  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 1

    SER VICE TECHNICAL GUIDE CONTENTS 1. MS MICROPROCESSOR CONTROL ·················· 4 2. MSZ, MSY MICROPROCESSOR CONTROL ······ 7 3. MXZ MICROPROCESSOR CONTROL ·············· 21 4. MFZ MICROPROCESSOR CONTROL ·············· 35 SPLIT -TYPE AIR CONDITIONERS No. OBT16 REVISED EDITION-G Please void OBT16 ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 2

    2 Revision A: • MXZ-3A30NA- 1 has been added. Revision B: • MXZ-2A20NA- 1 , MXZ-4A36NA, MSZ-FD, MSZ-D and MSY -D have been added. Revision C: • MXZ-2A20NA- 2 has been added. Revision D: • MSZ-GA•NA and MSY -GA•NA have been added. Revision E: • MSZ-FE•NA, MSZ-GE•NA, MSY -GE•NA and MXZ-B•NA have been added. Revision F: • MXZ-2 ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 3

    3 1. MS MICROPROCESSOR CONTROL ·································································································· ················· 4 Indoor unit models Outdoor unit models MS-A09/12W A MU-A09/12W A 1-1. COOL OPERA TION ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 4

    4 1-1. COOL ( ) OPERA TION 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat's OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature. 1-2. DR Y ( ) OPERA T ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 5

    5 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature. 2. Indoor fan speed control Indoor fan operates at the set speed by F AN SPEED CONTROL button. When thermostat OFF (compressor OFF), fan speed becomes V ery Low . In AUTO the fan speed is as follows. 4. Coil frost prevention Coil frost ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 6

    6 1-3. AUTO V ANE OPERA TION 1. Horizontal vane ECONO COOL ( ) operation (ECONOmical operation) When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 3.6°F (2°C) higher than that in COOL mode. Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger (indoor coil thermist ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 7

    7 2-1. COOL ( ) OPERA TION 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat's OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature. ON -1.8°F(-1°C) or ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 8

    8 2-2. DR Y ( ) OPERA TION Set temperature is as shown on the right chart. The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room tem- perature. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature d ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 9

    9 (2) Cold air prevention control MSZ-A09/12/15/17 MSZ-FD MSZ-FE MSZ-D MSZ-GE When the compressor is not operating, ( ) if the temperature of room temperature thermistor is less than 66°F (19°C), the fan stops. ( ) if the temperature of room temperature thermistor is 66°F (19°C) or more and ( ) if the temperature of indoor coil thermistor is le ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 10

    10 set position set speed set position set speed Indoor fan Compressor normal Outdoor fan R.V . coil (21S4) OFF (COOL) OFF Maximum frequency horizontal Horizontal vane V ery Low (temperature of indoor coil thermistor > 64 °F) 30 seconds 30 seconds 30 seconds 40 seconds 5 seconds 5 seconds 40 seconds OFF (39°C) (18°C) OFF OFF ON (HEA T) ON ON ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 11

    11 (2) Mode change In case of the following conditions, the operation mode is changed. COOL mode changes to HEA T mode when 15 minutes have passed with the room temperature 2 - 4°F (1 - 2°C) below the set temperature. HEA T mode changes to COOL mode when 15 minutes have passed with the room temperature 2 - 4°F (1 - 2°C) above the set temperatur ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 12

    12 <SWING operation> In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”. According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is decided. Then when the downward blow has been finished, next horizontal blow time is decided ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 13

    13 MUZ-A24 MUY -A24 MUZ-D MUY -D MUZ-FE18 MUZ-GA MUY -GA MUZ-GE24 MUY -GE24 POWER SUPPL Y NOISE FIL TER CIRCUIT RESISTOR RELA Y SMOOTHING CAP ACITOR CURRENT TRANSFORMER COMPRESSOR REACTOR P W V U N IPM PFC U W MS 3~ V + Function of main parts NAME FUNCTION INTELLIGENT POWER MODULE (IPM) It supplies 3-phase AC power to compressor . SMOOTHING CAP ACI ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 14

