    GPC 14 SEER R-410A Package Air Conditioners with R-410A Copyright © 2009 - 2010 Goodman Manufacturing Company, L.P. RT6322007r6 September 2010 **Note that these tax credits are subject to specific requirements set forth in the American Recovery and Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman recommends that consumers consult ...

  • Goodman Mfg RS6300011 - page 2

    PRODUCT IDENTIFICA TION 2 The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure ...

  • Goodman Mfg RS6300011 - page 3

    PRODUCT IDENTIFICA TION 3 The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. GPC1424H41AA GPC1430H41AA GPC1436H41AA GPC1442H41AA GPC1448H41AA GPC1460H41AA The United States Environmental Protection Agency (“EPA”) ...

  • Goodman Mfg RS6300011 - page 4

    4 PRODUCT DESIGN GPC Package Cooling Units are designed for outdoor instal- lations only in either residential or light commercial applica- tions. The connecting ductwork (Supply and Return) can be con- nected for either horizontal or vertical airflow. In the vertical application a matching Roof Curb is recommended. A return air filter must be inst ...

  • Goodman Mfg RS6300011 - page 5

    PRODUCT DESIGN 5 36" 36" 24" P L E N U M U N I T P L A T F O R M C U R B Rooftop Installation - Horizontal (H) In installations where the unit is installed above ground level and not serviceable from the ground (Example: Roof Top in- stallations), the installer must provide service platform for ser- vice person with rails or guards i ...

  • Goodman Mfg RS6300011 - page 6

    6 PRODUCT DIMENSIONS GPC14[24-60]H41A* Ch ass i s M o d el A B GPC 142 4 33 3 0½ GPC 143 0 33 3 0½ GPC 143 6 33 3 5½ GPC 144 2 33 3 5½ GPC 144 8 33 3 8½ GPC 146 0 33 3 8½ Dime n s ion s in i n c he s La rge Sm a l l Me d i u m 34.075 66.5 42 4. 51 2 14 . 0 00 14 . 0 00 SUP PLY 6.50 0 RE TU RN 4.500 BACK VI EW (DUC T OPEN I NGS) A 14 . 0 00 B ...

  • Goodman Mfg RS6300011 - page 7

    PRODUCT DESIGN 7 HKR ELECTRICAL DA T A All wires and overcurrent protection devices are sized for use with electric heaters only and without refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent protection du ...

  • Goodman Mfg RS6300011 - page 8

    ACCESSORIES 8 GPC14[24-60]H41A* P ar t N u mb er D esc ri p t i o n O T 18- 60 A O utdoor T her mos ta t Ki t w /Loc ko ut S tat O T /E HR 18 - 60 E me r gen c y Heat Relay Ki t HK R E l ec tr i c Heat K i t P CCP1 01 -103 Roof Cur b P C P101 - 103 Downflow P l enum K i t P C P101 - 103R8 Downfl ow P l enum K i t w / R - 8 Ins ul ation G PCE D1 01- ...

  • Goodman Mfg RS6300011 - page 9

    BLOWER PERFORMANCE DA T A 9 Dry Coil Data GPC14[24-60]H41A* 0. 1 0 .2 0 .3 0 .4 0 .5 0 .6 0 . 7 0 . 8 C F M 9 34 75 9 75 5 63 8 58 1 4 8 9 - - W A T T S 9 57 77 67 38 39 0 - - C F M 9 90 83 7 80 1 74 4 69 6 6 5 2 6 0 1 - W ATT S 1 07 9 4 10 5 11 0 1 1 9 1 3 3 14 2 - C F M 106 1 9 89 9 47 9 25 8 76 - - - W ATT S 1 26 1 3 4 14 6 15 8 16 9 - - - C F M ...

