    The world's first EOCR with built-in ZCT (bottom hole & terminal type) will save space, time and wiring through unique development design during installation. with compact size, possible to be applied to various panel size. the protection function added for high groud fault current. most suitable for low frequency circumstance (5Hz~, Invet ...

  • Schneider Electric FBZ2 - page 4

    Applications Building Office, commercial business, residence, school, hospital Industrial facilities Petrochemical, electronic, glass, steel, semiconductor, chemical, medicine, cement, paint ...

  • Schneider Electric FBZ2 - page 5

    Public institutions Gas, water supply and drainage, airport, train, port Control power ● 24 VDC ● 85~260 VAC/DC, 50/60 Hz Composition by function ● Earth Fault ● i3BZ, iFBZ (with Modbus RS-485) ● 3BZ2, FBZ2 (without Modbus RS-485) Contact contact ● A-Type ● 95-96(b), 97-98(a) : OL ● 57-58(a) : GR ● C-Type ● 95-96(b), 97-98(a) : ...

  • Schneider Electric FBZ2 - page 6

    6 EOCR-i3BZ/iFBZ/3BZ2/FBZ2 EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT, EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT Earth fault detection by built-in ZCT Multifunctional motor protection for rated motor currents up to 80A (Definite Overcurrent protection) : Over ...

  • Schneider Electric FBZ2 - page 7

    7 EOCR-i3BZ/iFBZ/3BZ2/FBZ2 EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT, EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT Item Operating Condition & Setting Range Operation Time Over Current (oc) Load current(In) exceeds threshold(Is) Definite(Def) : 0.2~30s Adjust ...

  • Schneider Electric FBZ2 - page 8

    8 EOCR-i3BZ/iFBZ/3BZ2/FBZ2 EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT, EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT Over Current Rated Setting Range(A) Definite TCC : 0.5~80A Inverse & th TCC : 0.5~32A *** CAUTION : Do not use any external CT Under Current Ra ...

  • Schneider Electric FBZ2 - page 9

    9 EOCR-i3BZ/iFBZ/3BZ2/FBZ2 EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT, EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT Time-current characteristic cur ve 2. Definite characteristic 3. Inverse thermal characteristic (0.5~32A) 1. Inverse characteristic (0.5~32A) ...

  • Schneider Electric FBZ2 - page 10

    10 EOCR-i3BZ/iFBZ/3BZ2/FBZ2 EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT, EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT Over current and time setting tips ● Over current Setting tips in definite TCC mode 1. Over current threshold (OC) : - Set the OC at the rating ...

  • Schneider Electric FBZ2 - page 11

    11 EOCR-i3BZ/iFBZ/3BZ2/FBZ2 EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT, EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT Front face 3 phase currents (In) and the leakage current are displayed every 2 seconds in sequence. Bar graph  it shows the load factor to OC s ...

  • Schneider Electric FBZ2 - page 12

    12 EOCR-i3BZ/iFBZ/3BZ2/FBZ2 EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT, EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT L1 current display 2sec 2sec 2sec 2sec L2 current display Rotate L3 current display GF current 3 phase digital ammeter function  Blocking displ ...

  • Schneider Electric FBZ2 - page 13

    1 Password 2 Selection of Phase 3 TCC Selection 4 Frequency 5 Fail Safe Reversed Phase 6 detection 7 Over Current Threshold 8 Start Delay Time 9 Over Current Duration Under Current 10 Threshold Under Current 11 Duration Earth Fault 12 (Ground Fault) Threshold 13 Earth Fault Duration 14 EF starting Delay 15 Phase Loss 16 Phase Loss Time 17 Unbalance ...

  • Schneider Electric FBZ2 - page 14

    Threshold of Alert output, set by % of the over current threshold (oc). If the load current is higher than this value, alert output(07-08 contact) is energized according to the setting of “ ALo:XX ” . If the load current is detected, alert output(07-08 contact) is energized. The alert threshold is no meaning for this operation. Refer to the Ale ...

  • Schneider Electric FBZ2 - page 15

    15 EOCR-i3BZ/iFBZ/3BZ2/FBZ2 EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT, EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT Trip Indication Trip Indication after trip with UP/ DN button pressing Trip Cause Indication Contents of Indication L1 LED on L2 LED on L3 LED on ...