    14 3. Purpose of P AM adoption P AM (Pulse Amplitude Modulation) has been adopted for the ef fi ciency improvement and the adaptation to IEC harmonic cur- rent emission standard Outline of simple partial switching method In conventional inverter models, DIODE MODULE recti fi es AC voltage to DC voltage, SMOOTHING CAP ACITOR makes its DC waveform ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 15

    15 4. Intelligent power module IPM consists of the following components · IGBT (x6): Converts DC waveform to 3-phase AC waveform and outputs it. · Drive Circuit: Drives transistors. · Protection circuit: Protects transistors from overcurrent. Since the above components are all integrated in IPM, IPM has a merit to make the control circuit simpli ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 16

    16 2-7-4. Characteristics of sine wave control in case of brushless DC motor ● Although ordinary 3-phase induction motor requires energy to excite the magnetic fi eld of rotor , brushless DC motor does not need it. So, higher ef fi ciency and torque are provided. ● This control provides the most ef fi cient waveform corresponding to the rota ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 17

    17 2-8. OPERA TIONAL FREQUENCY CONTROL OF OUTDOOR UNIT 1. Outline The operational frequency is as following: First, the target operational frequency is set based on the difference between the room temperature and the set tempera- ture. Second, the target operational frequency is regulated by discharge temperature protection, high pressure protectio ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 18

    18 (2) T ime chart OFF T ime Ti m e ON Operational frequency of the compressor Commanded to open Standard opening degree Opening degree is corrected according to discharge temperature. (Refer to (3)) Positioning Air conditioner ON Air conditioner OFF (thermostat off) LEV opening degree About 15 minutes 2-9. EXP ANSION V AL VE CONTROL (LEV CONTROL) ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 19

    19 (3) Control data F E D C B A T arget discharge temperature Operational frequency of the compressor 30 50 70 90 1 10 130 23 38 53 69 84 99 (Hz) (Hz) ( Other models ) ( MUZ-FE18 MUZ-GE24 MUY -GE24 ) (a) Reference value of target discharge temperature COOL / HEA T ( MUZ ) °F/°C Applied model A B C D E F MUZ-A09/12 COOL 122/50 127/53 140/60 151/66 ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 20

    20 2. Pre-heat control ON condition (1) Pre-heat control is turned ON for 15 or 30 minutes after the breaker is turned ON. (2) 30 min. after the unit is stopped, pre-heat control is turned ON for 15 or 30 minutes and turned OFF for 30 minutes. This is repeated as shown in the graph until the breaker is turned OFF . When the defrost thermistor reads ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 21

    21 3-1. INVERTER SYSTEM CONTROL POWER SUPPL Y NOISE FIL TER CIRCUIT RESISTOR RELA Y SMOOTHING CAP ACITOR CURRENT TRANSFORMER COMPRESSOR REACTOR P W V U N IPM PFC U W MS 3~ V + 3-1-1. Inverter main power supply circuit Function of main parts NAME FUNCTION INTELLIGENT POWER MODULE (IPM) It supplies 3-phase AC power to compressor . SMOOTHING CAP ACIT ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 22

    22 3. Power factor improvement Booster coil reactor and PFC rectify AC to DC and control its voltage. In the motor drive system of sine wave control, power factor can be improved by reducing harmonics. PFC and reactor stabi- lize the voltage of DC supplied to inverter circuit and make its waveform smooth. 4. Intelligent power module IPM consists of ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 23

    23 3-2. EXP ANSION V AL VE CONTROL (LEV CONTROL) Linear expansion valve (LEV) is controlled by “Thermostat ON” commands given from each unit. Indoor unit status LEV opening Stop of all indoor unit Opening before stop → 500 pulses in 15 minutes When outdoor unit is operating, some indoor units stop and some operate. COOL: 5 pulses (full closed ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 24

    24 In COOL mode, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (super heat) at the heat exchanger , and when temperature difference develops, the indoor coil thermistors adjust LEV opening to diminish the super heat. This action is called Evaporation T emperature Protection. Indoor heat exchanger (MXZ-3A30NA) ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 25