  • Goodman Mfg RS6300011 - page 10

    10 BLOWER PERFORMANCE DA T A 30 40 50 60 70 80 90 11 0 1 2 0 100 13 0 14 0 15 0 100 90 80 70 60 50 40 30 20 10 OUT P UT B TU/ H R x 10 00 BT U OUTPUT vs TEMPER AT URE RISE CHART TEMPERAT URE RISE 600 C FM 700 900 1000 1100 1200 140 0 160 0 1800 2000 220 0 240 0 C F M FORMULA S BTU OUTPUT = CFM x 1.08 x RISE RISE = BTU OUTPUT 1.0 8 ÷ CF M 800 ...

  • Goodman Mfg RS6300011 - page 11

    P ACKAGE COOLING SPECIFICA TIONS 11 GPC14[24-30]H41AA IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters. (1) Maximum Overcurrent Protection D ...

  • Goodman Mfg RS6300011 - page 12

    P ACKAGE COOLING SPECIFICA TIONS 12 GPC14[36-42]H41AA IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters. (1) Maximum Overcurrent Protection D ...

  • Goodman Mfg RS6300011 - page 13

    P ACKAGE COOLING SPECIFICA TIONS 13 IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters. (1) Maximum Overcurrent Protection Device: MUST use Ti ...

  • Goodman Mfg RS6300011 - page 14

    14 COOLING PERFORMANCE DA T A GPC1424H41AA MOD E L : G P C 1424H41A * EX PAN DE D P ER FO R MANC E D ATA C OOL I NG OP E R AT I ON De s ign Sub c ooli ng , 9 ± 2°F @ the l i qui d a c c e s s fitting c onn e ct i on A HRI 9 5 te s t c ondi t io ns . Desi gn S upe r he at 5 ± 2 °F @ the c om pr es sor s uct i o n a cce ss fi tti n g co n nect io ...

  • Goodman Mfg RS6300011 - page 15

    15 COOLING PERFORMANCE DA T A GPC1424H41AA MOD E L : G PC 1424H41A * EX PA N DE D P ER F O R M AN C E D AT A C OOL I NG OP ER AT I ON De s i gn Sub cooli ng , 9 ± 2°F @ the l i qui d acce s s f i tting c onn e ct i on A HRI 9 5 te s t c ondi t i ons . De s i gn S upe r he at 5 ± 2 °F @ the c om pr es sor s u cti on a cce ss fi t ti ng co n nect ...

  • Goodman Mfg RS6300011 - page 16

    16 COOLING PERFORMANCE DA T A GPC1430H41AA MOD E L : G P C 1430H41A * EX PAN DE D P ER F O R M AN C E D ATA C OOLI NG OP ER ATI ON De s i gn S ubc ooli ng , 1 0 ± 2 °F @ the l i qui d a c ce s s f i tting c onnec tion A RI 9 5 test c ondi tio ns . De s i g n S up e rh e at 1 0 ± 2 °F @ the c o m p r es sor sucti o n acc ess f itt i n g co n n e ...

  • Goodman Mfg RS6300011 - page 17

    17 COOLING PERFORMANCE DA T A GPC1430H41AA MOD E L : G PC 1430H41A * EX PA N DE D P ER F O R M AN C E D AT A C OOL I NG OP ER AT I ON De s ign S ubc ool i ng , 1 0 ± 2 °F @ the l i qui d a c ce s s f i tting c onne ct i on A R I 9 5 t e st conditio ns . De s i g n Sup e rh e at 1 0 ± 2 °F @ the c o m p r es so r suct i o n acc ess f itt i n g c ...

  • Goodman Mfg RS6300011 - page 18

    18 COOLING PERFORMANCE DA T A GPC1436H41AA MOD E L : G P C 1436H41A * EX PAN DE D P ER F O R M AN C E D ATA C OOLI NG OP ER ATI ON De s i gn Sub cooli ng , 10 ± 2 °F @ t he l iqui d a cc e ss fitting con ne c t i on A RI 95 te st c onditi ons. De s i gn S uperhe at 9 ± 2 °F @ t he c omp r e ssor su cti o n acc ess f it ti n g co n n e cti o n . ...

