    CKF 50 Hz Condensing Unit s • Refer to Service Manual RS6100004 for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. • Models listed on page 3. RT6111009r4 January 2012 This manual is to ...

  • Goodman Mfg Condensing Units - page 2

    PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause p ...

  • Goodman Mfg Condensing Units - page 3

    PRODUCT IDENTIFICA TION 3 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. CKF24-2M CKF24-2N CKF36-2M CKF36-2N CKF36-5M CKF36-5N CKF48-5M CKF48-5N CKF60-5M CKF60-5N CKF70-5M CKF70-5N * Indicates minor revision & is not used for ord ...

  • Goodman Mfg Condensing Units - page 4

    PRODUCT DESIGN 4 CKF 50 Hz models are available in 2 through 6 ton sizes. They are designed for 220/240 to 380 volt single phase appli- cations. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet. These units are designed for free air discharg ...

  • Goodman Mfg Condensing Units - page 5

    PRODUCT DESIGN 5 H W D Dimensions M o d el D i m en si o n s - W x D x H C KF 24- 2* 26 " [ 6 60] x 26" [ 66 0] x 29¾ [ 7 56] C KF 36- 2* 26 " [ 6 60] x 26" [ 66 0] x 29¾ [ 7 56] C KF 36- 5* 26 " [ 6 60] x 26" [ 66 0] x 29¾ [ 7 56] C KF 48- 5* 29 " [ 7 37] x 29" [ 73 7] x 29¾ [ 7 56] C KF 60- 5* 29 " ...

  • Goodman Mfg Condensing Units - page 6

    CONDENSING UNIT SPECIFICA TIONS 6 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. CKF2 4 - 2 * CK F 3 6 - 2 * CKF3 6 -5 * CKF4 8 -5 * CKF 6 0 - 5* CKF7 0 - 5 * C ooli ng C a ...

  • Goodman Mfg Condensing Units - page 7

    7 COOLING PERFORMANCE DA T A CKF24-2* M O DE L: CKF24- 2* / A 2 4 - 00 - 2 RA C OOL IN G OP E R A T ION O utdoor Am bient Te m per ature 65°F 75°F 85°F 95°F 105°F 115 ° F 118°F 125°F E nte r i ng Indoor W et B ulb Tem pe r ature ID B Air f low 59 63 67 71 59 63 67 71 5 9 6 3 6 7 71 5 9 63 67 71 59 63 67 7 1 5 9 63 67 71 59 53 67 7 1 59 63 6 ...

  • Goodman Mfg Condensing Units - page 8

    8 COOLING PERFORMANCE DA T A CKF24-2* M O DE L: CKF24- 2* / A 2 4 - 00 - 2 RA C OOL IN G OP E R A T ION O utdoor Am bient Te m per ature 65 75 85 95 105 115 118°F 125°F E nte r i ng Indoor W et B ulb Tem pe r ature I D B * A i r f l o w 5 96 36 77 15 96 36 7 7 1 5 9 6 3 6 7 7 1 5 9 6 3 6 7 7 1 5 96 36 7 7 1 5 96 3 6 7 7 1 5 9 5 3 6 7 7 1 5 9 6 3 ...

  • Goodman Mfg Condensing Units - page 9

    9 COOLING PERFORMANCE DA T A CKF36-2* M O DEL: CK F36- 2* / A 36- 00- 2 C OOL IN G OP E R ATIO N O utdoor Am bi e nt Tem per a t ur e 65° F 75°F 85° F 95° F 105° F 115° F 1 18° F 125°F E nte r ing I ndoor W et B ulb Te m pe r a t ure ID B A ir flow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 53 67 71 59 63 67 ...

  • Goodman Mfg Condensing Units - page 10

    10 COOLING PERFORMANCE DA T A CKF36-2* M O DEL: CK F36- 2* / A 36- 00- 2 C OOL IN G OP E R ATIO N O utdoor Am bi e nt Tem per a t ur e 65 75 85 95 105 115 11 8°F 125 °F E nte r ing I ndoor W et B ulb Te m pe r a t ure I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 7 7 1 5 9 6 3 6 7 7 1 5 96 36 77 15 96 3 6 7 7 1 5 9 5 3 6 7 7 1 5 9 6 3 6 ...

  • Goodman Mfg Condensing Units - page 11

    11 COOLING PERFORMANCE DA T A CKF36-5* M O DEL: C KF36-5* / A R36-00- 2 C OOL I N G OP E R AT ION O utdoo r Am bie nt Te m pe r ature 65° F 75° F 85° F 95° F 105°F 1 15°F 118° F 125°F E nte r ing I ndoor Wet B ulb Te m pe r ature ID B Air fl ow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 5 3 67 71 59 63 67 71 ...

  • Goodman Mfg Condensing Units - page 12

    12 COOLING PERFORMANCE DA T A CKF36-5* M O DEL: C KF36-5* / A R36-00- 2 C OOL I N G OP E R AT ION O utdoo r Am bie nt Te m pe r ature 65 75 85 95 1 05 115 118°F 125°F E nte r ing I ndoor Wet B ulb Te m pe r ature I D B * A i r f l o w 5 96 36 77 15 96 36 7 7 1 5 9 6 3 6 7 7 1 5 9 6 3 6 7 7 1 5 9 6 36 7 7 1 5 96 3 6 7 7 1 5 9 5 3 6 7 7 1 5 9 6 3 6 ...

