Summary
  • Hitachi EH-150 - page 1

    HITACHI PROGRAMMABLE CONTROLLER RESISTANCE TEMPERATURE DETECTIVE INPUT MODULE(EH-PT4) APPLICATION MANUAL NJI- 324(X) ...

  • Hitachi EH-150 - page 2

    WARNING To ensure that the equipment described by this manual. As well as all equipment connected to and used with it, operate satisf actorily and safety, all applicable local and national codes that apply to installing and operating the equipment must be followed. Since codes can vary geographically and can change with time, it is the user’s res ...

  • Hitachi EH-150 - page 3

    LIMITED WARRANTY AND IMITATION OF LIABILITY Hitachi Industrial Equipment Syst ems Co., Ltd. (Hitachi) warrant s to the original purchaser that the programmable logic controller (PLC) manuf actured by Hitachi is free from defects in material and workmanship under normal use and serv ice. The obligation of Hitachi under this warranty shall be limited ...

  • Hitachi EH-150 - page 4

    Copyright 2002 by Hitachi Industrial Equipment Systems Co., Ltd. All Right Reserved – Printed in Japan The Information and/or drawing set forth in this document and all right in and to inventions disclosed herein and patent which might be grant ed thereon disclosing or employing and the materials, methods, te chniques or apparatus described herei ...

  • Hitachi EH-150 - page 5

    Safety Precautions Read this manual and related documents thoroughly before installing, operating, performing preventive maintenance or performing inspection, and be sure to use the unit correctly. Use this product after acquiring adequate knowledge of the unit, all safety information, and all cautionary information. Also, make sure this manual ent ...

  • Hitachi EH-150 - page 6

    2. About wiring REQUIRED l Always perform grounding (FE terminal). If grounding is not performed, there is a risk of electric shocks and malfunctions. CAUTION l Connect power supply that meets rating. If a power supply that does not meet rating is connected, fire may be caused. l The wiring operation should be performed by a qualified personnel. If ...

  • Hitachi EH-150 - page 7

    4. About preventive maintenance DANGER l Do not connect the , of the battery in reverse. Also, do not charge, disassemble, heat, place in fire, or short circuit the battery. There is a risk of explosion or fire. PROHIBITED l Do not disassemble or modify the unit. These actions may result in fire or malfunction. CAUTION l Turn off the power supply b ...

  • Hitachi EH-150 - page 8

    Revision No. Content Date Manual No. ...

  • Hitachi EH-150 - page 9

    Table of c ontent s 1. Introduction 1-1 to 1-4 1.1 Before Use ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 1-2 1.2 Precaution on Use ・・・・・・・・・・・・・・・・・・・・・・・・・ ...

  • Hitachi EH-150 - page 10

    10. Example of Programming 10-1 to 10-4 10.1 Example of Programming 1 ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 10-1 10.2 Example of Programming 2 (Offset adjustment) ・・・・・・・・・・・・・・・・・・・・・・・・・ 10-4 11. Trouble ...

  • Hitachi EH-150 - page 11

    1.Introduction 1- 1 1. Introduction This manual describes how to operate the EH-PT4 (Resistance Temperature Detective input module) properly, which is one of the special function module of EH-150 Programmable Logic controller(PLC). Carefully read this manual to familiarize yourself with the procedures respectively of installation, operation, and ma ...

  • Hitachi EH-150 - page 12

    1.Introduction 1- 2 1.1 Before Use The resistance temperature detective input module (hear after EH-PT4) has been carefully manufactured, but you are kindly advised to make the following checks on receipt of it. (1) The type and specification of the module are as specified by the order. (2) No damage is caused to the equipment during transport. If ...

  • Hitachi EH-150 - page 13

    1.Introduction 1- 3 1.2 Precautions on Use (1) Before the installation and removal of the module, turn off the power. (2) Before the connection of the external wiring and removal of the terminal board, turn off the power. (3) The terminal board handles fine signals. Therefore upon handling the module or wiring, be careful not to apply a voltage on ...

  • Hitachi EH-150 - page 14

    2. Structure and Nameplate 2-1 2. Structure and Nameplate 2.1 Structure and Name of Each Part Name and function of each part Type EH-PT4 Weight Approx. 180 g Dimensions(mm) No. Name Function Remarks 1) Lock button This is used when removing the module from the base unit. After it is installed to the base unit, the fixation can be reinforced using s ...

  • Hitachi EH-150 - page 15

    3.Specification 3- 1 3. Specification 3.1 Specification list Table 3.1 shows the specifications of EH-PT4. Table 3.1 Specification Item Specification Type EH-PT4 Resistance temperature detective Platinum resistance temperature detective Pt100 (IEC 751) Platinum resistance temperature detective Pt1000 Temperature conversion data Signed 15 bits (In n ...

