    SER VICE MANUAL CONTENTS 1. TECHNICAL CHANGES ··································· 2 2. P ART NAMES AND FUNCTIONS ····················· 3 3. SPECIFICA TION ················································ 4 4. OUTLINES AND DIMENSIONS ······? ...

  • Mitsubishi Electronics MUY-GE09NA - page 2

    2 MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUY -GE09NA MUY -GE12NA MUY -GE15NA MUY -GE18NA 1. New model 1 TECHNICAL CHANGES ...

  • Mitsubishi Electronics MUY-GE09NA - page 3

    3 MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUY -GE09NA MUY -GE12NA MUY -GE15NA Air outlet Drain outlet Piping Drain hose Air inlet (back and side) MUZ-GE18NA MUY -GE18NA Piping Air outlet Drain hose Drain outlet Air inlet (back and side) 2 P ART NAMES AND FUNCTIONS ...

  • Mitsubishi Electronics MUY-GE09NA - page 4

    4 Outdoor unit model MUZ-GE09NA MUY -GE09NA MUZ-GE12NA MUY -GE12NA Capacity Rated (Minimum~Maximum) Cooling 1 Btu/h 9,000 ( 3,800 ~ 12,200 ) 9,000 ( 3,800 ~ 12,200 ) 12,000 ( 3,800 ~ 13,600 ) 12,000 ( 3,800 ~ 13,600 ) Heating 47 1 Btu/h 10,900 ( 4,500 ~ 14,100 ) — 14,400 ( 5,500 ~ 18,100 ) — Capacity Heating 17 2 Btu/h 8,700 — 1 1,200 — Pow ...

  • Mitsubishi Electronics MUY-GE09NA - page 5

    5 Outdoor unit model MUZ-GE15NA MUY -GE15NA MUZ-GE18NA MUY -GE18NA Capacity Rated (Minimum~Maximum) Cooling 1 Btu/h 14,000 ( 3,100 ~ 18,200 ) 14,000 ( 3,100 ~ 18,200 ) 17,200 ( 3,700 ~ 18,700 ) 17,200 ( 3,700 ~ 18,700 ) Heating 47 1 Btu/h 18,000 ( 4,800 ~ 20,900 ) — 21,600 ( 3,500 ~ 25,200 ) — Capacity Heating 17 2 Btu/h 15,900 — 17,200 — P ...

  • Mitsubishi Electronics MUY-GE09NA - page 6

    6 T est condition ARI Mode T est Indoor air condition (°F) Outdoor air condition (°F) Dry bulb W et bulb Dry bulb Wet bulb SEER (Cooling) "A-2" Cooling Steady State at rated compressor Speed 80 67 95 (75) "B-2" Cooling Steady State at rated compressor Speed 80 67 82 (65) "B-1" Cooling Steady State at minimum compress ...

  • Mitsubishi Electronics MUY-GE09NA - page 7

    7 Unit: inch MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUY -GE09NA MUY -GE12NA MUY -GE15NA Liquid pipe :1/4 (flared) Gas pipe :3/8 (flared) (GE09/12) 1/2 (flared) (GE15) 6-23/32 2 5-7/8 2-23/32 1-3/4 15-3/4 12 ~ 12-3/4 13-9/16 11 / 1 6 1-9/16 7/8 21-5/8 1 1-1/32 13/32 31-1/2 19-1 1/16 5-15/16 1 1-29/32 17/32 29/32 1 1-1/4 Air in handle Air in Air out 2- 3/8 ...

  • Mitsubishi Electronics MUY-GE09NA - page 8

    8 MUZ-GE09NA MUZ-GE12NA 5 WIRING DIAGRAM MUY -GE09NA MUY -GE12NA ...

  • Mitsubishi Electronics MUY-GE09NA - page 9

    9 MUZ-GE15NA MUY -GE15NA ...

  • Mitsubishi Electronics MUY-GE09NA - page 10

    10 MUZ-GE18NA MUY -GE18NA ...

  • Mitsubishi Electronics MUY-GE09NA - page 11

    11 Unit: inch MUZ-GE09NA MUY -GE09NA Outdoor heat exchanger Flared connection Defrost thermistor RT6 1 ( MUZ ) Discharge temperature thermistor RT6 2 Flared connection Stop valve (with strainar) Stop valve (with service port) Refrigerant flow in cooling Compressor 4-way valve Refrigerant flow in heating ( MUZ ) Refrigerant pipe ø3/8 (with heat ins ...

