    INST ALLA TION AND OPERA TION INSTRUCTIONS BCP-3 Hydronic Multi-Stage Boiler Control Blue (Output 2) White (Output 3) Y ellow (Output 1) Boiler SYS Pump DHW Pump SET SET SYSTEM = 147F TARGET = 150F Output 1 2 Line Alphanumeric Display Displays sensor values and menu settings Output Lights indicate output status Display Section Locking Screws Black ...

  • Weil-McLain BCP-3 - page 2

    2 BCP-3 Installation and Operation Manual thermostat is satisfied. Another, is a Setback input that will switch the heating system to a lower set point determined by the Set Back setting. T ype of Radiation in Building Reset Ratio Offset Radiators (Steel & Cast Iron) 1.00 (O) : 1.00 (S) 0˚F Baseboard (Finned copper tube& Cast Iron) 1.00 ( ...

  • Weil-McLain BCP-3 - page 3

    3 BCP-3 Installation and Operation Manual Mounting the Controller • The BCP-3 is designed to mount on a 1900 (4”x4”) deep electrical box. • If additional room is needed for wiring use the extension skirt provided. • Place the BCP-3 in an indoor convenient location near the unit to be controlled and away from excessive heat or cold. • Pa ...

  • Weil-McLain BCP-3 - page 4

    4 BCP-3 Installation and Operation Manual IMPORT ANT Determining the proper location for the Outdoor Sensor is very important. The BCP-3 will base the heat on the outdoor temperature information it receives from this location. If the sensor is in the sun, or covered with ice, its reading will be different from the actual outdoor temperature. Outdoo ...

  • Weil-McLain BCP-3 - page 5

    5 BCP-3 Installation and Operation Manual Output Mode T able Output Mode Description Output 1 (Y ellow Wires) Output 2 (Blue Wires) Output 3 (White Wires) Notes 1-On/Off+1-Pump One On/Off boiler and a System pump Sys Pump Boiler Not used 1-On/Off+2-Pump One On/Of f boiler , a System pump and a Domestic Hot W ater Pump Sys Pump Boiler DHW Pump 2-On/ ...

  • Weil-McLain BCP-3 - page 6

    6 BCP-3 Installation and Operation Manual T1 T2 COM COM T3+ T3- EXT+ EXT- P+ P- COM 24V AC System Sensor Outdoor Sensor Enable Dry Contact Setback Timer 120 V AC Wiring 1 Lo/Hi Boiler + System Pump System Pump ( Y ellow/Output 1) Boiler Lo (Blue/ Output 2) Boiler Hi ( White/ Output 3) DHW Call Pow er (Black) 120 V AC L N L N T1 T2 COM COM T3+ T3- E ...

  • Weil-McLain BCP-3 - page 7

    7 BCP-3 Installation and Operation Manual Weil McLain V1.00 (c) 2008 BCP-3 Boiler Control Loading Default Values... DISPLAY UNIT: F C SENSOR FAULT: Output On Output Off SETUP COMPLETE! PRESS SET Startup Menu SYSTEM= 68 F TARGET= 150 F ------MAIN------ Set Point 170 F <Out. Reset> <Settings> <Maintenance> <Sys. Startup> <I ...

  • Weil-McLain BCP-3 - page 8

    8 BCP-3 Installation and Operation Manual Button and Navigating Menus The BCP-3 has three buttons. • The SET button function varies. When the Default Screen is displayed, pressing the SET Button views the MENU. When in the Menus and settings, the SET Button accepts the selected entry or setting value. • When in the menus, pressing the Up and Do ...

  • Weil-McLain BCP-3 - page 9

    9 BCP-3 Installation and Operation Manual Outdoor Reset Mode • When Output-On is selected, the BCP-3 will energize all boiler and system relays when the System reads SHORT or OPEN and Outdoor is below Outdoor Cutoff. Thus, all boilers will run on their limits. However , if the Outdoor sensor fails and the Outdoor reads SHORT or OPEN , the BCP-3 w ...

