of Windows CE 5.0. Before you using the FTP Server fun ction, please do follow the step s as below to configure the basic settings properly . The default setting of FTP Server function in Windows CE ...

  • Advantech ADAM-5560 - page 140

    ADAM-5560 Series User Man ual 132 2. Click “Device Management”. 3. Click “Configure FTP Server”. ...

  • Advantech ADAM-5560 - page 141

    133 ADAM-5560 Series User Manu al Chapter 5 Network Functions 4. Enter the “FTP Server Configuration” page. 5. Check “FTP Server Enabled”, un-check “Allow Ano nymous Users”, change “Default Directory” as “HardDiskFTP”. Click “Submit” button. ...

  • Advantech ADAM-5560 - page 142

    ADAM-5560 Series User Man ual 134 6. Click “Reboot” button. 7. After the ADAM-5560 was rebooted, following p age will be shown again. ...

  • Advantech ADAM-5560 - page 143

    135 ADAM-5560 Series User Manu al Chapter 5 Network Functions 8. Scroll down the p age. Check the “Home Directory” for all users and th en click “Submit” button. 9. W ait for a moment for resetting. ...

  • Advantech ADAM-5560 - page 144

    ADAM-5560 Series User Man ual 136 10. After re setting, following p age will be sh own again. The basic settings for FTP Server have been configured. 11 . Right-click the mouse and then add a new directory “New Folder” under “HardDisk” directory of ADAM-5560 Series Cont roller . ...

  • Advantech ADAM-5560 - page 145

    137 ADAM-5560 Series User Manu al Chapter 5 Network Functions 12. Enter the name for the new folder as “FTP”. 13. Enter “HardDiskFTP” directory . ...

  • Advantech ADAM-5560 - page 146

    ADAM-5560 Series User Man ual 138 14. Add “T est FTP” directory . 15. T ype “ftp ://192.168.1.5” to login the FTP Server . Y ou will see the warning message because anonymous login is n ot allowed now . ...

  • Advantech ADAM-5560 - page 147

    139 ADAM-5560 Series User Manu al Chapter 5 Network Functions 16. Click “Login As” item to enter t he user name and passwo rd. 17. Login the FTP Server by usern ame: user1 and p assword: “user1”. ...

  • Advantech ADAM-5560 - page 148

    ADAM-5560 Series User Man ual 140 18. The “T est FTP” directory can be accessed now . 19. T ry to upload files onto FTP Server . ...

  • Advantech ADAM-5560 - page 149

    141 ADAM-5560 Series User Manu al Chapter 5 Network Functions 20. Upload the directory of “OPC” onto FTP Server . 21. Uploading process is proceedin g. ...

  • Advantech ADAM-5560 - page 150

    ADAM-5560 Series User Man ual 142 22. The uploaded “OPC” director y will be shown. 23. Check the files under “OPC” directory in FTP client. ...

  • Advantech ADAM-5560 - page 151

    143 ADAM-5560 Series User Manu al Chapter 5 Network Functions 24. Check the files under “OPC” directory o n the ADAM-5560. 5.3 Email Alarm Function There is an example for demonstrating how to sen d an email from ADAM-5560 Series Controller . Please refer to following info. 1. Open “AdvMailDemo.mwt”. ...

  • Advantech ADAM-5560 - page 152

    ADAM-5560 Series User Man ual 144 2. The function block is included by “AdvT oolPack” library . Double-click “main” to see the function block. 3. T ype the correct settings in the “Init” fields as below and try to run this e xample directly . Note! The sending email function is only suppor ted by mail server via intranet within enterpri ...

  • Advantech ADAM-5560 - page 153

    145 ADAM-5560 Series User Manu al Chapter 5 Network Functions 5.4 SQL Server Function There is an example for demonstrating how to use the built-in SQL Server function on ADAM-5560 Series Controller . Pl ease refer to following info. 1. Open “AdvSQLDemo.mwt”. 2. T ype to run this example directly . ...

  • Advantech ADAM-5560 - page 154

    ADAM-5560 Series User Man ual 146 SQL Function Block Reference: AdvSQL_Init Function: Initialize SQL mobile dat abase. 1. Enable: (BOOL), Enable AdvSQL function blocks. 2. DataBaseName: (STRING) , SQL mobile database na me. 3. T ableName: (STRING), SQL mobile dat abase table name. 4. ColumnT otal: (INT), T otal number of fields in SQL mobile data b ...