  • Schneider Electric FBZ2 - page 16

    16 EOCR-i3BZ/iFBZ/3BZ2/FBZ2 EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT, EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT Wiring Examples EOCR-i3BZ/iFBZ OL : b, GR : a EOCR-i3BZ/iFBZ OL : 1a 1b, GR : 1a 3 phase line Diagram 3 phase line Diagram 3 phase line Diagram Si ...

  • Schneider Electric FBZ2 - page 17

    17 EOCR-i3BZ/iFBZ/3BZ2/FBZ2 EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT, EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT Dimensions EOCR-i3BZ / 3BZ2 (Bottom Hole) EOCR-i3BZ / 3BZ2 (Teminal Type) 70 95 82 ∅ 4.5 6- M 4 21.4 21.4 108.1 45.3 53.3 91.3 3- ∅ 12 108.1 2 ...

  • Schneider Electric FBZ2 - page 18

    18 EOCR-i3BZ/iFBZ/3BZ2/FBZ2 EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT, EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT Order Code i3BZ Intelligent, panel mounting unit  Basic Unit iFBZ Intelligent, flush mounting unit 3BZ2 Economic, panel mounting unit FBZ2 Econ ...

  • Schneider Electric FBZ2 - page 19

    19 Communication setting value Please set the Modbus communication parameters by PCON or HMI for the communication.  Slave address  Baud rate  Parity  Communication loss timeout Slave address The EOCR has slave addresses from 1 to 247. The factory default setting is 1. Baud rate The Communication speed provided is like below.  1.2kbp ...

  • Schneider Electric FBZ2 - page 20

    20 Communication Guide The standard connection conforms to the Modbus specifications, sepecially 2 wire multidrop serial bus diagram, presented at the website of Modbus.org in 2002 (Modbus_over_serial_line_V1.pdf, Nov.2002). Simple wiring diagram is like below. The characteristics is like below in case of a direct connection to the bus. Items Conte ...

  • Schneider Electric FBZ2 - page 21

    21 Communication Guide Bus connection thr ough a SCA type junction box 1. Master (PLC, PC or communication module) 2. Modbus cable (It is different according to the master side or a master having polarization combined to the other part of Bus) 3. Junction box 4. Modbus cable 5. Line terminators : 120 Ω - 0.25W Please use a cable with 2pair shiede ...

  • Schneider Electric FBZ2 - page 22

    Built_in ZCT catalog_EN ⓒ 2009 Samwha EOCR Ltd.-All rights reserved. 04/2009 Head Office 6 th floor, Jeil Bldg., 94-46, Youngdeungpo-Dong 7Ka, Youngdeungpo-Ku, Seoul, Korea Tel. 82 2 3473 2340 / Fax 82 2 3473 1159 Iksan Plant 574, Yongie-dong, Iksan-shi, Junbuk, Korea Tel. 82 63 835 5033 / Fax 82 63 835 4175 www.eocr.com ...

Производитель Schneider Electric Категория Outboard Motor

Документы, которые мы получаем от производителя устройства Schneider Electric FBZ2 мы можем разделить на несколько групп. Это в частности:
- технические чертежи Schneider Electric
- инструкции обслуживания FBZ2
- паспорта изделия Schneider Electric
- информационные брошюры
- энергетические этикетки Schneider Electric FBZ2
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Schneider Electric FBZ2.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Schneider Electric FBZ2, инструкции обслуживания, короткие инструкции или инструкции пользователя Schneider Electric FBZ2. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Schneider Electric FBZ2.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Schneider Electric FBZ2, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Schneider Electric FBZ2 пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Schneider Electric FBZ2.

Полная инструкция обслуживания Schneider Electric, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Schneider Electric FBZ2 - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Schneider Electric FBZ2, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Schneider Electric FBZ2, которое найдем в данном документе
3. Советы по использованию основных функций устройства Schneider Electric FBZ2 - которые должны облегчить нам первые шаги во время использования Schneider Electric FBZ2
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Schneider Electric FBZ2
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Schneider Electric FBZ2 в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Schneider Electric FBZ2?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Schneider Electric FBZ2, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Schneider Electric FBZ2 со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)