Инструкция обслуживания APC 480kW 400V

32 страниц 1.94 mb
Скачать

Перейти на страницу of 32

Summary
  • APC 480kW 400V - page 1

    APC Silcon 480kW 400V UPS User Guide Copyright ©2000 APC Denmark ApS Information in this document is subject to change without notice and does not represent a commitment on the part of the vendor ...

  • APC 480kW 400V - page 2

    2 User Guide APC Silcon 480kW 400V UPS 990-4041 Thank You Thank you for chosing APC Silcon. Please read this User Guide thoroughly prior to installing the system as it provides important information on safe and efficient installation and use. The installation and use of this product must comply with national, federal, state, municipal and local cod ...

  • APC 480kW 400V - page 3

    990-4041 User Guide APC Silcon 480kW 400V UPS 3 Contents: 1.0 Introduction 4 1.1 Display Unit 4 2.0 Stop/Start UPS and Operating the External Service Bypass Panel 5 2.1 Stop UPS (for stand-by) 5 2.2 Start UPS (from stand-by) 5 2.3 Stop UPS (for complete power down) 6 2.3.1 Switching off the UPS 6 2.4 Start UPS (from complete power down) 8 2.4.1 UPS ...

  • APC 480kW 400V - page 4

    4 User Guide APC Silcon 480kW 400V UPS 990-4041 Introduction 1.0 Introduction This UPS system is designed to offer reliable and problem-free power supply for several years. The system requires only a minimum of maintenance, but we recommend you follow the maintenance guidelines described in section 6.0 Maintenance & Testing. 1.1 Display Unit Th ...

  • APC 480kW 400V - page 5

    Stop/Start UPS and Operating the External Service Bypass 990-4041 User Guide APC Silcon 480kW 400V UPS 5 2.0 Stop/Start UPS and Operating the External Service Bypass Panel Only qualified electricians should start up or shut down APC Silcon UPS systems and instructions in the Installation Guide should be followed. Prior to being serviced, the APC Si ...

  • APC 480kW 400V - page 6

    6 User Guide APC Silcon 480kW 400V UPS 990-4041 Stop/Start UPS and Operating the External Service Bypass 2.3 Stop UPS (for complete power down) 2.3.1 Switching off the UPS CAUTION! If the UPS system is equipped with a Service Bypass Panel, and if the load must remain energized by mains, refer to the Operating Service Bypass Panel sections in this g ...

  • APC 480kW 400V - page 7

    Stop/Start UPS and Operating the External Service Bypass 990-4041 User Guide APC Silcon 480kW 400V UPS 7 The UPS is now isolated. Maintenance/repair, disconnection or removal can now be carried out. 1. Open front doors 2. Note that step 3 will interrupt output volta ge and activate the alarm! The red LED alarm below the display will light up The ac ...

  • APC 480kW 400V - page 8

    8 User Guide APC Silcon 480kW 400V UPS 990-4041 Stop/Start UPS and Operating the External Service Bypass 2.4 Start UPS (from complete power down) 2.4.1 UPS start-up CAUTION! Make sure all cable connections are in place prior to first start-up. NOTICE! After first system start-up, check that battery temperature is displayable (press and simultaneous ...

  • APC 480kW 400V - page 9

    Stop/Start UPS and Operating the External Service Bypass 990-4041 User Guide APC Silcon 480kW 400V UPS 9 System start-up now completed. NOTICE! One of the following display messages will appear by UPS start-up: • “ STD ” : Standard (single system) • “ PAR ” : Parallel System • “ ECO ” : Economy mode (single or parallel systems) (L ...

  • APC 480kW 400V - page 10

    10 User Guide APC Silcon 480kW 400V UPS 990-4041 Stop/Start UPS and Operating the External Service Bypass 2.5 Operating the External Service Bypass Switch (single systems) 2.5.1 Bypassing the Single System UPS APC Silcon UPS Mains Load Service Bypass Switch Action 1. Press on the ke yboard 2. Press or on the ke yboard until 3. Press on the ke yboar ...

  • APC 480kW 400V - page 11

    Stop/Start UPS and Operating the External Service Bypass 990-4041 User Guide APC Silcon 480kW 400V UPS 11 2.5.2 Switching the Single System UPS from External Bypass into Normal UPS Operation CAUTION! Do not leave UPS out of service for more than 48 hours. Refer to section 2.3 Stop (for complete power down). APC Silcon UPS Load Service Bypass Switch ...