  • Advantech ADAM-5560 - page 155

    147 ADAM-5560 Series User Manu al Chapter 5 Network Functions AdvSQL_SelectLastDa t a Function: Read the last reco rd from SQL mobile database . 1. Enable: (BOOL), Enable AdvSQL function blocks. 2. DataBaseName: (STRING), SQL mobile dat abase name. Rreserved fo r handling more than one SQL mo bile database in the fu ture. 3. ColumnIndex: (INT), The ...

  • Advantech ADAM-5560 - page 156

    ADAM-5560 Series User Man ual 148 ...

  • Advantech ADAM-5560 - page 157

    Chapter 6 6 Miscellaneous Functions ...

  • Advantech ADAM-5560 - page 158

    ADAM-5560 Series User Man ual 150 6.1 Advantech Utilities There are four Advantech utilities which a re pre-inst alled on ADAM-5560 Series Con- troller . The major functions are as below . Adam.NET Utility: CE version of ADAM Utility for configuring ADAM-5560 Series Local ADAM-5560 I/O Modules, ADAM- 4000 Remot e I/O Modules, ADAM-6000 and ADAM-556 ...

  • Advantech ADAM-5560 - page 159

    151 ADAM-5560 Series User Manu al Chapter 6 Miscellaneous Functions 6.2 Change Language Interface of CE 1. Enter “Control Panel”. 2. Run “Regional Settings”. ...

  • Advantech ADAM-5560 - page 160

    ADAM-5560 Series User Man ual 152 3. Click “User Interface Language” folder and select “Chinese (T aiwan)” item. 4. Click “OK” to finish the change . ...

  • Advantech ADAM-5560 - page 161

    153 ADAM-5560 Series User Manu al Chapter 6 Miscellaneous Functions 5. Click “OK” to reboot the ADAM-5560. 6. The Language Interface has been changed correctly . ...

  • Advantech ADAM-5560 - page 162

    ADAM-5560 Series User Man ual 154 6.3 Example of Configuring T ouch Screen 1. Run the “T ouch Screen Config” utility . 2. Select COM port as COM3, for example. ...

  • Advantech ADAM-5560 - page 163

    155 ADAM-5560 Series User Manu al Chapter 6 Miscellaneous Functions 3. Click “OK” and reboot the ADAM-5560 syste m. 4. Enter “Control Panel”. ...

  • Advantech ADAM-5560 - page 164

    ADAM-5560 Series User Man ual 156 5. Run “S tylus” to set the properties. 6. Click “Recalibrate” but ton. ...

  • Advantech ADAM-5560 - page 165

    157 ADAM-5560 Series User Manu al Chapter 6 Miscellaneous Functions 7. Follow the instructions and use finger to press the t arget on the screen. 8. Follow the instructions and use finger to press the t arget on the screen. ...

  • Advantech ADAM-5560 - page 166

    ADAM-5560 Series User Man ual 158 9. Follow the instructions and use finger to p ress the target on the screen. 10. Follow the instructions and use fing er to press the targe t on the screen. ...

  • Advantech ADAM-5560 - page 167

    159 ADAM-5560 Series User Manu al Chapter 6 Miscellaneous Functions 11 . Follow the instructions and use finger to press the target on the scree n. 12. Press “Enter” key to accept the new settings. ...

  • Advantech ADAM-5560 - page 168

    ADAM-5560 Series User Man ual 160 13. Click “OK” to finish the recalibration. 6.4 Save and Upload Project Source 1. Open a project and click “Program Con trol Dialog”. ...

  • Advantech ADAM-5560 - page 169

    161 ADAM-5560 Series User Manu al Chapter 6 Miscellaneous Functions 2. Click “Download” button. Check the “Inclu de Sources” item and then click “Download”. 3. The “Upload” button will be activated w hen project source code has been downloaded correctly . ...

  • Advantech ADAM-5560 - page 170

    ADAM-5560 Series User Man ual 162 4. Click “Upload” button and then click “Project Source” to te st uploading source function. 5. Click “OK” to proceed with uploading the project source. ...