  • Goodman Mfg RS6300011 - page 19

    19 COOLING PERFORMANCE DA T A GPC1436H41AA MOD E L : G PC 1436H41A * EX PA N DE D P ER F O R M AN C E D AT A C OOL I NG OP ER AT I ON De s i gn Sub cooli ng , 10 ± 2 °F @ t he l iqui d a cc e ss fitting con ne c t i on A RI 95 te st cond i tions. De sign S uperhe at 9 ± 2 °F @ t he c omp r e ssor su cti o n acc ess f it ti n g co n n e cti o n ...

  • Goodman Mfg RS6300011 - page 20

    20 COOLING PERFORMANCE DA T A GPC1442H41AA MOD E L : G P C 1442H 41A * EX PAN DE D P ER FO R M ANC E D AT A C OOLI NG OP E R ATION Desi g n Su b co o l i n g , 8 ± 2 ° F @ th e l i q u i d acc ess f it ti ng co n n e cti o n A H R I 9 5 test c o n d i t i o n s. D esi g n Su p er h ea t 8 ± 2 ° F @ t h e co m p re sso r su ct io n ac ces s fi t ...

  • Goodman Mfg RS6300011 - page 21

    21 COOLING PERFORMANCE DA T A GPC1442H41AA MOD E L : G PC 1442H41A * EX PA N DE D P ER F O R M AN C E D AT A C OOL I NG OP ER AT I ON Desi g n Su b co o l i n g, 8 ± 2 ° F @ th e l iqu i d acc ess f it ti n g co n n e ct i o n A HR I 9 5 t est c o n d i t i o n s. D esi g n Su p er h ea t 8 ± 2 ° F @ t h e co m pr e s s or suc t i on acce s s f ...

  • Goodman Mfg RS6300011 - page 22

    22 COOLING PERFORMANCE DA T A GPC1448H41AA MOD E L : G P C 1448H41A * EX PAN DE D P ER F O R M AN C E D ATA C OOLI NG OP ER ATI ON De s i gn Sub cooli ng , 10 ± 2 °F @ the l i qui d a c ce s s f i tting c onne c tion A HRI 95 te s t c ondi ti ons . Desi gn S u pe r he at 1 0 ± 2 °F @ t he c ompr e ss or suc tion ac c es s fi t ti n g c onne c t ...

  • Goodman Mfg RS6300011 - page 23

    23 COOLING PERFORMANCE DA T A GPC1448H41AA MOD E L : G PC 1448H41A * EX PA N DE D P ER F O R M AN C E D AT A C OOL I NG OP ER AT I ON De s i gn Sub cooli ng , 10 ± 2 °F @ the l i qui d acce s s f i tting c onnec tion A HRI 95 te s t c ondi ti ons . Desi gn S u pe r he a t 10 ± 2 ° F @ t he c o mpr e ss or suc tion a c c e s s fi t tin g c onne ...

  • Goodman Mfg RS6300011 - page 24

    24 COOLING PERFORMANCE DA T A GPC1460H41AA MOD E L : G P C 1460H41A * EX PAN DE D P ER F O R M AN C E D ATA C OOLI NG OP ER ATI ON Desi g n Su b co o l i n g, 6 ± 2 ° F @ th e l iqu i d acc ess f it ti n g co n n e cti o n A H R I 9 5 t est c on d i t i o n s. D esi g n Su p er h ea t 9 ± 2° F @ th e co m p re s s or s uct io n a cc e s s fit t ...

  • Goodman Mfg RS6300011 - page 25

    25 COOLING PERFORMANCE DA T A GPC1460H41AA MOD E L : G PC 1460H41A * EX PA N DE D P ER F O R M AN C E D AT A C OOL I NG OP ER AT I ON De s i gn Sub cooli ng , 6 ± 2 °F @ the l i quid ac c es s fi t t i n g co nne c tion AH RI 9 5 t e s t c ond iti ons. De sign S upe r hea t 9 ± 2 °F @ the c ompre s s or sucti o n a c ce s s f itting c onne c ti ...

