    All phases of this installation must comply with the NATIONAL, STATE & LOCAL CODES . In the absence of local codes, the installation must conform with National Electric Code -- ANSI/NFPA 70 or "LATEST REVISION." Since Trane has a policy of continuous product and product data improvement, it reserves the right to change design and spec ...

  • Trane YCZ036F1/3M0B - page 2

    Page 2 GENERAL INFORMA TION IMPORTANT: Read this entire manual before beginning installation procedures. ▲ WARNING: BODILY INJURY CAN RESULT FROM HIGH VOLTAGE ELECTRICAL COMPONENTS, FAST MOVING FANS, AND COMBUSTIBLE GAS. FOR PROTECTION FROM THESE INHERENT HAZARDS DURING INSTALLATION AND SERVICING, THE ELECTRICAL SUPPLY MUST BE DISCONNECTED AND TH ...

  • Trane YCZ036F1/3M0B - page 3

    Page 3 TYPICAL ROOFTOP INSTALLATION WITH BAYCURB030A,038A (YCZ036,050,060F Models) TYPICAL ROOFTOP INSTALLATION WITH FULL PERIMETER CURBS (YCZ036,050,060F Models) 1 ROOF INSULA TION ROOF DECK FIELD SUPPLIED RIGID INSULA TION SUPPL Y AIR DUCT RETURN AIR DUCT ROOF MOUNTING CURB FIELD SUPPLIED CANT STRIP FIELD SUPPLIE D SUPPORTS A T EACH END OF CURB R ...

  • Trane YCZ036F1/3M0B - page 4

    Page 4 DIMENSIONAL D A T A 3 YCZ036,050,060F OUTLINE – BACK MODE L CORNER WEIGHT (LBS) NET UNIT WEIGHT (LBS) AB C D E F G H J K L M N P W1 W2 W3 W4 YCZ03 6F 161 106 10 4 157 528 64 36 29-3/16 18-9/16 11-1/ 16 6-9/16 11-1/8 17 18-1/2 25-1/2 17-1/2 10 3 8-3/4 YCZ0 50F 1 72 121 137 196 62 6 65-1/8 45 33-3/8 21-1/ 16 15-1/16 4-15/16 9-1/ 8 21-15/ 16 ...

  • Trane YCZ036F1/3M0B - page 5

    Page 5 4 DIMENSIONAL D A T A YCZ036,050,060F OUTLINE – FRONT CLEARANCE T O COMBUSTIBLE MA TERIAL BO TTOM 0.0" BA CK 1. 0" LEFT S I DE 6. 0" RIGHT SIDE 6.0" FRONT SIDE 12.0" T OP 36.0" RECOMM ENDED SER VICE CLEARANC E BA CK * 6.0" LEFT SIDE 30.0" RIGHT SIDE 24.0" FR ONT 42.0" * 18" WITH F RESH ...

  • Trane YCZ036F1/3M0B - page 6

    Page 6 5 6 CONVERTING HORIZONTAL TO DOWNFLOW REQUIRED CLEARANCE FOR UNIT INSTALLATION AND ROOF PENETRATION HOLE SIZE REQUIRED E F HOLE IN ROOF WOOD NAILER SIDE RAIL SERVICE CLEARANCE LINES SERVICE CLEARANCE LINES A B C D SUPPLY AIR RETURN AIR HEATER EXCHANGER TUBES HORIZONTAL SUPPLY AIR COVER HORIZONTAL RETURN AIR COVER SHEET METAL SCREWS NOTE SUPP ...

  • Trane YCZ036F1/3M0B - page 7

    Page 7 LOCA TIONS AND RECOMMEND A TIONS HORIZONTAL AIRFLOW APPLICATION 1. These units are design certified for outdoor installations. These units may be installed directly on wood flooring or on Class A, Class B, or Class C roof covering material. The discharge air from the condenser fans must be unrestricted for a minimum of 3 feet above the unit. ...