  • Hitachi EH-150 - page 16

    3.Specification 3- 2 3.2 Terminal layout and internal circuit Terminal layout Internal circuit No. Signal name 1) b0 2) B0 3) b1 4) B1 5) b2 6) B2 7) b3 8) B3 9) 24V DC+ 10) A0 11) NC 12) A1 13) NC 14) A2 15) NC 16) A3 17) NC 18) 24V DC- Note 1) Current terminals and a voltage terminals of unused channels should be wired. By this wiring read data b ...

  • Hitachi EH-150 - page 17

    4. Block Diagram 4-1 4. Block Diagram 4.1 Internal Block Diagram Figure 4.1 shows the internal block diagram. Figure 4.1 Internal Block Diagram Note: V/F conversion refers to the conversion of voltage(V) to frequency(F). RTD External grounding ・・・ B0 b0 A3 B3 b3 External wiring CPU Bus 24 V DC − External power 24V DC 24 V DC+ EH-PT4 V/F con ...

  • Hitachi EH-150 - page 18

    5. External Wiring 5-1 5. External Wiring 5.1 Resistance Temperature Detective Connection Method and External Wiring Figure 5.1 External Wiring Note 1: The external wire length shall be less than 200 m for each channel. In addition, the total resistance of the wires of each channels to be connected to the current terminals (A0 to A3, B0 to B3) shal ...

  • Hitachi EH-150 - page 19

    6. Setting 6-1 6. Setting 6.1 Setting of temperature range This module can be set to three temperature ranges by the dip switch shown in below. Table 6.1 Temperature rage setting Temperature measurement range Setting switch Pt100 -20 to +40 ° C ON OFF Pt100 -50 to +400 ° C ON OFF Pt1000 -50 to +400 ° C ON OFF Note: Do not use the setting which i ...

  • Hitachi EH-150 - page 20

    7. Collection of Temperature Data 7-1 7. Collection of Temperate Data 7. 1 I/O Allocation The temperature data of each channel is collected in the CPU as the temperature conversion data corresponding to the temperature. (1) I/O assignment The I/O assignment shall be set as “ WX4W" by your programming software or the peripheral equipment. (2) ...

  • Hitachi EH-150 - page 21

    7. Collection of Temperate Data 7-2 7.2 Temperature Data (1) Content of temperature conversion data [range : -50 to +400 ° C] (Pt100/ Pt1000) The meaning of the each bit( b0 to b15) of temperature conversion data (in WX**) is as shown below. The sum of the bit “ 1 ” is the measured temperature. <For example> (1) HF800 = “ 1111 1000 000 ...

  • Hitachi EH-150 - page 22

    7. Collection of Temperate 7-3 (2) Content of temperature conversion data [range : -20 to +40 ° C] (Pt100) The meaning of the each bit( b0 to b15) of temperature conversion data (in WX**) is as shown below. The sum of the bit “ 1 ” is the measured temperature. <For example> (1) HE000 = “ 1110 0000 0000 0000" (HE) (H0) (H0) (H0) -8 ...

  • Hitachi EH-150 - page 23

    7. Collection of Temperate Data 7-4 7.3 Example of Calculation The program shown below as an example converts the temperature conversion data in WR0 to BCD 4 digit data in WM6. In case the temperature is minus, the bit internal output R0 will be turned on. (1) Because the calculation with sign is that by double words, extend the word temperature co ...

  • Hitachi EH-150 - page 24

    7.Collection of Temperature Data 7-5 7.4 Correspondence Table between Temperature and Temperature Data (1)Pt100/Pt1000 -50 to +400 ºC range Table 7.4.1 Pt100 -50 to +400 ºC range Temperature conversion data Temperature ( ºC ) Note1) Decimal data Hexadecimal data Pt100 resistance ( Ω ) Note 2) Temperature ( ºC ) Note1) Decimal data Hexadecimal ...

  • Hitachi EH-150 - page 25

    7.Collection of Temperature Data 7-6 (1)Pt100 -20 to +40 ℃ range Table 7.4.2 Pt100 -50 to +40 ºC range Temperature conversion data Temperature ( ºC ) Note1) Decimal data Hexadecimal data Pt100 resistance ( Ω ) -25 55296 D800 90.19 -20 57344 E000 92.16 -15 59392 E800 94.12 -10 61440 F000 96.09 -5 63488 F800 98.04 0 0 0000 100.00 5 2048 0800 10 ...