  • APC 480kW 400V - page 12

    12 User Guide APC Silcon 480kW 400V UPS 990-4041 Stop/Start UPS and Operating the External Service Bypass NOTICE! If battery has been disconnected, please refer to section 2.4.1 UPS start-up. Action 1. Set the input s witch (Q001) to position 1 2. W ait 5 sec. Open the front door of the UPS and press the green ON k ey 3. Press on the k eyboard 4. P ...

  • APC 480kW 400V - page 13

    Stop/Start UPS and Operating the External Service Bypass 990-4041 User Guide APC Silcon 480kW 400V UPS 13 2.6 Operating the External Service Bypass Switch (parallel systems) 2.6.1 Bypassing the Parallel UPS System (All UPSs) Service bypass switch Load Mains APC Silcon UPS APC Silcon UPS CAUTION! Do not leave UPS out of service for more than 48 hour ...

  • APC 480kW 400V - page 14

    14 User Guide APC Silcon 480kW 400V UPS 990-4041 Stop/Start UPS and Operating the External Service Bypass Action Steps 1-4 apply to all the parallel systems. Note that this will switch all systems into bypass operation 1. Press on the ke yboard 2. Press or on the keyboard until 3. Press on the keyboard 4. Press on the ke yboard All systems switch t ...

  • APC 480kW 400V - page 15

    Stop/Start UPS and Operating the External Service Bypass 990-4041 User Guide APC Silcon 480kW 400V UPS 15 2.6.2 Switching the Parallel System from External Bypass into Normal UPS Operation NOTICE! If battery has been disconnected, please refer to section 2.4.1 UPS start-up. Service bypass switch Load Mains APC Silcon UPS APC Silcon UPS ...

  • APC 480kW 400V - page 16

    16 User Guide APC Silcon 480kW 400V UPS 990-4041 Stop/Start UPS and Operating the External Service Bypass Action 1. Check that the output s witch (Q004) is set to position 0 2. Check that all output s witches (Q002) are set to position 1 3. Set input switches (Q001) to position 1 4. W ait 10 secs. Open the UPS front door and press the green ON butt ...

  • APC 480kW 400V - page 17

    Stop/Start UPS and Operating the External Service Bypass 990-4041 User Guide APC Silcon 480kW 400V UPS 17 2.7 Isolating one UPS in a Parallel Configuration for Service/Maintenance 2.7.1 Isolating one UPS in a Parallel/Redundant System In a redundant system one UPS may be isolated for service/maintenance without affecting other parallel UPS(s). Serv ...

  • APC 480kW 400V - page 18

    18 User Guide APC Silcon 480kW 400V UPS 990-4041 Stop/Start UPS and Operating the External Service Bypass 2.7.2 Switching Back the UPS to Normal Rarallel/Redundant Operation The UPS will automatically switch to normal operation and start load-sharing with the other parallelled UPS(s). Action 1. Set the input switch (Q001) and the output switch (Q00 ...

  • APC 480kW 400V - page 19

    Operation 990-4041 User Guide APC Silcon 480kW 400V UPS 19 3.0 Operation The display unit will read parameters, alarms/messages and measured values. LED alarm incorporates audible alarm, indicating unusual operating situations. The keyboard is used to program and control parameters and to display alarm messages and measured values. 3.1 Keyboard NOT ...

  • APC 480kW 400V - page 20

    20 User Guide APC Silcon 480kW 400V UPS 990-4041 Operation 3.2 Display of Measured Values To read measurements, press one or two keys simultaneously as shown below. (Illustrated values are examples only). 3.3 Using the Remote Display The remote display is an inactive unit that is unable to influence the operation of the APC Silcon UPS. It is imposs ...

  • APC 480kW 400V - page 21

    Operation 990-4041 User Guide APC Silcon 480kW 400V UPS 21 3.4 Economy Mode When the UPS is running in Economy Mode, the load will be supplied directly from mains and output voltages are UPS monitored. In the event of a mains disruption, the UPS will switch to battery mode without affecting the load. Prior to switching to bypass mode, leave the sys ...

  • APC 480kW 400V - page 22

    22 User Guide APC Silcon 480kW 400V UPS 990-4041 Parameter Settings 4.0 Parameter Settings Below tables show operating parameters programmable from keyboard. Only qualified users should alter programming parameters. See below examples. Parameter Settings * Factory settings in bold ** For systems with active Battery Monitor only *** Do not leave sys ...

  • APC 480kW 400V - page 23

    Parameter Settings 990-4041 User Guide APC Silcon 480kW 400V UPS 23 4.1 Programming Keys 4.2 Switching to Bypass Operation Programming Example Scrolls up through list Scrolls down through list Stores parameters/enters parameter stack Silences the audible alarm Chooses or changes parameters Displays time Return to normal window Accesses the alarm st ...