  • Trane YCZ036F1/3M0B - page 8

    Page 8 LOCA TIONS AND RECOMMEND A TIONS 15. Access and service clearances for the unit must be given careful consideration when locating the duct entrance open- ings. Figure 4 provides unit dimensions. 16. All fabricated outdoor ducts should be as short as possible. CLEARANCES 1. The recommended clearances for single-unit installations are illustra ...

  • Trane YCZ036F1/3M0B - page 9

    Page 9 INST ALLA TION IMPORTANT: Do not lift the unit without test lifting for balance and rigging. Do not lift the unit in windy conditions or above personnel. Do not lift the unit by attaching a clivus, hooks, pins, or bolts to the unit casing, casing hardware, corner lugs, angles, tabs, or flanges. Failure to observe these warnings may result in ...

  • Trane YCZ036F1/3M0B - page 10

    Page 10 INST ALLA TION ROOFTOP -- UNITS For roof top applications using a field fabricated frame and ducts, use the following procedure: 1. The frame must be located and secured by bolting or welding to the roof. Flashing is required. 2. The hole in the roof must be prepared in advance of installing the unit. 3. Secure the ducts to the roof. TYPICA ...

  • Trane YCZ036F1/3M0B - page 11

    Page 11 INST ALLA TION GROUND LEVEL -- HORIZONTAL UNITS For ground level installations, the unit should be positioned on a pad the size of the unit or larger. The unit must be level on the pad. The pad must not come in contact with the structure (See Figure 11.) Be sure the outdoor portion of the supply and return air ducts are as short as possible ...

  • Trane YCZ036F1/3M0B - page 12

    Page 12 ATTACHING HORIZONTAL DUCTWORK TO UNIT All conditioned air ductwork should be insulated to minimize heating and cooling duct losses. Use a minimum of two (2) inches of insulation with a vapor barrier. The outside ductwork must be weatherproofed between the unit and the building. When attaching ductwork to a horizontal unit, provide a flexibl ...

  • Trane YCZ036F1/3M0B - page 13

    Page 13 CAUTION : Before making the gas pipe connection give seri- ous consideration to providing the required clearance neces- sary to remove the access panels on the unit (e.g., economizer and filter access panels). NOTE : In the absence of local codes, the installation must conform with American National Standard--Z223.1--National Fuel Gas Code, ...

  • Trane YCZ036F1/3M0B - page 14

    Page 14 NOTE: The shut-off gas cock must be installed outside of the unit and should meet the specifications of all applicable national and local codes . 2. Install a ground union joint downstream of the shut-off cock. This joint must also be installed outside of the unit. 3. Install a drip leg at least six (6) inches in depth next to the union as ...

  • Trane YCZ036F1/3M0B - page 15

    Page 15 INPUT CHECK AND ADJUSTMENT 1. Make sure all gas appliances are off except the furnace. 2. Clock the gas meter with the furnace operating (determine the dial rating of the meter) for one revolution. 3. Match the “Sec” column in the gas flow (in cfh) Table 3 with the time clocked. 4. Read the “Flow” column opposite the number of secon ...

  • Trane YCZ036F1/3M0B - page 16

    Page 16 ELECTRICAL CONNECTIONS Electrical wiring and grounding must be installed in accordance with local codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA 70, Latest Revision. ELECTRICAL POWER It is important that proper electrical power be available for the unit. Voltage variation should remain within the limits ...

  • Trane YCZ036F1/3M0B - page 17

    Page 17 YCZ-F FIELD WIRING DIAGRAM the Thermostat System Switch until power has been applied long enough to evaporate any liquid R-22 in the compressor. It is recommended that the sump heater be energized for eight (8) hours prior to starting. After all electrical wiring is complete, set the thermostat system switch in the OFF position so that the ...

  • Trane YCZ036F1/3M0B - page 18

    Page 18 ST ART - UP PRE-START QUICK CHECKLIST ● Is the unit properly located and level with the proper clearance? See Figure 4. ● Is the duct work correctly sized, run, taped, insulated, and weatherproofed with proper unit arrangement? See Ductwork Installation section. ● Is the gas piping correctly sized, run, trapped, and purged of air? See ...