    25 23 54 69 84 100 1 15 131 146 38 14 32 41 50 59 68 77 86 MXZ-2A/2B MXZ-3A/4A 23 Compressor operating frequency (Hz) 4Hz 01 02 03 04 05 06 07 08 09 10 LEV Opening (code) Determination of LEV standard opening in each indoor unit • The standard opening is on the straight line, which connects an each standard point in the section where divided into ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 26

    26 MXZ-3A30NA- 1 MXZ-4A36NA MXZ-3B24NA MXZ-3B30NA MXZ-4B36NA Exclusive LEV Standard opening (pulse) LEV Opening (code) 123456789 1 0 COOL 126 130 134 138 150 160 170 180 190 200 HEA T 248 248 258 266 274 280 286 292 300 306 Difference in capacity Difference in operation number Code3,4 Code5,6 Code7,8 Code9,10 Code1 1,12 Code13,14 Code15or above 23 ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 27

    27 (1) LEV opening correction by discharge temperature The target discharge temperature is determined according to frequency zone and number of operation unit of the com- pressor . <Correction> COOL DRY HEA T Discharge temperature ● 2 ● 2 ● Each correction • (Each gas pipe temperature thermistor - Minimum gas pipe temperature thermist ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 28

    28 Correct the LEV opening according to the difference between target discharge temperature and discharge temperature. (2) Separate correction (COOL,DRY) (Correction by the separate super heat) a) Correct the LEV separately by temperature difference between each gas pipe temperature and the minimum gas pipe temperature of all. Calculate each super ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 29

    29 3-3. OPERA TIONAL FREQUENCY RANGE b) Correct the LEV separately by temperature difference “ ∆ R T” between main/sub indoor coil thermistor . ∆ RT LEV opening correction (pulse) 10.8 ∆ RT 2 7.2 ∆ RT < 10.8 1 ∆ RT < 7.2 1 In addition, decrease the target discharge temperature corresponding ∆ RT . ∆ RT T emperature to be dec ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 30

    30 MXZ-3A30NA- 1 MXZ-4A36NA Number of operating unit Capacity code COOL (Hz) DRY (Hz) HEA T (Hz) Min. Max. Min. Max. Defrost 1 4 2 55 82 52 07 05 8 7 2 55 82 52 07 05 8 9,10 25 71 25 20 80 58 12 25 80 35 20 80 58 2 8 ~ 10 25 80 31 20 80 58 1 1 ~ 13 25 80 31 20 80 58 14 ~ 16 25 80 42 20 80 58 17 ~ 25 80 42 20 80 58 3 ( MXZ-3A ) 12 ~ 25 80 52 20 80 5 ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 31

    31 3-4. HEA T DEFROSTING CONTROL (1) Starting conditions of defrosting When the following conditions a) ~ c) are satisfied, the defrosting starts. a) The defrost thermistor reads 26.6°F or less. b) The cumulative operation time of the compressor has reached any of the set values (defrost interval: 40-150 min- utes). c) More than 5 minutes have pas ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 32

    32 COOL Fan speed changes so that the condensing temperature stays within the target range. Fan speed Revolution per minutes (rpm) MXZ-2B20NA- 1 MXZ-3B MXZ-4B 1 100 100 2 150 150 3 200 200 4 250 250 5 300 300 6 350 350 7 400 400 8 450 450 9 500 500 10 550 550 1 1 600 600 12 650 650 13 700 700 14 750 750 HEA T Fan speed is switched according to the ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 33

    33 1. Pre-heat control is turned ON for 15 or 30 minutes, after the breaker is turned ON. 2. 30 minutes after the unit is stopped, pre-heat control is turned ON for 15 or 30 minutes and turned OFF for 30 minutes. This is repeated as shown in the graph until the breaker is turned OFF . When the defrost thermistor reads less than 69.8°F , pre-heat c ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 34