  • Hitachi EH-150 - page 26

    8. Error Deception Processing 8-1 8. Error Detection Processing 8.1 Measured Temperature Range over (1)Interlock If temperate conversion data is over the measuring range or current terminal wiring is disconnected, the temperature conversion data becomes H7FFF. After this data is read, it is necessary to make a program externally for the treatment f ...

  • Hitachi EH-150 - page 27

    8. Error Detection Processing 8-2 8.2 Treatment for a Sudden Change of Temperature Conversion Data When the temperature conversion data is changed suddenly due to the disconnection of external wiring or influence of noise, the system judges it to be an abnormal condition. In the example shown below, every scanned data is read in. If a change of 5º ...

  • Hitachi EH-150 - page 28

    9. Mounting 9-1 9. Mounting 9.1 Installation (1) EH-PT4 module can be installed on both the basic base and expansion base. (2) Precaution on installation Upon the installation of the EH-150 series, consider the operability, maintainability and environment. (a) For use at proper ambient temperature range • Secure a sufficient space allowing a good ...

  • Hitachi EH-150 - page 29

    9. Mounting 9-2 9.4 Precautions on External Wiring Because the external wiring of the EH-PT4 handles fine signals, be sure to use a shielded wire to suppress the influence of external noise and place the wire separately from the power line and signal line of different voltage. Note) Weld joints of metallic conduits and ground the welded metallic co ...

  • Hitachi EH-150 - page 30

    10. Example of Programming 10-1 10. Example of Programming 10.1 Example of Programming 1 (1)Control contents (a) The program keeps the temperature of a liquid in a bath 10 to 12ºC higher than that of ambient air temperature. (b) When the temperature difference between the upper part and the lower part of the liquid is 3ºC or higher, the program t ...

  • Hitachi EH-150 - page 31

    10. Example of Programming 10-2 (3)Program (1) (2) (3) (4) (5) (6) (7) (8) (9) Y0000 Y0003 SS0 SS0 R003 R004 R00 2 SS0 If R0 or R1 turns on, turn the motor for a minute. However, if Y3 turns on, do not turn the motor. The program stores the difference between the temperature at the upper part of the liquid and the air temperature in WR5. When the a ...

  • Hitachi EH-150 - page 32

    10.Program 10-3 (10) (11) (12) (13) (14) R006 R005 M004 R004 R007 R004 R003 R001 R002 Turn on either R5 or R6 to turn on the heater and turn off the cooler. Turn on M4 to light the data abnormality lamp. Turn on any one of R1, R3 and R4 to light the temperature abnormality lamp. Turn on any one of R1, R3, R4, R7 and M4 to turn on the cooler and tur ...

  • Hitachi EH-150 - page 33

    10. Program 10-4 10.2 Example of Programming 2 (Offset adjustment) The resistance temperature detective itself has an built-in error, therefore an offset error may occur in temperature conversion data. An offset error occurs due to the change with the passage of time also. An example of correction by programming in this case is shown below. However ...

  • Hitachi EH-150 - page 34

    11. Troubleshooting 11-1 11 Troubleshooting If you have some problems, please find the cause according to the following countermeasures. If the problem is not solved despite this countermeasures, contact the sales office. If a spare unit is available, replace and see the condition. 11.1 The Allocation Error “ 41 ” is indicated in CPU. Error cod ...

  • Hitachi EH-150 - page 35

    12. Appendix 12-1 In the case of Hitachi twisted shielded cable (CO-DS-IREVV-SX,(10 pairs to 52)), the maximum conductor resistance in the cross section of 0.18mm 2 under the temperature 20 ° C is 121.5 ohm/km (according to Hitachi ’ s Guide Book). 12. Appendix 12.1 Calculation of External Wiring Resistance Assuming that the cross section and le ...

Производитель Hitachi Категория Weather Radio

Документы, которые мы получаем от производителя устройства Hitachi EH-150 мы можем разделить на несколько групп. Это в частности:
- технические чертежи Hitachi
- инструкции обслуживания EH-150
- паспорта изделия Hitachi
- информационные брошюры
- энергетические этикетки Hitachi EH-150
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Hitachi EH-150.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Hitachi EH-150, инструкции обслуживания, короткие инструкции или инструкции пользователя Hitachi EH-150. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Hitachi EH-150.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Hitachi EH-150, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Hitachi EH-150 пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Hitachi EH-150.

Полная инструкция обслуживания Hitachi, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Hitachi EH-150 - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Hitachi EH-150, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Hitachi EH-150, которое найдем в данном документе
3. Советы по использованию основных функций устройства Hitachi EH-150 - которые должны облегчить нам первые шаги во время использования Hitachi EH-150
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Hitachi EH-150
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Hitachi EH-150 в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Hitachi EH-150?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Hitachi EH-150, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Hitachi EH-150 со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)