  • Mitsubishi Electronics MUY-GE09NA - page 12

    12 MUZ-GE18NA MUY -GE18NA Outdoor heat exchanger Flared connection Defrost thermistor RT6 1 ( MUZ ) Discharge temperature thermistor RT6 2 Flared connection Stop valve (with strainar) Stop valve (with service port) Capillary tube O.D. 0.142 × I.D. 0.094 × 1-31/32 ( ø 3.6 × ø 2.4 × 50 ) Refrigerant flow in cooling Compressor 4-way valve Refrig ...

  • Mitsubishi Electronics MUY-GE09NA - page 13

    13 ADDITIONAL REFRIGERANT CHARGE (R410A: oz.) Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation. Model Outdoor unit precharged Refrigerant piping length (one way): ft. 25 30 40 50 60 65 MUZ-GE09NA MUY -GE09NA 1 lb. 12 oz. 0 1.62 4.86 8.10 1 1.34 12.96 MUZ-GE12NA MUY -GE12NA 2 lb. 9 oz. MUZ-GE15N ...

  • Mitsubishi Electronics MUY-GE09NA - page 14

    14 2) COOLING CAP ACITY CORRECTIONS Refrigerant piping length (one way: ft.) 25 (std.) 40 65 MUZ-GE09NA MUY -GE09NA MUZ-GE12NA MUY -GE12NA MUZ-GE15NA MUY -GE15NA MUZ-GE18NA MUY -GE18NA 1.0 0.954 0.878 3) HEA TING CAP ACITY (MUZ) Model Indoor air Outdoor intake air WB temperature ( ˚ F) IDB ( ˚ F) 5 1 52 53 54 34 55 5 TC TPC TC TPC TC TPC TC TPC T ...

  • Mitsubishi Electronics MUY-GE09NA - page 15

    15 65 70 75 75 70 65 15 14 13 12 11 10 9 8 7 6 5 Indoor intake air DB tem perature (°F) = 413 CFM Airflow 15 52 5 3 5 4 5 5 5 6 5 7 0 Outdoor intake air WB temperature (°F) 0.4 0.6 0.8 1.0 Ind oor intake air DB temperature (°F) T otal power consumption (kW) T otal capacity (1 0 3 Btu/h) This value of frequency is not the same as the actual frequ ...

  • Mitsubishi Electronics MUY-GE09NA - page 16

    16 7-3. CONDENSING PRESSURE Cooling Data is based on the condition of indoor humidity 50 %. Air flow should be set to High speed. MUZ-GE12NA MUY -GE12NA MUZ-GE09NA MUY -GE09NA 68 70 75 80 85 90 95 100 105 (°F) 120 140 160 180 200 (PSIG) (PSIG) 68 70 75 80 85 90 95 100 105 (°F) 280 320 360 400 440 Condensing pressure 86 80 75 70 Suction pressure O ...

  • Mitsubishi Electronics MUY-GE09NA - page 17

    17 5 1 52 53 54 55 56 5 7 5 (°F) 5 1 52 53 54 55 56 5 7 5 (°F) 60 85 11 0 135 160 185 210 220 245 270 295 320 345 370 Indoor DB temperature (°F) Condensing pressure Outdoor ambient temperature (PSIG) (PSIG) 75 70 65 58Hz Indoor DB temperature (°F) Suction pressure Outdoor ambient temperature 75 70 65 58Hz Heating (MUZ) Data is based on the cond ...

  • Mitsubishi Electronics MUY-GE09NA - page 18

    18 MUZ-GE18NA MUZ-GE15NA 5 1 52 53 54 55 56 5 7 5 (°F) 5 1 52 53 54 55 56 5 7 5 (°F) 60 85 11 0 135 160 185 210 260 296 332 368 404 440 Indoor DB temperature (°F) Condensing pressure Outdoor ambient temperature (PSIG) (PSIG) 75 70 65 54Hz Indoor DB temperature (°F) Suction pressure Outdoor ambient temperature 75 70 65 54Hz 5 1 52 53 54 55 56 5 ...