  • Advantech ADAM-5560 - page 171

    163 ADAM-5560 Series User Manu al Chapter 6 Miscellaneous Functions 6. Uploading project source has been finished. 6.5 Changing the Language Interface 1. Click “ExtrasOptions” item. ...

  • Advantech ADAM-5560 - page 172

    ADAM-5560 Series User Man ual 164 2. Select “T rad. Chinese” item. 3. Click “Apply” and “OK” buttons. ...

  • Advantech ADAM-5560 - page 173

    165 ADAM-5560 Series User Manu al Chapter 6 Miscellaneous Functions 4. Close Multiprog and then reloa d it. The Language Interface will change to T raditional Chinese correctly . ...

  • Advantech ADAM-5560 - page 174

    ADAM-5560 Series User Man ual 166 ...

  • Advantech ADAM-5560 - page 175

    Chapter A A RS-485 Networks ...

  • Advantech ADAM-5560 - page 176

    ADAM-5560 Series User Man ual 168 A.1 RS-485 Networks EIA RS-485 is the industry’ s most widel y used bidirectional, balance d transmission line standard. It is specifically developed for industrial multi-drop systems that should be able to transmit and receive data at high rates o r over long distan ces. The specifications of the EIA RS-4 85 pro ...

  • Advantech ADAM-5560 - page 177

    169 ADAM-5560 Series User Manu al Chapter A RS-485 Networks Figure A.1 Daisychaining St ar Layout In this scheme the repeaters are connected to drop-down cab les from th e main wire s of the first segment. A tree structure is the result. This scheme is not recommended when using long lines since it will cause a serious amount of sig nal distortion ...

  • Advantech ADAM-5560 - page 178

    ADAM-5560 Series User Man ual 170 Random This is a combination of daisyc hain and hierarchical structure. Figure A.3 Random structure A.3 Line T ermination Each discontinuity in impedance causes reflections and distortion. Whe n a imped- ance discontinuity occurs in the transm ission line the immediate ef fect is signal reflection. This will lead t ...

  • Advantech ADAM-5560 - page 179

    171 ADAM-5560 Series User Manu al Chapter A RS-485 Networks Example: Each input of t he receivers has a nomin al input impedance of 18 k feeding into a diode transistor- resistor biasing network that is equ ivalent to an 18 k input resistor tied to a common mode voltage of 2.4 V . It is this configuration, which provides the large common range of t ...

  • Advantech ADAM-5560 - page 180

    ADAM-5560 Series User Man ual 172 A.4 RS-485 Dat a Flow Control The RS-485 standard uses a single p air of wires to send and receive data. This line sharing requires some method to control the direction of the dat a flow . RTS (Request T o Send) and CTS (Clear T o Send) are the most commonly used methods. Figure A.6 RS-485 Dat a Flow Control with R ...

  • Advantech ADAM-5560 - page 181

    Chapter B B Grounding Reference ...

  • Advantech ADAM-5560 - page 182

    ADAM-5560 Series User Man ual 174 B.1 Field Grounding and Shielding Applications Unfortunately , it’s impossible to finish a system integration t ask at one time. W e always meet some trouble in the field. A communicat ion network or system isn’t sta- ble, induced noise or equipment is damag ed or there are storms. However , the most usual issu ...

  • Advantech ADAM-5560 - page 183

    175 ADAM-5560 Series User Manu al Chapter B G rounding Reference B.2.2 The ‘Frame Ground’ and ‘Grounding Bar ’ Figure B.2 Grounding Bar Grounding is one of the most important issues for our system. Just like Frame Ground of the computer , this signal offers a reference point of the electronic circu it inside the computer . If we want to com ...

  • Advantech ADAM-5560 - page 184

    ADAM-5560 Series User Man ual 176 B.2.3 Normal Mode and Common Mode Have you ever tried to measure the volt age between a live circuit and a concrete floor? How about the voltage between neutral and a concrete floor? Y ou will get non- sense values. ‘Hot’ and ‘Neutral’ are just relational signals: you will get 1 10V AC or 220V AC by measuri ...