  • Weil-McLain BCP-3 - page 10

    10 BCP-3 Installation and Operation Manual • If required: Adjust the RESET RA TIO in cold weather . If the ambient building temperatures are too cold in cold weather , move the ratio to a higher selection. That is, if 1.00 (O):1.00 (S) was initially selected, change the selection to 1.00 (O):1.25 (S). If the building temperatures are too warm in ...

  • Weil-McLain BCP-3 - page 11

    11 BCP-3 Installation and Operation Manual Minimum T arget (A vailable when Startup Control Mode = Outdoor Reset) Options: From 70 º F/21 ºC to 170 º F/77 ºC Default: 140 º F/60 ºC SET SET /Set Point/<Out. Reset>/Min. Tgt • The Minimum T arget T emperature must be set to the boiler manufacturer ’ s specification. Min Target: 140 F ...

  • Weil-McLain BCP-3 - page 12

    12 BCP-3 Installation and Operation Manual Minimum Runtime Options: 1 to 60 minutes Default: 2 minutes SET SET /<Settings>/<Stage>/Min. Runtime • This is the minimum amount of time any stage will run. • The Minimum Runtime for the lowest firing stage on a boiler starts after the purge cycle. • Initially , set the Min. Runtime to ...

  • Weil-McLain BCP-3 - page 13

    13 BCP-3 Installation and Operation Manual Domestic Hot W ater (DHW) Priority Options: NO and From 1 min to 120 min Default: NO SET SET /Settings>/DHW Prior . DHW Priority: 60m • The DHW Priority , with a value set to other than NO, provides the user with an adjustable DHW priority timer for the domestic hot water call. That is, initiating a D ...

  • Weil-McLain BCP-3 - page 14

    14 BCP-3 Installation and Operation Manual T roubleshooting No Display or LED Lights Check the power to the BCP-3. The BCP-3 requires 120V AC power to the Black wires or 24V AC to the right-most terminals. T urn the power off and back on to restore the display . If unsuccessful, make sure that the control's Display Cover is securely mounted to ...

  • Weil-McLain BCP-3 - page 15

    15 BCP-3 Installation and Operation Manual Boiler1 DHW Indirect Building Heat System Sensor Outdoor Sensor T1 T2 COM COM T3+ T3- EXT+ EXT- P+ P- COM 24VAC } System Sensor } Outdoor Sensor } DHW Call Dry Contact } Enable Dry Contact } Setback Dry Contact Boiler SYS Pump DHW Pump SET SET SYSTEM = 147F TARGET = 150F Y ellow Wires (Output 1) Blue Wires ...

  • Weil-McLain BCP-3 - page 16

    16 BCP-3 Installation and Operation Manual 500 Blaine Street Michigan City , Indiana 46360 219-879-6561 http://www .weil-mclain.com HT #059075-00 A Specifications V oltage Input: . . . . . . . 120 V AC 60 Hz(2 Black wires) /24V AC 60 Hz (24V Ac terminals) (Only One Power Source) Power Consumption: . . . . . . . . . . . . . . . . . . . . . . . . . ...

Производитель Weil-McLain Категория Boiler

Документы, которые мы получаем от производителя устройства Weil-McLain BCP-3 мы можем разделить на несколько групп. Это в частности:
- технические чертежи Weil-McLain
- инструкции обслуживания BCP-3
- паспорта изделия Weil-McLain
- информационные брошюры
- энергетические этикетки Weil-McLain BCP-3
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Weil-McLain BCP-3.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Weil-McLain BCP-3, инструкции обслуживания, короткие инструкции или инструкции пользователя Weil-McLain BCP-3. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Weil-McLain BCP-3.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Weil-McLain BCP-3, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Weil-McLain BCP-3 пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Weil-McLain BCP-3.

Полная инструкция обслуживания Weil-McLain, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Weil-McLain BCP-3 - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Weil-McLain BCP-3, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Weil-McLain BCP-3, которое найдем в данном документе
3. Советы по использованию основных функций устройства Weil-McLain BCP-3 - которые должны облегчить нам первые шаги во время использования Weil-McLain BCP-3
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Weil-McLain BCP-3
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Weil-McLain BCP-3 в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Weil-McLain BCP-3?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Weil-McLain BCP-3, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Weil-McLain BCP-3 со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)