  • Mitsubishi Electronics MUY-GE09NA - page 19

    19 7-4. ST ANDARD OPERA TION DA T A Model MSZ-GE09NA MSY -GE09NA MSZ-GE09NA MSZ-GE12NA MSY -GE12NA MSZ-GE12NA Item Unit Cooling Heating Cooling Heating T otal Capacity Btu/h 9,000 10,900 12,000 14,400 SHF - 0.82 — 0.74 — Input kW 0.660 0.760 0.960 1.170 Rated frequency Hz 59.5 77.5 69.0 77.0 Electrical circuit Indoor unit MSZ-GE09NA, MSY -GE09N ...

  • Mitsubishi Electronics MUY-GE09NA - page 20

    20 Model MSZ-GE15NA MSY -GE15NA MSZ-GE15NA MSZ-GE18NA MSY -GE18NA MSZ-GE18NA Item Unit Cooling Heating Cooling Heating To t a l Capacity Btu/h 14,000 18,000 17,200 21,600 SHF - 0.80 — 0.71 — Input kW 1.080 1.600 1.640 1.900 Rated frequency Hz 55.5 74.0 83.0 84.0 Electrical circuit Indoor unit MSZ-GE15NA, MSY -GE15NA MSZ-GE18NA, MSY -GE18NA Powe ...

  • Mitsubishi Electronics MUY-GE09NA - page 21

    21 7-5. CAP ACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY Capacity correction factors Input correction factors Input correction factors Capacity correction factors Correction of Cooling capacity The operational frequency of compressor Correction of Cooling total input The operational frequency of compressor Correction of Heating total inp ...

  • Mitsubishi Electronics MUY-GE09NA - page 22

    22 MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUY -GE09NA MUY -GE12NA MUY -GE15NA MUY -GE18NA 8-2. R.V . COIL CONTROL (MUZ) Heating . . . . . . . . . . . . . . . . . ON Cooling . . . . . . . . . . . . . . . . . OFF Dry . . . . . . . . . . . . . . . . . . . . OFF NOTE : The 4-way valve reverses for 5 seconds right before start-up of the compressor ...

  • Mitsubishi Electronics MUY-GE09NA - page 23

    23 9-1. CHANGE IN DEFROST SETTING (MUZ) Changing defrost finish temperature <JS> T o change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P .C. board. (Refer to 10-6-1.) Jumper Defrost fi nish temperature MUZ-GE09/12/15 MUZ-GE18 JS Soldered (Initial setting) 41°F (5°C) 48°F (9°C) None (Cut) 50°F (10°C) ...

  • Mitsubishi Electronics MUY-GE09NA - page 24

    24 Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled. 10-2. F AILURE MODE RECALL FUNCTION 1. Flow chart of failure mode recall function for the indoor/outdoor ...

  • Mitsubishi Electronics MUY-GE09NA - page 25

    25 2. Flow chart of the detailed outdoor unit failure mode recall function 2.Blinking pattern when outdoor unit is abnormal: ON OFF No beep Beeps Repeated cycle 2.5-second OFF 3-second ON Blinking at 0.5- second interval No beep Beeps Repeated cycle 2.5-second OFF 3-second ON Blinking at 0.5- second interval Repeated cycle Does the upper lamp of OP ...

  • Mitsubishi Electronics MUY-GE09NA - page 26

    26 3. Outdoor unit failure mode table POWER lamp (Indoor unit) Abnormal point (Failure mode / protection) LED indication (Outdoor P .C. board) Condition Remedy Indoor/ outdoor unit failure mode recall function Outdoor unit failure mode recall function OFF None (Normal) —— — — — 2-time fl ash 2.5 seconds OFF Outdoor power system — Overc ...

  • Mitsubishi Electronics MUY-GE09NA - page 27

    27 10-3. TROUBLESHOOTING CHECK T ABLE No. Symptom LED indication Abnormal point/ Condition Condition Remedy 1 Outdoor unit does not oper- ate. 1-time fl ash every 2.5 seconds Outdoor power sys- tem Overcurrent protection stop is continuously performed 3 times within 1 minute after the compressor gets started, or failure of re- start of compressor ...

  • Mitsubishi Electronics MUY-GE09NA - page 28

    28 10-4. TROUBLE CRITERION OF MAIN P ARTS MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUY -GE09NA MUY -GE12NA MUY -GE15NA MUY -GE18NA Part name Check method and criterion Figure Defrost thermistor (RT61) (MUZ) Fin temperature thermistor (RT64) Ambient temperature thermistor (RT65) Outdoor heat exchanger temperature thermistor (RT68) Measure the res ...

