    Manual 2100-511F Page 1 of 27 INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE HEA T PUMPS MODELS W18H1 W24H1 W24H1D W30H1 W30H1D W36H1 W36H1D W42H1 W42H1D W48H1 W48H1D W60H1 W60H1D Manual: 2100-51 1F Supersedes: 2100-51 1E File: V olume III T ab 17 Date: 02-17-12 Bard Manufacturing Company , Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just ...

  • Bard W42H1 - page 2

    Manual 2100-511F Page 2 of 27 Content s Figures Figure 1 Fresh Air Damper Assembly ................... 5 Figure 2 Unit Dimensions ...................................... 7 Figure 3A Mounting Instructions .............................. 8 Figure 3B Mounting Instructions - W18, W24, W30, W36 .... 9 Figure 3C Mounting Instructions - W42, W48, W60 ..... ...

  • Bard W42H1 - page 3

    Manual 2100-511F Page 3 of 27 GETTING OTHER INFORMA TION AND PUBLICA TIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Electrical Code ...................... ANSI/ ...

  • Bard W42H1 - page 4

    Manual 2100-511F Page 4 of 27 W ALL MOUNT GENERAL INFORMA TION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE W 42 H 1– A 10 X X X X X A NOTE: Vent options X, B and M are without exhaust capability. May require separate field supplied barometric relief in building. SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external sign ...

  • Bard W42H1 - page 5

    Manual 2100-511F Page 5 of 27 DUCT WORK All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both cons ...

  • Bard W42H1 - page 6

    Manual 2100-511F Page 6 of 27 s s e c c A e c i v r e S r o f d e r i u q e R s e c n a r a e l C w o l f r i A r e s n e d n o C e t a u q e d A d n a S L E D O M E D I S T F E L E D I S T H G I R H 6 3 W , H 0 3 W , H 4 2 W , H 8 1 W " 5 1 " 0 2 H 0 6 W , H 8 4 W , H 2 4 W " 0 2 " 0 2 o t d e r i u q e R s e c n a r a e l C m ...

  • Bard W42H1 - page 7

    Manual 2100-511F Page 7 of 27 *Optional top outlet (factory installed only) for W30H and W36H models only. FIGURE 2 ) l a n i m o N ( s t n e m e r i u q e R n o i t a l l a t s n I d n a l a r u t c e t i h c r A r o f t i n U c i s a B f o s n o i s n e m i D L E D O M H T D I W ) W ( H T P E D ) D ( T H G I E H ) H ( Y L P P U SN R U T E R AB C ...

  • Bard W42H1 - page 8

    Manual 2100-511F Page 8 of 27 FIGURE 3A W18H1, W24H1 MOUNTING INSTRUCTIONS ...

  • Bard W42H1 - page 9

    Manual 2100-511F Page 9 of 27 FIGURE 3B W30H1, W36H1 MOUNTING INSTRUCTIONS ...

  • Bard W42H1 - page 10

    Manual 2100-511F Page 10 of 27 FIGURE 3C W42H1, W48H1, W60H1 MOUNTING INSTRUCTIONS ...

  • Bard W42H1 - page 11

    Manual 2100-511F Page 11 of 27 FIGURE 4 ELECTRIC HEAT CLEARANCE W30H1, W36H1, W42H1, W48H1, W60H1 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is important to insure that the 1/4 inch minimum sp acing is maintained at all point ...

  • Bard W42H1 - page 12

    Manual 2100-511F Page 12 of 27 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 – MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS, FIGURE 2, FOR ACTUAL DIMENSIONS IF REQUIRED IF REQUIRED ...

  • Bard W42H1 - page 13

    Manual 2100-511F Page 13 of 27 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS ...

  • Bard W42H1 - page 14

    Manual 2100-511F Page 14 of 27 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed K ...

  • Bard W42H1 - page 15

    Manual 2100-511F Page 15 of 27 ST ART UP THESE UNITS REQUIRE R-410A REFRIGERANT AND POL YOL ESTER OIL. GENERAL: 1. Use separate service equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for R-410A refrigerant. 3. Use manifold gauges rated for R-410A (800 psi/250 psi low). 4. R-410A is a binary blend of ...

  • Bard W42H1 - page 16

    Manual 2100-511F Page 16 of 27 ST ART UP (Continued) IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dish washing detergent. HIGH & LOW PRESSURE SWITCH All W**H wall mounted air conditioner series models are supplied with a remote reset for the high and low pressure switch. If tripped, this pressure switch ...

  • Bard W42H1 - page 17

    Manual 2100-511F Page 17 of 27 SEQUENCE OF OPERATION COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. HEATI ...

  • Bard W42H1 - page 18

    Manual 2100-511F Page 18 of 27 120* SW 1 SW 2 TIM E (SEC) OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS-2668 A OFF LOW PRESSURE BYPASS TI MER SWITCH *(FACTORY SETTING 120 S ECONDS) ACCUMULATED DEFROST TIME TI M ER (FACTORY S ETTING 60 MIN.) ON FIGURE 8 DEFROST CONTROL BOARD ...