    34 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature. 3-9. DR Y OPERA TION 3-10. HEA T OPERA TION 2. High pressure protection In HEA T operation the indoor coil thermistor detects the temperature of the indoor heat exchanger . The compressor opera- tional frequency is controlled to preve ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 35

    35 4 MFZ MICROPROCESSOR CONTROL 3. Coil frost prevention Refer to MXZ MICROPROCESSOR CONTROL, COOL OPERA TION (3-8.2.). 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat's OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Refer to MXZ MICROP ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 36

    36 1. Thermostat control Refer to MXZ MICROPROCESSOR CONTROL, HEA T OPERA TION (3-10.1.). 4-3. HEA T ( ) OPERA TION 2. Indoor fan speed control (1) Indoor fan operates at the set speed by F AN SPEED CONTROL button. In Auto the fan speed is as follows. 3. High pressure protection In HEA T operation, the indoor coil thermistor detects the temperature ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 37

    37 4-5. INDOOR F AN MOTOR CONTROL (1) Rotational frequency feedback control The indoor fan motor is equipped with a rotational frequency sensor , and outputs signal to the microprocessor to feed- back the rotational frequency . Comparing the current rotational frequency with the target rotational frequency (Super High, High, Med., Low), the micropr ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 38

    38 4-6. AUTO V ANE OPERA TION Horizontal vane (1) Cold air prevention in HEA T operation When any of the following conditions occurs in HEA T operation, the vane angle changes to V ertical position automati- cally to prevent cold air blowing on users. Compressor is not operating. Defrosting is performed. Indoor coil thermistor reads 75.2°F or belo ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 39

    39 ...

  • Mitsubishi Electronics MUZ-FE09/12/18NA - page 40

    New publication, effective Sep. 2010. Specifications subject to change without notice. HEAD OFFICE: TOKYO BLDG.,2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAP AN © Copyright 2006 MITSUBISHI ELECTRIC CO.,L TD Distributed in Sep. 2010. No. OBT16 REVISED EDITION-G 6 Distributed in Mar . 2010. No. OBT16 REVISED EDITION-F 6 Distributed in Sep. 2009 ...

Производитель Mitsubishi Electronics Категория Air Conditioner

Документы, которые мы получаем от производителя устройства Mitsubishi Electronics MUZ-FE09/12/18NA мы можем разделить на несколько групп. Это в частности:
- технические чертежи Mitsubishi Electronics
- инструкции обслуживания MUZ-FE09/12/18NA
- паспорта изделия Mitsubishi Electronics
- информационные брошюры
- энергетические этикетки Mitsubishi Electronics MUZ-FE09/12/18NA
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Mitsubishi Electronics MUZ-FE09/12/18NA.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Mitsubishi Electronics MUZ-FE09/12/18NA, инструкции обслуживания, короткие инструкции или инструкции пользователя Mitsubishi Electronics MUZ-FE09/12/18NA. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Mitsubishi Electronics MUZ-FE09/12/18NA.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Mitsubishi Electronics MUZ-FE09/12/18NA, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Mitsubishi Electronics MUZ-FE09/12/18NA пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Mitsubishi Electronics MUZ-FE09/12/18NA.

Полная инструкция обслуживания Mitsubishi Electronics, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Mitsubishi Electronics MUZ-FE09/12/18NA - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Mitsubishi Electronics MUZ-FE09/12/18NA, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Mitsubishi Electronics MUZ-FE09/12/18NA, которое найдем в данном документе
3. Советы по использованию основных функций устройства Mitsubishi Electronics MUZ-FE09/12/18NA - которые должны облегчить нам первые шаги во время использования Mitsubishi Electronics MUZ-FE09/12/18NA
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Mitsubishi Electronics MUZ-FE09/12/18NA
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Mitsubishi Electronics MUZ-FE09/12/18NA в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Mitsubishi Electronics MUZ-FE09/12/18NA?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Mitsubishi Electronics MUZ-FE09/12/18NA, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Mitsubishi Electronics MUZ-FE09/12/18NA со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)