Инструкция обслуживания Bryant DELUXE 13 SEER 550A

28 страниц 1.58 mb
Скачать

Перейти на страницу of 28

Summary
  • Bryant DELUXE 13 SEER 550A - page 1

    Form No. PDS 550A.24.5 DELUXE 13 SEER AIR CONDITIONER WITH PURON ® (R-410A) 550A (60 Hz) Sizes 024 thru 060 Br yant’ s Quantum Plus 550A with Puron® provides a com- pletely unique collection of features which cannot be matched by any other f amily of equipment. The 550A f amily has been designed as the first air conditioning system utilizing B ...

  • Bryant DELUXE 13 SEER 550A - page 2

    —2— DIMENSIONS A99067 AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW. 2. MINIMUM OUTDOOR OPERATING AMBIENT ...

  • Bryant DELUXE 13 SEER 550A - page 3

    —3— RECOMMENDED TUBE DIAMETERS * For tube sets g reater than 50 ft, consult Residential Split System Application Guideline and Service Manual. CHECK-FLO-RA TER® PIST ON * Piston listed is f or any approv ed non-capillar y tube coil combination. Piston is shipped with outdoor unit and must be installed in an appro ved indoor coil. CHARGING SUBC ...

  • Bryant DELUXE 13 SEER 550A - page 4

    —4— SPECIFICA TIONS See notes on page 5. . UNIT SIZE-SERIES 024-D/E 030-D/E 036-D/E Operating Weight (Lb) 214 202 237 ELECTRICAL Unit V olts—Hertz—Phase 208/230—60—1 Operating V oltage Range* 187—253 Compressor— Rated Load Amps 13.5 14.7 15.4 Locked Rotor Amps 61.0 72.5 83.0 Condenser F an Motor—Full Load Amps 0.80 0.80 1.1 Min Un ...

  • Bryant DELUXE 13 SEER 550A - page 5

    —5— SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will operate satisfactorily . Operation outside these limits ma y result in unit f ailure. † If wire is applied at ambient greater than 30°C (86°F), consult T able 310-16 of the NEC (ANSI/NFP A 70). The ampacity of nonmetallic-sheathed cable (NM), t ...

  • Bryant DELUXE 13 SEER 550A - page 6

    —6— A CCESSOR Y USA GE GUIDELINE * For tubing line sets g reater than 50 ft, refer to Residential Split-System Long-Line Application Guideline and Service Manual. † Only when low-pressure s witch is used. ‡ Required for Lo w-Ambient Controller (full modulation feature) and MotorMaster® Control only . A CCESSOR Y DESCRIPTION AND USA GE (Lis ...

  • Bryant DELUXE 13 SEER 550A - page 7

    —7— A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Continued 11. Low-Ambient Pressure Switc h A long life pressure s witch which is mounted to outdoor unit service valve . It is designed to cycle the outdoor f an motor in order to maintain head pressure within normal operating limits (approximately 200 psig to 365 psig). The control ...

  • Bryant DELUXE 13 SEER 550A - page 8

    —8— COMBINA TION RA TINGS See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory TXV‡ 024-D , E CC5A/CD5AA030* 24,000 NONE — 13.00 13.00 11.20 CC5A/CD5AA024 24,000 NONE — 12.50 12.50 11.10 CC5A/CD5A W024 24,000 NONE ? ...

  • Bryant DELUXE 13 SEER 550A - page 9

    —9— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory TXV‡ 030-D , E F(A,B)4ANF030 28,600 TDR 12.50 — 12.50 11.10 F(A,B)4ANF036 29,000 TDR 12.50 — 12.50 10.95 FF1(B,C ,D)NA030 28,6 ...

  • Bryant DELUXE 13 SEER 550A - page 10

    —10— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory TXV‡ 036-D , E CK5A/CK5BA042 35,000 NONE — 13.00 13.00 11.20 CK5A/CK5BN042 34,000 NONE — 13.00 13.00 11.20 CK5A/CK5BW036 35,0 ...

  • Bryant DELUXE 13 SEER 550A - page 11

    —11— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory TXV‡ 036-D , E COILS + 355MA V042080 V ARIABLE SPEED FURNACE CC5A/CD5AA036 35,000 TDR 13.20 — 13.20 11.65 CC5A/CD5AA042 35,000 ...

  • Bryant DELUXE 13 SEER 550A - page 12

    —12— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory TXV‡ 042-D , E COILS + 333(B,J)A V060100 V ARIABLE SPEED FURNACE CC5A/CD5AA042 40,500 TDR 13.50 — 13.50 12.05 CC5A/CD5AC048 40, ...