  • Advantech ADAM-5560 - page 185

    177 ADAM-5560 Series User Manu al Chapter B G rounding Reference What’s th e purpose of high volt age transmissions? W e have all seen high volta ge transmission towers. The power plant raises the volt age while generating the power , then a local power st ation steps down the voltage . What is the purpose of high volt- age transmission wires ? A ...

  • Advantech ADAM-5560 - page 186

    ADAM-5560 Series User Man ual 178 Figure B.8 Single Point Grounding (2) The above diagram shows you that a sing le point grounding system will be a more stable system. If you use thin cable for powering these devices, the end device will actually get lower power . The thin cable will consume the energy . B.3 Shielding B.3.1 Cable Shield Figure B.9 ...

  • Advantech ADAM-5560 - page 187

    179 ADAM-5560 Series User Manu al Chapter B G rounding Reference Figure B.10 Double Isolated Cable Double isolated cable Figure 10 is an example of a doub le isolated cable. The first isolating layer of spiraled aluminum foil co vers the conductors. The second isolation layer is several bare conductors that spiral and cross over the first shield la ...

  • Advantech ADAM-5560 - page 188

    ADAM-5560 Series User Man ual 180 B.3.2 System Shielding Figure B.1 1 System Shielding  Never stripping too much of the plast ic cable cover . This is improper and can destroy the characteristics of the Sh iel ded-T wisted-Pair cable. Besides, the bare wire shield easily conduct s the noise.  Cascade these shields together by soldering. Pleas ...

  • Advantech ADAM-5560 - page 189

    181 ADAM-5560 Series User Manu al Chapter B G rounding Reference Figure B.13 System Shielding (1)  Shield connection (1) If you break into a cable, you might get in a hurry to achieve your goal. As in all electronic circuit s, a signal will use the p ath of least resis- tance. If we make a poor connection between the se two cables we will make a ...

  • Advantech ADAM-5560 - page 190

    ADAM-5560 Series User Man ual 182 B.4 Noise Reduction T echniques  Isolate noise sources in shielded enclosures.  Place sensitive equipment in shiel ded enclosure and away from computer equipment.  Use separate gro unds between noise sources and signals.  Keep ground/signal leads as short as possib le.  Use T wisted and Shielded sign ...

  • Advantech ADAM-5560 - page 191

    Chapter C C Reference Documents ...

  • Advantech ADAM-5560 - page 192

    ADAM-5560 Series User Man ual 184 Following resources are help ful for underst anding how to use Multiprog Softwa re and IEC-61 131-3 programming languages. C.1 Reference Document s  Multiprog Quick S tart Manual  Multiprog User ’s Manual  Mulitprog On-line Help  ADAM-5550KW Series User ’s Manua l (under Advantech Multiprog CD-ROM ? ...

  • Advantech ADAM-5560 - page 193

    185 ADAM-5560 Series User Manu al Chapter C Reference Documents ...

  • Advantech ADAM-5560 - page 194

    www .advantech.com Please verify specifications be fore quoting. This guide is intended for reference purposes only . All product specifications are subj ect to change without notice. No p art of this publicati on may be reproduced in any form or by any means, electronic, photocopying, recording or otherwise, without prior written permis- sion of t ...

Производитель Advantech Категория Universal Remote

Документы, которые мы получаем от производителя устройства Advantech ADAM-5560 мы можем разделить на несколько групп. Это в частности:
- технические чертежи Advantech
- инструкции обслуживания ADAM-5560
- паспорта изделия Advantech
- информационные брошюры
- энергетические этикетки Advantech ADAM-5560
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Advantech ADAM-5560.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Advantech ADAM-5560, инструкции обслуживания, короткие инструкции или инструкции пользователя Advantech ADAM-5560. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Advantech ADAM-5560.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Advantech ADAM-5560, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Advantech ADAM-5560 пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Advantech ADAM-5560.

Полная инструкция обслуживания Advantech, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Advantech ADAM-5560 - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Advantech ADAM-5560, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Advantech ADAM-5560, которое найдем в данном документе
3. Советы по использованию основных функций устройства Advantech ADAM-5560 - которые должны облегчить нам первые шаги во время использования Advantech ADAM-5560
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Advantech ADAM-5560
5. FAQ - чаще всего задаваемые вопросы