  • Goodman Mfg Condensing Units - page 13

    13 COOLING PERFORMANCE DA T A CKF48-5* MO DEL : C K F48-5* / A 48-00- 2 C OOL IN G OP E R AT ION O utdoor Am bient Te m pe rature 65° F 75° F 85°F 95° F 105°F 115°F 118°F 125°F E n te ring Indoo r We t B ulb Te m pe r atur e ID B Air flo w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 53 67 71 59 63 67 71 M Bh 4 ...

  • Goodman Mfg Condensing Units - page 14

    14 COOLING PERFORMANCE DA T A CKF48-5* MO DEL : C K F48-5* / A 48-00- 2 C OOL IN G OP E R AT ION O utdoor Am bient Te m pe rature 65 75 85 95 105 115 118°F 125°F E n te ring Indoo r We t B ulb Te m pe r atur e I D B * A i r f l o w 5 96 36 77 15 96 36 7 7 1 5 9 6 3 6 77 15 9 6 3 6 7 7 1 5 96 36 7 7 1 5 96 3 6 7 7 1 5 9 5 3 6 7 7 1 5 9 6 3 6 7 7 1 ...

  • Goodman Mfg Condensing Units - page 15

    15 COOLING PERFORMANCE DA T A CKF60-5* MO D EL: C KF6 0- 5* / A 60-00- 2 C OOL IN G OP E R AT ION O ut door Am bient Te m pe r ature 65° F 75°F 85° F 95°F 105°F 115° F 118° F 125°F E nte r ing Indoor W et B ulb Te m pe r a t ur e ID B Air f lo w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 53 67 71 59 63 67 71 ...

  • Goodman Mfg Condensing Units - page 16

    16 COOLING PERFORMANCE DA T A CKF60-5* MO D EL: C KF6 0- 5* / A 60-00- 2 C OOL IN G OP E R AT ION O ut door Am bient Te m pe r ature 65 75 85 95 105 115 118°F 125° F E nte r ing Indoor W et B ulb Te m pe r a t ur e I D B * A i r f l o w 5 96 36 77 15 96 3 6 77 15 9 6 3 6 77 15 9 6 3 6 7 7 1 5 96 36 7 7 1 5 96 3 6 7 7 1 5 9 5 3 6 7 7 1 5 9 6 3 6 7 ...

  • Goodman Mfg Condensing Units - page 17

    17 COOLING PERFORMANCE DA T A CKF70-5* MO D EL : C K F70 -5* / A60-00-2 C OOL IN G OP E R A T ION O utdoor Am bient Te m pe r at ure 65°F 75°F 85°F 95°F 105°F 115°F 118°F 125°F E nte r i ng Indoor W e t B ulb Tem pe rature ID B Air f low 59 6 3 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 5 9 63 67 71 59 63 67 71 59 53 67 71 59 63 67 7 1 M Bh ...

  • Goodman Mfg Condensing Units - page 18

    18 COOLING PERFORMANCE DA T A CKF70-5* MO D EL : C K F70 -5* / A60-00-2 C OOL IN G OP E R A T ION O utdoor Am bient Te m pe r at ure 65 75 85 95 105 1 15 11 8°F 12 5°F E nte r i ng Indoor W e t B ulb Tem pe rature I D B * A i r f l o w 5 9 6 3 6 7 7 1 5 9 6 3 6 7 7 1 5 9 6 3 6 7 7 1 5 9 6 36 7 7 1 5 9 6 3 6 7 7 1 5 9 6 3 6 7 7 15 95 36 77 15 96 3 ...

  • Goodman Mfg Condensing Units - page 19

    19 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a ...

  • Goodman Mfg Condensing Units - page 20

    WIRING DIAGRAMS 20 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICING OR INS T A LLING THIS UNIT . MUL TIPL E POW ER SOURCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAM AGE, PERSO NAL INJURY OR DEA TH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. CKF[24-36]M/N/P ...

  • Goodman Mfg Condensing Units - page 21

    WIRING DIAGRAMS 21 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICING OR INS T A LLING THIS UNIT . MUL TIPL E POW ER SOURCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAM AGE, PERSO NAL INJURY OR DEA TH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. CKF[48-70]M/N/P ...

Производитель Goodman Mfg Категория Air Conditioner

Документы, которые мы получаем от производителя устройства Goodman Mfg Condensing Units мы можем разделить на несколько групп. Это в частности:
- технические чертежи Goodman Mfg
- инструкции обслуживания Condensing Units
- паспорта изделия Goodman Mfg
- информационные брошюры
- энергетические этикетки Goodman Mfg Condensing Units
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Goodman Mfg Condensing Units.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Goodman Mfg Condensing Units, инструкции обслуживания, короткие инструкции или инструкции пользователя Goodman Mfg Condensing Units. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Goodman Mfg Condensing Units.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Goodman Mfg Condensing Units, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Goodman Mfg Condensing Units пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Goodman Mfg Condensing Units.

Полная инструкция обслуживания Goodman Mfg, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Goodman Mfg Condensing Units - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Goodman Mfg Condensing Units, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Goodman Mfg Condensing Units, которое найдем в данном документе
3. Советы по использованию основных функций устройства Goodman Mfg Condensing Units - которые должны облегчить нам первые шаги во время использования Goodman Mfg Condensing Units
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Goodman Mfg Condensing Units
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Goodman Mfg Condensing Units в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Goodman Mfg Condensing Units?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Goodman Mfg Condensing Units, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Goodman Mfg Condensing Units со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)