© 200 8 Panaso n ic HA Ai r- Con di tio n ing (M ) Sd n . Bhd . (1 196 9-T). All ri gh ts re se rv ed . Un aut ho r ized co pyin g and dis tri bu t io n is a viol a ti on of law . Order No. MAC0804027A2 Air Conditioner CS-E9GFEW -2 CU-E9GFE-2 CS-E12GFEW -2 CU-E12GFE-2 CS-E18GFEW -2 CU-E18GFE-2 CU-2E15GBE CU-3E18EBE CU-3E23CBPG CU-4E27CBPG T ABLE O ...
-
Panasonic CU-2E15GBE - page 2
2 1 Safety Precautions • Read the following “SAFET Y PRECAUTIONS” carefully before perform any servicing. • Electrical work must be installed or serviced by a licen sed elec trician. Be sure to u se the corr ect rating of the power pl ug a nd main circuit for the model installed. • The caution items stated here must be followed because th ...
-
Panasonic CU-2E15GBE - page 3
3 17. After completion of installation or service, confirm ther e is no leakage or refrigerant gas. It may gener ate toxic gas when the refrigerant contacts with fire. 18. Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when refrigerant contacts with fire. 1. Do not install the unit at place where leakage of f ...
-
Panasonic CU-2E15GBE - page 4
4 2 S pecifications 2.1. CS-E9GFEW- 2 CU-E9GFE-2 ITEM UNIT INDOOR UNIT OUTDOOR UNIT Performance T est Condition ISO5151 C O O L I N G Capacity kW 2.50 (0.80 ~ 3.00) kcal/h 2150 (690 ~ 2580) BTU/h 8500 (2700 ~ 10200) EER W/W 4.39 (4.57 ~ 3.85) kcal/hW 3.77 (3.94 ~ 3.31) Noise Level dB (A) High 38, Low 27, QLo 23 High 46 Power level dB High 54, Low 4 ...
-
Panasonic CU-2E15GBE - page 5
5 1. Cooling capacities are based on indoor tempera ture of 27 ° C Dry Bulb (80.6 ° F Dry Bulb), 19.0 ° C Wet Bulb (66.2 ° F W et Bulb) and outdoor air temperature of 35 ° C Dry Bulb (95 ° F Dry Bulb), 24 ° C W et Bulb (75.2 ° F Wet Bulb) 2. Heating capacities are bas ed on ind oor temperature of 20 ° C Dry Bulb (68 ° F Dry Bulb) and outd ...
-
Panasonic CU-2E15GBE - page 6
6 2.2. CS-E12GFEW -2 CU-E12GFE-2 ITEM UNIT INDOOR UNIT OUTDOOR UNIT Performance T est Condition ISO5151 C O O L I N G Capacity kW 3.50 (0.80 ~ 3.80) kcal/h 3010 (690 ~ 3270) BTU/h 1 1900 (2700 ~ 13000) EER W/W 3.63 (4.32 ~ 3.33) kcal/hW 3.12 (3.73 ~ 2.87) Noise Level dB (A) High 39, Low 28, QLo 24 High 48 Power level dB High 55, Low 44, QLo 40 High ...
-
Panasonic CU-2E15GBE - page 7
7 1. Cooling capacities are based on indoor tempera ture of 27 ° C Dry Bulb (80.6 ° F Dry Bulb), 19.0 ° C Wet Bulb (66.2 ° F W et Bulb) and outdoor air temperature of 35 ° C Dry Bulb (95 ° F Dry Bulb), 24 ° C W et Bulb (75.2 ° F Wet Bulb) 2. Heating capacities are bas ed on ind oor temperature of 20 ° C Dry Bulb (68 ° F Dry Bulb) and outd ...
-
Panasonic CU-2E15GBE - page 8
8 2.3. CS-E18GFEW -2 CU-E18GFE-2 ITEM UNIT INDOOR UNIT OUTDOOR UNIT Performance T est Condition ISO5151 C O O L I N G Capacity kW 5.00 (0.90 ~ 5.60) BTU/h 17100 (3100 ~ 19100) kcal/h 4300 (770 ~ 4820) EER W/W 3.23 (3.53 ~ 2.93) kcal/hW 2.77 (3.02 ~ 2.52) Noise Level dB (A) High 44, Low 36, QLo 32 H igh 47 Power level dB High 60, Low 52, QLo 48 High ...