  • Goodman Mfg RS6300011 - page 26

    26 COOLING PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures incr ...

  • Goodman Mfg RS6300011 - page 27

    WIRING DIAGRAMS 27 WARN I NG HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT . MULTI PLE POWE R S OUR CES MAY B E PRESENT . F AILURE TO DO SO MAY CAUSE PROPERTY DAM AGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. GPC14[24-60]H41AA ...

  • Goodman Mfg RS6300011 - page 28

    28 GPC 14 SEER R-410A 5mm Package Air Conditioners GPC Package Cooling Units are designed for outdoor instal- lations only in either residential or light commercial applica- tions. The connecting ductwork (Supply and Return) can be con- nected for either horizontal or vertical airflow. In the vertical application a matching Roof Curb is recommended ...

  • Goodman Mfg RS6300011 - page 29

    PRODUCT DESIGN 29 Location and Clearances NOTE: To ensure proper condensate drainage, unit must be installed in a level position. 36" 36" 10" UNIT WALL 36" Outside Slab Installation - Horizontal (H) Minimum clearances are required to avoid air recirculation and keep the unit operating at peak efficiency. 36" 36" 24&quo ...

  • Goodman Mfg RS6300011 - page 30

    P ACKAGE COOLING SPECIFICA TIONS 30 IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters. (1) Maximum Overcurrent Protection Device: MUST use Ti ...

  • Goodman Mfg RS6300011 - page 31

    P ACKAGE COOLING SPECIFICA TIONS 31 IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters. (1) Maximum Overcurrent Protection Device: MUST use Ti ...

  • Goodman Mfg RS6300011 - page 32

    32 COOLING PERFORMANCE DA T A GPC1424H41AB 5MM COILS MOD E L : G P C 1424H41A * EX PAN DE D P ER F O R M AN C E D ATA C OOLI NG OP ER ATI ON O ut d o o r A m b i en t T em p er atu r e 65 75 8 5 95 10 5 115 E n t eri n g In d o o r W e t B u lb T em p e r at u r e I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 7 ...

  • Goodman Mfg RS6300011 - page 33

    33 COOLING PERFORMANCE DA T A GPC1424H41AB 5MM COILS MOD E L : G P C 1424H41A * EX PAN DE D P ER F O R M AN C E D ATA C OOL ING OP E R AT ION O ut d o o r A m b i en t T em p er atu r e 65 75 8 5 95 10 5 115 E n t e ri n g In d o or W e t B u lb T em p e r at u r e I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 ...

  • Goodman Mfg RS6300011 - page 34

    34 COOLING PERFORMANCE DA T A GPC1430H41AB 5MM COILS MOD E L : G P C 1430H41A * EX PAN DE D P ER F O R MANC E D ATA C OOLING OP ER ATION Ou t doo r A m bi en t Te mpera ture 65 75 8 5 95 10 5 115 E nte r i ng I nd oor We t Bulb T e m pe r a ture I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 6 36 77 1 MB ...

  • Goodman Mfg RS6300011 - page 35

    35 COOLING PERFORMANCE DA T A GPC1430H41AB 5MM COILS MOD E L : G P C 1430H41A * EX PAN DE D P ER F O R M AN C E D ATA C OOL ING OP E R AT ION O ut d o o r A m b i en t T em p er atu r e 65 75 8 5 95 10 5 115 E n t e ri n g In d o or W e t B u lb T em p e r at u r e I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 ...

  • Goodman Mfg RS6300011 - page 36

    36 COOLING PERFORMANCE DA T A GPC1436H41AB 5MM COILS MOD E L : G P C 1436H 41A * EX PAN DE D P ER FO R M ANC E D AT A C OOLI NG OP E R ATION O u t doo r A m bi ent Te mpera ture 65 75 8 5 95 10 5 115 E nte r ing I nd oor We t Bulb T e m pe r a ture I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 6 36 77 1 ...