  • APC 480kW 400V - page 24

    24 User Guide APC Silcon 480kW 400V UPS 990-4041 Parameter Settings To return to normal operation Follow same procedure to program other parameters. Action 6. Press to enter parameter stac k 7. Press or until 8. Press until 9. Press to store 10. Press to exit Display sho ws Bypass operation : YES Bypass operation : N O Normal operation load power x ...

  • APC 480kW 400V - page 25

    Alarms and Events 990-4041 User Guide APC Silcon 480kW 400V UPS 25 5.0 Alarms and Events Alarms are indicated by the red lamp (above the left hand corner of the keyboard) and a 30 seconds acoustic signal. An alarm is registered in the alarm stack as long as it is present, and if more in the same order as they arise. Certain alarms, such as battery ...

  • APC 480kW 400V - page 26

    26 User Guide APC Silcon 480kW 400V UPS 990-4041 Alarms and Events 5.3 Possible Alarms Alarms Description Action 1. Peak current limiter active Peak current limiter activated and UPS switched to bypass operation. System overload Check for blown fuses in installation 2. Bypass power supply fault Fault in redundant PSU for bypass. UPS still 100% able ...

  • APC 480kW 400V - page 27

    Alarms and Events 990-4041 User Guide APC Silcon 480kW 400V UPS 27 Alarms Description Action 23. Main inverter failure Temperature of main inverter, too high or inverter fuse blown Check fan, check for airflow obstructions, check for overload, check fuse 24. High temperature of delta inverter Temperature of delta inverter, too high Check fan, check ...

  • APC 480kW 400V - page 28

    28 User Guide APC Silcon 480kW 400V UPS 990-4041 Alarms and Events 5.4 Rectifying Alarm Messages Following actions may rectify alarm: • Check local mains supply. Fuses may be blown or supply switched off accidentally • Check if UPS cooling air intake is blocked • Check if load exceeds maximum output capacity • If, with mains power switched ...

  • APC 480kW 400V - page 29

    Maintenance & Testing 990-4041 User Guide APC Silcon 480kW 400V UPS 29 6.0 Maintenance & Testing UPS maintenance should be carried out by trained service engineers only. Service and maintenance contract is recommended. 6.1 Fan It is recommended to replace fans every 3 years. 6.2 Battery Monitoring Test Systems with built-in batteries have a ...

  • APC 480kW 400V - page 30

    30 User Guide APC Silcon 480kW 400V UPS 990-4041 Maintenance & Testing If the UPS is to be taken out of operation for an extended period, disconnect the battery in order to prevent discharging. For details, refer to Installation Guide. Action 1. Press 2. Press or until 3. Press 4. Press 5. W ait about 1 sec. 6. W ait until backup times expires ...

  • APC 480kW 400V - page 31

    Warranty 990-4041 User Guide APC Silcon 480kW 400V UPS 31 7.0 Warranty 7.1 APC Silcon UPS Limited Factory Warranty APC warrants that the unit, when properly installed and commissioned by APC or APC authorized service personnel, shall be free from defects in materials and workmanship for a period of (1) year from the date of installation or maximum ...

  • APC 480kW 400V - page 32

    32 User Guide APC Silcon 480kW 400V UPS 990-4041 How to Contact APC 8.0 How to Contact APC APC Corporate 132 Fairgrounds Road West Kingston, RI 02892 USA Telephone: 401 789-5735 Fax: 401 789-3710 PowerFax™: 800 347-FAXX Pre-sales Technical Support 877-474-5266 (1-877-4Silcon) Post-sales Technical Support 877-287-7835 (1-877-2UPS-TEK) Web: www.apc ...

Производитель APC Категория Power Supply

Документы, которые мы получаем от производителя устройства APC 480kW 400V мы можем разделить на несколько групп. Это в частности:
- технические чертежи APC
- инструкции обслуживания 480kW 400V
- паспорта изделия APC
- информационные брошюры
- энергетические этикетки APC 480kW 400V
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания APC 480kW 400V.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа APC 480kW 400V, инструкции обслуживания, короткие инструкции или инструкции пользователя APC 480kW 400V. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия APC 480kW 400V.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства APC 480kW 400V, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании APC 480kW 400V пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей APC 480kW 400V.

Полная инструкция обслуживания APC, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией APC 480kW 400V - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания APC 480kW 400V, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся APC 480kW 400V, которое найдем в данном документе
3. Советы по использованию основных функций устройства APC 480kW 400V - которые должны облегчить нам первые шаги во время использования APC 480kW 400V
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем APC 480kW 400V
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра APC 480kW 400V в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся APC 480kW 400V?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с APC 480kW 400V, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с APC 480kW 400V со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)