  • Bryant DELUXE 13 SEER 550A - page 13

    —13— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory TXV‡ 048-D , E CC5A/CD5AA060* 46,500 NONE — 13.00 13.00 11.50 CC5A/CD5AC048 45,000 NONE — 12.50 12.50 11.35 CC5A/CD5A W048 46 ...

  • Bryant DELUXE 13 SEER 550A - page 14

    —14— COMBINA TION RA TINGS Continued * T ested combination. † In most cases, only one method should be used to achie ve TDR function. Using more than one method in a system ma y cause degradation in perf ormance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a furnace equipped with TDR. Most Br yant furnaces are equipped with TD ...

  • Bryant DELUXE 13 SEER 550A - page 15

    —15— DET AILED COOLING CAP A CITIES* See notes on page 24. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** T o ...

  • Bryant DELUXE 13 SEER 550A - page 16

    —16— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant DELUXE 13 SEER 550A - page 17

    —17— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant DELUXE 13 SEER 550A - page 18

    —18— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant DELUXE 13 SEER 550A - page 19

    —19— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant DELUXE 13 SEER 550A - page 20

    —20— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant DELUXE 13 SEER 550A - page 21

    —21— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant DELUXE 13 SEER 550A - page 22

    —22— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant DELUXE 13 SEER 550A - page 23

    —23— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant DELUXE 13 SEER 550A - page 24

    —24— DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight variation in capacity may occur . † T otal and sensible capacities are net capacities . Bl ...

  • Bryant DELUXE 13 SEER 550A - page 25

    —25— CONDENSER ONL Y RA TINGS* See notes on page 26. SST °F CONDENSER ENTERING AIR TEMPERA TURES °F 55 65 75 85 95 105 115 125 550A024-D/E 30 TCG SDT KW 25.9 75.0 1.30 24.5 85.0 1.48 23.1 95.0 1.68 21.7 105.0 1.90 20.3 115.0 2.13 18.9 125.0 2.39 17.5 135.0 2.66 16.0 145.0 2.96 35 TCG SDT KW 28.7 75.0 1.28 27.1 85.0 1.46 25.6 95.0 1.66 24.1 10 ...

  • Bryant DELUXE 13 SEER 550A - page 26

    —26— CONDENSER ONL Y RA TINGS* Continued * ARI listing applies only to systems shown in Ratings and P erf or mance table. KW — T otal Po wer (Kw) SDT — Saturated T emperature Leaving Compressor (°F) SST — Saturated T emperature Entering Compressor (°F) TCG — Gross Cooling Capacity (1000 Btuh). SST °F CONDENSER ENTERING AIR TEMPERA TU ...

  • Bryant DELUXE 13 SEER 550A - page 27

    —27— MA TCHED SYSTEM A98599 SYSTEM DESIGN SUMMAR Y 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan e xter nal static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature without low-ambient operation accessory is 55°F (12.8°C). 3. Maximum outdoor operating air temperature ...

  • Bryant DELUXE 13 SEER 550A - page 28

    SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 550A.24.4 © 1999 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 —2 8— PRINTED IN U.S.A. Catalog No. 5255-002 11-99 GUIDE SPECIFICATIONS GENERAL System Description Outdoor-mounted, air-coole ...

Производитель Bryant Категория Air Conditioner

Документы, которые мы получаем от производителя устройства Bryant DELUXE 13 SEER 550A мы можем разделить на несколько групп. Это в частности:
- технические чертежи Bryant
- инструкции обслуживания DELUXE 13 SEER 550A
- паспорта изделия Bryant
- информационные брошюры
- энергетические этикетки Bryant DELUXE 13 SEER 550A
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Bryant DELUXE 13 SEER 550A.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Bryant DELUXE 13 SEER 550A, инструкции обслуживания, короткие инструкции или инструкции пользователя Bryant DELUXE 13 SEER 550A. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Bryant DELUXE 13 SEER 550A.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Bryant DELUXE 13 SEER 550A, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Bryant DELUXE 13 SEER 550A пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Bryant DELUXE 13 SEER 550A.

Полная инструкция обслуживания Bryant, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Bryant DELUXE 13 SEER 550A - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Bryant DELUXE 13 SEER 550A, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Bryant DELUXE 13 SEER 550A, которое найдем в данном документе
3. Советы по использованию основных функций устройства Bryant DELUXE 13 SEER 550A - которые должны облегчить нам первые шаги во время использования Bryant DELUXE 13 SEER 550A
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Bryant DELUXE 13 SEER 550A
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Bryant DELUXE 13 SEER 550A в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Bryant DELUXE 13 SEER 550A?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Bryant DELUXE 13 SEER 550A, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Bryant DELUXE 13 SEER 550A со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)