-
Panasonic CU-2E15GBE - page 9
9 1. Cooling capacities are based on indoor tempera ture of 27 ° C Dry Bulb (80.6 ° F Dry Bulb), 19.0 ° C Wet Bulb (66.2 ° F W et Bulb) and outdoor air temperature of 35 ° C Dry Bulb (95 ° F Dry Bulb), 24 ° C W et Bulb (75.2 ° F Wet Bulb) 2. Heating capacities are bas ed on ind oor temperature of 20 ° C Dry Bulb (68 ° F Dry Bulb) and outd ...
-
Panasonic CU-2E15GBE - page 10
10 3 Location of Controls and Component s 3.1. Indoor Unit 3.2. Out door Unit 3.3. Remote Control ...
-
Panasonic CU-2E15GBE - page 11
11 4 Dimensions 4.1. Out door Unit 4.1.1. CU-E9GFE-2 CU-E12GFE-2 ...
-
Panasonic CU-2E15GBE - page 12
12 4.1.2. CU-E18GFE-2 ...
-
Panasonic CU-2E15GBE - page 13
13 5 Refrigeration Cycle Diagram 5.1. CS-E9GFEW -2 CU-E9GFE-2 CS-E12GFEW -2 CU-E12GFE-2 If piping length is over rated length , ad ditional refrigerant should be added as shown in the table. Model Piping size Rated Length (m) Max. Elevation (m) Min. Piping Length (m) Max. Piping Length (m) Additional Refrigerant (g/m) Gas Liquid E9GFE-1/E12GFE-1 3/ ...
-
Panasonic CU-2E15GBE - page 14
14 5.2. CS-E18GFEW -2 CU-E18GFE-2 If piping length is over rated length, additional refrigerant should be added as shown in the table. Model Piping size Rated Length (m) Max. Elevation (m) Min. Piping Length (m) Max. Piping Length (m) Additional Refrigerant (g/m) Gas Liquid E18GFE-1 1/2” 1/4” 7.5 15 3 20 20 ...
-
Panasonic CU-2E15GBE - page 15
15 6 Wiring Connection Diagram 6.1. Out door Unit 6.1.1. CU-E9GFE-2 CU-E12GFE-2 ...
-
Panasonic CU-2E15GBE - page 16
16 6.1.2. CU-E18GFE-2 ...
-
Panasonic CU-2E15GBE - page 17
17 7 Electronic Circuit Diagram 7.1. Out door Unit 7.1.1. CU-E9GFE-2 CU-E12GFE-2 ...
-
Panasonic CU-2E15GBE - page 18
18 7.1.2. CU-E18GFE-2 ...
-
Panasonic CU-2E15GBE - page 19
19 7.1.3. Main Printed Circuit Board CU-E9GFE-2 CU-E12GFE-2 ...
-
Panasonic CU-2E15GBE - page 20
20 7.1.4. Main Printed Circuit Board CU-E18GFE-2 ...
-
Panasonic CU-2E15GBE - page 21
21 8 Disassembly and Assembly Instructions 8.1. Out door Unit 8.1.1. CU-E9GFE-2 CU-E12GFE-2 1. Remove the 3 screws of the T op Panel. Fig. 13 2. Remove the 6 screws of the Front Panel. Fig. 14 3. Remove the screw of the T erminal Board Cover . 4. Remove the T op Cover of the Control Board by 4 hooks. Fig. 15 5. Remove the Control Board as follows: ...
-
Panasonic CU-2E15GBE - page 22
22 8.1.2. CU-E18GFE-2 1. Remove the 4 screws of the T op Panel . Fig. 19 2. Remove the 10 scre ws of the Front Panel. Fig. 20 3. Remove the T op Cover of the Ele ctronic Controller . Fig. 21 4. Remove the Control Board. Fig. 22 5. Remove the 8 screws of the Electronic Controller . Fig. 23 • Be save to return the wiring to its original position ? ...
-
Panasonic CU-2E15GBE - page 23
23 9 T echnical Dat a 9.1. Operation Characteristics CS-E9GFEW-2 CU-E9GFE-2 ...
-
Panasonic CU-2E15GBE - page 24
24 ...
-
Panasonic CU-2E15GBE - page 25
25 ...