  • Goodman Mfg RS6300011 - page 37

    37 COOLING PERFORMANCE DA T A GPC1436H41AB 5MM COILS MOD E L : G PC1436H41A * EX PA NDE D P ER FO R M AN C E D ATA C OOL ING OPER ATION O ut d o or A m b i en t T em p er atu r e 65 75 8 5 95 10 5 115 E nt eri ng In d oo r W et B ulb T em p er atu re I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 6 36 7 ...

  • Goodman Mfg RS6300011 - page 38

    38 COOLING PERFORMANCE DA T A GPC1442H41AB 5MM COILS MOD E L : G P C 1442H41A * EX PAN DE D P ER F O R M AN C E D ATA C OOLI NG OP ER ATI ON O ut d o o r A m b i en t T em p er atu r e 65 75 8 5 95 10 5 115 E n t eri n g In d o o r W e t B u lb T em p e r at u r e I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 7 ...

  • Goodman Mfg RS6300011 - page 39

    39 COOLING PERFORMANCE DA T A GPC1442H41AB 5MM COILS MOD E L : G P C 1442H41A * EX PAN DE D P ER F O R M ANC E D ATA C OOLIN G OPE R A TION Ou t doo r A mbi e nt Te m pera ture 65 75 8 5 95 10 5 115 E nte r i ng I nd oor Wet Bulb T e m pe r a ture I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 6 36 77 1 ...

  • Goodman Mfg RS6300011 - page 40

    40 COOLING PERFORMANCE DA T A GPC1448H41AB 5MM COILS MOD E L : G P C 1448H41A B EX PA N DE D P ER FO R MANC E D ATA C OOLI NG OP ER ATI ON O ut d o o r A m b i en t T em p er atu r e 65 75 8 5 95 10 5 115 E n t eri n g In d o o r W e t B u lb T em p e r at u r e I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 ...

  • Goodman Mfg RS6300011 - page 41

    41 COOLING PERFORMANCE DA T A GPC1448H41AB 5MM COILS MOD E L : G P C 1448H41A B EX PA N DE D P ER F O R M AN C E D ATA C OOL ING OP ER ATI ON O ut d o o r A m b i en t T em p er atu r e 65 75 8 5 95 10 5 115 E n t e ri n g In d o o r W et B u lb T em p er at u re I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 ...

  • Goodman Mfg RS6300011 - page 42

    42 COOLING PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures incr ...

  • Goodman Mfg RS6300011 - page 43

    WIRING DIAGRAMS 43 WARN I NG HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT . MULTI PLE POWE R S OUR CES MAY B E PRESENT . F AILURE TO DO SO MAY CAUSE PROPERTY DAM AGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. GPC14[24-48]H41AB ...

Производитель Goodman Mfg Категория Air Conditioner

Документы, которые мы получаем от производителя устройства Goodman Mfg RS6300011 мы можем разделить на несколько групп. Это в частности:
- технические чертежи Goodman Mfg
- инструкции обслуживания RS6300011
- паспорта изделия Goodman Mfg
- информационные брошюры
- энергетические этикетки Goodman Mfg RS6300011
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Goodman Mfg RS6300011.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Goodman Mfg RS6300011, инструкции обслуживания, короткие инструкции или инструкции пользователя Goodman Mfg RS6300011. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Goodman Mfg RS6300011.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Goodman Mfg RS6300011, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Goodman Mfg RS6300011 пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Goodman Mfg RS6300011.

Полная инструкция обслуживания Goodman Mfg, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Goodman Mfg RS6300011 - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Goodman Mfg RS6300011, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Goodman Mfg RS6300011, которое найдем в данном документе
3. Советы по использованию основных функций устройства Goodman Mfg RS6300011 - которые должны облегчить нам первые шаги во время использования Goodman Mfg RS6300011
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Goodman Mfg RS6300011
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Goodman Mfg RS6300011 в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Goodman Mfg RS6300011?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Goodman Mfg RS6300011, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Goodman Mfg RS6300011 со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)