  • Mitsubishi Electronics MUY-GE09NA - page 29

    29 10-5. TROUBLESHOOTING FLOW Are the voltages balanced? Disconnect the connector (CN61) between compressor and the intelligent power module (IPM). Replace the inverter P .C. board. Check the voltage between terminals. Check the compressor . See 10-5. “Check of compressor”. No Ye s See 10-5. “Check of open phase”. ● With the connector bet ...

  • Mitsubishi Electronics MUY-GE09NA - page 30

    30 F Check of compressor start failure D Check of compressor winding E Check of compressor operation time ● Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance be- tween the compressor terminals. <<Measurement point>> at 3 points BLK - WHT BLK - RED WHT - RED <<Judgemen ...

  • Mitsubishi Electronics MUY-GE09NA - page 31

    31 Is the resistance of thermistor normal? (Refer to 10-6.1.) Reconnect the connector of thermistor . T urn ON the power supply and press EMERGENCY OPERA TION switch. No Replace the thermistor except RT64. When R T64 is abnormal, replace the inverter P .C. board. Does the unit operate for 10 minutes or more without showing thermistor abnormality? O ...

  • Mitsubishi Electronics MUY-GE09NA - page 32

    32 I Check of outdoor fan motor Is the resistance of outdoor fan motor normal? (Refer to 10-4.) Replace the outdoor fan motor . Replace the inverter P .C. board. No Ye s Disconnect CN932 from the inverter P .C. board, and measure the resistance of the outdoor fan motor . MUZ-GE09/12/15NA MUY -GE09/12/15NA Is the resistance between each ter- minal o ...

  • Mitsubishi Electronics MUY-GE09NA - page 33

    33 J Check of power supply Is there voltage 208/230 V AC between the indoor terminal block S1 and S2? No Ye s Replace the indoor electronic control P .C. board. Rectify indoor/outdoor connecting wire. Ye s If light up, OK. If fl ash, refer to 10-3. Does The upper lamp of OPERA TION INDICA TOR lamp on the indoor unit light up? Dose LED on the inver ...

  • Mitsubishi Electronics MUY-GE09NA - page 34

    34 Press OPERA TE/ST OP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1 Expansion valve operates in full-opening direction. OK. NOTE : After check of LEV , do the undermentioned operations. 1. T urn OFF the power supply and turn ON it again. 2. Press RESET butt ...

  • Mitsubishi Electronics MUY-GE09NA - page 35

    35 L Check of inverter P .C. board Check the outdoor fan motor . (Refer to 10-5. .) Is the fuse (F901) blown on the in- verter P .C. board? Check the connection of the connectors (CN931, CN932) of the outdoor fan motor . If the connection is poor , make it correct. Operate the outdoor unit by starting EMERGENCY OPERA TION. Check the LED indication ...

  • Mitsubishi Electronics MUY-GE09NA - page 36

    36 M How to check miswiring and serial signal error T urn OFF inverter-controlled lighting equipment. T urn OFF the power supply and then turn ON again. Press EMERGENCY OPERA TION switch. • • • A Is serial signal error indicated 6 minutes later? B Ye s Reinstall either the unit or the light away from each other . Attach a fi lter on remote c ...

  • Mitsubishi Electronics MUY-GE09NA - page 37

    37 N Electromagnetic noise enters into TV sets or radios Ye s Is the unit grounded? No Ground the unit. Ye s Is the distance between the antennas and the indoor unit within 9.91 ft., or is the distance between the antennas and the outdoor unit within 9.91 ft.? No Extend the distance between the antennas and the indoor unit, and/or the antennas and ...

  • Mitsubishi Electronics MUY-GE09NA - page 38

    38 -4 14 32 50 68 86 104 0 10 20 30 40 50 60 70 80 90 100 T emperature(°F) Defrost thermistor(RT61) (MUZ) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68) T emperature(°F) Discharge temperature thermistor(RT62) 32 50 68 86 104 122 140 158 176 194 212 230 248 0 100 200 300 400 500 600 700 32 50 68 86 104 122 ...

  • Mitsubishi Electronics MUY-GE09NA - page 39

    39 -4 14 32 50 68 86 104 0 10 20 30 40 50 60 70 80 90 100 T emperature(°F) Defrost thermistor(RT61) (MUZ) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68) T emperature(°F) Discharge temperature thermistor(RT62) 32 50 68 86 104 122 140 158 176 194 212 230 248 0 100 200 300 400 500 600 700 32 50 68 86 104 122 ...