-
Panasonic CU-2E15GBE - page 26
26 ...
-
Panasonic CU-2E15GBE - page 27
27 CS-E12GFEW -2 CU-E12GFE-2 ...
-
Panasonic CU-2E15GBE - page 28
28 ...
-
Panasonic CU-2E15GBE - page 29
29 ...
-
Panasonic CU-2E15GBE - page 30
30 ...
-
Panasonic CU-2E15GBE - page 31
31 CS-E18GFEW -2 CU-E18GFE-2 ...
-
Panasonic CU-2E15GBE - page 32
32 ...
-
Panasonic CU-2E15GBE - page 33
33 ...
-
Panasonic CU-2E15GBE - page 34
34 ...
-
Panasonic CU-2E15GBE - page 35
35 9.2. Sensible Cap acity Chart O CS-E9GFEW -2 CU-E9GFE-2 O CS-E12GFEW-2 CU-E12GFE-2 O CS-E18GFEW-2 CU-E18GFE-2 220V Outdoor T emp. ( ° C) 230V 30 ° C3 5 ° C4 0 ° C4 6 ° C 240V TC SHC IP TC SHC IP TC SHC IP TC SHC IP D.B. W .B. kW kW kW kW kW kW kW kW kW kW kW kW 27 17.0 2.48 2.13 0.52 2.32 2.05 0.56 2.16 1.97 0.60 1.96 1.88 0.65 19.0 2.50 0. ...
-
Panasonic CU-2E15GBE - page 36
36 10 Exploded V iew and Replacement Part s List 10.1. Indoor Unit ...
-
Panasonic CU-2E15GBE - page 37
37 REF . NO. P ART NAME AND DESCRIPTION QTY . C S-E9GFEW-2 CS-E12GFEW-2 CS-E18GFEW-2 REMARKS B1 EV APORA TOR ASS'Y 1 CW1786554 ← CW1800652 B1-7 FLARE NUT 1 CW1723546 ←← B2 FITTING SPRING / THERMISTOR 1 CW380120 ←← B3 GROUNDING TIP (W/WASHER) 1 CW1 13783J ←← B5 FLARE NUT 1 CW1 1984 8J ← CW1 19849J C1 TURBO F AN ASS'Y 1 CW17 ...
-
Panasonic CU-2E15GBE - page 38
38 (Note) • All parts are supplied from ACBU, Japan. • "O" marked parts are recommended to be kept in stock. F10 CASING (LEFT ) 1 CW1768075 ←← F1 1 FIXTU RE, REF . PIPING 1 CW1768082 ←← F12 REINFORC E PLA TE ASS'Y 1 CW1768099 ←← F13 THERMAL IN SULA TION ASS'Y 1 CW1768107 ←← K1 REMOTE CONTROL 1 CWA75C3096 ←? ...
-
Panasonic CU-2E15GBE - page 39
39 10.2. CU-E9GFE-2 CU-E12GFE-2 Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not k ept as standard service part s. ...
-
Panasonic CU-2E15GBE - page 40
40 (Note) • All parts are supplied from PHAAM, Malaysia (V endor Code: 061). • "O" maked parts are recommended to be kep t in stock. REF . NO. P ART NAME AND DESCRIPTION QTY . CU-E9GFE-2 CU-E12GFE-2 REMARK 1 CHASSY ASSY 1 CWD50K2073 ← 2 ANTI - VIBRA TION BUSHING 3 CWH50077 ← 3 COMPRESSOR 1 5RS102XBC01 ← O 4 NUT - COMPRESSOR MOUN ...
-
Panasonic CU-2E15GBE - page 41
41 10.3. CU-E18GFE-2 Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not k ept as standard service part s. ...
-
Panasonic CU-2E15GBE - page 42
42 (Note) • All parts are supplied from PHAAM, Malaysia (V endor Code: 061). • "O" maked parts are recommended to be kep t in stock. [PHAAM] Printed in Malaysia SFSC0804-00 REF . NO. P ART NAME AN D DESCRIPTION QTY . CU-E18GFE-2 REMARK 1 CHASSY ASSY 1 CWD 50K2085 2 ANTI - VIBRA TION BUSHING 3 CWH50077 3 COMPRESSOR 1 5CS130XAE04 O 4 NU ...