  • Trane YCZ036F1/3M0B - page 19

    Page 19 ST ART - UP 8. Set the thermostat at the desired temperature setting and the unit will function automatically. STARTING THE UNIT IN THE GAS HEATING MODE 1. Check to make sure all grilles and registers are open and all unit access doors are closed before start-up. 2. Purge the gas supply line of air by opening the union ahead of the unit. Wh ...

  • Trane YCZ036F1/3M0B - page 20

    Page 20 o DIP SWITCHES (TYPICAL SETTINGS) SEQUENCE OF OPERA TION ICM FAN CONTROL The rollout switch (FS) is located in the gas compartment near the inlet of the burners. This is a single use device designed to protect against any form of flame rollout. If this device is opened the gas valve is immediately de-energized and the control (IGN) will loc ...

  • Trane YCZ036F1/3M0B - page 21

    Page 21 TROUBLESHOOTING CHART SYSTEM FAULTS ELECTRICAL REFRIGERANT CIRCUIT P -PRIMARY CAUSES S-SECONDARY CAUSES Liquid Pressure T oo high Liquid Pressure T oo Low Suction Pressure T oo High Suction Pressure T oo Low Liquid Refrigerant floodback (TXV System) Liquid Refrig. floodback (Cap. T ube System) I. D . Coil Frosting Compressor Runs Inadequate ...

  • Trane YCZ036F1/3M0B - page 22

    Page 22 ROUTINE MAINTENANCE BY OWNER You can do some of the periodic maintenance functions for your YCZ-F unit yourself; this includes replacing the disposable or cleaning the permanent air filters, cleaning the unit cabinet, cleaning the condenser coil, and conducting a general unit inspection on a regular basis. When the system is in constant ope ...

  • Trane YCZ036F1/3M0B - page 23

    Page 23 LIMITED W ARRANTY COMBINATION GAS ELECTRIC AIR CONDITIONER YCZ, YCY AND YCX Models Less Than 20 Tons for Residential Use* (Parts Only) This limited war ranty is extended by American Standard Inc., to the original purc haser and to any succeeding owner of the real proper ty to whic h the Combination Gas Electric Air Conditioner is originally ...

  • Trane YCZ036F1/3M0B - page 24

    Page 24 Technical Literature - Printed in U.S.A. LIMITED W ARRANTY COMBINATION GAS ELECTRIC AIR CONDITIONER YCZ, YCY, YCX, YCC, YCD, YCH, YCP, YHC and YSC Models Less Than 20 Tons for Commercial Use* (Parts Only) his warranty is e xtended b y Amer ican Standard Inc., to the original purchaser and to any succeeding o wner of the real proper ty to wh ...

Производитель Trane Категория Ventilation Hood

Документы, которые мы получаем от производителя устройства Trane YCZ036F1/3M0B мы можем разделить на несколько групп. Это в частности:
- технические чертежи Trane
- инструкции обслуживания YCZ036F1/3M0B
- паспорта изделия Trane
- информационные брошюры
- энергетические этикетки Trane YCZ036F1/3M0B
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Trane YCZ036F1/3M0B.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Trane YCZ036F1/3M0B, инструкции обслуживания, короткие инструкции или инструкции пользователя Trane YCZ036F1/3M0B. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Trane YCZ036F1/3M0B.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Trane YCZ036F1/3M0B, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Trane YCZ036F1/3M0B пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Trane YCZ036F1/3M0B.

Полная инструкция обслуживания Trane, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Trane YCZ036F1/3M0B - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Trane YCZ036F1/3M0B, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Trane YCZ036F1/3M0B, которое найдем в данном документе
3. Советы по использованию основных функций устройства Trane YCZ036F1/3M0B - которые должны облегчить нам первые шаги во время использования Trane YCZ036F1/3M0B
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Trane YCZ036F1/3M0B
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Trane YCZ036F1/3M0B в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Trane YCZ036F1/3M0B?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Trane YCZ036F1/3M0B, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Trane YCZ036F1/3M0B со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)