  • Bard W42H1 - page 19

    Manual 2100-511F Page 19 of 27 TROUBLESHOOTING SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDURE 1. NOTE: A thorough understanding of the defrost cycle sequence is essential. Review that section earlier in this manual prior to troubleshooting the control. Turn on AC power supply to unit. 2. Turn thermostat blower switch to “fan on” – th ...

  • Bard W42H1 - page 20

    Manual 2100-511F Page 20 of 27 CHECKING TEMPERATURE SENSOR OUTSIDE UNIT CIRCUIT 1. Disconnect temperature sensor from board and from outdoor coil. 2. Use an ohmmeter and measure the resistance of the sensor. Also use ohmmeter to check for short or open. 3. Check resistance reading to chart of resistance. Use sensor ambient temperature. (Tolerance o ...

  • Bard W42H1 - page 21

    Manual 2100-511F Page 21 of 27 TROUBLESHOOTING FIGURE 9 FAN BLADE SETTING TABLE 2 FAN BLADE DIMENSION REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles. 3. Remove screws holding fan shroud to condenser and bottom. Nine (9) screws. 4. Unwire condenser fa ...

  • Bard W42H1 - page 22

    Manual 2100-511F Page 22 of 27 TABLE 3A COOLING PRESSURE TABLE Low side pressure ± 4 PSIG High side pressure ± 10 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate charge w ...

  • Bard W42H1 - page 23

    Manual 2100-511F Page 23 of 27 TABLE 4 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conducto ...

  • Bard W42H1 - page 24

    Manual 2100-511F Page 24 of 27 TABLE 5 RECOMMENDED AIRFLOW TABLE 6 INDOOR BLOWER PERFORMANCE l e d o M d e t a R * M F C d e t a R * P S E d e d n e m m o c e R e g n a R w o l f r i A d e e p S y r o t c a F n o i t c e n n o C H 8 1 W0 0 6 1 0 3 .5 2 7 - 5 7 5h g i H H 4 2 W0 0 80 2 .0 5 9 - 0 0 7h g i H H 0 3 W0 0 0 10 4 .0 0 3 1 - 0 3 9h g i H ...

  • Bard W42H1 - page 25

    Manual 2100-511F Page 25 of 27 TABLES 7 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY TABLE 8 ELECTRIC HEAT s l e d o M1 - V 0 4 21 - V 8 0 23 - V 0 4 23 - V 8 0 23 - V 0 6 4 W Ks p m AH U T Bs p m AH U T Bs p m AH U T Bs p m AH U T Bs p m AH U T B 47 . 6 10 5 6 3 14 . 4 10 4 2 0 1 58 . 0 25 6 0 7 11 . 8 10 0 8 2 1 64 . 4 10 0 5 0 25 . 2 10 6 3 5 12 ...

  • Bard W42H1 - page 26

    Manual 2100-511F Page 26 of 27 W18H1-A W24H1-A W24H1-B W24H1-C W30H1-A W30H1-B W30H1-C W36H1-A W36H1-B W36H1-C W42H1-A W42H1-B W42H1-C W48H1-A W48H1-B W48H1-C W60H1-A W60H1-B W60H1-C TABLE 9 OPTIONAL ACCESSORIES r e b m u N t r a P 4 0 A - A 2 0 H W H EX 8 0 A - A 2 0 H W H EX 4 0 A - H 4 2 W H EX 8 0 A - H 4 2 W H EX 6 0 B - H 4 2 W H EX 5 0 A - 0 ...

  • Bard W42H1 - page 27

    Manual 2100-511F Page 27 of 27 TABLE 10 VENT & CONTROL OPTIONS W18, W24 W30, W36 W42, W48, W60 r e b m u N t r a Pn o i t p i r c s e D 4 1 - C M CT D O XXX 5 1 - C M C) y l n o e s a h P - 1 V 0 3 2 ( t i K t r a t S 1 XXX 1 1 1 K S) y l n o e s a h P - 1 V 0 3 2 ( t i K t r a t S 2 XXX 8 2 - C M CC A L XXX 2 - D A F Bd r a d n a t S - r e p m ...

Производитель Bard Категория Heat Pump

Документы, которые мы получаем от производителя устройства Bard W42H1 мы можем разделить на несколько групп. Это в частности:
- технические чертежи Bard
- инструкции обслуживания W42H1
- паспорта изделия Bard
- информационные брошюры
- энергетические этикетки Bard W42H1
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Bard W42H1.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Bard W42H1, инструкции обслуживания, короткие инструкции или инструкции пользователя Bard W42H1. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Bard W42H1.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Bard W42H1, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Bard W42H1 пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Bard W42H1.

Полная инструкция обслуживания Bard, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Bard W42H1 - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Bard W42H1, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Bard W42H1, которое найдем в данном документе
3. Советы по использованию основных функций устройства Bard W42H1 - которые должны облегчить нам первые шаги во время использования Bard W42H1
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Bard W42H1
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Bard W42H1 в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Bard W42H1?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Bard W42H1, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Bard W42H1 со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)