  • Bryant 650A - page 1

    Form No. PDS 650A.24.2 QUANTUM PLUS 13 SEER HEAT PUMP WITH PURON™ REFRIGERANT 650A (60 Hz) Sizes 024 thru 060 The Quantum Plus line of split-system outdoor units has been e xpanded to include the Model 650A 13 SEER heat pump (with efficiencies up to 14.5 SEER). Homeowners will appreci- ate the Quantum Plus with Puron Refrigerant because of its e ...

  • Bryant 650A - page 2

    —2— DIMENSIONS A94148 ACCESS PANEL 1 1 / 4 "  1. Allow 30 in. clearance to service end of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side, and 24 in. between units for proper airflow. Minimum outdoor operating ambient in cooling mode is 55 ° F (unless low ambient control is used) max 125 ° F. 2. Maximum o ...

  • Bryant 650A - page 3

    —3— RECOMMENDED TUBE DIAMETERS * RST—Refrigeration Service T ubing, standard refrigerant gr ade tubing. NO TES: 1. T ube diameters are f or lengths up to 50 ft. For tubing lengths g reater than 50 ft, consult the Application Guideline and Service Manual f or Residential Split- System Air Conditioners and Heat Pumps using Puron Refrigerant. 2. ...

  • Bryant 650A - page 4

    —4— SPECIFICA TIONS See notes on page 5. UNIT SIZE-SERIES 024-A,C 030-A,C 036-A,C Operating Weight (Lb) 214 205 217 ELECTRICAL Unit V olts—Hertz—Phase 208/230—60—1 Operating V oltage Range* 187—253 Compressor Rated Load Amps 15.1 14.7 15.4 Compressor Locked Rotor Amps 61.0 72.5 83.0 Condenser F an Motor—Full Load Amps 0.8 1.1 1.1 Mi ...

  • Bryant 650A - page 5

    —5— SPECIFICA TIONS Contin ued * P er missible limits of the v oltage range at which the unit will oper ate satisfactorily . Operation outside these limits may result in unit f ailure. † If other than uncoated (non-plated), 60°C or 75°C (140° or 167°F) insulation, copper wire (solid wire f or 10 A WG and smaller , stranded wire f or large ...

  • Bryant 650A - page 6

    —6— THERMOST A TS AND A CCESSORIES * Do not use in zoning heat pump applications. † This plate is designed to cov er surrounding wall area located behind ther mostat. ‡ Thermostat conversion kit is a 24-v ac accessor y that can tur n a 4-wire ther mostat application into a 5-wire application. This kit can also be used to replace a broken th ...

  • Bryant 650A - page 7

    —7— A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) 1. Compressor Start Assist—Capacitor and Relay Star t capacitor and star t relay which giv es a “hard” boost to compressor motor at each star t-up. SUGGESTED USE: Installations where interconnecting tube length e xceeds 50 ft. Installations where outdoor design temperature e x ...

  • Bryant 650A - page 8

    —8— COMBINA TION RA TINGS* See notes on page 9. UNIT SIZE- SERIES INDOOR UNIT CFM†† ARI ST ANDARD RA TINGS* Cooling Heating TC Seasonal Efficiency SEER EER High-T emp Low-T emp HSPF Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ Puron TXV Puron TXV & TDR** TC COP TC COP 024-A,C FX4ANF030† 800 25,000 TDR&a ...

  • Bryant 650A - page 9

    —9— COMBINA TION RA TINGS Continued * Ratings are net values reflecting the eff ects of circulating fan heat. Supplemental electr ic heat is not included. Ratings are based on: Cooling Standard: 80°F (27°C) db 67°F (19°C) wb indoor entering air temperature and 95°F (35°C) db air entering outdoor unit. High-T emp Heating Standard: 70°F ( ...

  • Bryant 650A - page 10

    —10— 650AN060-B,C FV4A006 650AN048-A,C FV4A005 650AN042-A,C FV4A003 650AN036-A,C FX4A042 650AN030-A,C FX4A030 650AN024-A,C FX4A030 BASED ON INDOOR ENT . AIR A T 70˚F AND A T RA TED CFM 23.4 20.5 17.6 14.7 11.7 8.8 5.9 2.9 80 70 60 50 40 30 20 10 0 -10 OUTDOOR TEMPERA TURE, ˚F BUILDING HEA T LOSS, 1000 BTU/HR UNIT INTEGRA TED HEA TING CAP A ...

  • Bryant 650A - page 11

    —11— DET AILED COOLING CAP A CITIES* See notes on page 14. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** T o ...

  • Bryant 650A - page 12

    —12— DET AILED COOLING CAP A CITIES* Continued See notes on page 14. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant 650A - page 13

    —13— DET AILED COOLING CAP A CITIES* Continued See notes on page 14. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant 650A - page 14

    —14— DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight variation in capacity may occur . † T otal and sensible capacities are net capacities. Blo ...

  • Bryant 650A - page 15

    —15— HEA T PUMP HEA TING PERFORMANCE See notes on page 17. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES °F – 3 7 1 72 73 74 75 76 7 EDB CFM Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T ota ...

  • Bryant 650A - page 16

    —16— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 17. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES °F – 3 7 1 72 73 74 75 76 7 EDB CFM Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtu ...

  • Bryant 650A - page 17

    —17— HEA T PUMP HEA TING PERFORMANCE Continued * The Btuh heating capacity values sho wn are net “integrated” values from which the defrost eff ect has been subtracted. The Btuh heating from supplement heaters should be added to those v alues to obtain total system capacity . † The kw values include the compressor , outdoor f an motor, an ...

  • Bryant 650A - page 18

    —18— System Design 1. Intended f or outdoor installation with free air inlet and outlet. Outdoor fan e xternal static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor operating air temper ature f or cooling mode without low-ambient operation accessory is 55°F (12.8°C). 3. Maximum outdoor operating air temper ature f or cooling ...

  • Bryant 650A - page 19

    —19— ...

  • Bryant 650A - page 20

    SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 650A.24.1 © 1998 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indianapolis, IN 46231 —2 0— PRINTED IN U.S.A. Catalog No. 5265-002 1-99 SERVICE TRAINING Packaged Service Training programs are an excellent ...

Производитель Bryant Категория Heat Pump

Документы, которые мы получаем от производителя устройства Bryant 650A мы можем разделить на несколько групп. Это в частности:
- технические чертежи Bryant
- инструкции обслуживания 650A
- паспорта изделия Bryant
- информационные брошюры
- энергетические этикетки Bryant 650A
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Bryant 650A.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Bryant 650A, инструкции обслуживания, короткие инструкции или инструкции пользователя Bryant 650A. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Bryant 650A.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Bryant 650A, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Bryant 650A пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Bryant 650A.

Полная инструкция обслуживания Bryant, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Bryant 650A - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Bryant 650A, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Bryant 650A, которое найдем в данном документе
3. Советы по использованию основных функций устройства Bryant 650A - которые должны облегчить нам первые шаги во время использования Bryant 650A
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Bryant 650A
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Bryant 650A в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Bryant 650A?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Bryant 650A, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Bryant 650A со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)