  • Mitsubishi Electronics MUY-GE09NA - page 40

    40 1 1-1. MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUY -GE09NA MUY -GE12NA MUY -GE15NA NOTE : T urn OFF power supply before disassembling. OPERA TING PROCEDURE PHOTOS 1. Removing the cabinet (1) Remove the screw fixing the service panel. (2) Pull down the service panel and remove it. (3) Remove the screws fixing the conduit cover . (4) Remove the conduit c ...

  • Mitsubishi Electronics MUY-GE09NA - page 41

    41 OPERA TING PROCEDURE PHOT OS 2. Removing the inverter assembly , inverter P .C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P .C. board> CN721 (R.V . coil) (MUZ) CN931, CN932 (Fan motor) CN641 (Defrost thermistor (MUZ) and discharge tempera- ture ...

  • Mitsubishi Electronics MUY-GE09NA - page 42

    42 OPERA TING PROCEDURE PHOT OS 5. Removing outdoor fan motor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P .C. board> CN931, CN932 (Fan motor) (3) Remove the propeller nut. (Photo 7) (4) Remove the propeller . (Photo 7) (5) Remove the screws fixing the fan motor . (Photo 7) (6) Remove t ...

  • Mitsubishi Electronics MUY-GE09NA - page 43

    43 1 1-2. MUZ-GE18NA MUY -GE18NA NOTE: T urn OFF power supply before disassembling. OPERA TING PROCEDURE PHOT OS 1. Removing the cabinet (1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover . (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover . (7 ...

  • Mitsubishi Electronics MUY-GE09NA - page 44

    44 OPERA TING PROCEDURE PHOT OS 2. Removing the inverter assembly , inverter P .C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con- nectors: <Inverter P .C. board> CN721 (R.V .coil) (MUZ) CN931, CN932 (Fan motor) CN641 (Defrost thermistor (MUZ) and discharge temperature ...

  • Mitsubishi Electronics MUY-GE09NA - page 45

    45 Ambient tem- perature thermistor Outdoor heat exchanger tempera- ture thermistor Defrost thermistor OPERA TING PROCEDURE PHOTOS 4. Removing the discharge temperature thermistor , defrost thermistor , outdoor heat exchanger tempera- ture thermistor and ambient temperature thermistor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect ...

  • Mitsubishi Electronics MUY-GE09NA - page 46

    46 ...

  • Mitsubishi Electronics MUY-GE09NA - page 47

    47 ...

  • Mitsubishi Electronics MUY-GE09NA - page 48

    HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAP AN © Copyright 2009 MITSUBISHI ELECTRIC CO.,L TD Distributed in Jul. 2009. No. OBH 549 5 Made in Japan New publication, effective Jul. 2009 Specifications subject to change without notice. TM ...

Производитель Mitsubishi Electronics Категория Air Conditioner

Документы, которые мы получаем от производителя устройства Mitsubishi Electronics MUY-GE09NA мы можем разделить на несколько групп. Это в частности:
- технические чертежи Mitsubishi Electronics
- инструкции обслуживания MUY-GE09NA
- паспорта изделия Mitsubishi Electronics
- информационные брошюры
- энергетические этикетки Mitsubishi Electronics MUY-GE09NA
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Mitsubishi Electronics MUY-GE09NA.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Mitsubishi Electronics MUY-GE09NA, инструкции обслуживания, короткие инструкции или инструкции пользователя Mitsubishi Electronics MUY-GE09NA. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Mitsubishi Electronics MUY-GE09NA.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Mitsubishi Electronics MUY-GE09NA, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Mitsubishi Electronics MUY-GE09NA пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Mitsubishi Electronics MUY-GE09NA.

Полная инструкция обслуживания Mitsubishi Electronics, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Mitsubishi Electronics MUY-GE09NA - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Mitsubishi Electronics MUY-GE09NA, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Mitsubishi Electronics MUY-GE09NA, которое найдем в данном документе
3. Советы по использованию основных функций устройства Mitsubishi Electronics MUY-GE09NA - которые должны облегчить нам первые шаги во время использования Mitsubishi Electronics MUY-GE09NA
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Mitsubishi Electronics MUY-GE09NA
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Mitsubishi Electronics MUY-GE09NA в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Mitsubishi Electronics MUY-GE09NA?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Mitsubishi Electronics MUY-GE09NA, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Mitsubishi Electronics MUY-GE09NA со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)